Electrical network protection

Sepam series 10
Digital protection relays

Catalogue
2012
Sepam series 10 Contents

Introduction 3
Sepam protection relays, the product of experience 3

Selection guide for all applications 4


Panorama of Sepam applications 4

Presentation 7
Presentation of Sepam series 10 7

Applications 8
Sepam 10 series applications 8

Functions Sepam series 10 9


Protection functions 9
Protection and measurement functions 10
Control and monitoring 11

Connection 12
Operating diagram 12
Connection to Sepam series 10 15

Characteristics 16
Protection functions 16
Measurements 17
Electrical characteristics 18
Environmental characteristics 19

Dimensions 21
User-machine interface and dimensions 21

Sensors 22
Core balance CTs CSH120, CSH200, GO110 22

Power supply 23
PS100 High-availability power supply 23

Ordering information 25
Sepam series 10 25

1
2
Introduction Sepam protection relays,
the product of experience

A complete range for many different needs


PE50773_SE

Protection relays constantly monitor the power network and trip the circuit breakers
to isolate the faulty portion under fault conditions: overload, short-circuit, insulation
fault.
The Sepam range of protection relays is designed for all protection applications in
medium-voltage public and industrial distribution networks.
It is made up of four series of relays with increasing performance levels:
„„ Sepam series 10 for simple applications.
„„ Sepam series 20 for current or voltage applications.
„„ Sepam series 40 for current and voltage applications.
„„ Sepam series 60 for demanding applications.
„„ Sepam series 80 for critical or custom applications.

A multi-functional range of digital relays


Each Sepam series offers all the functions required for the intended application:
Sepam, a complete range of protection relays. „„ effective protection of life and property
„„ accurate measurements and detailed diagnosis
„„ integral equipment control
„„ local or remote indications and operation.

A Sepam solution for every application


For each electrotechnical application, Sepam offers the relay suited to the protection
needs of your network:
„„ substations (incomer or feeder type)
„„ transformers
„„ motors
„„ generators
„„ busbars
„„ capacitors.

Schneider Electric, a global offer


World leader in power & control
Schneider Electric makes electricity safe, as well as facilitating and improving its use.
Worldwide presence
Schneider Electric contributes to customer performance through its unique selection
of products, solutions and services, as well as its dynamic policy of innovation.
Over 13 000 points of sale and 205 factories in 190 countries
PE50528

You can be sure of finding the range of products meeting your needs and complying
perfectly with local standards.
Our technicians are always on hand to provide solutions tailored to your needs and
all the technical assistance you may require.

Schneider Electric, vast experience in protection


relays
Breaking new ground back in 1982, Merlin Gerin launched Sepam, the first multi-
functional, digital protection relay. Today, with the extended Sepam range (series 10,
Schneider Electric, by your side in over 190 countries. 20, 40, 60 and 80), you benefit from over 30 years of experience on the part of the
Schneider Electric R&D teams.
More than 600 000 Sepam relays have been installed in over 130 countries and in
every sector of activity:
„„ energy production and distribution
Sepam for reliability and quality, from „„ infrastructure: airports, tunnels, public transportation, water treatment
design on through to operation „„ industry: automobile, mines, semiconductors, metallurgy, petrochemicals
n Design based on dependability studies, complying „„ commercial sector: shopping centres, hospitals.
with the functional-safety requirements of standard
IEC 61508.
n Product development and manufacturing certified
ISO 9001.
n Environmentally friendly manufacturing certified
ISO 14001.
n Service quality ensured by decentralized logistics
and support
n Compliance with international standards and local
certification.

3
Selection guide for all Selection guide for all applications
applications

series 10 series 20

Protections
Current b b b b b
Voltage b b
Frequency b b
phase and phase and earth fault breaker disconnection
Specifics earth fault earth fault overcurrent failure by rate of
overcurrent overcurrent change of
frequency
Applications
Substation A B N S20 S24

Busbar B21 B22

Transformer A B N T20 T24

Motor M20

Generator
Capacitor
Characteristics
Logic inputs/ Inputs 4 0 0 0 to 10 0 to 10
outputs Outputs 7 3 3 4 to 8 4 to 8
Temperature sensors 0 to 8 0 to 8
Current 3I + Io 3I + Io Io 3I + Io
Channel Voltage 3V + Vo
LPCT (1) Yes
Communication ports 1 1 to 2 1 to 2
IEC61850 Protocol Yes Yes
Redudancy
Goose message
Matrix (2) Yes Yes
Control Logic equation editor
Logipam (3)
Backup Lithium battery (4)
Other Front Memory cartridge
with settings
(1) LPCT: low-power current transducer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format 3.6 V front face exchangeable.

4
Selection guide for all Selection guide for all applications
applications

series 40 series 60

Protections
Current b b b b b b b b
Voltage b b b b b b b
Frequency b b b b b b b
directional directional directional directional directional
Specifics earth fault earth fault and earth fault earth fault earth fault and
phase phase
overcurrent overcurrent
Applications
Substation S40 S41 S42 S43 S44 S60 S62
(5) (5) (5) (5) (5)
S50 S51 S52 S53 S54

Busbar
Transformer T40 T42 T60 T62
(6) (6)
T50 T52

Motor M40 M41 M61

Generator G40 G60 G62

Capacitor C60

Characteristics
Logic inputs/ Inputs 0 to 10 0 to 28
outputs Outputs 4 to 8 4 to 16
Temperature sensors 0 to 16 0 to 16
Current 3I + Io 3I + Io
Channel Voltage 3V, 2U + Vo 3V, 2U + Vo or Vnt
LPCT (1) Yes Yes
Communication ports 1 to 2 1 to 2
IEC61850 Protocol Yes Yes
Redudancy Yes Yes
Goose message Yes
Matrix (2) Yes Yes
Control Logic equation editor Yes Yes
Logipam (3)
Backup 48 hours Lithium battery(4)
Other Front Memory cartridge
Yes
with settings
(1) LPCT: low-power current transducer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format 3.6 V front face exchangeable.

5
Selection guide for all Selection guide for all applications
applications

series 80

b b b b b b b b
b b b b b b b b
b b b b b b b b
directional directional disconnection transformer & machine voltage and frenquency capacitor-bank unbalance
earth fault earth fault and by rate of transformer- differential protection for 2 sets of
phase change of machine unit busbars
overcurrent frequency differential

S80 S81 S82 S84

B80 B83

T81 T82 T87

M81 M88 M87

G82 G88 G87

C86

0 to 42 0 to 42 0 to 42 0 to 42
5 to 23 5 to 23 5 to 23 5 to 23
0 to 16 0 to 16 0 to 16 0 to 16
3I + 2 x Io 2 x 3I + 2 x Io 3I + Io 2 x 3I + 2 x Io
3V + Vo 3V + Vo 2 x 3V + 2 x Vo 3V + Vo
Yes Yes Yes Yes
2 to 4 2 to 4 2 to 4 2 to 4
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Lithium battery(4) Lithium battery(4) Lithium battery(4) Lithium battery(4)
Yes Yes Yes Yes

(5) S5X applications are identical to S4X applications with the following additional functions:
b earth fault and phase overcurrent cold load pick-up,
b broken wire detection,
b fault locator.
(6) T5X applications are identical to T4X applications with the following additional functions:
b earth fault and phase overcurrent cold load pick-up
b broken wire detection.

6
Presentation Presentation of Sepam series 10

Sepam series 10 is a high-quality protection relay that represents the most cost-
PB103446_SE

effective solution available for essential protection functions. Highly ergonomic, it is


easy to install and set up.

Sepam series 10 specifics


Sepam series 10 monitors phase and/or earth-fault currents. Three models meet a
wide range of different needs :
„„ N: Sepam series 10 N protects against earth faults
„„ B: Sepam series 10 B protects against overloads, phase-to-phase faults and earth
faults
„„ A: Sepam series 10 A provides the same functions as Sepam series 10 B, with
also a communication port, more inputs and outputs, and additional protection and
monitoring functions.
Simplicity
„„ easy operation - screen, keys, pictograms, etc., good ergonomics
Sepam series 10. „„ fast set-up - installation, wiring, parameter setting directly on the relay without
a PC
„„ easy stock management - a single box, no accessories.
Reliability
„„ guaranteed protection of life and property - high-quality product, compliance
with standards, continuous self-test
„„ safety of operating personnel - all accessible parts are made of insulating
materials, light and compact product with no sharp edges
„„ environmentally friendly - compliance with the European RoHS directive, low
energy consumption, manufacture in factory certified ISO 14001 and recyclable to
more than 85%.
Productivity
„„ attractive, cost-effective product - easy to understand, no unnecessary
complications, suited to user needs
„„ improved availability of electricity - precise tripping set points and times, logic
discrimination, detailed information made spontaneously available to operator
following tripping.
„„ reduced maintenance costs - continuous self-tests to extend periods between
maintenance.
Functions ANSI Sepam series 10
code N B A
Protections
Earth-fault protection Standard 50N/51N o o o
Sensitive o o
High sensitivity o o o
Phase-overcurrent protection 50/51 n n
Thermal overload protection 49RMS n n
Phase-overcurrent and earth fault protection n n
cold load pick-up
Logic discrimination blocking send 68 n n n
blocking reception n
External tripping n
Measurements
Earth-fault current n n n
Phase currents n n
Peak demand currents n n
Control and supervision
Circuit breaker tripping and lockout 86 n n n
Tripping indication n n n
Trip-circuit supervision n
Remote circuit-breaker control n
Record of last fault n n
Record of last five events n
Communication
Modbus n
IEC 60870-5-103 n
Inputs/Outputs (number)
Earth-fault current inputs 1 1 1
Phase-current inputs - 2 or 3 3
Logic relay outputs 3 3 7
Logic inputs - - 4
Communication port - - 1
n Function available.
o Function availability depends on the Sepam model.

7
Applications Sepam series 10 applications

Protection applications
The primary applications for Sepam series 10 are:
„„ protection of secondary distribution networks (MV/MV and MV/LV substations)
„„ protection of buildings supplied with medium voltage (MV), including office
buildings, shopping centres, industrial buildings, warehouses, etc.
„„ protection of low-voltage networks by tripping a Masterpact NW circuit breaker not
equipped with a Micrologic control unit.

Power system protections

Utility network Industrial and commercial networks


DE53463

MV / MV substation MV / LV substation Customer MV substation

Main HV / MV Secondary
Main HV / MV substation
substation substation

Integration in a remote-control system


To manage MV substations, Sepam protection relays can be connected to Easergy
T200I remote-control and monitoring interfaces (RTU) for operation with PowerLogic
power-monitoring units and Flair fault detectors.
This flexible solution includes a number of functions:
„„ protection of incoming and outgoing circuits
„„ detection of fault currents
„„ switch management
„„ database containing event logs and measurements
„„ backed-up power supply
„„ communication via SCADA
„„ local and remote access via a web server.
PE50774_SE

8
Functions Protection functions
Sepam series 10

N B A Earth-fault protection (ANSI 50N-51N)


t Earth-fault protection detects overcurrents caused by phase-to-earth faults. It uses
DE53229

measurements of the fundamental component of the earth-fault current.


2 independent set points (Io> and Io>>)
„„ the low set point (Io>) offers definite time (DT) or IDMT settings with various types
of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT timer
hold.
„„ the high set point (Io>>) offers only the definite time (DT) setting. The minimum
setting results in instantaneous operation (ANSI 50).
Depending on the required level of sensitivity, there are three types of Sepam relays.
Sensitivity Sensor Setting range
Io> Io>> Io Standard 3 phase CTs or 1 earth-fault protection CT, 0.1...24 Ino
with rated primary current Ino
Sensitive (1) 3 phase CTs or 1 earth-fault protection CT, with rated 0.01...2.4 Ino
primary current Ino
High Special core balance CSH or GO, with ratio of 470/1 0.2...240 A primary,
sensitivity i.e. 0.0004...0.5 Ino
(1) Setting not available with Sepam series 10N.

N B A Phase-overcurrent protection (ANSI 50-51)


Phase-overcurrent protection detects overcurrents caused by phase-to-phase faults.
It uses the measurements of the fundamental component of currents drawn from two
or three phase CTs, with a secondary rating of 1 A or 5 A.
3 independent set points (I>, I>> and I>>>)
„„ 2 low set points (I> and I>>) offer definite time (DT) or IDMT settings with various
types of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT
timer hold.
„„ the high set point (I>>>) offers only the definite time (DT) setting.
The minimum setting results in instantaneous operation (ANSI 50).

t
DE53228

N B A Thermal image overload protection (ANSI 49 RMS)


This protection function is used to protect cables and HV/LV transformers against
overloads, based on measurement of the current drawn.
The function is based on a thermal model which calculates the temperature rise from
current measurements. The current measured is an RMS 3-phase current which
takes into account harmonics up to number 13.
Two protection settings
„„ the continuous maximum permissible current setting which corresponds to the
maximum thermal withstand of the protected devices (the continuous permissible
current corresponds to a temperature rise of 100 %).
„„ the setting for the equipment heating and cooling time constant.

Ith I> I>> I>>> I

9
Functions Protection and measurement
Sepam series 10 functions

N B A Phase-overcurrent and earth-fault protection cold


load pick-up
The desensitization function avoids nuisance tripping during energizing operations,
particularly following a long outage. It temporarily raises the protection set point.
High currents during energization may be due to:
„„ simultaneous energizing of all loads in an installation (air conditioning, heating,
etc.)
„„ magnetizing currents in power transformers (these currents can saturate the
phase-current sensors and create a false residual current on the secondary of the
sensors)
„„ motor starting currents.
Protection function Mode of action
Phase-overcurrent After circuit-breaker closing, the tripping set points (I> or I>>) are
protection increased or disabled for the set time.
Earth-fault protection After circuit-breaker closing, the tripping set points (Io> or Io>>) are
increased or disabled for the set time.
Or
This protection is restrained by sensor saturation detection (H2
measurement) (1)
(1) Setting not available with Sepam series 10 N.

N B A Logic discrimination (ANSI 68)


This function provides:
T = 100 ms „„ perfect tripping discrimination with phase-to-phase and phase-to-earth short-
DE53468

circuits, on all types of network


„„ faster tripping of the breakers closest to the source.
All Sepam series 10 relays (N, B and A) can send a blocking signal when a fault
is detected by the phase-overcurrent and earth-fault protection functions.
T > 100 ms
Only the Sepam series 10 A relays can receive blocking signals which inhibit
Logic discrimination ensures tripping within 100 ms for a protection tripping. A saving mechanism (exclusive Sepam function) ensures back-up
fault affecting the substation busbars, while maintaining protection in the event of a blocking link failure.
discrimination with the feeders.

N B A External tripping
A Sepam series 10 A can receive, via a logic input, a tripping order from an external
protection device.

N B A Earth-fault current
This function displays the value of the fundamental of the earth-fault current.
For this measurement and for earth-fault protection (ANSI 50N/51N), the zero-
sequence input must be connected either to the common point of the three phase
CTs or to one earth-fault protection CT or to a CSH120, CSH200 or GO110 core
balance CT.

N B A Phase currents
This function displays the rms phase-current values and takes into account
harmonics up to order 13. On Sepam series 10•4••, this function displays the three
phase currents. On Sepam series 10•3••, only the A and C phases are connected
and displayed.

N B A Peak demand currents


This function displays the greatest average current on each of the three phases and
indicates the current absorbed by peak loads.

10
Functions Control and monitoring
Sepam series 10

N B A Circuit breaker tripping and lockout (ANSI 86)


DE53167

Trip Closing Sepam can be used in all types of circuit-breaker control systems.
orders orders
Functions of the output relays
Relay outputs Standard assignment
O1 Circuit-breaker tripping
A 10
Closing inhibit
9 (ANSI86)
O2 Closing inhibited
O2 8
7 O3 Tripping indication
6
5
4
Trip-circuit supervision
O1
3 N B A
This function continuously monitors the trip circuit to make sure that it has not been
interrupted. The system shown opposite runs a low current through the trip circuit.
Sepam checks that the current is effectively present.

Shunt trip unit Closing coil


N B A Remote circuit-breaker control
Circuit-breaker control with a Sepam The circuit breaker can be remotely controlled via the communication system. A
series 10B or N.
Sepam logic input is used to select the operating mode (local or remote).

N B A Record of last fault


DE53168

Displays the characteristics of the last fault. Sepam indicates the fault source, the
D 18
Trip
orders
Closing
orders value of the three phase currents and the earth current at the time of tripping.
O4 17
The information is stored in memory until the next fault.
Origin of recorded faults : I>, I>>, Io>, Io>> and thermal overload protection.
A 10
Closing inhibit
9
(ANSI86)
O2 8
7

6
5
N B A Record of last five events
O1 4
3
Displays the characteristics of the last five events. For each event, Sepam indicates
the fault source, the value of the three phase currents and the earth current at the
time of the event and the date and time of the event.
D 5 The events are numbered in order of occurrence and the last five are memorized.
I2 4
2
Recorded events:
I1 1 „„ tripping due to I>, I>>, I>>>,Io>, Io>>, thermal overload protection
„„ tripping via input signal from external device
„„ fault in tripping circuit
„„ circuit-breaker opening and closing initiated by communication
„„ tripping due to I>, I>>, Io> or Io>> (logic discrimination back-up)
Shunt trip unit Closing coil

Circuit-breaker control with a Sepam


series 10A.
N B A Communication
Sepam series 10 A relays are equipped with an RS485 communication port.
The desired protocol (two available) must be set up in the parameters:
Modbus, IEC 60870-5-103.
Communication can be used for a number of functions:
„„ reading of measurements
„„ reading of status conditions
„„ reading of time-stamped measurements and events (two tables containing 100
events are available)
„„ time setting and synchronisation
„„ transmission of remote controls

N B A Operating language
On delivery, the default language is English. The languages that may be selected are
UK English, US English, French, German, Italian, Portuguese, Spanish and Turkish.

11
Connection Operating diagram

N B A Sepam series 10 N

IA

DE53186
IB
IC

A 14
B 13
15
O3 12
25 11
14
24
13
23 10
9
Io > S O2 8
7
Io I > R
12 2-240 A
1 S 1
22
R
CSH120 11 6
CSH200 21 Io >> 5
GO110 O1 4
Io 3
0.2-24 A 2
Reset 1

Other connection possibilities


depending on the model

A A
DE53184
DE53185

B B
C C

B B
15 15
25 25
14 14
24 24
13 13
23 23

12 12
CT
22 Io 1A/5A 22 Io
11 11
21 21

Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES

12
Connection Operating diagram

N B A Sepam series 10 B

IA

DE53189
IB
IC

I> A 14
B I> 13
15 IA
O3 12
25 max 1 S 11
14 IB R
24
13 IC I >>
23 10
9
49 RMS S O2 8
R 7

S 1
R
6
5
Io > O1 4
Io I > 3
2-240 A 2
12 1 S 1
22
R
11
21 Io >>
Io
0.2-24 A
Reset

Other connection possibilities


depending on the model

A A
DE53188

DE53187_SE

B B
C C

15 B 15 B
25 IA 25 IA max
14 14
24 IB 24
13 13
23 IC 23 IC
Io
12 12 2-240 A
CT 22
1A/5A Io 22
11 CSH120 11
21 Io
CSH200 21 0.2 - 24 A
GO110

Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES

13
Connection Operating diagram

N B A Sepam series 10 A

IA

DE53192
IB
IC

I> A 14
B IA I> 13
15
max O3 12
25 1 S 11
14 IB R
24
13 IC
I >>
23 10
9
49 RMS S O2 8
R 7

S 1
R
6
5
Io > 1 O1 4
3
I > 2
12 Io
1 S 1
22
R
11
21 Io >>

9
D Ext
I4
8 S
Local / remote
Reset
R
7
External I3 1
6
tripping

C RS 485
1 C
COM
2 S
3 D0
D 18
4 D1
O4 17

68
16
D O5 15
5
Circuit breaker I2
4
closed 14
3 O6 13
2
TCS
Circuit I1 Watchdog
1 12
breaker open 11
O7
10

Other connection possibilities


depending on the model

A A
DE53191

DE53190_SE

B B
C C

15 B 15 B
25 IA 25 IA
14 14
24 IB 24 IB
13 13
23 IC 23 IC
Io
12 12 2 - 240 A
CT 22
1A/5A Io 22
11 CSH120 11
21 Io
CSH200 21 0.2-24 A
GO110

Customization via
Logic inputs Standard assignment
parameter settings
I1 Circuit breaker open NO
I2 Circuit breaker closed NO
I3 External tripping YES
I4 Local / remote YES
Customization via
Relay outputs Standard assignment
parameter settings
O1 Circuit breaker tripping YES
O2 Circuit breaker lockout YES
O3 Tripping indication YES
O4 Circuit breaker closing by remote control NO
O5 Blocking send YES
O6 Indication of trip circuit fault (TCS) YES
O7 Watchdog NO

14
Connection Connection to Sepam series 10

A Connector A: supply and logic outputs 01 to 03


DE53234

Diagram Terminals Signals


1-2 Auxiliary power supply
14
A
13 3-4 and 5-6 Logic output O1

DE53230
12 O3
11
7-8 and 9-10 Logic output O2
10
9
8 O2
11-12 and Logic output O3
7 13-14
6
5
4 O1
3
2
1

Connector B: inputs for phase and earth-fault currents


Diagram Terminals Signals
B 13-15, 23-25 Phase-current inputs
15
25 IA 12-22 Input for earth-fault current Io
DE53231

14
„„ for standard and sensitive earth-fault protection
B 24 IB
13 „„ for high sensitivity earth-fault protection (rating
Sepam series 10 N and 10 B. 23 IC
2...240 A)
12
22 Io
2-240 A 11-21 Input for earth-fault current Io, only for high
11
21
Io sensitivity earth-fault protection (rating 0.2..24 A)
0.2-24 A

A Connector C : 2-wire RS485 communication port


DE53235

Diagram Terminals Signals


RS 485 1 Common
DE53232

C 2 Shielding
C S D0 D1
1 2 3 4 3 D0 communication - negative polarity (A)
4 D1 communication - positive polarity (B)

Connector D: additional logic inputs/outputs


Diagram Terminals Signals
1-2, 4-5, Independent logic inputs
D
18 6-7, 8-9
O4 17
DE53233

10-11-12 Logic output O7: watchdog


16
O5 15
13-14, 15-16, Logic outputs: normally open contact
14
O6 13 17-18
12
11
O7
10
9
I4 8
D C B 7
I3 6
Sepam series 10 A. 5
I2 4
3
2
I1 1

Wiring
Identification Type of terminal Wiring
B Screw, 4 mm (0.16 in) 1…6 mm2 (AWG 18…10) - 2 lugs maximum
Screw clamp, 3 mm „„ 1 wire: 0,2...2.5 mm² (AWG 24...12)
A , C et D
(0,12 in) „„ 2 wires: 0.2...1 mm² (AWG 24...18)
Screw, 4 mm (0,16 in) 6 mm² green/yellow wire (AWG 10)

15
Characteristics Protection functions

Sec Protection function 50/51, 50N/51N


DE53195

1000
Tripping curve
„„ DT: Definite time
„„ SIT/A: IEC standard inverse
„„ VIT/B: IEC very inverse
„„ LTI/B: IEC long-time inverse
„„ EIT/C: IEC extremely inverse
100 „„ MI/D: IEEE moderately inverse
„„ VI/E: IEEE very inverse
„„ EI/F: IEEE extremely inverse
„„ RI
I>, I>>, I>> set points
10 DT curve 0.1...24 In (minimum: 1 A)
LTI/B IDMT curves 0.1...2,4 In (minimum: 1 A)
Accuracy ±5 % or ±0.02 In
RI Drop out/pick up ratio 95 %
SIT/A
Transient overshoot < 10 %

1
Io>, Io>> set points
VIT/B DT curve Standard version Setting range: 0.1…24 Ino
(minimum: 1 A)
Sensitive version Setting range: 0.01…2.4 Ino
(minimum: 0.1 A)
EIT/C
High sensitivity Rating 0.2…24 A Setting range: 0.0004…0.05 Ino
0.1 version (Ino = 470 A)
1 2 5 10 20 I/I>/I>> Rating 2.0…240 A Setting range: 0.004…0.5 Ino
or (Ino = 470 A)
Io/Io>
IDMT curves Standard version Setting range: 0.2…2.4 Ino
IEC curves SI, VI, LTI, EI and RI curve. (minimum: 1 A)
Sensitive version Setting range: 0.01…0.24 Ino
(minimum: 0.1 A)
Sec
DE53194

High sensitivity Rating 0.2…24 A Setting range: 0.0004…0.005 Ino


1000
version (Ino = 470 A)
Rating 2.0…240 A Setting range: 0.004…0.05 Ino
(Ino = 470 A)
Accuracy ±5 % ou ±0.02 Ino
Drop out/pick up ratio 95 %
100
Transient overshoot < 10 %
Time delay
DT curve 0.05...300 s
IEC, RI curves TMS: 0.02...2 (step: 0.01)
10
IEEE curve TD: 0.5...15 (step: 0.1)
Accuracy DT curve: ±2% or ±20 ms
IDMT curves: ±5% or ±20 ms
MI Timer hold Selection: ON/OFF. Common setting
VI for I> and Io> set points
1
Accuracy ±2 % or ±20 ms
EI
Characteristic times
Operation time < 40 ms at 2 x set point (typically 25 ms)
Overshoot time < 40 ms at 2 x set point
0.1
Reset time < 50 ms at 2 x set point
1 2 5 10 20 I/I>/I>>
or
Io/Io>
IEEE curves MI, VI, EI.
Protection function 49RMS
Set points
Alarm set point Setting range 50...100 % of permissible thermal capacity
Trip set point Setting range 0.1...2.4 In (value of permissible current)
Accuracy ±5 % or ±0,02 In
Drop out/pick up ratio 95 %
Time delay
Time constant Setting range 1...120 mn in 1 mn. steps
Tripping-time accuracy ±2 % or ±2 s

16
Characteristics Measurements

Measured characteristic Value


Rms phase current and peak Measurement range 0.1 In...1.5 In
demand currents Accuracy ±1 % typical at In
±2 % 0,3 In... 1.5 In
±5 % 0.1 In...0.3 In
Earth-fault current Range for standard version 0.1 Ino...1.5 Ino (or In)
Range for sensitive version 0.01 Ino...1.5 Ino (or In)
Range for high sensitivity 0.25...24 A primary or
version 2.5...240 A primary
Depending on the rating
Accuracy ±1 % typical at Ino (or In)
±2 % 0.3 Ino...1.5 Ino (or In)
±5 % 0.005 Ino...0.3 Ino (or In)
Phase tripping currentt Measurement range 0.1 In...40 In
Accuracy ±5 %
Earth-fault tripping current Range for standard version 0.1 Ino...40 Ino (or In)
Range for sensitive version 0.01 Ino...4 Ino (or In)
Range for high sensitivity 0.2...40 A primary or
version 2...400 A primary
Depending on the rating
Accuracy ±5 %

17
Characteristics Electrical characteristics

Current inputs Characteristics Conditions Value


Current transformer: Consumption at 1 A < 0.004 VA
„„ primary: 1…6300 A at 5 A < 0.1 VA
„„ secondary: 1 A or 5 A
Continuous thermal withstand - 4 In
Overload as per IEC 60255-6 1s 100 In
3s 40 In
CSH120, CSH200 or GO110 core Continuous thermal withstand - 300 A
balance CT Overload as per IEC 60255-6 1s 20 kA
Logic inputs Characteristics Applicable to DC value AC value
Sepam series 10 A, I1 to I4 Maximum voltage series 10 • •• A 125 V +20 % 120 V +20 %
series 10 • •• E 250 V +20 % 240 V +20 %
series 10 • •• F 250 V +20 % -
Frequency series 10 • •• • - 47…63 Hz
Typical switching threshold series 10 • •• A 14 V 12 V
series 10 • •• E 82 V 58 V
series 10 • •• F 154 V -
Typical consumption series 10 • •• • 3 mA 3 mA
Relay outputs Characteristics Conditions DC value AC value
Control relay outputs Maximum voltage - 250 V +20 % 240 V +20 %
Sepam series 10 B and N, O1…O3 Frequency - - 47…63 Hz
Sepam series 10 A, O1…O4
Rated current - 5A
Breaking capacity Resistive load 4 A/24 V 5 A/100…240 V
4 A/48 V
0,7 A/127 V
0,3 A/220 V
Load L/R < 40 ms 5 A/24 V -
1 A/48 V
0,1 A/220 V
Load cos j > 0,3 - 5 A/100…240 V
Making capacity and withstand ANSI C37.90, clause 6.7 30 A, 2000 cycles
200 ms
Indication relay output Maximum voltage - 250 V +20 % 240 V +20 %
Sepam series 10 A, O5...O7 Frequency - - 47…63 Hz
Rated current - 2A
Breaking capacity Load L/R < 20 ms 2 A/24 V -
1 A/48 V
0.5 A/127 V
0.15 A/220 V
Load cos j > 0,3 - 1 A/100…240 V
Serial link Characteristics
Sepam series 10 A only 2-wire RS485

Auxiliary power supply


Sepam must be supplied with AC or DC power.
It is protected against reversed polarity. The supply voltage depends on the Sepam
version.
Sepam series 10 x xx A Sepam series 10 x xx E Sepam series 10 x xx F
DC AC DC AC DC AC
Rated voltage 24…125 V ±20 % 100…120 V ±20 % 110…250 V ±20 % 100…240 V ±20 % 220…250 V ±20 % -
Typical consumption 3 VA
Maximum consumption 8 VA
Inrush current < 20 A for 100 ms
Acceptable momentary outages IEC 60255-11 class A : 100 %; 100 ms ; (3 relays excited)

18
Characteristics Environmental characteristics

Electromagnetic compatibility Standard Level / Class Value


Tests
Overall IEC 60255-26 A -
EN 50263 - -
Radiated emission CISPR22 A -
EN 55022 A -
IEC 60255-25 - -
Conducted emission CISPR22 A -
EN 55022 A -
IEC 60255-25 - -
Immunity tests – Radiated disturbances
Radiated RF fields IEC 60255-22-3 - 10 V/m ; 80…1000 MHz ; 1.4...2.7 GHz
IEC 61000-4-3 3 10 V/m ; 80…2000 MHz
ANSI C37.90.2 (2004) - 20 V/m ; 80…1000 MHz
Electrostatic discharges IEC 60255-22-2 - 8 kV air ; 6 kV contact
IEC 61000-4-2 3 8 kV air ; 6 kV contact
ANSI C37.90.3 - 8 kV air ; 6 kV contact
Magnetic field at power frequency IEC 61000-4-8 4 30 A/m (continuous)
100 A/m (for 1...3 s)
Immunity tests – Conducted disturbances
Conducted RF disturbances IEC 61000-4-6 3 10 V ; 0.15...80 MHz
IEC 60255-22-6 -
Fast transient bursts IEC 60255-22-4 4 kV CM (1) ; 5 kHz
IEC 61000-4-4 4
ANSI C37.90.1 - 4 kV ; CM (1) and DM (2), 5 kHz
Damped oscillatory wave IEC 60255-22-1 - 2.5 kV DM (2)
IEC 61000-4-18 3 1 kV DM (2)
100 kHz and 1 MHz

ANSI C37.90.1 - 2.5 kV CM (1) and DM (2)

Surges IEC 60255-22-5 - 1.2/50 µs ; 10/700 µs ; 2 kV CM (1);


IEC 61000-4-5 3 1 kV DM (2)

Power frequency for status inputs IEC 60255-22-7 - 300 V CM (1) ; 150 V DM (2)
IEC 61000-4-16 4

Safety
Safety tests
General IEC 60255-27 - -
Dielectric withstand at power frequency IEC 60255-5 - 2 kV 1 mn: logic input/outputs and supply,
IEC 60255-27 RS485 port
ANSI C37.90 - 1.5 kV ; 1 mn between open contacts
Surges 1.2/50 µs IEC 60255-5 5 kV for logic inputs and outputs
IEC 60255-27 3 kV for RS485 port
Insulation resistance IEC 60255-27 - 500 V CM (1) and DM (2)
R > 100 MWB ; R > 10 MWA

(1) CM : common mode


(2) DM : differential mode

19
Characteristics Environmental characteristics

Climatic withstand Standard Level / Class Value


In operation
Exposure to cold IEC 60068-2-1 Ad -40 °C (104 °F); 96 h
Exposure to dry heat IEC 60068-2-2 Bd +70 °C (158 °F); 96 h
Exposure to damp heat IEC 60068-2-78 Cab 93 % HR; 40 °C; 56 days
Salt mist IEC 60068-2-52 Kb/2 3 cycles of 24 hours each
Corrosive atmosphere / 2 gas test IEC 60068-2-60 Ke 21 days; 75 % HR; 25 °C (77 °F);
0.5 ppm H2S; 1 ppm SO2
Influence of corrosion/ 4 gas test IEC 60068-2-60 Method 3 21 days; 75 % HR; 25 °C (77 °F);
10+/-5 H2S; 200+/-20 SO2; 200+/-20
NO2; 10+/-5 CI2 (10-9 vol/vol)
EIA 364-65A IIIA 42 days; 75 % HR; 30 °C (86 °F);
100+/-20 H2S; 200+/-50 SO2; 200+/-50
NO2; 20+/-5 CI2 (10-9 vol/vol)
Storage in original packaging
Exposure to cold IEC 60068-2-1 - -40 °C (104 °F); 96 h
Exposure to dry heat IEC 60068-2-2 Bd +70 °C (158 °F); 96 h
Exposure to damp heat IEC 60068-2-78 Cab 93 % HR; 40 °C; 56 days
Temperature variation IEC 60068-2-14 Nb 5 °C/mn at -40...+70 °C (-40...+158 °F)

Mechanical robustness
In operation
Vibrations IEC 60255-21-1 2 1 Gn; 10...150 Hz; 1 cycle
Shocks IEC 60255-21-2 2 10 Gn for 11 ms
Earthquakes IEC 60255-21-3 2 2 Gn horizontal, 1 Gn vertical
De-energized
Vibrations IEC 60255-21-1 2 2 Gn; 10...150 Hz; 20 cycles
Shocks IEC 60255-21-2 2 30 Gn for 11 ms
Bumps IEC 60255-21-2 2 20 Gn for 16 ms
Enclosure protection
Front panel IEC 60529 IP54 -
NEMA 250 Type 12 -
Rear panel IEC 60529 IP40 -
Shocks IEC 62262 IK7 2 Joules
Fire resistance IEC 60695-2-11 - 650 °C

Certification Standard Reference document


Harmonized standard: EN 50263 Directives and amendments:
„„ 89/336/EEC Electromagnetic
Compatibility (EMC) Directive
‡‡ 92/31/EEC Amendment
‡‡ 93/68/EEC Amendment
„„ 73/23/EEC Low-Voltage Directive
‡‡ 93/68/CEE Amendment

20
Dimensions User-machine interface and
dimensions

User-machine interface
1  Back-lit display

DE53450_SE
2  Status LEDs
3  Fault LEDs
4  Button for Sepam reset and maximeter reset
5  Battery housing (Sepam series 10 A)
6  Protection cover for settings
7  Identification zone
8  Lead-seal accessory
9  Button for setting selection and confirmation
10  Buttons for selection in a menu
11  Button to cancel entry
12  Buttons for setting adjustments
13  Button for menu selection and LED test
14  Menu pictograms
15  Cursor for menu selection

Dimensions
DE53451_SE

Characteristics Applicable to Value


Dimensions series 10 • •• • 180 x 140 x 90 mm / 7.09" x 5.51" x 3.54"
Weight depending on series 10 N 1• • 1.15 kg/2.53 pounds
number of current inputs series 10 B 3• • 1.26 kg/2.78 pounds
series 10 A 4• • 1.46 kg/3.22 pounds
Type of battery series 10 A •• • 1/2 AA Li 3.6 V

21
Sensors Core balance CTs
CSH120, CSH200, GO110

Function
The specifically designed CSH120 and CSH200 core balance CTs are used for direct
residual current measurement. The only difference between them is the diameter.
PE50032

Due to their low voltage insulation, they may be used only on cables with earthed
shielding.

Characteristics
CSH120 CSH200 GO110
Inner diameter 120 mm (4.7 in) 200 mm (7.9 in) 110 mm (4.33 in)
Weight 0.6 kg (1.32 lb) 1.4 kg (3.09 lb) 3.2 kg (7.05 Ilb)
Accuracy ±5 % à 20 °C (68 °F) < 0,5 % (10...250 A)
±6 % max. from -25 °C to 70 °C < 1,5 % (10...250 A)
Core balance CTs CSH120 and CSH200. (-13 °F to +158 °F)
Transformation ratio 1/470
Maximum permissible current 20 kA - 1 s
Operating temperature -25 °C to +70 °C (-13 °Fto +158 °F)
Storage temperature -40 °C to +85 °C (-40 °F to +185 °F)

GO110 dimensions CSH120 and CSH200 dimensions


4 horizontal fixing 4 vertical fixing
holes, Diam. 5 mm holes, Diam. 5 mm
DE53440

DE53446

Dimensions A B D E F H J K L
CSH120 mm 120 164 44 190 76 40 166 62 35
in 4.72 6.46 1.73 7.48 2.99 1.57 6.54 2.44 1.38
CSH200 mm 200 256 46 274 120 60 257 104 37
in 7.87 10.1 1.81 10.8 4.72 2.36 10.1 4.09 1.46
GO110 mm 110 110 72 148 - 57 - - -
in 4.33 4.33 2.83 5.83 2.24

22
Power supply PS100 High-availability
power supply

PS100 backup power supply for MV/LV


PM100592

substations
Applications
The power supply unit supplies backup operating power for:
„„ MV switchgear motor mechanisms and circuit breaker coils
„„ Transmission equipment (e.g. radio)
„„ Control units such as RTU or Automatic Transfer System
„„ Protection relays, Fault Passage Indicators and others electronic devices
High availability power supply
A battery ensures uninterrupted operation of the whole substation in the event of
loss of the main supply. The backup power supply unit:
„„ Includes a regulated and temperature-compensated charger
„„ Stops the battery before deep discharge
„„ Carries out a battery check every 12 hours
Backup solution for MV switchgear power needs in „„ Measures battery ageing
the event of micro outages and power interruptions. „„ Forwards monitoring information via a Modbus communication port and output
„„ Easy maintenance with only one battery relays
„„ Battery remote monitoring
„„ High level of insulation to protect the electronic PS100 benefits
devices in harsh MV environments Only one battery
„„ Compliant with standards IEC 60 255-5 (10kV level) Traditional backup power supplies require a set of 2 or 4 batteries to produce 24V
or 48V, with complicated replacement and adjustment of the battery pack. The
PS100 needs only one battery, simplifying replacement. The battery is a standard
sealed lead-acid 12V battery with a 10-year service. It can be purchased easily,
anywhere in the world.
Improved availability of MV/LV substations
The PS100 is designed to ride through power network interruptions of up to 48
hours. It is associated with a battery selected to meet the required backup time.

+
For example, a 38Ah battery provides 12 hours of backup power supply to a SM6
switchboard including 4 Sepam units.
The PS100 protects and optimises the battery with state-of-the-art monitoring.
Battery PS100 A Modbus communication port forwards monitoring data to allow optimised
maintenance operations. Perfect integration with the Easergy range to control and
monitor your distribution network.
The PS100 stops supplying power and reserves an “additional Energy backup” to
PM102301

restart the installation after an extended power interruption.


The “additional Energy backup” can be enabled with a local push button to provide
energy for restarting the protection relays and operating the MV switchgear.
Withstands severe substation environments
The PS100 includes 10 kV insulation, electronic protection against overvoltage and
overloads, and automatic restart after a fault.

Main features
„„ DIN rail mounting for easy integration in any LV cabinet or MV/LV substation.
„„ 2 power supply outputs:
- 12Vdc - 18W permanent / 100W 20s (for modem, radio, RTU,etc.)
- 48Vdc or 24 Vdc - 300W /1 minute (for switchgear operating mechanism
motors) and 90W / permanent for protection relays, electronic devices, etc.
„„ RJ45 Modbus communication port
„„ 2 output relays (AC supply ON, Battery ON)
„„ Diagnostic with LEDs
„„ 1 sealed lead-acid 12V battery with a 10-year service life (from 7Ah to 40Ah)
„„ Power supply paralleling available with a 2nd PS100 to increase availability or to
provide additional power
„„ -40°C to +70°C operating temperature
„„ Dimensions : 125 x 165 x 160 mm (H x W x D mm)
References
PS100-24V EMS58580 Back-up Power supply
12V, 24V output
PS100-48V EMS58581 Back-up Power supply
12V, 48V output
Bat24AH EMS58582 Long life battery
12V - 24A.h
Bat38AH EMS58583 Long life battery
12V - 38A.h

23
Power supply PS100 High-availability
power supply

Power supply PS100-48V PS100-24V


Input AC voltage Rated ~ 110V to 240V, +10%, -15%
= 110V ,+20%, -20%
Limits 380 Vacdc
Protection Electronic protection against reversal polarity, over voltage and overloads short circuit.
Automatic restart after fault.
Output Vcc Voltage 48 Vdc ± 10% 24 Vdc ± 10%
Current 2 A rated 4 A rated
8 A for 15 s , 17 A peak for 50 16 A for 15 s , 25 A peak for 50 ms
ms
Power 90 W rated with/without battery
300 W (1 mn) with battery only
Protection Electronic protection. Automatic restart after fault
Limits without battery total outputs are limited to 90 W
Redundancy 2 units may be connected in parallel to increase availability or to provide additional power
Output 12V – radio Voltage 12Vdc -10% + 25%
Current 1.5A rated 8A 20s
Power 18W / 100W 20s
Protection By electronic
Limits A limitation, dedicated for radio units, is set up to avoid the battery discharge:
„„ 1,5A in emitting mode 3 mn, 8 A peak 20s each minute
„„ Limitation option can be disabled by communic
Battery system Battery (not include in the PS100) Battery system - no risk of explosion, no acid leakage and no servicing requirement
and connector (1m, included)
Battery recycling Batteries are exempt from the requirements of RoHS and WEEE, and they should be
labeled, collected and recycled under the provisions of the Battery Directive.
Battery capacity From 7Ah to 40Ah. 2 models are available: 24 Ah and 38 Ah.
For others models, see battery suppliers
Autonomy Depending on the load.
Average usage : up to 16h with 10 open/close of a switchgear
Battery monitoring „„ protection against serious discharge of the battery
„„ periodical battery tests
„„ indication of battery failure (short-circuit)
„„ indication of the available capacity by communication
Charge duration 10 h to 24 h (depending on the load)
Battery average service life 10 years
Energy Backup „„ Optional Energy Backup can be enabled with a local push button to provide energy for
restarting the protection relays at installation restart.
„„ Forecast backup reservation : 300 W - 1mm
Auxiliary contact 2 dry contact “battery ON” and “AC supply ON” (voltage presence)
Relay type – breaking capacity 2A 24V, 1A 48V , 0,15A 220V
Display
LEDs PS100 watch dog Status of unit
No AC supply AC supply outage
48V/24V ON 48V/24V output ON
12V ON 12V output ON
Battery fault Battery end of life : need to be replaced
Communication Modbus communication life indicator
Test – reset push button PS100 ON Operate a test of the battery
PS100 OFF Restart the Energy Backup after a long mains outage.
Communication & Monitoring
Protocol Modbus RS 485 - Configuration of Modbus address by means of rotary switch
Connector RJ45 2
DATA transmission status with date and time „„ AC supply voltage presence
„„ Battery state (disconnected, failure, available capacity, optional backup reservation)
„„ PS100 Global Status READY/Internal Fault
„„ 12 V and 48 V or 24 V output failure
„„ Threshold Serious discharge, threshold Energy Back up
„„ Charge indicator/ diagnosis information
„„ Reset
Setting „„ AC voltage loss threshold , DC Serious battery discharge threshold …
„„ Battery Test frequency
„„ Energy Back up enable/ disable
Command „„ Restart 12V / 48V (Energy Back up)
„„ Run led test
„„ Run battery test
Time stamped events 100 events
Characteristics (extracts)
Dielectric IEC 60 255-5 Insulation (50 Hz/1min) : 10 KV
Surge (1,2/50μs) : 20 KV
Electromagnetic (extract) IEC 61 000-4-4 (level 4) 4KV CM; 5kHz - 100 Khz
Climatic IEC 61 000-4-8 (level 5) 100A/m continuous; 1000 A/m 1 - 3s
Mechanical IEC 61 000-4-12 (level 3) 100kHz, 2kV CM, 1kV DM
-40°C +70°C Operating . -40°C +85°C Storage
Size 125x165x160 mmv(HxWxP)
Weight 2,6 kg
IEC 60 068-2-5 Vibration 10 to 500Hz : 2g
IEC 60529 IP 20 IK 7
NF C 13100 According to EDF specification
Battery size Bat24Ah : 125x175x166 (HxWxD)
Bat38Ah : 170x165x197 (HxWxD)
Safety IEC 60255-5
Energy efficiency ≥ 92%

24
Ordering information Sepam series 10

Catalogue numbers
Sepam series 10
Type Cat. no Quantity
Sepam series 10 N 11 A REL59817
Sepam series 10 N 11 E REL59819
Sepam series 10 N 13 A REL59818
Sepam series 10 N 13 E REL59820
Sepam series 10 B 31 A REL59800
Sepam series 10 B 31 E REL59801
Sepam series 10 B 41 A REL59802
Sepam series 10 B 41 E REL59805
Sepam series 10 B 42 A REL59803
Sepam series 10 B 42 E REL59806
Sepam series 10 B 43 A REL59804
Sepam series 10 B 43 E REL59807
Sepam series 10 A 41 A REL59808
Sepam series 10 A 41 E REL59811
Sepam series 10 A 41 F REL59814
Sepam series 10 A 42 A REL59809
Sepam series 10 A 42 E REL59812
Sepam series 10 A 42 F REL59815
Sepam series 10 A 43 A REL59810
Sepam series 10 A 43 E REL59813
Sepam series 10 A 43 F REL59816
Replacement parts
Type Cat. no Quantity
CCA 680 set of spare connectors REL59798
Core balance CTs
Type Cat. no Quantity
Split core balance CTs, dia. 110 mm GO110 50134
Core balance CTs, dia. 120 CSH120 59635
Core balance CTs, dia. 200 CSH200 59636

A Sepam series 10 catalogue number comprises different


elements:
Sepam series 10 X X X X

Range Sepam series 10

Model
Earth-fault protection N
Phase-overcurrent and earth-fault protection B
Phase-overcurrent and earth-fault protection,
A
logic inputs and communication port

Number of current inputs


1 earth-fault input 1
2 phase-current inputs + 1 earth-fault input 3
3 phase-current inputs + 1 earth-fault input 4

Sensitivity of earth-fault protection


Standard (0.1…24 Ino) (1) 1
Sensitive (0.01…2,4 Ino) (1) 2
High sensitivity (0.2…24 A and 2…240 A) (2) 3

Supply voltage
24…125 V DC and 100…120 V AC A
110…250 V DC and 100…240 V AC E
220…250 V DC and high-threshold logic inputs F
(1) Uses 1 A/5 A sensors.
(2) Uses CSH CTs.

25
Notes

26
Notes

27
ART.833133 © Schneider Electric Industries SAS - Tous droits réservés

Schneider Electric Industries SAS


35, rue Joseph Monier As standards, specifications and designs change from time
CS 30323 to time, please ask for confirmation of the information given
F - 92506 Rueil Malmaison Cedex (France) in this publication.
Tél. : +33 (0)1 41 29 70 00
RCS Nanterre 954 503 439 Design: Schneider Electric Industries SAS
Capital social 896 313 776 € Photos: Schneider Electric Industries SAS This document has been
www.schneider-electric.com Printed: Altavia Connexion - Made in France printed on recycled paper

SEPED307026EN /2 04-2012