EN Sensor MUST be positioned horizontal to vertically downwards and MUST be perpendicular to the target surface. Sensor MUST not be positioned above horizontal e.g. in upward direction.
90˚
2 Sensor position to target area
EN Always position the sensor to view the centre of the target area.
EN Sensor must NEVER be targeted
viewing the bolted connection. 3 Target Area EN Target area MUST be MATT BLACK (Flat Black) by painting with a high temperature stove paint. The painted area should be square e.g. deep as the busbar is wide. NEVER rectangular or circular.
A=B
4 Cable Sensor Installation
EN The grey ambient sensor MUST NOT be in contact with the cable being measured and ensure it is in the local ambient air. • LV (up to 1000v AC) – mounting distance MUST be 50 to 75mm (2” to 3”) from the lower end of the connecting lug • MV (up to 13.8kV) – mounting distance MUST be 150mm (6”) from the lower end of the connecting lug NOTE: all local and country specific standards for clearance should be adhered to for mounting the sensors.