Range 1.5 TR to 6 TR
( 5 kW to 21 kW )
Bulletin # 068/2012
Supersedes Bulletin # 068/2010
SKM Ducted Mini Split Systems
Contents
Introduction .........................................2 Recommended Line Sizes................18
Legend................................................2 Typical Refrigeration Piping ..............19
Nomenclature .....................................3 Typical Wiring Diagram.....................21
Features & Specification............... 4-10 Dimensional Data .............................25
Combination Ratings ........................11 Outdoor Unit Clearance
Electrical Data ..................................13 and Spacing...............................28
Options .............................................15 Guide Specification...........................30
Fan Performance ..............................16
Legend
The following legends are used throughout
this manual: LADB .... Leaving Air Dry Bulb
LAWB ... Leaving Air Wet Bulb
AFR ...... Air Flow Rate lbs ......... Pounds weight (British units)
cfm ....... Cubic feet per minute l/s .......... Liters per second
dB ........ Decibels Mbh ...... 1000 Btuh
EADB .... Entering Air Dry Bulb OD ........ Outside Diameter
EAWB .... Entering Air Wet Bulb Ph ......... Phase
ET ......... Evaporating Temperature Pa ......... Pascals
Hz ........ Hertz SC ........ Sensible Capacity
kW ........ Kilowatts TC ......... Total Capacity
kg ......... Kilograms TR ........ Tons of refrigeration = 12 MBH
kPa ...... Kilo Pascals V ........... Volts
Introduction
The Ducted Mini Split system from SKM consists of RXV (a high efficiency- TOP discharge Air Cooled
Condensing Unit); and RXH-DC (a high efficiency-SIDE Discharge Air cooled Condensing Unit) matching with
DCYP (a low noise, ceiling suspended indoor fan coil unit). This split systems are ideally suited for apartments,
houses, offices, shops, small residences, and in small commercial establishments.
SKM ducted mini split system are available in different models covering 1.5 TR to 6 TR (5 kW to 21 kW) at
nominal AHRI condition, which make them ideally suited for a very small foot print for space saving and a
pleasant exterior appearance.
SKM ducted mini split units are suitable to operate in a wide range of ambient temperature.
SKM ducted mini split units are internally wired and all that required to be done on site is ducting, refrigerant
piping, power supply and suitable room thermostat installation and field wiring, which reduces the installation
work and consequently keeps to a minimum cost.
NOMENCLATURE
OUTDOOR ( TOP DISCHARGE AIR COOLED CONDENSING UNIT )
R X V - 020- Y
S1: 220-240V/1Ph/50Hz
Remote Air Cooled Condenser Y: 380-415V/3Ph/50Hz
Direct Expansion
Power Supply 5 : 50 Hz
Nominal Capacity in MBh
Frequency 6 : 60 Hz
INDOOR UNIT
FCU - DCY P - 12 / 4 / X G
G=Galvanised Finish
Fan Coil Unit F=Painted FInish
• Design - Outdoor condensing units are ideal for rooftop or ground installation. Units have a pleasant exterior appearance
and have a very small footprint for space saving installation.
• High efficiency Coils - 3/8” OD Hi-x tubes; mechanically bonded to hi-efficiency aluminium fins to match for a maximum
efficiency.
• Hermetic Compressor - High efficiency hermetically sealed compressor located on engineered mounts for safe, quiet and
vibration free operation.Compresssors are selected for reliability and power efficiency.
• Cabinet Construction - Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.
• High Efficiency Fan Motor – Permanently lubricated fan motor and is precisely matched to a metal propeller type Fan
blades which provides a maximum efficiency.
• Brass Service Valves – Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.
• Ease of Service and Installation – Designed to make servicing easier for the contractor, access panels are provided
for all controls and the compressor from the side of the unit.
• Compressor Short Cycling Protection – To protect the compressor against rapid short cycling.
• High and Low Pressure Protection - To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.
(1) MBh 20.3 23.3 29.6 35.2 48.4 56.3 66.6 68.5
Cooling Capacity
kW 5.9 6.8 8.7 10.3 14.2 16.5 19.5 20.1
MBh 18.3 20.8 26.9 31.7 44.7 52.6 62.0 63.8
Cooling Capacity (2)
kW 5.4 6.1 7.9 9.3 13.1 15.4 18.2 18.7
380/3/60Hz
Power Supply V / Ph / Hz 220/1/60Hz
220/3/60Hz
Type - Reciprocating Scroll
Compressor
Qty. - 1 1 1 1 1 1 1 1
Type Waffle Louver Fins and Inner Grooved tubes 3/8"OD
Coil ft² 8 12 16 16 16 16 16 16
Face Area
m² 0.74 1.11 1.49 1.49 1.49 1.49 1.49 1.49
Type Propeller,Direct Drive
Condenser
Blade Dia. / Qty 460 / 1 460 / 1 460 / 1 460 / 1 560 / 1 560 / 1 560 / 1 560 / 1
Fan
cfm 2310 2350 2370 2370 5450 5340 5340 5340
Air Flow
l/s 1090 1109 1118 1118 2572 2520 2520 2520
Type TEAO (Totally Enclosed Air Over) Motor
Motor
Size Watts 100 100 100 100 370 370 370 370
Refrigerant Operating Charge (R-22) lbs / kg 2.43 / 1.10 3.11 / 1.41 3.87 / 1.76 4.11 / 1.86 4.25/ 1.93 6.93 / 3.14 7.09 / 3.21 7.54 / 3.42
Unit Approximate Weight lbs / kg 202 / 92 202 / 92 221 / 100 228 / 103 242 / 110 277 / 125 277 / 125 284 / 129
Width 23 23 26 26 29 29 29 29
Dimensions (inches) Depth 23 23 26 26 29 29 29 29
Height 25 33 37 37 33 33 33 33
Liquid 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Pack valves Connections (inches)
Suction 5/8 5/8 5/8 3/4 3/4 3/4 3/4 7/8
Notes: 1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry
bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb.
2. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of
115ºF (46ºC) dry bulb..
• Design - Outdoor condensing units with side discharge air delivery are ideal for rooftop or ground installation and ledge
installation. This unit has a pleasant exterior aesthetic design and has a very small footprint for space saving installation.
• High Efficiency Coils – 3/8” O.D. inner grooved copper tubes with mechanically bonded to aluminium corrugated fins to
attain maximum efficiency.
• Compressor – Uses high efficiency rotary or scroll hermetic compressor located on engineered mounts for safe, quite and
vibration free operation.
• Cabinet Construction- Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.
• Brass Service Valves – Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.
• High efficiency fan motor – permanently lubricated fan motor and it is precisely matched to plastic propeller type blades
which provides a maximum efficiency.
• Ease of service and installation – designed to make servicing easier for the contractor; access panel are also provided
for all controls from the side of the unit.
• Compressor Short Cycling Protection – To protect the compressor against rapid short cycling.
• High and Low Pressure Protection – To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.
Fan
cfm 1766 1766 2510 2510 3414 3902 3902
Air Flow
l/s 833 833 1185 1185 1611 1841 1841
Type TEAO (Totally Enclosed Air Over) Motor
Motor Size Watts 55 53 75 75 190 65 65
Qty 1 1 1 1 1 2 2
Type R-22
Refrigerant Operating Charge
kg 1 1.4 1.9 2.1 2.5 2.8 3.2
Unit Approximate Weight kg 42 49 62 84 97 99 103
Width 33.1 33.1 35.2 35.2 39.0 35.4 35.4
Dimensions (inches) Depth 12.8 12.8 12.3 12.3 13.9 13.4 13.4
Height 27.4 27.4 33.9 33.9 38.0 46 46
Liquid 1/4 3/8 3/8 3/8 3/8 3/8 3/8
Pack valves Connections (inches)
Suction 1/2 5/8 5/8 3/4 3/4 3/4 3/4
• Heavy gauge galvanized casing and fan housing. Hot dip is standard.
• Evaporator coils equipped with plain tubes and aluminium fins which give high capacity sensible and latent cooling capabilities.
Notes: (1). Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC)
dry bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb.
(2). Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature
of 115ºF (46ºC) dry bulb.
Notes: • Nominal cooling capacities are based on the following conditions: Evaporator entering air of 80/67ºF (27/19.5ºC) dry
bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC).
Compressor
LRA 51 60.1 84 130 56 52 73
Condenser motor FLA 0.5 0.62 0.74 0.74 1.32 0.67 0.67
No of Condenser motor 1 1 1 1 1 2 2
Compressor
LRA 42 66.51 95 101 164 164 188
Condenser motor FLA 0.53 0.67 0.86 0.86 1.17 0.75 0.75
No of Condenser motor 1 1 1 1 1 2 2
Options
Thermostat
Thermostat is wall mounted decorative type, with large LCD and backlight. Buttons are provided for power on/off, fan speed selection,
cooling or heating mode selection, set point adjustment and sleep mode selection. Indoor temperature and set point are displayed
simultaneously. Apart from that, display provides fan mode (high, medium, low or auto) and operating mode (cool or heat).
Note: Optional remote control and remote sensor are available on request.
Electric Heater
Electric heaters are available as an option with “U” shaped finned tubular heating elements with automatic reset thermal safety
cut-out. Order should specify FEH1 for Variant 1 and FEH2 for Variant 2. With the indoor units.
Heater Contactors are not included as standard and must be field supplied and installed.
Expansion Valves
Expansion Valves can be used as an option instead of orifice for the following combinations:
RXH-D Model Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)
(Side Discharge 25 (7.6) 50 (15.2) 75 (22.9) 100 (30.5) 120 (36.6)
Condensing Unit) Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid
20 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8
25 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 1/2
30 5/8 3/8 3/4 3/8 3/4 1/2 7/8 1/2 7/8 1/2
40 3/4 3/8 3/4 3/8 7/8 1/2 7/8 1/2 7/8 1/2
45 3/4 3/8 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2
50 3/4 3/8 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2
60 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2
Notes :
The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant connections
available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.
Legend:
4
1
6
1
REFRIGERANT PIPING 6
Legend:
2
2
5
5
1
3
Typical Wiring Diagram - RXV & DCYP THERMOSTAT WITH 3SPEED SWITCH
(BY OTHERS / OPTION)
** 220~240V/1PH/50HZ
L N E
** 220~240V/1PH/50HZ
FIELD SUPPLY
G L N
EQUIP. GRND.
FM
FH
FL
H
N
C
L
FIELD SIDE
CONTACTOR ANTI SHORT
FAN MOTOR CYCLE TIMER LPS HPS
S L1 L2
CAPACITOR
220~240V
1 1
C C1 TO INDOOR UNIT FROM INDOOR UNIT
FIELD CONNECTIONS
R T1 T2 2 2
RUN CAPACITOR
UNIT SIDE
START
RELAY MOTOR BODY
EARTHING
FM
FM
FH
FH
FL
FL
N
N
E
E
START CAPACITOR FAN FAN
MOTOR MOTOR (IF APPLICABLE)
1 2
L1 L2 L3 N Grd L N E
GROUNDING LUG
FM
FH
FL
CRANKCASE
H
C
L
FIELD SIDE
HEATER
(AUX. CONTACT)
1
CONTACTOR FROM INDOOR UNIT
ANTI SHORT FIELD CONNECTIONS
CYCLE TIMER LPS HPS 2
220-240V
L1 L2 L3 1
FROM INDOOR UNIT
FIELD CONNECTIONS
T1 T2 T3 2
UNIT SIDE
3~ 3~
MOTOR MOTOR
MOTOR BODY
EARTHING
FM
FM
FH
FH
FL
FL
N
N
E
BLACK
CN201 CN200
R
RED
CN9
C
Y/G
P.C.B
CN206 CAP1
FIELDSIDE
RED
RED
CN38 L
FROM
BLACK
N
CN39
BLACK
BLACK
WHITE
WHITE
OUTDOOR UNIT
CN203 CT2 1
CN40
XP1 XS1
XP2 XS2
CN208
JUNCTIONBOX
T3
TRANS
Y/G
UNITSIDE
K1 K3
BLACK
RED
CAP2
BLUE
RED FAN
A1
21
5
3
1
T4 XT2
KM8
FM
FH
RED
FL
N
E
22
6
4
2
A2
RED FAN
BLACK
BLACK MOTOR
BLACK
RED
XT1 CODE PART NAME
L N 1 CAP1, 2 CAPACITOR
K1, K2 HIGH, LOWPRESSURESWITCH
TRANS POWERTRANSFORMER
POWER
FAN OUT DOORFAN
Y/G
T4 RESISTANCE
LN1 T3 RESISTANCE
XP1~ 2, XS1~ 2 CONNECTORS
TOINDOORUNIT
CT2 CURRENTDETECT
OUTDOOR UNIT(RXH- 020 5DC & RXH- 025 5DC) XT1 5WAYTERMINAL
XT2 TERMINAL
KM8 CONTACTOR
RED
CN201 CN200 R
K2 SW1
S
RED BLACK COMP.
CN9
BLACK
WHITE
RED
C Y/G
P.C.B
CN206 CAP1
RED
RED
CN38 THERMOSTAT WITH 3SPEED SWITCH
(BY OTHERS / OPTION)
CN39
CN203
WHITE
BLACK
CT2 CN40
CN208
XP1 XS1
XP2 XS2
WHITE
BLUE
FIELD SIDE
TRANS L
FROM N
OUT DOOR UNIT
1
Typical Wiring Diagram - RXH-D & DCYP
RED
K1
CAP2
A1
5
3
1
21
XT4
RED
BLUE
K3
JUNCTION BOX
KM8
T4
6
4
2
Y/G
22
A2
T3 R FAN
BLACK
RED
BLACK
BLACK
UNIT SIDE
SKM Ducted Mini Split Systems
BLACK
MOTOR BODY
EARTHING
N
FH
FM
FL
E
N
FH
FM
FL
E
BLACK
RED
RED
RED CAP 1, 2 CAPACITOR FAN FAN (APPLICABLE FOR
MOTOR MOTOR
XT2 XT1 K1, K3 HIGH, LOW PRESSURESWITCH RXH- 040 5DC + DCYP- 12)
1 2
TRANS POWER TRANSFORMER
L N 1 3 4 INDOOR UNIT(DCYP- 10 & 12)
FAN OUT DOOR FAN
T4 ROOM TEMPARATURE
CN208
RT3
T3
CN206
XS2 XP2 XS1 XP1 HI-PRO K1
R
CN203
XS3 XP3 CT1
CN201 CN100 CN200
BLACK
ORANGE
RED
WHITE
BLUE
BLACK
L
FIELD SIDE
RED
FROM N
BLACK OUT DOOR UNIT
1
KM1
ORANGE A1 A2
XT6 RED 1 2
WHITE 3 4
BLUE 5 6
JUNCTION BOX
21 22
Y/G
Y/G
FAN3 BLACK
CODE PARTNAME
Typical Wiring Diagram - RXH-D & DCYP
RED
BLUE
BLACK
COMP COMPRESSOR
BLUE BLUE W(T3) FAN3,FAN4 OUTDOORFAN
WHITE
CAP3,CAP4 FANCAPACITOR
V(T2)
UNIT SIDE
N
FH
FM
FL
E
N
FH
FM
FL
E
Y/G T5 TRANSFORMER
1 2 3 4 A B C N 1 2 RT3 PIPETEMP. SENSOR
L.P. SW LOWPRESSURESWITCH
XT4 XT3
XT2 4WAYTERMINAL
POWER K1 TEMP. PROTECTSWITCH
380~ 415V/3PH/50Hz CN100-208 P.C. BOARDSOCKETS
INDOOR UNIT(DCYP- 15)
1 L N
23
24
POWER SUPPLY:- 380~415V/3PH/50HZ
CN208
CN206
CN203
CN09
CT1
CN201 CN100 CN200
XS8 XP8
XS7 XP7
XS9 XP9
L-PRO
L
FIELD SIDE
BLACK
FROM N
RT3
R
ORANGE
RED
WHITE
BLUE
YELLOW
RT4
BLACK OUT DOOR UNIT
1
KM1
ORANGE A1 A2
XT5 RED 1 2
WHITE
WHITE 3 4
BLUE BLUE 5 6
JUNCTION BOX
21 22
WHITE
WHITE
RED
Typical Wiring Diagram - RXH-D & DCYP
Y/G
Y/G FAN
UP
CODE PARTNAME
BLUE
BLACK
COMP COMPRESSOR
RED YELLOW W(T3) FAN3,FAN4 OUTDOORFAN
WHITE
CAP3,CAP4 FANCAPACITOR
V(T2)
UNIT SIDE
N
FH
FM
FL
E
N
FH
FM
FL
E
[102] 0.75 2
[19] [51]
4
4
Ø3/8 [9.5] x 4 NOS.
[44]
L W
0.79
[20]
3
A
H
2 SUCTION Ø ACCESS
LIQUID Ø
CABLE ENTRY
HOLE Ø25MM(WITH
RUBBER GROMMET)
[25]
1
0.75
[19] 2
[102]
4
[51]
4
LEGEND
1. CONDENSER FAN
2. COMPRESSOR
3. CONTROL PANEL
4. CONDENSER COIL
1.8
[102]
29 29
[737] [736]
0.79
[20]
1
[813]
3
[838]
32
33
SUCTION Ø
ACCESS
2
LIQUID Ø
CABLE ENTRY
HOLE Ø25MM(WITH
RUBBER GROMMET)
[25]
1
Dimensional Data
[862]
33.9
[13]
0.5
[13]
0.5
5.6 22.1
[141] [560]
5.6 24.1
[141] [608]
[346]
[324]
[371]
13.6
12.8
14.6
[335]
[313]
[360]
13.2
12.3
14.2
ALLDIMENSIONSAREININCHES[mm]
ALLDIMENSIONSAREININCHES[mm]
[1167]
46
7.1 24.6
[181] [624]
[370]
[340]
[390]
14.6
13.4
15.4
[378]
[354]
[414]
14.9
13.9
16.3
5.9 23.2
ALL DIMENSIONS AREIN INCHES[MM] [150] [590]
ALL DIMENSIONSAREININCHES[mm]
Dimensional Data
TERMINAL
CONNECTION
2 2
[51] [51]
L
L
DRAIN
K
K
DRAIN
Ø3/4 [19] Ø3/4 [19]
M
M
4 4
1.5 A 8.5 1.5 A 8.5
[38] [216] [38] [216]
B
B
[25]
LIQUID 6
D1
F
FILTER
REMOVAL
1
[38]
1.5
[25]
DDP K L M
6 UNIT
LEGEND DIMENSIONS FOR
MODEL INCH MM INCH MM INCH MM
DxA
1 INSULATED R.A.PLENUM 06
F
CONNECTION SIZES
DDP A B C D D1 F G L IQ UID Ø SUC TION Ø
UNIT 3R 4R 3R 4R
MODEL
INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM
06 23 584 33 838 21.5 546 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 5/8 16
08 27 686 37 940 25.5 648 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 5/8 16
10 27 686 37 940 25.5 648 14.5 368 14.84 377 17.32 440 18.67 474 3/8 10 3/8 10 5/8 16 5/8 16
12 39 991 49 1245 37.5 952 12 305 12.5 317 15 381 16.42 417 3/8 10 3/8 10 5/8 16 7/8 22
15 45 1143 55 1397 43.5 1105 12 305 12.5 317 15 381 16.42 417 1/2 13 1/2 13 7/8 22 7/8 22
18 45 1143 55 1397 43.5 1105 14.5 368 14.84 377 17.32 440 18.67 474 1/2 13 1/2 13 1 1/8 29 1 1/8 29
21 51 1295 61 1549 49.5 1257 14.5 368 14.84 377 17.32 440 18.67 474 1/2 13 1/2 13 1 1/8 29 1 1/8 29
No obstacle POWER
SOURCE
1525mm
CONTROL CIRCUIT
AIR OUT
CONTROL
AIR IN PANEL
SPACING FOR
SE RVICE
LIQUID
SUCTION SPACING FOR AI R
FLOW
AIR IN
AIR IN
[356]
14
[762]
30
SPACING FOR
SE RVICE
[356]
14
14
[762]
[762]
30
30
30 45 30
[762] [1143] [762]
SINGLE UNIT:-
SPACING FOR
SERVICE
20
1 [ 50
[ 30 2 8]
5]
12 ]
5
[ 30
33 ]
8
[ 83
2
[ 50 0
8]
1
[ 30 2
5]
12 ]
5
[ 30
48 9]
1
[12
GUIDE SPECIFICATIONS
Ducted mini split Air Conditioning system shall composed of a compact design indoor fan coil unit and floor or Rooftop
mounted outside air cooled condensing unit, rated with AHRI standards 210/240.
CONDENSING UNIT:
The condensing unit shall be composed of compressor, condenser, coil, condenser fan and motor.
CONDENSER COIL
The condenser coil shall be air cooled constructed of high efficiency inner grooved copper tube mechanically expanded into
hi-efficiency aluminum fins.
COMPRESSOR
Compressor shall be hermetic type, refrigerant gas cooled, furnished with internal overload protection device.
CONDENSER FAN
For side discharge air delivery the condenser fan shall be direct driven propeller type, equipped with statically and dynamically
balanced plastic (ASG20) blades. Complete fan assembly is equipped with heat protect BW 130°C condenser fan guard.
For top discharge air delivery, the fan shall be equipped with statically and dynamically balanced alloy blades, and inherent
corrosion resistant shaft. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard.
MOTOR
The motor shall be totally enclosed air over (TEAO), six pole.
CONTROLS
Condensing unit shall be provided with a control panel enclosure comprising all electrical control devices except for the field
supplied room thermostat and shall include the following components as minimum:
• Compressor and condenser fan motor contactor
• Anti recycling time delay relay
• Terminal for external connections.
INDOOR UNIT:
The indoor unit/air handler shall be composed of evaporator coil, fan motor assembly and the metering device.
EVAPORATOR COIL
Evaporator coil shall be constructed of seamless copper tubes with 5/16” OD, mechanically bonded to aluminium fins. The coil
consists of headers of seamless copper and flow control distributor.
EVAPORATOR FAN
Fan shall be double inlet, double width, direct driven with centrifugal type wheel. Fan wheel shall be with multi forward curved
blades. Fan shall be statically and dynamically balanced. Fan housing and wheel shall be made of galvanized steel sheet.
MOTOR
Motor shall be single phase, 3 speed permanent split capacitor type, suitable for 220-240V/1Ph/50-60Hz.Highly efficient with
integral thermal protection. Motor shall have high power factor and shall be with permanent lubricated sleeve bearings.
METERING DEVICE
Indoor unit shall be equipped with refrigerant flow control device.
CASING
The unit casing shall be made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM-A525 that shall be
phospatized and then electro statically dry powder coated of approx 60 microns to provide an extremely tough, scratch resistance,
and excellent anti corrosive protection.
NOTES: