Water Delta Ts
Chillers Plant-Main Components
Cooling Load
Tower AHU
FCU
FAHU
13’C
56’F
4.5’C
40’F
If Chiller Maximum Cap. is 600 TR: It can COOL 1000 gpm of CH.W.
4.5’C
Pumps
Cooling
Towers
Energy
Meters
Occupants
Satisfaction
Enviro.
Effect
What will happen to CH. W. Sys. Components
when Delta Temp. Differ (Keep Changing)?
gpm Delta-T TR
1000 1 42
1000 2 83
1000 3 125
1000 4 167
1000 5 208
1000 6 250
1000 7 292
1000 8 333
1000 9 375
1000 10 417
1000 11 458
1000 12 500
1000 13 542
1000 14 583
1000 15 625
1000 16 667
4.5’C 5.5’C
40’F 42’F
600- TR/Chiller
1000
gpm/
Pump
13.5’C 14.5’C
56’F 58’F
gpm Delta-T TR
500 4 83.3
600 4 100
700 4 117
800 4 133
900 4 150
1000 4 167
1400 4 233
1100 4 183
1200 4 200
1500 4 250
1800 4 300
2000 4 333
2500 4 417
3000 4 500
4000 4 667
4.5 12.2
’C ’C
40’F 54’F
600- TR/Chiller
4000-
gpm
Pump
6.7 14.5
’C ’C
44’F 58’F
If we have a Building Load 600 TR: How many Chiller we will Work?
5000
3’F gpm
4000
gpm
6’F
3000
gpm
9’F
2000
gpm
12’F
1000
gpm
16’F
If we have a Building Load 600 TR: How many Chiller we will Work?
4.5’C 4.5’C
40’F 40’F
6.7’C 13’C
44’F 56’F
Chillers
Pumps
Cooling
Towers
Energy
Meters
Occupants
Satisfaction
Enviro.
Effect (-)
Pumps
Cooling
Towers
Energy
Meters
Occupants
Satisfaction
Enviro.
Effect
Pumps
Cooling
Towers
Energy
Meters
Occupants
Satisfaction
What will happen to Power Consumption Ratio
when the need for CH. W. Flow decrease?
Results-
Once high gpm Delta-T TR
chilled-water 1000 1 41.7
Delta Ts is 1000 2 83.3
1000 3 125.0
achieved, mo 1000 4 166.7
re Btu’s (J/s) 1000 5 208.3
of cooling 1000 6 250.0
will be 1000 7 291.7
1000 8 333.3
accomplished 1000 9 375.0
per gallon 1000 10 416.7
(liter) of 1000 11 458.3 J/S)
1000 12 500.0
chilled-water 1000 13 541.7
distributed. 1000 14 583.3
1000 15 625.0
Results-
Pressure losses
and pumping
energy will
decline
considerably in
existing hydronic
hydronic cooling One Working Pump
systems and Compare to 5-Pumps
smaller pumps
and piping may
be installed in
new hydronic hydronic
cooling systems.
Results-
Also, water chiller
capacities will
no longer be
limited by
maximum
cooler flow
rates chilled-
water storage
tanks will store
many more MJ
ton/hours (MJ)
of cooling.
Results-
This
fundamental
approach
provides
significant, en
during
improvements
in the
performance
of variable- hydronic
flow hydronic
cooling
systems.
Results-
Maximize the
cooling
efficiency
of Cooling
Coil and
prevent
over
flooding of
CH. Water
& increase
Delta-T
Results-
Anther
important
benefit is
the cooling
transferred
from
Primary
Circuit to
Secondary
Circuit
1’C+/-1’C
Results-
The efficient
cooling &
pumping
means less
Working:
•
• Chillers.
•
• C. Towers.
•
• Pumps. •
• Dhs Per TR.
The Challenge: How to achieve & maintain
High Delta-T?
Estimate of Situation: The Need for Balancing
and/or re-balancing of CH. W. Flow System.
ASHRAE
5- Oversized
3- Automatic Main Piping
Flow Limiting Method
Valves
2- Manual
Balance
Using DRV
Method 4- Reverse
Return
Method
1- No
Balancing
Method
When CH.W. Pumps are located below loads, How can u transfer Cooling?
The 5th Annual Middle East District
Our Solution
has revealed at: Cooling Summit – 2013 @ Qatar
WORKSHOP