Ducted Mini Split System

Range 1.5 TR to 6 TR
( 5 kW to 21 kW )

Bulletin # 068/2012
Supersedes Bulletin # 068/2010
SKM Ducted Mini Split Systems

Contents
Introduction .........................................2 Recommended Line Sizes................18
Legend................................................2 Typical Refrigeration Piping ..............19
Nomenclature .....................................3 Typical Wiring Diagram.....................21
Features & Specification............... 4-10 Dimensional Data .............................25
Combination Ratings ........................11 Outdoor Unit Clearance
Electrical Data ..................................13 and Spacing...............................28
Options .............................................15 Guide Specification...........................30
Fan Performance ..............................16

Legend
The following legends are used throughout
this manual: LADB .... Leaving Air Dry Bulb
LAWB ... Leaving Air Wet Bulb
AFR ...... Air Flow Rate lbs ......... Pounds weight (British units)
cfm ....... Cubic feet per minute l/s .......... Liters per second
dB ........ Decibels Mbh ...... 1000 Btuh
EADB .... Entering Air Dry Bulb OD ........ Outside Diameter
EAWB .... Entering Air Wet Bulb Ph ......... Phase
ET ......... Evaporating Temperature Pa ......... Pascals
Hz ........ Hertz SC ........ Sensible Capacity
kW ........ Kilowatts TC ......... Total Capacity
kg ......... Kilograms TR ........ Tons of refrigeration = 12 MBH
kPa ...... Kilo Pascals V ........... Volts

Introduction
The Ducted Mini Split system from SKM consists of RXV (a high efficiency- TOP discharge Air Cooled
Condensing Unit); and RXH-DC (a high efficiency-SIDE Discharge Air cooled Condensing Unit) matching with
DCYP (a low noise, ceiling suspended indoor fan coil unit). This split systems are ideally suited for apartments,
houses, offices, shops, small residences, and in small commercial establishments.

SKM ducted mini split system are available in different models covering 1.5 TR to 6 TR (5 kW to 21 kW) at
nominal AHRI condition, which make them ideally suited for a very small foot print for space saving and a
pleasant exterior appearance.

SKM ducted mini split units are suitable to operate in a wide range of ambient temperature.

SKM ducted mini split units are internally wired and all that required to be done on site is ducting, refrigerant
piping, power supply and suitable room thermostat installation and field wiring, which reduces the installation
work and consequently keeps to a minimum cost.

SKM Ducted Mini Split Air Conditioning Units are:

Built in the Gulf... For the World.

2 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

NOMENCLATURE
OUTDOOR ( TOP DISCHARGE AIR COOLED CONDENSING UNIT )
R X V - 020- Y
S1: 220-240V/1Ph/50Hz
Remote Air Cooled Condenser Y: 380-415V/3Ph/50Hz

Direct Expansion

Vertical Discharge Nominal Capacity in Mbh

OUTDOOR ( TOP DISCHARGE AIR COOLED CONDENSING UNIT )


R X V - 021- R
S2: 220V/1Ph/60Hz
Remote Air Cooled Condenser R: 380V/3Ph/60Hz
T: 220-230V/3Ph/60Hz
Direct Expansion

Vertical Discharge Nominal Capacity in Mbh

OUTDOOR ( SIDE DISCHARGE AIR COOLED CONDENSING UNIT )


R X H - 020 - 5 D C
Remote Air Cooled Condenser
Direct Expansion C = Cooling only
Horizontal Discharge

Matching to Ducted Indoor Units

Power Supply 5 : 50 Hz
Nominal Capacity in MBh
Frequency 6 : 60 Hz

INDOOR UNIT
FCU - DCY P - 12 / 4 / X G
G=Galvanised Finish
Fan Coil Unit F=Painted FInish

Type of cooling coil: X = DX coil,


Direct Drive

No. of rows for cooling coil


P : Ceiling suspended with plenum (3 or 4 rows)

Unit size nom. x 100 cfm


(06,08,10,12,15,18, & 21)

Air Conditioning Equipment . Built in the Gulf... for the World 3


SKM Ducted Mini Split Systems

VERTICAL DISCHARGE AIR COOLED CONDENSING UNIT - RXV

Design Features: (Air Cooled units up to 6.0 Tons of Refrigeration)

• Design - Outdoor condensing units are ideal for rooftop or ground installation. Units have a pleasant exterior appearance
and have a very small footprint for space saving installation.

• High efficiency Coils - 3/8” OD Hi-x tubes; mechanically bonded to hi-efficiency aluminium fins to match for a maximum
efficiency.

• Hermetic Compressor - High efficiency hermetically sealed compressor located on engineered mounts for safe, quiet and
vibration free operation.Compresssors are selected for reliability and power efficiency.

• Cabinet Construction - Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.

• High Efficiency Fan Motor – Permanently lubricated fan motor and is precisely matched to a metal propeller type Fan
blades which provides a maximum efficiency.

• Brass Service Valves – Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.

• Ease of Service and Installation – Designed to make servicing easier for the contractor, access panels are provided
for all controls and the compressor from the side of the unit.

• Compressor Short Cycling Protection – To protect the compressor against rapid short cycling.

• High and Low Pressure Protection - To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.

4 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems
SPECIFICATION (RXV - VERTICAL DISCHARGE CONDENSING UNITS) - 50HZ
Model RXV 020 025 030 040 045 050 060 070
(1) MBh 18.5 23.7 28.7 32.5 41.0 50.9 59.9 61.3
Cooling Capacity
kW 5.4 6.9 8.4 9.5 12.0 14.9 17.6 18.0
(2) MBh 16.6 21.4 26.1 29.3 37.8 47.4 55.2 56.7
Cooling Capacity
kW 4.9 6.3 7.6 8.6 11.1 13.9 16.2 16.6
Power Supply V / Ph / Hz 220-240/1/50 380-415/3/50
Type - Reciprocating Scroll
Compressor
Qty. - 1 1 1 1 1 1 1 1
Type Waffle Louver Fins and Inner Grooved tubes 3/8"OD
Coil ft² 8 12 16 16 16 16 16 16
Face Area
m² 0.74 1.11 1.49 1.49 1.49 1.49 1.49 1.49
Condenser

Type Propeller,Direct Drive


Blade Dia. / Qty 460 / 1 460 / 1 460 / 1 460 / 1 560 / 1 560 / 1 560 / 1 560 / 1
Fan
cfm 2100 2170 2200 2200 4420 4350 4350 4350
Air Flow
l/s 991 1024 1038 1038 2086 2053 2053 2053
Type TEAO (Totally Enclosed Air Over) Motor
Motor
Size Watts 100 100 100 100 250 250 250 250
Refrigerant Operating Charge (R-22) lbs / kg 2.43 / 1.10 3.11 / 1.41 3.87 / 1.76 4.11 / 1.86 4.25/ 1.93 6.93 / 3.14 7.09 / 3.21 7.54 / 3.42
Unit Approximate Weight lbs / kg 202 / 92 202 / 92 221 / 100 228 / 103 242 / 110 277 / 125 277 / 125 284 / 129
Width 23 23 26 26 29 29 29 29
Dimensions (inches) Depth 23 23 26 26 29 29 29 29
Height 25 33 37 37 33 33 33 33
Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Pack valves Connections (inches)
Suction 5/8 5/8 5/8 3/4 3/4 3/4 3/4 7/8

SPECIFICATION (RXV - VERTICAL DISCHARGE CONDENSING UNITS) - 60HZ


Model RXV 021 026 031 041 046 051 061 071

(1) MBh 20.3 23.3 29.6 35.2 48.4 56.3 66.6 68.5
Cooling Capacity
kW 5.9 6.8 8.7 10.3 14.2 16.5 19.5 20.1
MBh 18.3 20.8 26.9 31.7 44.7 52.6 62.0 63.8
Cooling Capacity (2)
kW 5.4 6.1 7.9 9.3 13.1 15.4 18.2 18.7
380/3/60Hz
Power Supply V / Ph / Hz 220/1/60Hz
220/3/60Hz
Type - Reciprocating Scroll
Compressor
Qty. - 1 1 1 1 1 1 1 1
Type Waffle Louver Fins and Inner Grooved tubes 3/8"OD
Coil ft² 8 12 16 16 16 16 16 16
Face Area
m² 0.74 1.11 1.49 1.49 1.49 1.49 1.49 1.49
Type Propeller,Direct Drive
Condenser

Blade Dia. / Qty 460 / 1 460 / 1 460 / 1 460 / 1 560 / 1 560 / 1 560 / 1 560 / 1
Fan
cfm 2310 2350 2370 2370 5450 5340 5340 5340
Air Flow
l/s 1090 1109 1118 1118 2572 2520 2520 2520
Type TEAO (Totally Enclosed Air Over) Motor
Motor
Size Watts 100 100 100 100 370 370 370 370
Refrigerant Operating Charge (R-22) lbs / kg 2.43 / 1.10 3.11 / 1.41 3.87 / 1.76 4.11 / 1.86 4.25/ 1.93 6.93 / 3.14 7.09 / 3.21 7.54 / 3.42
Unit Approximate Weight lbs / kg 202 / 92 202 / 92 221 / 100 228 / 103 242 / 110 277 / 125 277 / 125 284 / 129
Width 23 23 26 26 29 29 29 29
Dimensions (inches) Depth 23 23 26 26 29 29 29 29
Height 25 33 37 37 33 33 33 33
Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Pack valves Connections (inches)
Suction 5/8 5/8 5/8 3/4 3/4 3/4 3/4 7/8

Notes: 1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry
bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb.
2. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of
115ºF (46ºC) dry bulb..

Air Conditioning Equipment . Built in the Gulf... for the World 5


SKM Ducted Mini Split Systems

SIDE DISCHARGE AIR COOLED CONDENSING UNIT - RXH-DC

Design Features: (Air cooled units up to 5 Tons of Refrigeration)

• Design - Outdoor condensing units with side discharge air delivery are ideal for rooftop or ground installation and ledge
installation. This unit has a pleasant exterior aesthetic design and has a very small footprint for space saving installation.

• High Efficiency Coils – 3/8” O.D. inner grooved copper tubes with mechanically bonded to aluminium corrugated fins to
attain maximum efficiency.

• Compressor – Uses high efficiency rotary or scroll hermetic compressor located on engineered mounts for safe, quite and
vibration free operation.

• Cabinet Construction- Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.

• Brass Service Valves – Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.

• High efficiency fan motor – permanently lubricated fan motor and it is precisely matched to plastic propeller type blades
which provides a maximum efficiency.

• Ease of service and installation – designed to make servicing easier for the contractor; access panel are also provided
for all controls from the side of the unit.

• Electronic control board for all models.

• Compressor Short Cycling Protection – To protect the compressor against rapid short cycling.

• High and Low Pressure Protection – To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.

6 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems
SPECIFICATION (RXH - SIDE DISCHARGE CONDENSING UNIT) - 50HZ
Model RXH 020 - 5DC 025 - 5DC 030 - 5DC 040 - 5DC 045 - 5DC 050 - 5DC 060 - 5DC
MBh 18.0 24.3 30.4 36.5 42.8 49.5 58.6
Nominal Cooling Capacity
kW 5.3 7.1 8.9 10.7 12.5 14.5 17.2
Power Supply V / Ph / Hz 220-240/1/50 380-415/3/50
Type Rotary Scroll
Compressor
Qty. 1 1 1 1 1 1 1
Coil Type Hydrophilic aluminium Corrugated Fin and Innergroved Copper Tube
Type Propeller Direct Drive
Qty 1 1 1 1 1 2 2
Condenser

Fan
cfm 1766 1766 2510 2510 3414 3902 3902
Air Flow
l/s 833 833 1185 1185 1611 1841 1841
Type TEAO (Totally Enclosed Air Over) Motor
Motor Size Watts 55 53 75 75 190 65 65
Qty 1 1 1 1 1 2 2
Type R-22
Refrigerant Operating Charge
kg 1 1.4 1.9 2.1 2.5 2.8 3.2
Unit Approximate Weight kg 42 49 62 84 97 99 103
Width 33.1 33.1 35.2 35.2 39.0 35.4 35.4
Dimensions (inches) Depth 12.8 12.8 12.3 12.3 13.9 13.4 13.4
Height 27.4 27.4 33.9 33.9 38.0 46 46
Liquid 1/4 3/8 3/8 3/8 3/8 3/8 3/8
Pack valves Connections (inches)
Suction 1/2 5/8 5/8 3/4 3/4 3/4 3/4

SPECIFICATION (RXH - SIDE DISCHARGE CONDENSING UNIT) - 60HZ


Model RXH 020 - 6DC 025 - 6DC 030 - 6DC 040 - 6DC 045 - 6DC 050 - 6DC 060 - 6DC
MBh 19.7 23.5 31.7 35.2 47.4 48.6 57.0
Nominal Cooling Capacity
kW 5.8 6.9 9.3 10.3 13.9 14.2 16.7
Power Supply V / Ph / Hz 220/1/60
Type Rotary Scroll
Compressor
Qty. 1 1 1 1 1 1 1
Coil Type Hydrophilic aluminium Corrugated Fin and Innergroved Copper Tube
Type Propeller Direct Drive
Qty 1 1 1 1 1 2 2
Fan
Condenser

cfm 2001 2001 2825 2825 3414 3531 3561


Air Flow
l/s 944 944 1333 1333 1611 1666 1681
Type TEAO (Totally Enclosed Air Over) Motor
Motor Size Watts 47 53 100 100 190 65 65
Qty 1 1 1 1 1 2 2
Type R-22
Refrigerant Operating Charge
kg 1 1.45 1.9 2.1 2.5 2.8 3
Unit Approximate Weight kg 39 48 61 65 100 104 107
Width 33.1 33.1 35.2 35.2 39.0 35.4 35.4
Dimensions (inches) Depth 12.8 12.8 12.3 12.3 13.9 13.4 13.4
Height 27.4 27.4 33.9 33.9 38.0 46 46
Liquid 1/4 3/8 3/8 3/8 3/8 3/8 3/8
Pack valves Connections
Suction 1/2 5/8 5/8 3/4 3/4 3/4 3/4
Notes: Nominal cooling capacity is based on 80/67°F (27/19.5°C) dry bulb/wet bulb evaporator entering air temperature and 95°F
(35°C) condenser entering air temperature.

Air Conditioning Equipment . Built in the Gulf... for the World 7


SKM Ducted Mini Split Systems

INDOOR UNIT - DCYP

Design and Features

• High efficiency coil with high efficiency wavy corrugated fins.

• High efficiency, low power consumption PSC electric motor.

• High efficiency forward curved fan for quiet operation.

• Heavy gauge galvanized casing and fan housing. Hot dip is standard.

• Insulated heavy gauge drain pan.

• Isolating grommet for an additional vibration isolation.

• Easy wiring / electrical and piping connections.

• Evaporator coils equipped with plain tubes and aluminium fins which give high capacity sensible and latent cooling capabilities.

• Equipped with refrigerant flow control – orifice or expansion valve.

8 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems
SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXV) - 50HZ
Indoor Unit DCYP 06 08 10 12 15 18 21 21
Matched Outdoor Unit RXV 020 025 030 040 045 050 060 070
(1)
Mbh 18.5 23.7 28.7 32.5 41.0 50.9 59.9 61.3
Cooling Capacity
kW 5.4 6.9 8.4 9.5 12.0 14.9 17.6 18.0
(2)
Mbh 16.6 21.4 26.1 29.3 37.8 47.4 55.2 56.7
Cooling Capacity
kW 4.9 6.3 7.6 8.6 11.1 13.9 16.2 16.6
cfm 686 785 1061 1331 1536 1914 2200 2200
Nominal Air Flow Rate
l/s 324 370 501 628 725 903 1038 1038
Type Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
No. Of Row / FPI # 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12
inch 12 12 16 12 12 16 16 16
Height
mm 305 305 406 305 305 406 406 406
Coil
inch 20 24 24 36 42 42 48 48
Length
mm 508 610 610 914 1067 1067 1219 1219
ft2 1.67 2.00 2.67 3.00 3.50 4.67 5.33 5.33
Face Area 2
m 0.15 0.19 0.25 0.28 0.33 0.43 0.50 0.50
Metering Device Type Orifice Expansion valve
Type Double Inlet Double Width Centrifugal Forward Curve Direct Drive
Fan Code 7-7 7-7 9-7 7-7 7-7 9-7 9-7 9-7
Quantity # 1 1 1 2 2 2 2 2
Type 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2 2
inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2
Liquid Ø
mm 9.5 9.5 9.5 9.5 12.7 12.7 12.7 12.7
Connection Sizes
inch 5/8 5/8 5/8 5/8 7/8 1 1/8 1 1/8 1 1/8
Suction Ø
mm 15.8 15.8 15.8 15.8 22.2 28.5 28.5 28.5
lbs. 60 67 82 87 109 134 141 141
Unit Approximate Weight
Kg. 27.3 30.5 37.3 39.5 49.5 60.9 64.1 64.1

SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXV) - 60HZ


Indoor Unit DCYP 06 08 10 12 15 18 21 21
Matched Outdoor Unit RX V 021 026 031 041 046 051 061 071
MBh 20.3 23.3 29.6 35.2 48.4 56.3 66.6 68.5
Cooling Capacity (1)
kW 5.9 6.8 8.7 10.3 14.2 16.5 19.5 20.1
MBh 18.3 20.8 26.9 31.7 44.7 52.6 62.0 63.8
Cooling Capacity (2)
kW 5.4 6.1 7.9 9.3 13.1 15.4 18.2 18.7
cfm 583 735 984 1147 1450 1804 2190 2190
Nominal Air Flow Rate
l/s 275 347 464 541 684 851 1034 1034
Type Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
No. Of Row / FPI # 4 / 12 3 / 12 3 / 12 3 / 12 4 / 12 3 / 12 3 / 12 3 / 12
inch 12 12 16 12 12 16 16 16
Height
mm 305 305 406 305 305 406 406 406
Coil
inch 20 24 24 36 42 42 48 48
Length
mm 508 610 610 914 1067 1067 1219 1219
ft2 1.67 2.00 2.67 3.00 3.50 4.67 5.33 5.33
Face Area
m2 0.15 0.19 0.25 0.28 0.33 0.43 0.50 0.50
Metering Device Type Orifice Expansion valve
Type Double Inlet Double Width Centrifugal Forward Curve Direct Drive
Fan Code 7-7 7-7 9-7 7-7 7-7 9-7 9-7 9-7
Quantity # 1 1 1 2 2 2 2 2
Type 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2 2
inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2
Liquid Ø
mm 9.5 9.5 9.5 9.5 12.7 12.7 12.7 12.7
Connection Sizes
inch 5/8 5/8 5/8 5/8 7/8 1 1/8 1 1/8 1 1/8
Suction Ø
mm 15.8 15.8 15.8 15.8 22.2 28.5 28.5 28.5
lbs. 63 67 82 87 114 134 141 141
Unit Approximate Weight
Kg. 28.6 30.5 37.3 39.5 51.8 60.9 64.1 64.1

Notes: (1). Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC)
dry bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb.
(2). Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature
of 115ºF (46ºC) dry bulb.

Air Conditioning Equipment . Built in the Gulf... for the World 9


SKM Ducted Mini Split Systems
SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXH-DC) - 50H
HZ
Indoor Unit DCYP 06 08 10 12 15 18 21
Matched Outdoor Unit RXH 020-5DC 025-5DC 030-5DC 040-5DC 045-5DC 050-5DC 060-5DC
MBh 18.0 24.3 30.4 36.5 42.8 49.5 58.6
Nominal Cooling Capacity
kW 5.3 7.1 8.9 10.7 12.5 14.5 17.2
cfm 686 785 1061 1331 1536 1914 2200
Nominal Air Flow Rate
l/s 324 370 501 628 725 903 1038
Type Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
No. Of Row / FPI # 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12 3 / 12
inch 12 12 16 12 12 16 16
Height
mm 305 305 406 305 305 406 406
Coil
inch 20 24 24 36 42 42 48
Length
mm 508 610 610 914 1067 1067 1219
ft2 1.67 2.00 2.67 3.00 3.50 4.67 5.33
Face Area 2
m 0.15 0.19 0.25 0.28 0.33 0.43 0.50
Metering Device Type Orifice
Type Double Inlet Double Width Centrifugal Forward Curve Direct Drive
Fan Code 7-7 7-7 9-7 7-7 7-7 9-7 9-7
Quantity # 1 1 1 2 2 2 2
Type 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2
inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2
Liquid Ø
mm 9.5 9.5 9.5 9.5 12.7 12.7 12.7
Connection Sizes
inch 5/8 5/8 5/8 5/8 7/8 1 1/8 1 1/8
Suction Ø
mm 15.8 15.8 15.8 15.8 22.2 28.5 28.5
lbs. 60 67 82 87 109 134 141
Unit Approximate Weight
Kg. 27.3 30.5 37.3 39.5 49.5 60.9 64.1

SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXH-DC) - 60HZ


Indoor Unit DCYP 06 08 10 12 15 18 21
Matched Outdoor Unit RXH 020-6DC 025-6DC 030-6DC 040-6DC 045-6DC 050-6DC 060-6DC
MBh 19.7 23.5 31.7 35.2 47.4 48.6 57.0
Nominal Cooling Capacity
kW 5.8 6.9 9.3 10.3 13.9 14.2 16.7
cfm 583 735 984 1147 1450 1804 2190
Nominal Air Flow Rate
l/s 275 347 464 541 684 851 1034
Type Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
No. Of Row / FPI # 4 / 12 3 / 12 3 / 12 3 / 12 4 / 12 3 / 12 3 / 12
inch 12 12 16 12 12 16 16
Height
mm 305 305 406 305 305 406 406
Coil
inch 20 24 24 36 42 42 48
Length
mm 508 610 610 914 1067 1067 1219
ft2 1.67 2.00 2.67 3.00 3.50 4.67 5.33
Face Area 2
m 0.15 0.19 0.25 0.28 0.33 0.43 0.50
Metering Device Type Orifice
Type Double Inlet Double Width Centrifugal Forward Curve Direct Drive
Fan Code 7-7 7-7 9-7 7-7 7-7 9-7 9-7
Quantity # 1 1 1 2 2 2 2
Type 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2
inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2
Liquid Ø
mm 9.5 9.5 9.5 9.5 12.7 12.7 12.7
Connection Sizes
inch 5/8 5/8 5/8 5/8 7/8 1 1/8 1 1/8
Suction Ø
mm 15.8 15.8 15.8 15.8 22.2 28.5 28.5
lbs. 63 67 82 87 114 134 141
Unit Approximate Weight
Kg. 28.6 30.5 37.3 39.5 51.8 60.9 64.1

Notes: • Nominal cooling capacities are based on the following conditions: Evaporator entering air of 80/67ºF (27/19.5ºC) dry
bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC).

10 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Combination Ratings - RXV and DCYP Units


Capacity Ratings 50Hz - High Speed
Air on coil Temperature DB/WB-80/67°F (26.6/19.4°C) Air on coil Temperature DB/WB-76/63°F (24.4/17.2°C)
Outdoor Indoor Indoor Unit
ESP Ambient(Condenser Entering Air)Temperature Ambient(Condenser Entering Air)Temperature
Unit Unit Air Flow Rate
95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C) 95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
RXV DCYP CFM in.wg (Pa)
MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW
020 06/30 686 0.1 (25) 18.5 13.9 1.8 17.6 13.6 1.9 16.6 13.2 2.0 16.1 13.0 2.1 17.1 14.0 1.8 16.3 13.6 1.9 15.4 13.3 2.0 14.9 13.1 2.0
025 06/40 680 0.1 (25) 23.9 16.7 2.5 22.7 16.2 2.6 21.5 15.8 2.8 20.9 15.5 2.9 22.3 16.8 2.4 21.2 16.4 2.5 20.0 15.9 2.7 19.4 15.6 2.8
025 08/30 785 0.1 (25) 23.7 16.9 2.5 22.6 16.5 2.6 21.4 16.1 2.8 20.8 15.9 2.9 22.2 17.1 2.4 21.1 16.6 2.5 19.9 16.2 2.7 19.3 15.9 2.8
030 08/40 777 0.1 (25) 27.2 19.1 2.7 26.0 18.6 2.8 24.7 18.1 3.0 24.1 17.9 3.1 25.4 19.2 2.6 24.2 18.7 2.7 22.9 18.2 2.9 22.3 18.0 3.0
030 10/30 1061 0.1 (25) 28.7 21.6 2.7 27.4 21.1 2.9 26.1 20.7 3.1 25.4 20.4 3.2 26.6 21.7 2.6 25.4 21.2 2.8 24.0 20.7 3.0 23.4 20.5 3.1
040 10/40 1046 0.1 (25) 32.5 24.1 2.5 30.9 23.5 2.7 29.3 22.9 3.0 28.4 22.6 3.1 30.2 24.2 2.5 28.7 23.6 2.6 27.1 23.0 2.8 26.3 22.7 2.9
040 12/30 1331 0.1 (25) 32.5 25.5 2.5 30.9 25.0 2.7 29.3 24.4 3.0 28.4 24.1 3.1 30.2 25.7 2.5 28.7 25.1 2.6 27.1 24.6 2.8 26.3 24.3 2.9
045 12/40 1317 0.1 (25) 41.5 30.3 3.3 39.9 29.7 3.7 38.3 29.1 4.1 37.5 28.8 4.3 38.9 30.6 3.2 37.3 30.0 3.6 35.7 29.4 4.1 35.0 29.1 4.3
045 15/30 1536 0.1 (25) 41.0 30.8 3.3 39.4 30.2 3.7 37.8 29.7 4.1 37.1 29.4 4.3 38.4 31.1 3.2 36.9 30.5 3.6 35.3 29.9 4.0 34.6 29.6 4.2
050 15/40 1519 0.1 (25) 49.5 35.6 3.5 47.8 35.0 3.9 46.1 34.3 4.4 45.2 34.0 4.6 46.3 36.0 3.4 44.7 35.3 3.9 43.0 34.6 4.3 42.1 34.3 4.6
050 18/30 1914 0.1 (25) 50.9 38.6 3.5 49.2 37.9 3.9 47.4 37.3 4.4 46.4 37.0 4.7 47.6 38.9 3.4 45.9 38.3 3.9 44.1 37.6 4.4 43.3 37.2 4.6
060 18/40 1882 0.1 (25) 60.6 44.1 4.3 58.3 43.2 4.9 55.8 42.3 5.5 54.7 41.8 5.8 56.6 44.5 4.2 54.3 43.5 4.8 51.9 42.6 5.4 50.8 42.1 5.7
060 21/30 2200 0.1 (25) 59.9 44.8 4.3 57.6 43.9 4.9 55.2 43.1 5.5 54.0 42.7 5.8 55.9 45.2 4.2 53.7 44.3 4.8 51.3 43.4 5.4 50.2 42.9 5.7
070 21/30 2200 0.1 (25) 61.3 45.3 4.5 59.0 44.5 5.2 56.7 43.6 5.8 55.6 43.2 6.1 57.3 45.7 4.4 55.1 44.9 5.1 52.8 44.0 5.8 51.7 43.5 6.1
070 21/40 2150 0.1 (25) 65.1 48.8 4.6 62.7 47.9 5.3 60.1 46.9 5.9 58.9 46.5 6.2 60.8 49.2 4.5 58.4 48.3 5.2 56.0 47.3 5.8 54.8 46.8 6.1

Capacity Ratings 50Hz - Medium Speed


Air on coil Temperature DB/WB-80/67°F (26.6/19.4°C) Air on coil Temperature DB/WB-76/63°F (24.4/17.2°C)
Outdoor Indoor Indoor Unit
ESP Ambient(Condenser Entering Air)Temperature Ambient(Condenser Entering Air)Temperature
Unit Unit Air Flow Rate
95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C) 95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
RXV DCYP CFM in.wg (Pa)
MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW
020 06/30 501 0.2 (50) 17.3 11.9 1.8 16.5 11.6 1.9 15.6 11.2 2.0 15.2 11.1 2.0 16.0 11.9 1.7 15.3 11.6 1.8 14.5 11.3 1.9 14.0 11.1 1.9
025 08/40 587 0.2 (50) 23.7 15.9 2.5 22.5 15.4 2.6 21.3 14.9 2.8 20.7 14.7 2.9 22.1 16.0 2.4 21.0 15.5 2.5 19.8 15.0 2.7 19.2 14.8 2.8
030 10/30 730 0.2 (50) 26.6 17.9 2.6 25.4 17.5 2.8 24.1 17.0 3.0 23.5 16.8 3.1 24.8 18.1 2.5 23.6 17.6 2.7 22.4 17.1 2.9 21.8 16.9 3.0
040 10/40 728 0.2 (50) 29.6 19.8 2.4 28.3 19.3 2.6 26.9 18.7 2.8 26.2 18.5 2.9 27.6 20.0 2.4 26.3 19.4 2.5 24.9 18.9 2.7 24.2 18.6 2.8
040 12/30 990 0.2 (50) 30.8 22.0 2.5 29.3 21.5 2.7 27.8 20.9 2.9 27.1 20.6 3.0 28.6 22.2 2.4 27.2 21.6 2.6 25.8 21.0 2.8 25.1 20.7 2.9
045 12/40 982 0.2 (50) 38.8 26.1 3.2 37.4 25.5 3.6 35.9 24.9 4.1 35.2 24.6 4.3 36.4 26.4 3.1 35.0 25.8 3.6 33.6 25.2 4.0 32.8 24.9 4.2
045 15/30 1202 0.2 (50) 39.3 27.3 3.2 37.8 26.8 3.6 36.3 26.2 4.1 35.6 25.9 4.3 36.8 27.7 3.1 35.4 27.1 3.6 33.9 26.5 4.0 33.2 26.2 4.2
050 15/40 1194 0.2 (50) 46.8 31.5 3.4 45.2 30.9 3.9 43.6 30.2 4.3 42.8 29.9 4.6 43.8 31.8 3.4 42.3 31.2 3.8 40.7 30.5 4.3 39.9 30.2 4.5
050 18/30 1430 0.2 (50) 48.3 33.4 3.4 46.7 32.8 3.9 45.0 32.2 4.4 44.1 31.9 4.6 45.2 33.8 3.4 43.6 33.1 3.8 42.0 32.5 4.3 41.1 32.1 4.6
060 18/40 1422 0.2 (50) 56.6 38.1 4.2 54.5 37.2 4.8 52.3 36.3 5.4 51.2 35.9 5.7 52.9 38.4 4.2 50.9 37.6 4.8 48.7 36.6 5.4 47.6 36.2 5.7
060 21/30 1636 0.2 (50) 56.6 38.7 4.2 54.5 37.9 4.8 52.2 37.1 5.4 51.1 36.7 5.7 52.8 39.1 4.2 50.8 38.3 4.8 48.6 37.4 5.4 47.5 37.0 5.7
070 21/30 1636 0.2 (50) 57.9 39.2 4.4 55.8 38.4 5.1 53.6 37.6 5.8 52.6 37.2 6.1 54.2 39.7 4.4 52.1 38.8 5.0 50.0 38.0 5.7 48.9 37.5 6.0
070 21/40 1626 0.2 (50) 61.1 42.1 4.5 58.9 41.2 5.2 56.6 40.3 5.8 55.4 39.9 6.1 57.1 42.5 4.4 54.9 41.6 5.1 52.7 40.6 5.7 51.5 40.2 6.1

Capacity Ratings 60Hz - High Speed


Air on coil Temperature DB/WB-80/67°F (26.6/19.4°C) Air on coil Temperature DB/WB-76/63°F (24.4/17.2°C)
Outdoor Indoor Indoor Unit
ESP Ambient(Condenser Entering Air)Temperature Ambient(Condenser Entering Air)Temperature
Unit Unit Air Flow Rate
95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C) 95°F (35°C) 105°F (41°C) 115°F (46°C) 120°F (49°C)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
RXV DCYP CFM in.wg (Pa)
MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW MBh MBh kW
021 06/30 581 0.1 (25) 18.9 13.2 1.9 17.9 12.8 2.0 17.0 12.4 2.2 16.5 12.3 2.2 17.6 13.3 1.8 16.6 12.9 2.0 15.6 12.5 2.1 15.1 12.3 2.2
021 06/40 583 0.1 (25) 20.3 14.3 2.0 19.3 14.0 2.1 18.3 13.6 2.3 17.8 13.4 2.3 18.8 14.4 1.9 17.7 14.0 2.0 16.7 13.6 2.2 16.2 13.3 2.2
026 06/40 583 0.1 (25) 22.9 15.4 2.2 21.7 14.9 2.3 20.4 14.4 2.4 19.8 14.1 2.5 21.4 15.5 2.1 20.2 15.0 2.2 18.9 14.5 2.4 18.3 14.2 2.4
026 08/30 735 0.1 (25) 23.3 16.4 2.2 22.1 15.9 2.4 20.8 15.4 2.5 20.2 15.2 2.6 21.8 16.5 2.2 20.6 16.0 2.3 19.3 15.5 2.4 18.6 15.3 2.4
031 08/40 732 0.1 (25) 28.1 19.0 3.0 26.8 18.5 3.1 25.6 18.0 3.2 24.9 17.7 3.3 26.2 19.2 2.9 25.0 18.6 3.0 23.7 18.1 3.1 23.1 17.9 3.2
031 10/30 984 0.1 (25) 29.6 21.3 3.1 28.2 20.8 3.2 26.9 20.3 3.3 26.2 20.0 3.4 27.6 21.5 2.9 26.3 20.9 3.1 25.0 20.4 3.2 24.3 20.1 3.3
041 10/40 986 0.1 (25) 35.7 24.7 3.2 33.9 24.0 3.4 32.2 23.4 3.6 31.3 23.1 3.7 33.2 24.9 3.1 31.5 24.2 3.3 29.8 23.5 3.4 29.0 23.2 3.6
041 12/30 1147 0.1 (25) 35.2 25.0 3.2 33.5 24.4 3.4 31.7 23.7 3.6 30.9 23.4 3.7 32.7 25.2 3.1 31.1 24.5 3.2 29.4 23.9 3.4 28.6 23.5 3.5
046 12/40 1150 0.1 (25) 44.8 30.0 3.9 43.1 29.3 4.4 41.4 28.7 4.9 40.6 28.4 5.1 42.0 30.4 3.8 40.4 29.7 4.3 38.7 29.0 4.8 37.9 28.7 5.0
046 15/40 1450 0.1 (25) 48.4 34.5 4.0 46.5 33.8 4.5 44.7 33.1 4.9 43.8 32.8 5.1 45.3 34.9 3.9 43.5 34.2 4.4 41.7 33.4 4.9 40.8 33.1 5.1
051 15/40 1450 0.1 (25) 54.4 36.9 4.2 52.7 36.2 4.7 50.9 35.5 5.2 50.0 35.1 5.5 50.8 37.2 4.1 49.2 36.5 4.6 47.4 35.8 5.2 46.6 35.4 5.4
051 18/30 1804 0.1 (25) 56.3 39.7 4.2 54.5 39.0 4.7 52.6 38.3 5.3 51.6 37.9 5.6 52.5 40.1 4.1 50.8 39.4 4.6 49.0 38.6 5.2 48.0 38.2 5.5
061 18/40 1807 0.1 (25) 66.9 45.8 5.2 64.7 44.9 5.9 62.4 44.1 6.6 61.2 43.6 7.0 62.7 46.4 5.1 60.5 45.4 5.8 58.2 44.5 6.6 57.0 44.0 6.9
061 21/30 2190 0.1 (25) 66.6 47.2 5.2 64.3 46.3 5.9 62.0 45.5 6.6 60.9 45.1 7.0 62.4 47.7 5.1 60.1 46.8 5.8 57.8 45.9 6.6 56.7 45.4 6.9
071 18/40 1807 0.1 (25) 68.9 46.6 5.5 66.6 45.7 6.2 64.2 44.7 7.0 63.0 44.3 7.3 64.6 47.2 5.4 62.3 46.2 6.1 60.0 45.2 6.9 58.8 44.7 7.2
071 21/30 2190 0.1 (25) 68.5 47.9 5.5 66.2 47.0 6.2 63.8 46.1 6.9 62.6 45.7 7.3 64.3 48.5 5.3 62.0 47.6 6.1 59.7 46.6 6.9 58.5 46.2 7.2

*See notes in page 12

Air Conditioning Equipment . Built in the Gulf... for the World 11


SKM Ducted Mini Split Systems

Combination Ratings - RXH-D and DCYP Units


Capacity Ratings 50Hz - High Speed
Air on coil Temperature DB/WB-80/67°F (26.6/19.4°C)
Outdoor Indoor Indoor Unit
ESP Ambient(Condenser Entering Air)Temperature
Unit Unit Air Flow Rate
95°F (35°C) 105°F (41°C) 115°F (46°C)
TC SC PI TC SC PI TC SC PI
RXH-5DC DCYP CFM in.wg (Pa)
MBh MBh kW MBh MBh kW MBh MBh kW
020 06/30 686 0.1 (25) 18.0 13.7 1.9 17.0 13.4 2.0 16.0 13.0 2.1
025 06/40 680 0.1 (25) 24.4 16.9 2.4 23.5 16.5 2.6 22.6 16.2 2.8
025 08/30 785 0.1 (25) 24.3 17.1 2.4 23.4 16.8 2.6 22.4 16.5 2.8
030 08/40 777 0.1 (25) 28.9 19.7 2.9 27.8 19.3 3.2 26.8 18.9 3.6
030 10/30 1061 0.1 (25) 30.4 22.2 3.0 29.2 21.8 3.3 28.0 21.4 3.6
040 10/40 1046 0.1 (25) 36.5 25.6 3.7 35.1 25.1 4.1 33.6 24.5 4.6
040 12/30 1331 0.1 (25) 36.5 27.0 3.7 35.1 26.5 4.1 33.6 25.9 4.6
045 12/40 1317 0.1 (25) 43.4 31.0 4.0 41.8 30.4 4.6 40.0 29.8 5.1
045 15/30 1536 0.1 (25) 42.8 31.5 4.0 41.2 30.9 4.5 39.5 30.2 5.1
050 15/40 1519 0.1 (25) 48.1 35.1 4.3 46.3 34.4 4.9 44.3 33.6 5.5
050 18/30 1914 0.1 (25) 49.5 38.0 4.3 47.5 37.4 4.9 45.5 36.6 5.5
060 18/40 1882 0.1 (25) 59.3 43.6 5.3 56.9 42.7 5.9 54.2 41.7 6.5
060 21/30 2200 0.1 (25) 58.6 44.3 5.3 56.2 43.5 5.9 53.6 42.6 6.5

Capacity Ratings 60Hz - High Speed


Air on coil Temperature DB/WB-80/67°F (26.6/19.4°C)
Outdoor Indoor Indoor Unit
ESP Ambient(Condenser Entering Air)Temperature
Unit Unit Air Flow Rate
95°F (35°C) 105°F (41°C) 115°F (46°C)
TC SC PI TC SC PI TC SC PI
RXH-6DC DCYP CFM in.wg (Pa)
MBh MBh kW MBh MBh kW MBh MBh kW
020 06/30 581 0.1 (25) 18.4 13.0 2.0 17.4 12.6 2.1 16.5 12.3 2.3
020 06/40 583 0.1 (25) 19.7 14.1 2.1 18.7 13.8 2.2 17.8 13.4 2.3
025 06/40 583 0.1 (25) 23.0 15.4 2.2 21.8 14.9 2.3 20.5 14.4 2.4
025 08/30 735 0.1 (25) 23.5 16.4 2.2 22.3 16.0 2.3 21.0 15.5 2.5
030 08/40 732 0.1 (25) 30.0 19.8 3.0 28.9 19.3 3.3 27.8 18.9 3.6
030 10/30 984 0.1 (25) 31.7 22.1 3.0 30.5 21.6 3.4 29.3 21.2 3.7
040 10/40 986 0.1 (25) 35.6 24.7 3.5 34.3 24.2 3.9 32.8 23.6 4.3
040 12/30 1147 0.1 (25) 35.2 25.0 3.5 33.9 24.5 3.9 32.5 24.0 4.2
045 12/40 1150 0.1 (25) 43.8 29.6 4.4 42.6 29.1 4.8 41.3 28.6 5.3
045 15/40 1450 0.1 (25) 47.4 34.2 4.5 46.0 33.6 4.9 44.6 33.1 5.4
050 15/40 1450 0.1 (25) 47.2 34.1 4.5 45.9 33.6 5.0 44.4 33.0 5.4
050 18/30 1813 0.1 (25) 48.6 36.9 4.6 47.2 36.3 5.0 45.6 35.8 5.4
060 18/40 1814 0.1 (25) 57.3 42.2 5.4 55.6 41.5 5.9 53.8 40.8 6.4
060 21/30 2190 0.1 (25) 57.0 43.7 5.4 55.4 43.1 5.9 53.6 42.5 6.4
Notes : 1. Shaded areas represent matched cooling capacities based as per AHRI Standards 210/240, 80/67ºF (26.6/19.4ºC) DB/WB temperature
of air entering the indoor coil and 95ºF outside air dry bulb. Capacities at other ambient temperature as shown.
2. For matched conditions, at entering condition other than shown, consult SKM.
3. Direct interpolation is permissible but extrapolation is prohibited.
4. Combination ratings are based on indoor and outdoor units at the same elevation and connected by 25 ft. (7.6 m) of refrigerant tubing.
For tubing in excess of 25 feet, slight capacity reduction will occur (approximately 0.5% per 50 feet length). Do not exceed 120 feet
tubing length without checking with SKM.

5. TC - Total cooling capacity in Mbh (1000 Btuh)


SC - Sensible cooling capacity in Mbh (1000 Btuh)
PI - Power input in kW (compressor only)
To convert Mbh to kW, divide by 3.413
To convert cfm to l/s, divide by 2.12
6. It’s recommended to use expansion valve when operating at 115ºF ambient and above.

12 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Electrical Data - RXV & DCYP


Vertical Discharge Outdoor Unit: RXV-50Hz
Model RXV 020 025 030 040 045 050 060 070
Power Supply 220-240V/1Ph/50Hz 380-415V/3Ph/50Hz
Electrical

Comp. RLA 11.4 15 16.5 15.3 7.3 9.6 10.5 10.9


LRA 51 58 58 85 50 61.8 74 74
Condenser motor FLA 0.9 0.9 0.9 0.9 0.7 0.7 0.7 0.7
MFA 32 40 40 40 20 25 25 32
Unit Characteristics
MCA 15 20 22 20 10 13 14 15

Indoor Unit: DCYP-50Hz


Unit Size DCYP 06 08 10 12 15 18 21 21
Type - 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2 2
High 1.3 1.4 1.3 2.6 2.8 2.6 2.8 2.8
Maximum
Speed Medium 0.9 1.1 1.1 1.8 2.2 2.2 2.2 2.2
Amps
Low 0.8 0.8 0.8 1.6 1.6 1.6 1.8 1.8

Vertical Discharge Outdoor Unit: RXV-60Hz


Model RXV 021 026 031 041 046 051 061 071
(i) 220V/1Ph/60Hz (i) 220V/3Ph/60Hz
Power Supply
- (ii) 380V/3Ph/60Hz
Electrical

(i) 11.2 13.2 16.2 19.4 15.6 18.2 21.4 22.0


RLA
(ii) - - - - 9.4 11 12 13.2
COMPRESSOR
(i) 55 56 65 90 91 124 156 156
LRA
(ii) - - - - 54 75 70 70
(i) 0.9 0.9 0.9 0.9 2.5 2.5 2.5 2.5
FLA
(ii) - - - - 0.8 0.8 0.8 0.8
(i) 32 32 40 50 40 50 63 63
MFA
(ii) - - - - 25 32 32 32
Unit Characteristics
(i) 15 18 21 25 22 25 29 30
MCA
(ii) - - - - 13 15 16 17

Indoor Unit: DCYP-60Hz


Unit Size DCYP 06 08 10 12 15 18 21 21
Type - 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2 2
High 1.1 1.4 1.5 2.2 2.8 3 3.4 3.4
Maximum
Speed Medium 0.8 0.95 1.25 1.6 1.9 2.5 2.6 2.6
Amps
Low 0.7 0.75 0.9 1.4 1.5 1.8 1.9 1.9

Air Conditioning Equipment . Built in the Gulf... for the World 13


SKM Ducted Mini Split Systems

Electrical Data - RXH-D & DCYP

Side Discharge Outdoor Unit: RXH-D-50Hz


Model RXH- 5DC 020 025 030 040 045 050 060
Power Supply 220-240V/1Ph/50Hz 380-415V/3Ph/50Hz
RLA 16 20 30 32 11 11.5 14
Electrical

Compressor
LRA 51 60.1 84 130 56 52 73
Condenser motor FLA 0.5 0.62 0.74 0.74 1.32 0.67 0.67
No of Condenser motor 1 1 1 1 1 2 2

Indoor Unit: DCYP-50Hz


Unit Size DCYP 06 08 10 12 15 18 21
Type - 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2
High 1.3 1.4 1.3 2.6 2.8 2.6 2.8
Maximum
Speed Medium 0.9 1.1 1.1 1.8 2.2 2.2 2.2
Amps
Low 0.8 0.8 0.8 1.6 1.6 1.6 1.8

Side Discharge Outdoor Unit: RXH-D-60Hz


Model RXH- 6DC 020 025 030 040 045 050 060
Power Supply 220V/1Ph/60Hz
RLA 16 20 30 32 36 36 43
Electrical

Compressor
LRA 42 66.51 95 101 164 164 188
Condenser motor FLA 0.53 0.67 0.86 0.86 1.17 0.75 0.75
No of Condenser motor 1 1 1 1 1 2 2

Indoor Unit: DCYP-60Hz


Unit Size DCYP 06 08 10 12 15 18 21
Type - 220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
Motor Size Watts 150 150 150 150 150 150 150
Quantity # 1 1 1 2 2 2 2
High 1.1 1.4 1.5 2.2 2.8 3 3.4
Maximum
Speed Medium 0.8 0.95 1.25 1.6 1.9 2.5 2.6
Amps
Low 0.7 0.75 0.9 1.4 1.5 1.8 1.9

14 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Options
Thermostat
Thermostat is wall mounted decorative type, with large LCD and backlight. Buttons are provided for power on/off, fan speed selection,
cooling or heating mode selection, set point adjustment and sleep mode selection. Indoor temperature and set point are displayed
simultaneously. Apart from that, display provides fan mode (high, medium, low or auto) and operating mode (cool or heat).

Note: Optional remote control and remote sensor are available on request.

Electric Heater
Electric heaters are available as an option with “U” shaped finned tubular heating elements with automatic reset thermal safety
cut-out. Order should specify FEH1 for Variant 1 and FEH2 for Variant 2. With the indoor units.

No. Of Heater Elements x kW


Unit Size
Variant 1 Variant 2
06 1 x 1.0 2 X 1.0
08 1 x 1.5 2 X 1.5
10 1 x 1.0 + 1 x 1.5 3 X 1.5
12 1 x 3.0 2 X 3.0
15 1 x 3.0 2 X 3.0
18 1 x 4.0 2 X 4.0
21 1 x 4.0 2 X 4.0

Heater Contactors are not included as standard and must be field supplied and installed.

Expansion Valves
Expansion Valves can be used as an option instead of orifice for the following combinations:

RXV-020 + DCYP-06/3 up to RXV-040 + DCYP-12/3 for 50Hz.


RXV-021 + DCYP-06/3 up to RXV-041 + DCYP-12/3 for 60Hz.

Air Conditioning Equipment . Built in the Gulf... for the World 15


SKM Ducted Mini Split Systems

Fan Performance - 50Hz


3 Rows 4 Rows
External Static Pressure
Speed DCYP
inwg 0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4
Pa 25 50 75 100 25 50 75 100
cfm 686 667 643 613 680 660 636 604
06
l/s 324 315 304 289 321 312 300 285
cfm 785 759 736 711 777 753 730 704
08
l/s 371 358 347 336 367 355 345 332
cfm 1061 1002 924 835 1046 983 906 817
10
l/s 501 473 436 394 493 464 428 386
cfm 1331 1291 1241 1178 1317 1276 1223 1156
High 12
l/s 628 609 586 556 622 602 577 546
cfm 1536 1490 1445 1388 1519 1476 1429 1368
15
l/s 725 703 682 655 717 696 674 645
cfm 1914 1798 1655 1491 1882 1761 1618 1456
18
l/s 903 848 781 703 888 831 763 687
cfm 2200 2021 1830 1623 2150 1943 1759 1562
21
l/s 1038 954 864 766 1015 917 830 737
cfm 517 501 481 454 514 498 478 449
06
l/s 244 236 227 214 243 235 225 212
cfm 604 590 574 553 601 587 571 549
08
l/s 285 278 271 261 284 277 270 259
cfm 721 730 711 669 724 728 706 661
10
l/s 340 344 336 315 341 344 333 312
cfm 1023 990 947 887 1016 982 937 875
Medium 12
l/s 483 467 447 419 480 463 442 413
cfm 1231 1202 1165 1116 1224 1194 1155 1104
15
l/s 581 567 550 526 578 563 545 521
cfm 1442 1430 1369 1268 1444 1422 1354 1251
18
l/s 681 675 646 599 681 671 639 590
cfm 1665 1636 1552 1430 1680 1626 1532 1404
21
l/s 957 897 822 736 933 869 795 711
cfm 397 384 358 324 396 381 355 321
06
l/s 187 181 169 153 187 180 167 152
cfm 485 466 445 421 482 463 442 419
08
l/s 229 220 210 199 228 219 209 198
cfm 465 466 474 448 464 467 474 445
10
l/s 219 220 224 211 219 220 224 210
cfm 776 744 691 625 773 738 684 618
Low 12
l/s 366 351 326 295 365 348 323 291
cfm 957 918 876 828 951 912 870 822
15
l/s 451 433 413 391 449 431 411 388
cfm 987 1012 993 899 988 1014 987 889
18
l/s 466 478 469 424 466 478 466 419
cfm 1122 1151 1113 990 1150 1168 1117 990
21
l/s 836 814 775 721 831 804 761 705

16 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Fan Performance - 60Hz


3 Rows 4 Rows
External Static Pressure
Speed DCYP
inwg 0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4
Pa 25 50 75 100 25 50 75 100
cfm 581 587 583 570 583 587 581 566
06
l/s 274 277 275 269 275 277 274 267
cfm 735 724 711 696 732 721 707 692
08
l/s 347 341 335 328 346 340 334 327
cfm 984 990 991 982 986 991 989 978
10
l/s 464 467 467 463 465 468 467 461
cfm 1147 1151 1136 1106 1150 1149 1130 1095
High 12
l/s 541 543 536 522 543 542 533 517
cfm 1457 1433 1406 1374 1450 1425 1397 1364
15
l/s 688 676 664 648 684 673 659 643
cfm 1804 1813 1811 1789 1807 1814 1807 1780
18
l/s 851 856 854 844 853 856 853 840
cfm 2190 2141 2057 1955 2180 2097 2007 1901
21
l/s 1034 1010 971 923 1029 990 947 897
cfm 442 426 404 379 440 423 401 376
06
l/s 209 201 191 179 208 200 189 177
cfm 565 547 528 508 562 544 525 505
08
l/s 267 258 249 240 265 257 248 238
cfm 612 585 594 627 607 584 597 630
10
l/s 289 276 280 296 287 275 282 298
cfm 876 841 795 744 871 834 788 737
Medium 12
l/s 414 397 375 351 411 394 372 348
cfm 1148 1111 1071 1030 1140 1103 1064 1023
15
l/s 542 524 506 486 538 520 502 483
cfm 1180 1156 1204 1263 1172 1158 1214 1267
18
l/s 557 545 568 596 553 547 573 598
cfm 1362 1355 1420 1472 1355 1362 1436 1473
21
l/s 862 852 834 809 858 846 826 799
cfm 327 302 275 247 326 300 273 246
06
l/s 155 143 130 117 154 142 129 116
cfm 452 427 403 380 449 425 401 378
08
l/s 213 202 190 179 212 201 189 178
cfm 517 447 396 367 511 443 394 366
10
l/s 244 211 187 173 241 209 186 173
cfm 635 585 532 478 630 581 528 475
Low 12
l/s 299 276 251 226 297 274 249 224
cfm 888 841 794 748 882 835 789 743
15
l/s 419 397 375 353 416 394 372 351
cfm 1015 895 813 771 1001 887 808 770
18
l/s 479 422 383 364 472 418 382 363
cfm 1132 1005 921 884 1112 992 915 882
21
l/s 638 640 639 632 638 640 638 630

Air Conditioning Equipment . Built in the Gulf... for the World 17


SKM Ducted Mini Split Systems

Recommended Suction and Liquid Line Sizes


Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)
RXV Model(Vertical Discharge
25 (7.6) 50 (15.2) 75 (22.9) 100 (30.5) 120 (36.6)
Condensing Unit)
Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid
020 021 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8
025 026 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 1/2
030 031 5/8 3/8 3/4 3/8 3/4 1/2 7/8 1/2 7/8 1/2
040 041 3/4 3/8 3/4 3/8 7/8 1/2 7/8 1/2 7/8 1/2
045 046 3/4 3/8 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2
050 051 3/4 3/8 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2
060 061 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2
070 071 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2

RXH-D Model Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)
(Side Discharge 25 (7.6) 50 (15.2) 75 (22.9) 100 (30.5) 120 (36.6)
Condensing Unit) Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid
20 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8
25 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 1/2
30 5/8 3/8 3/4 3/8 3/4 1/2 7/8 1/2 7/8 1/2
40 3/4 3/8 3/4 3/8 7/8 1/2 7/8 1/2 7/8 1/2
45 3/4 3/8 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2
50 3/4 3/8 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2
60 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2

Notes :

1. Pipe diameters are based on equivalent length of copper tubing sizes.


2. Pipe sizes are based on 2ºF (1.1ºC) or less temperature losses for liquid and suction line in equivalent pipe length.
3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet.
4. Do not exceed 120 feet piping length without checking with SKM.
5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE
Guide and Data Book.

The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant connections
available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.

18 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Typical Refrigeration Piping - RXV & DCYP

Legend:

1. RXV Air Cooled Condensing Unit


2. DX DCYP Fan Coil Unit
5 2 3. Liquid Line
4. Suction Line
5. Metering Device
6. Packed Valves

4
1

6
1

REFRIGERANT PIPING 6

Correct design and size of refrigerant


piping is necessary for proper operation.
The refrigerant piping generally should be
designed to accomplish the following:

a. To ensure proper refrigerant feed to 4


3
the evaporator.
b. To provide practical refrigerant line
sizes without excessive pressure
5
drop.
c. To maintain uniform return of 2
lubricating oil to the compressor.
d. To prevent refrigerant from entering
the compressor and causing compressor
damage due to “slugging”.

Air Conditioning Equipment . Built in the Gulf... for the World 19


SKM Ducted Mini Split Systems

Typical Refrigeration Piping - RXH-D & DCYP

Legend:

1. RXH-D Air Cooled Condensing Unit


2. DX DCYP Fan Coil Unit
3. Liquid Line
4. Suction Line
5. Metering Device
6. Packed Valves

2
2
5
5

1
3

20 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Typical Wiring Diagram - RXV & DCYP THERMOSTAT WITH 3SPEED SWITCH
(BY OTHERS / OPTION)
** 220~240V/1PH/50HZ

L N E
** 220~240V/1PH/50HZ
FIELD SUPPLY

G L N

EQUIP. GRND.

FM
FH

FL

H
N

C
L

FIELD SIDE
CONTACTOR ANTI SHORT
FAN MOTOR CYCLE TIMER LPS HPS
S L1 L2
CAPACITOR

220~240V
1 1
C C1 TO INDOOR UNIT FROM INDOOR UNIT
FIELD CONNECTIONS
R T1 T2 2 2
RUN CAPACITOR

R JN. BOX FOR


C CUSTOMER
CONNECTION
S FIELD WIRING (BY OTHERS)
COMPRESSOR

UNIT SIDE
START
RELAY MOTOR BODY
EARTHING

FM

FM
FH

FH
FL

FL
N

N
E

E
START CAPACITOR FAN FAN
MOTOR MOTOR (IF APPLICABLE)
1 2

OUTDOOR UNIT MODEL (RXV - 020,025,030 & 040) INDOOR UNIT(DCYP)

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)
** (380~415V / 3PH / 50HZ) ** 220~240V/1PH/50HZ

L1 L2 L3 N Grd L N E

GROUNDING LUG

FM
FH

FL
CRANKCASE

H
C
L

FIELD SIDE
HEATER

(AUX. CONTACT)
1
CONTACTOR FROM INDOOR UNIT
ANTI SHORT FIELD CONNECTIONS
CYCLE TIMER LPS HPS 2
220-240V

L1 L2 L3 1
FROM INDOOR UNIT
FIELD CONNECTIONS
T1 T2 T3 2

JN. BOX FOR


CUSTOMER
CONNECTION

UNIT SIDE
3~ 3~
MOTOR MOTOR
MOTOR BODY
EARTHING
FM

FM
FH

FH
FL

FL
N

N
E

COMPRESSOR CONDENSER FAN


MOTOR MOTOR
FAN FAN FIELD WIRING (BY OTHERS)
MOTOR MOTOR
1 2

OUTDOOR UNIT MODEL (RXV - 045,050,060 & 070) INDOOR UNIT(DCYP)

Typical Wiring Diagram - RXH-D & DCYP


POWER SUPPLY: 220~ 240V/1PH/50HZ

BLACK

CN201 CN200
R

K2 SW1 THERMOSTAT WITH 3SPEED SWITCH


S (BY OTHERS / OPTION)
RED COMP.
WHITE
BLUE

RED
CN9
C
Y/G
P.C.B
CN206 CAP1
FIELDSIDE
RED

RED
CN38 L
FROM
BLACK

N
CN39
BLACK

BLACK
WHITE

WHITE

OUTDOOR UNIT
CN203 CT2 1
CN40
XP1 XS1

XP2 XS2

CN208

JUNCTIONBOX
T3
TRANS
Y/G
UNITSIDE

K1 K3
BLACK

RED
CAP2
BLUE
RED FAN
A1
21
5
3
1

T4 XT2
KM8

FM
FH
RED

FL
N

E
22
6
4
2

A2

RED FAN
BLACK

BLACK MOTOR

BLACK

INDOORUNIT(DCYP- 06 & DCYP- 08)


BLACK

RED
XT1 CODE PART NAME
L N 1 CAP1, 2 CAPACITOR
K1, K2 HIGH, LOWPRESSURESWITCH
TRANS POWERTRANSFORMER
POWER
FAN OUT DOORFAN
Y/G

T4 RESISTANCE
LN1 T3 RESISTANCE
XP1~ 2, XS1~ 2 CONNECTORS
TOINDOORUNIT
CT2 CURRENTDETECT
OUTDOOR UNIT(RXH- 020 5DC & RXH- 025 5DC) XT1 5WAYTERMINAL
XT2 TERMINAL
KM8 CONTACTOR

Air Conditioning Equipment . Built in the Gulf... for the World 21


22
POWER SUPPLY: 220~240V/1PH/50HZ

RED

CN201 CN200 R

K2 SW1
S
RED BLACK COMP.
CN9

BLACK
WHITE
RED

C Y/G
P.C.B
CN206 CAP1

RED
RED
CN38 THERMOSTAT WITH 3SPEED SWITCH
(BY OTHERS / OPTION)
CN39
CN203

WHITE
BLACK
CT2 CN40
CN208

XP1 XS1
XP2 XS2
WHITE
BLUE
FIELD SIDE

TRANS L
FROM N
OUT DOOR UNIT
1
Typical Wiring Diagram - RXH-D & DCYP

RED

K1
CAP2
A1

5
3
1

21
XT4

RED
BLUE

K3
JUNCTION BOX

KM8
T4

6
4
2
Y/G

22
A2
T3 R FAN
BLACK
RED

BLACK
BLACK
UNIT SIDE
SKM Ducted Mini Split Systems

BLACK
MOTOR BODY
EARTHING
N
FH
FM
FL
E
N
FH
FM
FL
E

CODE PART NAME


BLACK

BLACK
RED
RED
RED CAP 1, 2 CAPACITOR FAN FAN (APPLICABLE FOR
MOTOR MOTOR
XT2 XT1 K1, K3 HIGH, LOW PRESSURESWITCH RXH- 040 5DC + DCYP- 12)
1 2
TRANS POWER TRANSFORMER
L N 1 3 4 INDOOR UNIT(DCYP- 10 & 12)
FAN OUT DOOR FAN
T4 ROOM TEMPARATURE

Air Conditioning Equipment . Built in the Gulf... for the World


POWER T3 PIPETEMPARATURE
XP1~ 2, XS1~ 2 CONNECTORS
CT2 CURRENT DETECT
L N E 1
KM8 CONTACTOR
TOINDOORUNIT TOINDOORUNIT
XT3, XT4 TERMINAL
OUTDOOR UNIT(RXH- 030 5DC & RXH- 040 5DC) K2 TEMPARETUREPROTECTOR SWITCH
CN100-208 P.C. BOARD SOCKETS
POWER SUPPLY:- 380~415V/3PH/50HZ
L.P. SW

THERMOSTAT WITH 3SPEED SWITCH


CN09 T5 (BY OTHERS / OPTION)
T4
RT4

CN208
RT3
T3

CN206
XS2 XP2 XS1 XP1 HI-PRO K1
R

CN203
XS3 XP3 CT1
CN201 CN100 CN200

BLACK
ORANGE
RED
WHITE
BLUE
BLACK
L
FIELD SIDE

RED
FROM N
BLACK OUT DOOR UNIT
1

KM1
ORANGE A1 A2
XT6 RED 1 2
WHITE 3 4
BLUE 5 6

JUNCTION BOX
21 22

Y/G
Y/G
FAN3 BLACK
CODE PARTNAME
Typical Wiring Diagram - RXH-D & DCYP

RED
BLUE

BLACK
COMP COMPRESSOR
BLUE BLUE W(T3) FAN3,FAN4 OUTDOORFAN
WHITE
CAP3,CAP4 FANCAPACITOR
V(T2)
UNIT SIDE

CAP3 COMP. KM1 ACCONTACTOR


RED
U(T1) MOTOR BODY XT1 5 WAYTERMINAL
EARTHING XT5, XT6 CONNECTOR

N
FH
FM
FL
E
N
FH
FM
FL
E

XS8-9, XP8-9 CONNECTORS


H-PRO HIGHPRESSURESWITCH
Y/G FAN FAN CT1 CURRENTDETECTOR
MOTOR MOTOR
SKM Ducted Mini Split Systems

Y/G T5 TRANSFORMER
1 2 3 4 A B C N 1 2 RT3 PIPETEMP. SENSOR
L.P. SW LOWPRESSURESWITCH
XT4 XT3
XT2 4WAYTERMINAL
POWER K1 TEMP. PROTECTSWITCH
380~ 415V/3PH/50Hz CN100-208 P.C. BOARDSOCKETS
INDOOR UNIT(DCYP- 15)
1 L N

TOINDOOR UNIT TOINDOOR UNIT

Air Conditioning Equipment . Built in the Gulf... for the World


OUTDOOR UNIT(RXH- 045 5DC)

23
24
POWER SUPPLY:- 380~415V/3PH/50HZ

THERMOSTAT WITH 3SPEED SWITCH


HI-PRO K1 T5 (BY OTHERS / OPTION)

CN208

CN206
CN203

CN09
CT1
CN201 CN100 CN200

XS8 XP8
XS7 XP7

XS9 XP9
L-PRO
L
FIELD SIDE

BLACK
FROM N

RT3
R
ORANGE
RED
WHITE
BLUE
YELLOW

RT4
BLACK OUT DOOR UNIT
1

KM1
ORANGE A1 A2
XT5 RED 1 2
WHITE
WHITE 3 4
BLUE BLUE 5 6

JUNCTION BOX
21 22

WHITE
WHITE

RED
Typical Wiring Diagram - RXH-D & DCYP

Y/G
Y/G FAN
UP
CODE PARTNAME
BLUE

BLACK
COMP COMPRESSOR
RED YELLOW W(T3) FAN3,FAN4 OUTDOORFAN
WHITE
CAP3,CAP4 FANCAPACITOR
V(T2)
UNIT SIDE

CAP3 COMP. KM1 ACCONTACTOR


RED
XT6 U(T1) MOTOR BODY XT1 5 WAYTERMINAL
WHITE EARTHING XT5, XT6 CONNECTOR
SKM Ducted Mini Split Systems

N
FH
FM
FL
E
N
FH
FM
FL
E

BLACK XS8-9, XP8-9 CONNECTORS


BLACK H-PRO HIGHPRESSURESWITCH
Y/G FAN BLUE Y/G FAN FAN
Y/G CT1 CURRENTDETECTOR
DOWN MOTOR MOTOR
XT1 T5 TRANSFORMER
1 2 3 4 A B C N 1 2 RT3 PIPETEMP. SENSOR
Y/G L.P. SW LOWPRESSURESWITCH
RED YELLOW XT2
XT2 4WAYTERMINAL
POWER K1 TEMP. PROTECTSWITCH
CAP4
380~ 415V/3PH/50Hz CN100-208 P.C. BOARDSOCKETS
INDOOR UNIT(DCYP-18 & 21)

Air Conditioning Equipment . Built in the Gulf... for the World


1 L N

TOINDOOR UNIT TOINDOORUNIT

OUTDOOR UNIT(RXH- 050 & 060 5DC)


SKM Ducted Mini Split Systems

Dimensional Data OUTDOOR UNITS - VERTICAL DISCHARGE

Model: RXV-020 to 040

[102] 0.75 2
[19] [51]
4

DIMEN SIO NS ARE IN INCH ES [MM]


MO DEL
L W H A
23 23 25 24
RXV- 020 [584] [584] [635] [610]
23 23 33 32
RXV- 025 [584] [584] [838] [813]
26 26 37 36
RXV- 030 [660] [660] [940] [914]
26 26 37 36
RXV- 040
[102]

[660] [660] [940] [914]


1.7 MOUNT. HOLES
4

4
Ø3/8 [9.5] x 4 NOS.
[44]

L W
0.79
[20]

3
A
H

2 SUCTION Ø ACCESS
LIQUID Ø
CABLE ENTRY
HOLE Ø25MM(WITH
RUBBER GROMMET)
[25]
1

Model: RXV-045 to 070

0.75
[19] 2
[102]

4
[51]
4

LEGEND
1. CONDENSER FAN
2. COMPRESSOR
3. CONTROL PANEL
4. CONDENSER COIL

NOTE: MODEL RXV- 045 (1 ROW)


MODEL RXV- 050,060 & 070 ( 2 ROWS)

1.8
[102]

[45] MOUNT. HOLES


4

Ø3/8 [9.5] x 4 NOS.

29 29
[737] [736]
0.79
[20]

1
[813]

3
[838]
32
33

SUCTION Ø
ACCESS
2
LIQUID Ø

CABLE ENTRY
HOLE Ø25MM(WITH
RUBBER GROMMET)
[25]
1

Air Conditioning Equipment . Built in the Gulf... for the World 25


SKM Ducted Mini Split Systems

Dimensional Data

OUTDOOR UNITS - SIDE DISCHARGE

Models: RXH-020-DC & RXH-025-DC Models: RXH-030-DC & RXH-040-DC


35.2
33.1 [895]
[842]
[694]
27.4

[862]
33.9
[13]
0.5

[13]
0.5
5.6 22.1
[141] [560]

5.6 24.1
[141] [608]
[346]

[324]

[371]
13.6

12.8

14.6

[335]

[313]

[360]
13.2

12.3

14.2
ALLDIMENSIONSAREININCHES[mm]

ALLDIMENSIONSAREININCHES[mm]

Models: RXH-045-DC Models: RXH-050-DC & RXH-060-DC


35.4
39
[990]
[900]
[966]
38

[1167]
46

7.1 24.6
[181] [624]
[370]

[340]

[390]
14.6

13.4

15.4
[378]

[354]

[414]
14.9

13.9

16.3

5.9 23.2
ALL DIMENSIONS AREIN INCHES[MM] [150] [590]
ALL DIMENSIONSAREININCHES[mm]

26 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Dimensional Data

DCYP INDOOR UNITS

UNIT SIZES 06 - 10 UNIT SIZES 12 - 21


4-5/8 Ø [16] TERMINAL
1 2 3 MTG.HOLES 1 2 3
CONNECTION
WITH RUBBER
GROMMETS

TERMINAL
CONNECTION

2 2
[51] [51]
L

L
DRAIN
K

K
DRAIN
Ø3/4 [19] Ø3/4 [19]
M

M
4 4
1.5 A 8.5 1.5 A 8.5
[38] [216] [38] [216]
B
B

0.75 C 0.75 11.25 G


[19] [19] [286]
1
[25]
1

[25]

LIQUID 6
D1

F
FILTER
REMOVAL

SUCTION FREE RETURN-STANDARD 5


LEFT HAND UNIT SHOWN
RIGHT HAND UNIT OPPOSITE

1
[38]
1.5

[25]

DDP K L M
6 UNIT
LEGEND DIMENSIONS FOR
MODEL INCH MM INCH MM INCH MM
DxA

1 INSULATED R.A.PLENUM 06
F

3R / 4R 22 559 27.68 703 2.64 67


2 SUPPLY FAN 08
12
3 FAN MOTOR 3R / 4R + HEATER 21.78 553 29.41 747 4.61 117
15
4 COOLING COIL
10 3R / 4R 26.12 663 29.93 760 0.79 20
5 ACCESS PANEL 5 18
FILTER 3R / 4R + HEATER 26.82 681 31.66 804
6 FILTER 21 1.82 46
REAR RETURN-OPTIONAL REMOVAL
(DUCTED)

CONNECTION SIZES
DDP A B C D D1 F G L IQ UID Ø SUC TION Ø
UNIT 3R 4R 3R 4R
MODEL
INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM

06 23 584 33 838 21.5 546 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 5/8 16

08 27 686 37 940 25.5 648 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 5/8 16

10 27 686 37 940 25.5 648 14.5 368 14.84 377 17.32 440 18.67 474 3/8 10 3/8 10 5/8 16 5/8 16

12 39 991 49 1245 37.5 952 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 7/8 22

15 45 1143 55 1397 43.5 1105 12 305 12.5 317 15 381 16.42 417 1/2 13 1/2 13 7/8 22 7/8 22

18 45 1143 55 1397 43.5 1105 14.5 368 14.84 377 17.32 440 18.67 474 1/2 13 1/2 13 1 1/8 29 1 1/8 29

21 51 1295 61 1549 49.5 1257 14.5 368 14.84 377 17.32 440 18.67 474 1/2 13 1/2 13 1 1/8 29 1 1/8 29

ALL DIMENSIONS ARE IN INCHES [MM]

Air Conditioning Equipment . Built in the Gulf... for the World 27


SKM Ducted Mini Split Systems

Outdoor Unit Clearance & Spacing

No obstacle POWER
SOURCE

1525mm
CONTROL CIRCUIT
AIR OUT
CONTROL
AIR IN PANEL

SPACING FOR
SE RVICE

LIQUID
SUCTION SPACING FOR AI R
FLOW

AIR IN
AIR IN
[356]
14
[762]
30

SPACING FOR
SE RVICE

30 SINGLE UNIT 30 SPACING FOR AI R


[762] [762] FLOW
[356]

[356]
14

14
[762]

[762]
30

30

30 45 30
[762] [1143] [762]

MULTIPLE UNITS ALL DIMENSIONS ARE IN INCHES[MM]

28 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

Outdoor Unit Clearance & Spacing

SINGLE UNIT:-

SPACING FOR
SERVICE

20
1 [ 50
[ 30 2 8]
5]

12 ]
5
[ 30

33 ]
8
[ 83

2
[ 50 0
8]
1
[ 30 2
5]
12 ]
5
[ 30

48 9]
1
[12

ALL DIMENSIONS ARE IN INCHES[MM]

Air Conditioning Equipment . Built in the Gulf... for the World 29


SKM Ducted Mini Split Systems

GUIDE SPECIFICATIONS
Ducted mini split Air Conditioning system shall composed of a compact design indoor fan coil unit and floor or Rooftop
mounted outside air cooled condensing unit, rated with AHRI standards 210/240.

CONDENSING UNIT:
The condensing unit shall be composed of compressor, condenser, coil, condenser fan and motor.

CONDENSER COIL
The condenser coil shall be air cooled constructed of high efficiency inner grooved copper tube mechanically expanded into
hi-efficiency aluminum fins.

COMPRESSOR
Compressor shall be hermetic type, refrigerant gas cooled, furnished with internal overload protection device.

CONDENSER FAN
For side discharge air delivery the condenser fan shall be direct driven propeller type, equipped with statically and dynamically
balanced plastic (ASG20) blades. Complete fan assembly is equipped with heat protect BW 130°C condenser fan guard.
For top discharge air delivery, the fan shall be equipped with statically and dynamically balanced alloy blades, and inherent
corrosion resistant shaft. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard.

MOTOR
The motor shall be totally enclosed air over (TEAO), six pole.

CONTROLS
Condensing unit shall be provided with a control panel enclosure comprising all electrical control devices except for the field
supplied room thermostat and shall include the following components as minimum:
• Compressor and condenser fan motor contactor
• Anti recycling time delay relay
• Terminal for external connections.

INDOOR UNIT:
The indoor unit/air handler shall be composed of evaporator coil, fan motor assembly and the metering device.

EVAPORATOR COIL
Evaporator coil shall be constructed of seamless copper tubes with 5/16” OD, mechanically bonded to aluminium fins. The coil
consists of headers of seamless copper and flow control distributor.

EVAPORATOR FAN
Fan shall be double inlet, double width, direct driven with centrifugal type wheel. Fan wheel shall be with multi forward curved
blades. Fan shall be statically and dynamically balanced. Fan housing and wheel shall be made of galvanized steel sheet.

MOTOR
Motor shall be single phase, 3 speed permanent split capacitor type, suitable for 220-240V/1Ph/50-60Hz.Highly efficient with
integral thermal protection. Motor shall have high power factor and shall be with permanent lubricated sleeve bearings.

METERING DEVICE
Indoor unit shall be equipped with refrigerant flow control device.

CASING
The unit casing shall be made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM-A525 that shall be
phospatized and then electro statically dry powder coated of approx 60 microns to provide an extremely tough, scratch resistance,
and excellent anti corrosive protection.

30 Air Conditioning Equipment . Built in the Gulf... for the World


SKM Ducted Mini Split Systems

NOTES: