RET615E_H
A
Ordering Code: HBT-HBCAD-AB-C-1-B-N-N-1-XG A

RET615 X130
1
X100 BI1 HV-VT MCB Open
Aux. Power Supply 1 Uaux + 2
-
2 BI 2 3 Remote Position
3 4
IRF
IRF BI3 5 Fault Reset
4 6
5
PO1 BI4 7 OC Blocking-Downstream RET615
8
60-
HV CB CLOSE COMMAND 6 210V 9
7 not in use Ready Start Trip
N
60- 10
PO2 210V
U1 11 LatchedAck-F-S (Red Blink)
B GENERAL ALARMS LED1 B
GENERAL ALARMS 8 N
60- 12
9 210V DIFFERENTIAL PROT. TRIP LED2 LatchedAck-F-S (Red Blink)
U2 13 VOLTAGE INPUT
10 N
14 HV-SIDE O/C TRIP LED3 LatchedAck-F-S (Red Blink)
S01 60-
GENERAL START 210V 15
U3 LV-SIDE O/C & E/F TRIP LED4 LatchedAck-F-S (Red Blink)
11 N
12 60- 16 LED5 LatchedAck-F-S (Red Blink)
210V NEGATIVE SEQ. O/C TRIP
13 U0 17
S02 N VOLTAGE PROT. TRIP LED6 LatchedAck-F-S (Red Blink)
GENERAL OPERATE 18
HV EARTHING STATUS LED7 Follow-S (Green-Open), Follow-S (Red-Close)
14 X120
1/5A
IL1B 1 HV DISCONNECTOR STATUS LED8 Follow-S (Green-Open), Follow-S (Red-Close)
16
P03 N
2 LED9 Follow-S (Green-Open), Follow-S (Red-Close)
OPEN HV-CB / TRIP COIL 1 HV HV CIRCUIT BREAKER STATUS
17 1/5A
15 IL2B 3 LV RECLOSER-1 STATUS LED10 Follow-S (Green-Open), Follow-S (Red-Close)
N CURRENT INPUT
19 TCS1 4 (LV Winding-Wye LV RECLOSER-2 STATUS LED11 Follow-S (Green-Open), Follow-S (Red-Close)
18
1/5A Connected with Neutral)
C 20 IL3B 5 C
22 N
P04 6

21 1/5A
OPEN LV-CB / TRIP COIL 1 LV IL1 7
23 TCS2 N
24 8 ESC Clear
1/5A CURRENT INPUT
IL2 9
N (HV Winding-Delta Connected)
10
1/5A
IL3 11
N
12
1/5A
I0B 13
R
?
N
14

D
L D
X110
BI1 1 HV-CB SF6 Gas Press. Alarm
2
BI 2 3 HV-CB Spring Charge
X110
4
14
S03 BI3 5 HV-CB Fail
TCS-HV
16 6
15 HV-CB Open Status
BI4
17 7
S04
HV-CB Fail
19 BI5 8 HV-DS Open Status
18 9
20 BI6 HV-ES Open Status
S05
BLACKOUT STATUS 10
22
E 21 BI7 11 LV-CB1 Open Status E
23 12
S06
XFMR' Fan Start BI8 LV-CB2 Open Status
24 13

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
GENERAL IED PAGE 0 06/10/2018 EN 1/1
1 2 3 4 5 6 7 8

GENERAL IED PAGE


A General Logic State TRUE and FALSE A

NOT
IN OUT TRUE
O:38|T:2.5|I:4 1.)General.1.b2.NOT:3.IN
2.)Control_Interlocking.1.b3.CBXCBR1:1.ENA_OPEN

NOT
TRUE IN OUT FALSE
1.)General.1.b4.NOT:4.OUT O:43|T:2.5|I:3 1.)Control_Interlocking.1.b3.CBXCBR1:1.BLK_OPEN
2.)Control_Interlocking.1.c1.AND:2.B2
3.)Control_Interlocking.1.c1.AND:0.B2
4.)Control_Interlocking.1.c5.AND:1.B2
5.)Control_Interlocking.1.c5.AND:4.B2

B Local & Remote Control B

NOT Control
IN OUT CTRL_OFF OFF
O:39|T:2.5|I:11 CTRL_LOC LOCAL CONTROL_LOCAL
CTRL_STA STATION 1.)Control_Interlocking.1.c1.AND:2.B1
X130_BI2_REMOTE_OPTR CTRL_REM REMOTE 2.)Control_Interlocking.1.c5.AND:1.B1
1.)I_O.3.b3. O:44|T:2.5|I:0 CONTROL_REMOTE
1.)Control_Interlocking.1.c1.AND:0.B1
2.)Control_Interlocking.1.c5.AND:4.B1

Protection Setting GROUP Selection


PROTECTION
BI_SG_2 SG_LOGIC_SEL
BI_SG_3 SG_1_ACT
BI_SG_4 SG_2_ACT
C BI_SG_5 SG_3_ACT C
BI_SG_6 SG_4_ACT
SG_5_ACT
SG_6_ACT
O:8T:2.5|I:0

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
GENERAL IED PAGE 0 06/10/2018 EN 1/1
1 2 3 4 5 6 7 8

BINARY INPUT/OUTPUT PAGE


Binary outputs - X100 terminal block Binary outputs - X110 terminal block
A TCS 1&2 OUTPUT A
CLOSE COMMAND FOR HV CB
OR
HV_CB_CLOSE_COMMAND
1.)Control_Interlocking.1.d3.OR:24.O TCSSCBR1_ALARM B1 O
X100 (PSM).X100-PO1
1.)Supervision.1.d4.TCSSCBR1:1.ALARM B2
X110 (BIO).X110-SO1
GENERAL ALARMS O:106|T:2.5|I:37
TCSSCBR2_ALARM
OR20 1.)Supervision.1.d4.TCSSCBR2:2.ALARM
HV CB FAIL OUTPUT
TRPPTRC1_TRIP B1 O
1.)Protection.1.b7.TRPPTRC1:1.TRIP B2 OR6
B3 X100 (PSM).X100-PO2
TRPPTRC2_TRIP B4 X110_BI3_HV_CB_FAIL B1 O
1.)Protection.2.b7.TRPPTRC2:2.TRIP B5 1.)I_O.c3.OR:20.O B2
B3 X110 (BIO).X110-SO2
B6
TCSSCBR_ALARM B4
1.)Supervision.1.e3.OR:11.O
B7 AND
B8 B5
B9 CCBRBRF1_TRRET B1 O B6
SSCBR1_ALARMS
B10 1.)Protection.9.b6.CCBRBRF1:1.TRRET B2 O:125|T:2.5|I:4
1.)Supervision.1.b7.OR:25.O
B11 O:124|T:2.5|I:7
B12 CCBRBRF1_TRBU
B X130_BI1_HV_VT_MCB_OPEN B
B13 1.)Protection.9.b6.CCBRBRF1:1.TRBU
1.)I_O.3.b3.
B14 BLACKOUT STATUS
BLACKOUT_STATUS B15 AND20
1.)I_O.1.d7.AND20:0.O. B16
B17 HV_DS_CLOSED B1 O
X110_BI3_HV_CB_FAIL B18 1.)I_O.1.d4.NOT:6.OUT B2
1.)I_O.1.c3.OR:20.O B3 X110 (BIO).X110-SO3
B19
B20 HV_CB_CLOSED B4
CCBRBRF1_TRRET 1.)I_O.1.c4.NOT:10.OUT B5
1.)Protection.9.b6.CCBRBRF1:1.TRRET O:98|T:2.5|I:0
B6
X110_BI7_LV_CB1_CLOSED
CCBRBRF1_TRBU B7
1.)I_O.1.d4.OR:26.O
1.)Protection.9.b6.CCBRBRF1:1.TRBU B8
X110_BI7_LV_CB2_CLOSED B9
GENERAL START OUTPUT B10
1.)I_O.1.e4.OR:8.O
B11
GENERAL_START_PULSE B12
CMMXU1_LOW_ALARM
1.)Protection.4.b4.OR6:0.O 1.)Measurement.1.b3.CMMXU1:1.LOW_ALARM B13
X100 (PSM).X100-SO1
B14
GENERAL OPERATE OUTPUT CMMXU2_LOW_ALARM B15
1.)Measurement.1.c3.CMMXU2:2.LOW_ALARM B16
OR6 B17
C VMMXU1_LOW_ALARM B18 C
GENERAL_OPERATE B1 O 1.)Measurement.1.b5.VMMXU1:1.LOW_ALARM
1.)Protection.4.c4.OR6:12.O B2 B19
B3 X100 (PSM).X100-SO2 B20
TRPPTRC1_TRIP B4 O:92|T:2.5|I:0
1.)Protection.1.b7.TRPPTRC1:1.TRIP B5
B6
XFMR FAN START
TRPPTRC2_TRIP OR
1.)Protection.2.b7.TRPPTRC2:2.TRIP O:122|T:2.5|I:7
CMMXU1_HIGH_WARN B1 O
TRIP OUTPUT 1 (HV-CB) 1.)Measurement.1.b3.CMMXU1:1.HIGH_WARN B2
X110 (BIO).X110-SO4
HV_CB_OPEN_COMMAND O:??|T:2.5|I:??
CMMXU2_HIGH_WARN
1.)Control_Interlocking.1.d7.OR:6.O 1.)Measurement.1.c3.CMMXU2:2.HIGH_WARN
X100 (PSM).X100-PO3
TRIP LV SIDE CB
LV_CB_OPEN_COMMAND
1.)Logic.1.b7.OR:15.O
X100 (PSM).X100-PO4

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Created by:
BI_BO PAGE 0 06/10/2018 EN 1/2
Rev: Modification: Rel. date: Based on:
1 2 3 4 5 6 7 8

BINARY INPUT/OUTPUT PAGE


Binary inputs - X110 terminal block Binary inputs - X110 terminal block
A LV_CB1_OPENED A
SF6 GAS PRESSURE ALARM
OR OR
B1 O X110_BI1_GAS_PRESSURE_ALARM B1 O X110_BI7_LV_CB1_OPENED
B2 1.)Control_Interlocking.2.c1.NOT.5.IN B2 1.)LED.1.e7.LED10:10.OK
X110 (BIO).X110-Input 1 X110 (BIO).X110-Input 7
O:45|T:2.5|I:27 2.)Supervision.1.b2.SSCBR1:1.PRES_ALM_IN O:79|T:2.5|I:26

CB SPRING CHARGE
OR NOT
B1 O X110_BI2_CB_SPRING_CHARGED IN OUT LV_CB1_CLOSED
B2 1.)Control_Interlocking.2.b1.AND6:0.B2 O:14|T:2.5|I:8 1.)I_O.d6.AND20:0.B3
X110 (BIO).X110-Input 2 2.)I_O.e6.AND6:2.B5
O:57|T:2.5|I:10 2.)Supervision.1.b2.SSCBR1:1.SPR_CHR
3.)Supervision.1.d5.NOT:0.IN LV_CB2_OPENED 3.)LED.1.c7.LED10:10.ALARM

HV CB FAIL OR
B1 O X110_BI8_LV_CB2_OPENED
OR B2 1.)LED.1.e7.LED11:11.OK
B X110 (BIO).X110-Input 8 B
B1 O X110_BI3_HV_CB_FAIL O:78|T:2.5|I:8
B2 1.)I_O.1.b6.OR6:4.B2
X110 (BIO).X110-Input 3
O:88|T:2.5|I:20 2.)I_O.2.c5.OR20:1.B7
3.)Protection.9.c2.CCBRBRF1:1.CB_FAULT
4.)LED.1.b2.OR20.0.B10 NOT
HV_CB_OPENED
IN OUT LV_CB2_CLOSED
OR O:134|T:2.5|I:9 1.)I_O.d6.AND20:0.B4
2.)I_O.e6.AND6:2.B6
B1 O X110_BI4_HV_CB_OPENED 3.)LED.1.e7.LED11:11.ALARM
X110 (BIO).X110-Input 4 B2 1.)Control_Interlocking.1.b3.CBXCBR1:1.POSOPEN
O:11|T:2.5|I:14 2.)Supervision.1.b2.SSCBR1:1.POSOPEN
3.)Supervision.1.d1.OR:19.B1
4.)Supervision.1.d1.OR:0.B1
5.)LED.1.d7.LED9:9.OK
Binary inputs - X130 terminal block
NOT MCB OFF (HV VT)
IN OUT HV_CB_CLOSED X130_BI1_VT_MCB_OPEN
O:12|T:2.5|I:10 1.)I_O.d6.AND20:0.B2 1.)I_O.2.c5.OR20:1.B5
2.)I_O.e6.AND6:2.B2 X130 (AIM).X130-Input 1
2.)Protection.8.d1.OR:22.2
C 3.)Control_Interlocking.1.b3.CBXCBR1:1.POSCLOSE 3.)Supervision.2.b2.SEQRFUF1:1.MINCB_OPEN C
4.)Protection.7.c5.AND:3.B1 4.)LED.1.b2.OR20:0.B11
5.)Protection.9.c2.CCBRBRF1:1.POSCLOSE REMOTE STATUS
6.)Supervision.1.b2.SSCBR1:1.POSCLOSE
7.)Supervision.2.b2.SEQRFUF1:1.CB_CLOSED X130_BI2_REMOTE_OPTR
8.)LED.1.d7.LED9:9.ALARM 1.)General.1.c1.Control:0.CTRL_REM
HV_DS_OPENED X130 (AIM).X130-Input 2

OR FAULT RESET

B1 O X110_BI5_HV_DS_OPENED X130_BI3_EXT_RESET
B2 1.)Control_Interlocking.3.b2.DCSXSWI1:1.POSOPEN 1.)Protection.1.c1.TRPPTRC1:1.RST_LKOUT
X110 (BIO).X110-Input 5 X130 (AIM).X130-Input 3
2.)LED.1.d7.LED8:8.OK 2.)Protection.2.c1.TRPPTRC2:2.RST_LKOUT
O:42|T:2.5|I:4 3.)LED.2.b3.AND6:3.B3
DOWNSTREAM OC BLOCKING
X130_BI4_EXT_OC_BLOCKING
NOT 1.)Protection.5.b2.PHHPTOC1:1.BLOCK
X130 (AIM).X130-Input 4
2.)Protection.5.b6.PHIPTOC2:2.BLOCK
IN OUT HV_DS_CLOSED 3.)Protection.5.b2.PHIPTOC1:1.BLOCK
O:48|T:2.5|I:6 1.)I_O.d6.AND20:0.B1 4.)Protection.5.c2.PHLPTOC1:1.BLOCK
2.)I_O.e6.AND6:2.B1 5.)Protection.5.b6.PHHPTOC2:2.BLOCK
D 3.)Control_Interlocking.3.b2.DCSXSWI1:1.POSCLOSE 6.)Protection.5.c6.PHLPTOC2:2.BLOCK D
4.)Protection.7.c5.AND:3.B2 7.)Protection.6.b2.EFHPTOC2:2.BLOCK
5.)LED.1.d7.LED8:8.ALARM 8.)Protection.6.c2.EFLPTOC2:2.BLOCK
HV_ES_CLOSED 9.)LED.1.b2.OR20:0.B12

OR
B1
B2
O X110_BI6_HV_ES_CLOSED
1.)LED.1.c7.LED7:7.ALARM
mA Inputs - X130 Terminal Block
X110 (BIO).X110-Input 6
O:136|T:2.5|I:3 X130_AI1_TAP_CHANGER_POSITION
1.)Control_Interlocking.4.b3.T_F32_INT8:0.F32

NOT
IN OUT HV_ES_OPENED
O:137|T:2.5|I:7 1.)LED.1.c7.LED7:7.OK
RTD Inputs - X130 Terminal Block
X130_AI3_TRANSFORMER_AMBIENT_TEMP
E 1.)Protection.7.c2.T2PTTR1:1.TEMP_AMB E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Created by:
BI_BO PAGE 0 06/10/2018 EN 2/2
Rev: Modification: Rel. date: Based on:
1 2 3 4 5 6 7 8

CONTROL & INTERLOCKING PAGE


A High Voltage Side Circuit Breaker 1 A

CBXCBR1
X110_BI4_HV_CB_OPENED POSOPEN SELECTED
1.)I_O.1.c4.OR:14.O POSCLOSE EXE_OP CBXCBR1_EXE_OP
ENA_OPEN EXE_CL 1.)Control_Interlocking.1.e6.OR:6.B2
HV_CB_CLOSED ENA_CLOSE OPENPOS
1.)I_O.1.c4.NOT:10.OUT BLK_OPEN CLOSEPOS CBXCBR1_EXE_CL
BLK_CLOSE OKPOS 1.)Control_Interlocking.1.d1.OR:24.B1
TRUE AU_OPEN OPEN_ENAD
1.)General.1.b4.NOT:4.OUT AU_CLOSE CLOSE_ENAD
CBXCBR1_ENA_CLOSE ITL_BYPASS
1.)Control_Interlocking.2.b4.AND6:0.O O:61|T:5|I:1

FALSE
1.)General.1.b4.NOT:3.OUT
CBXCBR1_AU_OPEN
1.)Control_Interlocking.1.c7.OR:16.O
B B
CBXCBR1_AU_CLOSE
1.)Control_Interlocking.1.c4.OR:23.O

External CLOSING command for Circuit Breaker 1 External OPENING command for Circuit Breaker 1
AND AND
CONTROL_LOCAL B1 O CONTROL_LOCAL B1 O
1.)General.1.c3.Control:0.LOCAL B2 1.)General.1.c3.Control:0.LOCAL B2
O:49|T:2.5|I:2 OR O:62|T:2.5|I:1 OR
FALSE FALSE
1.)General.1.b3.NOT:3.OUT CBXCBR1_AU_CLOSE 1.)General.1.b4.NOT:3.OUT CBXBCR1_AU_OPEN
B1 O B1 O
B2 1.)Control_Interlocking.1.b3.CBXCBR1:1.AU_CLOSE B2 1.)Control_Interlocking.1.b3.CBXCBR1:1.AU_OPEN
AND O:58|T:2.5|I:23 AND O:70|T:2.5|I:16

CONTROL_REMOTE B1 O CONTROL_REMOTE B1 O
1.)General.1.c3.Control:0.REMOTE B2 1.)General.1.c4.Control:0.REMOTE B2
O:50|T:2.5|I:0 O:61|T:2.5|I:4
C FALSE FALSE C
1.)General.1.b3.NOT:3.OUT 1.)General.1.b4.NOT:3.OUT

Signals for Closing Coil of High Voltage Side Circuit Breaker 1 Signals for Opening Coil of High Voltage Side Circuit Breaker 1
OR OR
CBXCBR1_EXE_CL B1 O HV_CB_CLOSE_COMMAND TRPPTRC1_TRIP B1 O HV_CB_OPEN_COMMAND
1.)Contro_Interlocking.1.b5.CBXCBR1:1.EXE_CL B2 1.)I_O.2.b6. 1.)Protection.1.b7.TRPPTRC1:1.TRIP B2 1.)I_O.2.e6.
O:64|T:2.5|I:24 2.)Supervision.1.b2.SSCBR1:1.CLOSE_CB_EXE O:74|T:2.5|I:6 2.)Supervision.1.b2.SSCBR1:1.OPEN_CB_EXE
CBXCBR1_EXE_OP
1.)Control_Interlocking.1.b5.CBXCBR1:1.EXE_OP

High Voltage Side Circuit Breaker 1 Close Enable Logic High Voltage Side Disconnector 1
AND6 DCSXSWI1
DCSXSWI1_OKPOS B1 O CBXCBR1_ENA_CLOSE X110_BI5_HV_DS_OPENED POSOPEN OPENPOS
D 1.)Control_Interlocking.3.b3.DCSXSWI1:1.OKPOS B2 1.)Control_Interlocking.1.b3.CBXCBR1:1.ENA_CLOSE 1.)I_O.1.d4.OR:4.O POSCLOSE CLOSEPOS D
B3 OKPOS DCSXSWI1_OKPOS
X110_BI2_CB_SPRING_CHARGE B4 HV_DS_CLOSED 1.)Control_Interlocking.2.b1.AND6:0.B1
O:56|T:5|I:1
1.)Control_Interlocking.3.b3.DCSXSWI1:1.OKPOS B5 1.)I_O.1.d4.NOT:6.OUT
B6
NOT O:60|T:2.5|I:0
Tap Changer Position Indicator
TRPPTRC1_TRIP IN OUT
1.)Protection.1.b7.TRPPTRC1:1.TRIP O:55|T:2.5|I:1 TPOSSLTC1
BI0
BI1
NOT BI2
BI3
TRPPTRC2_TRIP IN OUT BI4
1.)Protection.2.b7.TRPPTRC2:2.TRIP O:54|T:2.5|I:2 T_F32_INT8 BI5
SIGN_BIT
X130_AI1_TAP_CHANGER_POSITION F32 INT8 TAP_POS
1.)I_O.4.b2. O:132|T:2.5|I:0 O:133|T:5|I:1
NOT
E X110_BI1_GAS_PRESSURE_ALARM IN OUT E
1.)I_O.1.b3.OR:27.O O:54|T:2.5|I:2

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Created by:
CONTROL_INTERLOCKING PAGE 0 06/10/2018 EN 1/1
Rev: Modification: Rel. date: Based on:
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


A TRPPTRC1 - Tripping Logic A

TRPPTRC1
OR6 OR6
BLOCK TRIP TRPPTRC1_TRIP
PHIPTOC1_OPERATE B1 O B1 O OPERATE CL_LKOUT 1.)I_O.2.b5.OR20:1.B1
1.)Protection.5.b3.PHIPTOC1:1.OPERATE B2 B2 RST_LKOUT 2.)I_O.2.d5.OR6:7.B2
B3 B3 O:47|T:2.5|I:1 3.)Control_Inerlocking.1.d6.OR:6.B1
PHLPTOC1_OPERATE B4 B4 4.)Control_Inerlocking.2.b1.NOT:1.IN
1.)Protection.5.c3.PHLPTOC1:1.OPERATE B5 B5 5.)Supervision.1.d1.OR:19.B2
B6 B6 6.)LED.2.a2.NOT:14.IN
PHHPTOC1_OPERATE 7.)LED.2.b2.NOT:15.IN
1.)Protection.5.b3.PHHPTOC1:1.OPERATE O:36|T:2.5|I:14 O:51|T:2.5|I:2

NSPTOC1_OPERATE
1.)Protection.7.b3.NSPTOC1:1.OPERATE

OR6
TR2PTDF1_OPERATE B1 O
1.)Protection.7.d3.TR2PTDF1:1.OPERATE B2
B B3 B
HREFPNDF1_OPERATE B4
1.)Protection.6.b7.HREFPDIF1:1.OPERATE B5
B6
CCBRBRF1_TRRET
1.)Protection.9.b6.CCBRBRF1:1.TRRET O:35|T:2.5|I:5

OR6
ROVPTOV1_OPERATE B1 O
1.)Protection.8.b3.ROVPTOV1:1.OPERATE B2
B3
ROVPTOV2_OPERATE B4
1.)Protection.8.b3.ROVPTOV2:2.OPERATE B5
B6
PHPTOV1_OPERATE
1.)Protection.8.b7.PHPTOV1:1.OPERATE O:37|T:2.5|I:13

PHPTOV2_OPERATE
1.)Protection.8.b7.PHPTOV2:2.OPERATE
PHPTUV1_OPERATE
C 1.)Protection.8.d3.PHPTUV1:1.OPERATE C
PHPTUV2_OPERATE
1.)Protection.8.d3.PHPTUV2:2.OPERATE
X110_BI1_RST_LOCKOUT
1.)I_O.3.c3

TRPPTRC2 - Tripping Logic


TRPPTRC2
OR6 OR6
BLOCK TRIP TRPPTRC2_TRIP
PHLPTOC2_OPERATE B1 O B1 O OPERATE CL_LKOUT 1.)I_O.2.b5.OR20:1.B2
1.)Protection.5.c7.PHLPTOC2:2.OPERATE B2 B2 RST_LKOUT 2.)I_O.2.d5.OR6:7.B3
B3 B3 O:55|T:2.5|I:2 3.)Control_Inerlocking.2.c1.NOT:2.IN
PHHPTOC2_OPERATE B4 B4 4.)Supervision.1.d1.OR:0.B2
1.)Protection.5.b7.PHHPTOC2:2.OPERATE B5 B5 5.)Logic.1.b6.OR:15.B1
B6 B6
PHIPTOC2_OPERATE
1.)Protection.5.b7.PHIPTOC2:2.OPERATE O:45|T:2.5|I:21 O:50|T:2.5|I:19

D EFLPTOC2_OPERATE D
1.)Protection.6.c3.EFLPTOC2:2.OPERATE
EFHPTOC2_OPERATE
1.)Protection.6.b3.EFHPTOC2:2.OPERATE
NSPTOC2_OPERATE
1.)Protection.7.b7.NSPTOC2:2.OPERATE

OR6
TR2PTDF1_OPERATE B1 O
1.)Protection.7.d3.TR2PTDF1:1.OPERATE B2
B3
HREFPNDF1_OPERATE B4
1.)Protection.6.b7.HREFPDIF1:1.OPERATE B5
B6
CCBRBRF1_TRRET
1.)Protection.9.b6.CCBRBRF1:1.TRRET O:43|T:2.5|I:27

T2PTTR1_OPERATE
E 1.)Protection.7.c3.T2PTTR1:1.OPERATE E
X110_BI1_RST_LOCKOUT
1.)I_O.3.c3

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 1/6
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


A General Start Logic General Operate Logic A

OR6 OR6 OR6 OR6


PHLPTOC1_START B1 O B1 O GENERAL_START PHLPTOC1_OPERATE B1 O B1 O GENERAL_OPERATE
1.)Protection.5.c3.PHLPTOC1:1.START B2 B2 1.)I_O.2.d6 1.)Protection.5.c3.PHLPTOC1:1.OPERATE B2 B2 1.)I_O.2.d5.OR6:7.B1
B3 B3 2.)LED.2.b2.NOT:12.IN B3 B3 2.)LED.2.b2.NOT:13.IN
PHIPTOC1_START B4 B4 PHIPTOC1_OPERATE B4 B4
1.)Protection.5.b3.PHIPTOC1:1.START B5 B5 1.)Protection.5.b3.PHIPTOC1:1.OPERATE B5 B5
B6 B6 B6 B6
PHHPTOC1_START PHHPTOC1_OPERATE
1.)Protection.5.b3.PHHPTOC1:1.START O:76|T:2.5|I:18 O:90|T:2.5|I:0 1.)Protection.5.b3.PHHPTOC1:1.OPERATE O:73|T:2.5|I:17 O:89|T:2.5|I:2

PHLPTOC2_START PHLPTOC2_OPERATE
1.)Protection.5.c7.PHLPTOC2:2.START 1.)Protection.5.c7.PHLPTOC2:2.OPERATE
PHIPTOC2_START PHIPTOC2_OPERATE
1.)Protection.5.b7.PHIPTOC2:2.START 1.)Protection.5.b7.PHIPTOC2:2.OPERATE
PHHPTOC2_START PHHPTOC2_OPERATE
1.)Protection.5.b7.PHHPTOC2:2.START 1.)Protection.5.b7.PHHPTOC2:2.OPERATE
B B
OR6
OR6
EFHPTOC2_START B1 O
1.)Protection.6.b3.EFHPTOC2:2.START B2 EFHPTOC2_OPERATE B1 O
B3 1.)Protection.6.b3.EFHPTOC2:2.OPERATE B2
EFLPTOC2_START B4 B3
1.)Protection.6.c3.EFLPTOC2:2.START EFLPTOC2_OPERATE B4
B5 1.)Protection.6.c3.EFLPTOC2:2.OPERATE
B6 B5
NSPTOC1_START B6
1.)Protection.7.b3.NSPTOC1:1.START O:77|T:2.5|I:1 NSPTOC1_OPERATE
1.)Protection.7.b3.NSPTOC1:1.OPERATE O:71|T:2.5|I:32
NSPTOC2_START
1.)Protection.7.b7.NSPTOC2:2.START NSPTOC2_OPERATE
1.)Protection.7.b7.NSPTOC2:2.OPERATE
HREFPNDF1_START
1.)Protection.6.b7.HREFPDIF1:1.START TR2PTDF1_OPERATE
1.)Protection.7.d3.TR2PTDF1:1.OPERATE
T2PTTR1_START
1.)Protection.7.c3.T2PTTR1:1.START
OR6
OR6 HREFPNDF1_OPERATE B1 O
C 1.)Protection.6.b7.HREFPDIF1:1.OPERATE B2 C
ROVPTOV1_START B1 O
1.)Protection.8.b3.ROVPTOV1:1.START B2 B3
T2PTTR1_OPERATE B4
B3 1.)Protection.7.c3.T2PTTR1:1.OPERATE
ROVPTOV2_START B4 B5
1.)Protection.8.b3.ROVPTOV2:2.START B5 B6
ARCSARC1_OPERATE
B6 1.)Optional_Functions.1.b5. O:72|T:2.5|I:31
PHPTOV1_START
1.)Protection.8.b7.PHPTOV1:1.START O:75|T:2.5|I:9
ARCSARC2_OPERATE
PHPTOV2_START 1.)Optional_Functions.1.c5.
1.)Protection.8.b7.PHPTOV2:2.START ARCSARC3_OPERATE
PHPTUV1_START 1.)Optional_Functions.1.c5.
1.)Protection.8.d3.PHPTUV1:1.START
PHPTUV2_START
1.)Protection.8.d3.PHPTUV2:2.START
AND6
ROVPTOV1_OPERATE B1 O
1.)Protection.8.b3.ROVPTOV1:1.OPERATE B2
D B3 D
ROVPTOV2_OPERATE B4
1.)Protection.8.b3.ROVPTOV2:2.OPERATE B5
B6
PHPTOV1_OPERATE
1.)Protection.8.b7.PHPTOV1:1.OPERATE O:74|T:2.5|I:1

PHPTOV2_OPERATE
1.)Protection.8.b7.PHPTOV2:2.OPERATE
PHPTUV1_OPERATE
1.)Protection.8.d3.PHPTUV1:1.OPERATE
PHPTUV2_OPERATE
1.)Protection.8.d3.PHPTUV2:2.OPERATE

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 2/6
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


High Voltage Side Overcurrent Protection Function Low Voltage Side Overcurrent Protection Function
A A
PHIPTOC1 PHIPTOC2
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHIPTOC1_OPERATE X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHIPTOC2_OPERATE
1.)I_O.3.c3. ENA_MULT START 1.)Protection.1.b1.OR6:14.B3 1.)I_O.3.c3. ENA_MULT START 1.)Protection.2.b1.OR6:21.B3
O:25|T:2.5|I:1 2.)Protection.4.c1.OR6:17.B2 O:20|T:2.5|I:2 2.)Protection.4.c1.OR6:17.B5
3.)Protection.5.c2.OR6:22.B1 3.)Protection.5.c6.OR6:26.B1
4.)Protection.9.b2.OR6:6.B1 4.)Disturbance_Recorder.1.c4.RDRE:1.C23
5.)Disturbance_Recorder.1.c4.RDRE:1.C20
PHIPTOC2_START
PHIPTOC1_START 1.)Protection.4.a1.OR6:18.B5
1.)Protection.4.a1.OR6:18.B2 2.)Disturbance_Recorder.1.b4.RDRE:1.C4
2.)Disturbance_Recorder.1.b4.RDRE:1.C1
PHHPTOC2
PHHPTOC1
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHHPTOC2_OPERATE
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHHPTOC1_OPERATE 1.)I_O.3.c3. ENA_MULT START 1.)Protection.2.b1.OR6:21.B2
1.)I_O.3.c3. ENA_MULT START 1.)Protection.1.b1.OR6:14.B2 O:18T:5|I:2 2.)Protection.4.c1.OR6:17.B6
O:24T:5|I:1 2.)Protection.4.c1.OR6:17.B3 3.)Protection.5.d6.OR6:26.B2
3.)Protection.5.d2.OR6:22.B2 4.)Disturbance_Recorder.1.c4.RDRE:1.C24
4.)Protection.9.b2.OR6:6.B2
B 5.)Disturbance_Recorder.1.c4.RDRE:1.C21 PHIPTOC2_START B
1.)Protection.4.a1.OR6:18.B6
PHIPTOC1_START 2.)Disturbance_Recorder.1.b4.RDRE:1.C5
1.)Protection.4.a1.OR6:18.B3
2.)Disturbance_Recorder.1.b4.RDRE:1.C2
PHLPTOC1
PHLPTOC1 X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHLPTOC2_OPERATE
1.)I_O.3.c3. ENA_MULT START 1.)Protection.2.b1.OR6:21.B1
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE PHLPTOC1_OPERATE O:23|T:5|I:1 2.)Protection.4.c1.OR6:17.B4
1.)I_O.3.c3. ENA_MULT START 1.)Protection.1.b1.OR6:14.B1 3.)Protection.5.d6.OR6:26.B3
O:23|T:5|I:1 2.)Protection.4.c1.OR6:17.B1 4.)Disturbance_Recorder.1.c4.RDRE:1.C22
3.)Protection.5.d2.OR6:22.B3
4.)Protection.9.b2.OR6:6.B3 PHLPTOC2_START
5.)Disturbance_Recorder.1.c4.RDRE:1.C19 1.)Protection.4.a1.OR6:18.B4
2.)Disturbance_Recorder.1.b4.RDRE:1.C6
PHLPTOC1_START
1.)Protection.4.a1.OR6:18.B1
2.)Disturbance_Recorder.1.b4.RDRE:1.C3

Grouped Function Operate Grouped Function Operate


C C
OR6 OR6
PHIPTOC1_OPERATE B1 O PHxPTOC_OPERATE_HVSIDE PHIPTOC2_OPERATE B1 O PHxPTOC_OPERATE_LVSIDE
1.)Protection.5.b3.PHIPTOC1:1.OPERATE B2 1.)Logic.1.b1.OR6:16.B1 1.)Protection.5.b7.PHIPTOC2:2.OPERATE B2 1.)Logic.1.b1.OR6:16.B2
B3 2.)LED.1.d3.LED3:3.ALARM B3 2.)LED.1.e2.OR:33.B1
PHHPTOC1_OPERATE B4 PHHPTOC2_OPERATE B4
1.)Protection.5.b3.PHHPTOC1:1.OPERATE B5 1.)Protection.5.b7.PHHPTOC2:2.OPERATE B5
B6 B6
PHLPTOC1_OPERATE PHLPTOC2_OPERATE
1.)Protection.5.c3.PHLPTOC1:1.OPERATE O:111|T:2.5|I:22 1.)Protection.5.c7.PHLPTOC2:2.OPERATE O:118|T:2.5|I:26

Low Voltage Side Earth-Fault Protection Function Low Voltage Side Restricted Earth-Fault Protection Function
EFHPTOC2 HREFPDIF1
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE EFHPTOC2_OPERATE BLOCK OPERATE HREFPNDF1_OPERATE
1.)I_O.3.c3. ENA_MULT START 1.)Protection.2.b1.OR6:21.B5 START 1.)Protection.1.b1.OR6:5.B2
O:19|T:5|I:2 2.)Protection.4.c1.OR6:32.B1 O:15|T:2.5|I:1 2.)Protection.2.b1.OR6:27.B2
3.)Protection.6.c2.OR:7.B1 3.)Protection.4.d1.OR6:31.B1
D 4.)Disturbance_Recorder.1.c4.RDRE:1.C26 4.)Protection.9.b2.OR6:8.B2 D
5.)Logic.1.b1.OR6:18.B2
EFHPTOC2_START 6.)Disturbance_Recorder.1.c4.RDRE:1.C38
1.)Protection.4.b1.OR6:1.B1 7.)LED.1.c2.OR6:20.B3
2.)Disturbance_Recorder.1.b4.RDRE:1.C7 HREFPNDF1_START
EFLPTOC2 1.)Protection.4.b1.OR6:1.B5
2.)Disturbance_Recorder.1.b4.RDRE:1.C11
X130_BI4_EXT_OC_BLOCKING BLOCK OPERATE EFLPTOC2_OPERATE
1.)I_O.3.c3. ENA_MULT START 1.)Protection.2.b1.OR6:21.B4
O:22T:5|I:2 2.)Protection.4.c1.OR6:32.B2
3.)Protection.6.c2.OR:7.B2
4.)Disturbance_Recorder.1.c4.RDRE:1.C25
EFLPTOC2_START
1.)Protection.4.b1.OR6:1.B2
2.)Disturbance_Recorder.1.b4.RDRE:1.C8

Grouped Function Operate


E OR E
EFHPTOC2_OPERATE B1 O EFxPTOC_OPERATE_LVSIDE
1.)Protection.6.b3.EFHPTOC2:2.OPERATE B2 1.)Logic.1.b1.OR6:16.B3
O:119|T:2.5|I:7 2.)LED.1.e2.OR:33.B2
EFLPTOC2_OPERATE
1.)Protection.6.c3.EFLPTOC2:2.OPERATE

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 3/6
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


High Voltage Side Negative Sequence Overcurrent Protection Function Low Voltage Side Negative Sequence Overcurrent Protection Function
A A
NSPTOC1 NSPTOC2
BLOCK OPERATE NSPTOC1_OPERATE BLOCK OPERATE NSPTOC2_OPERATE
ENA_MULT START 1.)Protection.1.b1.OR6:14.B4 ENA_MULT START 1.)Protection.2.b1.OR6:21.B6
O:26|T:5|I:1 2.)Protection.4.d1.OR6:32.B3 O:33|T:5|I:2 2.)Protection.4.d1.OR6:32.B4
3.)Protection.9.b2.OR6:6.B4 3.)Logic.1.b1.OR6:16.B5
4.)Logic.1.b1.OR6:16.B4 4.)Disturbance_Recorder.1.c4.RDRE:1.C28
5.)Disturbance_Recorder.1.c4.RDRE:1.C27 5.)LED.1.b6.OR:2.B2
6.)LED.1.b6.OR:2.B1
NSPTOC2_START
NSPTOC1_START 1.)Protection.4.b1.OR6:1.B4
1.)Protection.4.b1.OR6:1.B3 2.)Disturbance_Recorder.1.b4.RDRE:1.C10
2.)Disturbance_Recorder.1.b4.RDRE:1.C9
Transformer Operation Time Counter
Transformer Thermal Overload Protection Function
MDSOPT1
T2PTTR1 AND
BLOCK ALARM MDSOPT1_ALARM
BLOCK OPERATE T2PTTR1_OPERATE HV_CB_CLOSED B1 O POS_ACTIVE WARNING
B X130_AI3_TRANSFORMER_AMBIENT_TEMP TEMP_AMB START 1.)Protection.2.b1. 1.)I_O.1.c4.NOT:10.OUT B2 RESET B
1.)I_O.4.c2. ALARM 2.)Protection.4.d1.OR6:31.B2 O:128|T:2.5|I:3 O:129|T:5|I:1
BLK_CLOSE 3.)Logic.1.b1.OR6:16.B6 HV_DS_CLOSED
4.)Disturbance_Recorder.1.d4.RDRE:1.C39 1.)I_O.1.d4.NOT:6.OUT
O:65|T:5|I:1
T2PTTR1_START
1.)Protection.4.b1.OR6:1.B6
2.)Disturbance_Recorder.1.b4.RDRE:1.C12
T2PTTR1_ALARM
1.)Disturbance_Recorder.1.d4.RDRE:1.C40
T2PTTR1_BLK_CLOSE
1.)Disturbance_Recorder.1.c4.RDRE:1.C34

Transformer Differential Protection Function


TR2PTDF1
BLOCK OPERATE TR2PTDF1_OPERATE
BLK_OPR_LS OPR_LS 1.)Protection.1.b1.OR6:5.B1
BLK_OPR_HS OPR_HS 2.)Protection.2.b1.OR6:27.B1
C BLKD2H 3.)Protection.4.d1.OR6:32.B5 C
BLKD5H 4.)Protection.9.b2.OR6:8.B1
BLKDWAV 5.)Logic.1.b1.OR:18.B1
6.)Disturbance_Recorder.1.c4.RDRE:1.C35
O:16|T:2.5|I:1
TR2PTDF1_OPR_LS
1.)Disturbance_Recorder.1.c4.RDRE:1.C36
2.)LED.1.c2.OR6:20.B2
TR2PTDF1_OPR_HS
1.)Disturbance_Recorder.1.c4.RDRE:1.C37
2.)LED.1.c2.OR6:20.B1
TR2PTDF1_BLKD2H
TR2PTDF1_BLKD5H
TR2PTDF1_BLKDWAV

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 4/6
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


High Voltage Side Residual Overvoltage Protection Function High Voltage Side Phase Overvoltage Protection Function
A A
ROVPTOV1 PHPTOV1
BLOCK OPERATE ROVPTOV1_OPERATE BLOCK OPERATE PHPTOV1_OPERATE
START 1.)Protection.1.c1.OR6:13.B1 START 1.)Protection.1.c1.OR6:13.B3
O:29|T:5|I:1 2.)Protection.4.e1.AND6:1.B1 O:28|T:5|I:1 2.)Protection.4.e1.AND6:1.B3
3.)Protection.8.c2.OR:5.B1 3.)Protection.8.c6.OR:21.B1
4.)Disturbance_Recorder.1.c4.RDRE:1.C29 4.)Disturbance_Recorder.1.c4.RDRE:1.C31
ROVPTOV1_START PHPTOV1_START
1.)Protection.4.b1.OR6:9.B1 1.)Protection.4.b1.OR6:9.B3
2.)Disturbance_Recorder.1.b4.RDRE:1.C13 2.)Disturbance_Recorder.1.b4.RDRE:1.C15
ROVPTOV2 PHPTOV2
BLOCK OPERATE ROVPTOV2_OPERATE BLOCK OPERATE PHPTOV2_OPERATE
START 1.)Protection.1.c1.OR6:13.B2 START 1.)Protection.1.c1.OR6:13.B4
O:27|T:5|I:2 2.)Protection.4.e1.AND6:1.B2 O:31|T:5|I:2 2.)Protection.4.e1.AND6:1.B4
3.)Protection.8.c2.OR:5.B2 3.)Protection.8.c6.OR:21.B2
4.)Disturbance_Recorder.1.c4.RDRE:1.C30 4.)Disturbance_Recorder.1.c4.RDRE:1.C32
ROVPTOV2_START PHPTOV2_START
B 1.)Protection.4.b1.OR6:9.B2 1.)Protection.4.b1.OR6:9.B4 B
2.)Disturbance_Recorder.1.b4.RDRE:1.C14 2.)Disturbance_Recorder.1.b4.RDRE:1.C16

Grouped Function Operate Grouped Function Operate


OR OR
ROVPTOV1_OPERATE B1 O ROVPTOV_OPERATE PHPTOV1_OPERATE B1 O PHPTOV_OPERATE
1.)Protection.8.b3.ROVPTOV1:1.OPERATE B2 1.)Logic.1.c1.OR6:10.B3 1.)Protection.8.b7.PHPTOV1:1.OPERATE B2 1.)Logic.1.c1.OR6:10.B1
O:113|T:2.5|I:5 2.)LED.1.b6.OR6:29.B3 O:114|T:2.5|I:21 2.)LED.1.b6.OR6:29.B1
ROVPTOV2_OPERATE PHPTOV2_OPERATE
1.)Protection.8.b3.ROVPTOV2:2.OPERATE 1.)Protection.8.b7.PHPTOV2:2.OPERATE

High Voltage Side Phase Undervoltage Protection Function


OR PHPTUV1
SEQRFUF1_FUSEF_U B1 O BLOCK OPERATE PHPTUV1_OPERATE
1.)Supervision.2.b3.SEQRFUF1:1.FUSEF_U B2 START 1.)Protection.1.c1.OR6:13.B5
O:113|T:2.5|I:5 O:37|T:5|I:1 2.)Protection.4.e1.AND6:1.B5
C X130_BI1_HV_VT_MCB_OPEN 3.)Protection.8.e2.OR:17.B1 C
1.)I_O.3.b3. 4.)Disturbance_Recorder.1.c4.RDRE:1.C33
PHPTUV1_START
1.)Protection.4.b1.OR6:9.B5
2.)Disturbance_Recorder.1.b4.RDRE:1.C17
PHPTUV2
BLOCK OPERATE PHPTUV2_OPERATE
START 1.)Protection.1.c1.OR6:13.B6
O:39|T:5|I:2 2.)Protection.4.e1.AND6:1.B6
3.)Protection.8.e2.OR:17.B2
4.)Disturbance_Recorder.1.c4.RDRE:1.C34
PHPTUV2_START
1.)Protection.4.c1.OR6:9.B6
2.)Disturbance_Recorder.1.c4.RDRE:1.C18

Grouped Function Operate


D OR D
PHPTUV1_OPERATE B1 O PHPTUV_OPERATE
1.)Protection.8.d3.PHPTUV1:1.OPERATE B2 1.)Logic.1.c1.OR6:10.B2
O:109|T:2.5|I:17 2.)LED.1.b6.OR6:29.B2
PHPTUV2_OPERATE
1.)Protection.8.d3.PHPTUV2:2.OPERATE

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 5/6
1 2 3 4 5 6 7 8

PROTECTION FUNCTION PAGE


CB Failure Protection Function
A A
CCBRBRF1
OR6 OR6
BLOCK CB_FAULT_AL CCBRBRF1_TRBU
PHIPTOC1_OPERATE B1 O B1 O START TRBU 1.)LED.1.b2.OR20:0.B4
1.)Protection.5.b3.PHIPTOC1:1.OPERATE B2 B2 POSCLOSE TRRET CCBRBRF1_TRBU
B3 B3 CB_FAULT
PHHPTOC1_OPERATE 1.)I_O.1.c5.AND:7.B2
B4 B4 O:95|T:2.5|I:1 2.)I_O.2.c5.OR20:1.B9
1.)Protection.5.b3.PHHPTOC1:1.OPERATE B5 B5 3.)LED.1.b2.OR20:0.B6
B6 B6
PHLPTOC1_OPERATE CCBRBRF1_TRRET
1.)Protection.5.c3.PHLPTOC1:1.OPERATE O:70|T:2.5|I:6 O:87|T:2.5|I:11
1.)I_O.1.c5.AND:7.B1
2.)I_O.2.c5.OR20:1.B8
NSPTOC1_OPERATE 3.)Protection.1.b1.
1.)Protection.7.b3.NSPTOC1:1.OPERATE 4.)Protection.2.b1.
5.)LED.1.b2.OR20:0.B5
OR6
TR2PTDF1_OPERATE B1 O
1.)Protection.7.d3.TR2PTDF1:1.OPERATE B2
B3
HREFPNDF1_OPERATE B4
B 1.)Protection.6.b7.HREFPDIF1:1.OPERATE B
B5
B6
O:69|T:2.5|I:8

HV_CB_CLOSED
1.)I_O.1.c4.NOT:10.OUT
AND
HV_CB_CLOSED B1 O
1.)I_O.1.c4.NOT:10.OUT B2
O:2|T:2.5|I:6
TRPPTRC1_TRIP
1.)Protection.1.b7.TRPPTRC1:1.TRIP

C C

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
PROTECTION PAGE 0 06/10/2018 EN 6/6
1 2 3 4 5 6 7 8

SUPERVISION FUNCTION PAGE


A Circuit Breaker Condition Monitoring Function Logic for Circuit Breaker Monitoring Alarm A

SSCBR1 OR6
BLOCK TRV_T_OP_ALM SSCBR1_TRV_T_OP_ALM SSCBR1_TRV_T_OP_ALM B1 O
X110_BI4_HV_CB_OPENED POSOPEN TRV_T_CL_ALM 1.)Supervision.1.b5.OR6:28.B1 1.)Supervision.1.b3.SSCBR1:1.TRV_T_OP_ALM B2
1.)I_O.1.c4.OR:14.O POSCLOSE SPR_CHR_ALM B3
OPEN_CB_EXE OPR_ALM SSCBR1_TRV_T_CL_ALM SSCBR1_TRV_T_CL_ALM B4
HV_CB_CLOSED CLOSE_CB_EXE OPR_LO 1.)Supervision.1.b5.OR6:28.B2 1.)Supervision.1.b3.SSCBR1:1.TRV_T_CL_ALM B5
1.)I_O.1.c4.NOT:10.OUT PRES_ALM_IN IPOW_ALM B6
SSCBR1_SPR_CHR_ALM SSCBR1_SPR_CHR_ALM
PRES_LO_IN IPOW_LO O:83|T:2.5|I:28
HV_CB_OPEN_COMMAND SPR_CHR_ST CB_LIFE_ALM 1.)Supervision.1.b5.OR6:28.B3 1.)Supervision.1.b3.SSCBR1:1.SPR_CHR_ALM
1.)Control_Interlocking.1.d7.OR:6.O SPR_CHR MON_ALM OR
SSCBR1_OPR_ALM SSCBR1_OPR_ALM
HV_CB_CLOSE_COMMAND RST_IPOW PRES_ALM 1.)Supervision.1.b5.OR6:28.B4 1.)Supervision.1.b3.SSCBR1:1.OPR_ALM
RST_CB_WEAR PRES_LO B1 O SSCBR1_ALARMS
1.)Control_Interlocking.1.d3.OR:24.O B2 1.)I_O.1.c5.OR20:1.B4
RST_TRV_T OPENPOS SSCBR1_OPR_LO SSCBR1_OPR_LO
X110_BI_GAS_PRESSURE_ALARM RST_SPR_T INVALIDPOS 1.)Supervision.1.b3.SSCBR1:1.OPR_LO O:93|T:2.5|I:25 2.)LED.1.a2.OR20:0.B3
1.)Supervision.1.b5.OR6:28.B5
1.)I_O.1.b3.OR:27.O CLOSEPOS
O:76|T:5|I:1 SSCBR1_IPOW_ALM SSCBR1_IPOW_ALM
CB_SPRING_DISCHARGED 1.)Supervision.1.b5.OR6:28.B6 1.)Supervision.1.b3.SSCBR1:1.IPOW_ALM
B 1.)Supervision.1.d7.NOT:0.OUT B
SSCBR1_IPOW_LO
X110_BI2_CB_SPRING_CHARGED 1.)Supervision.1.b5.OR6:15.B1 OR6
1.)I_O.1.b3.OR:9.O
SSCBR1_CB_LIFE_ALM SSCBR1_IPOW_LO B1 O
1.)Supervision.1.c5.OR6:15.B2 1.)Supervision.1.b3.SSCBR1:1.IPOW_LO B2
B3
SSCBR1_MON_ALM SSCBR1_CB_LIFE_ALM B4
1.)Supervision.1.c5.OR6:15.B3 1.)Supervision.1.b3.SSCBR1:1.CB_LIFE_ALM B5
B6
SSCBR1_PRES_ALM SSCBR1_MON_ALM
1.)Supervision.1.c5.OR6:15.B4 1.)Supervision.1.b3.SSCBR1:1.MON_ALM O:84|T:2.5|I:15

SSCBR1_PRES_LO SSCBR1_PRES_ALM
1.)Supervision.1.c5.OR6:15.B5 1.)Supervision.1.b3.SSCBR1:1.PRES_ALM
SSCBR1_INVALIDPOS SSCBR1_PRES_LO
1.)Supervision.1.c5.OR6:15.B6 1.)Supervision.1.b3.SSCBR1:1.PRES_LO
SSCBR1_INVALIDPOS
1.)Supervision.1.b3.SSCBR1:1.INVALIDPOS

C Circuit Supervision for HV Side Breaker Trip Circuit Logic for Circuit Breaker Spring Charging C

OR TCSSCBR1 NOT
X110_BI4_HV_CB_OPENED B1 O BLOCK ALARM TCSSCBR1_ALARM X110_BI2_CB_SPRING_CHARGED IN OUT CB_SPRING_DISCHARGED
1.)I_O.1.c4.OR:14.O B2 O:80|T:5|I:1 1.)I_O.1.b6.OR:37.B1 1.)I_O.1.b3.OR:9.O O:65|T:2.5|I:1 1.)Supervision.1.b2.SSCBR1:1.SPR_CHR_ST
O:77|T:2.5|I:19 2.)Supervision.1.e2.OR:11.B1
TRPPTRC1_TRIP
1.)Protection.1.b7.TRPPTRC1:1.TRIP

Circuit Supervision for LV Side Breaker Trip Circuit HV Side Fuse Failure Supervision Function
OR TCSSCBR2 SEQRFUF1
X110_BI4_HV_CB_OPENED B1 O BLOCK ALARM TCSSCBR2_ALARM BLOCK FUSEF_3PH SEQRFUF1_FUSEF_3PH
1.)I_O.1.c4.OR:14.O B2 O:81|T:5|I:2 1.)I_O.1.b6.OR:37.B2 HV_CB_CLOSED CB_CLOSED FUSEF_U 1.)LED.1.b2.OR20:0.B7
O:68|T:2.5|I:0 2.)Supervision.1.e2.OR:11.B2 1.)I_O.1.c4.NOT:10.OUT DISCON_OPEN
TRPPTRC2_TRIP MINCB_OPEN
1.)Protection.2.b7.TRPPTRC2:2.TRIP X130_BI1_HV-VT_MCB_OPEN SEQRFUF1_FUSEF_U
D O:13|T:2.5|I:1 1.)Protection.8.d1.OR:22.B1 D
1.)I_O.3.b3.
2.)LED.1.b2.OR20:0.B8

Group Function Alarm


OR
TCSSCBR1_ALARM B1 O TCSSCBR_ALARM
1.)Supervision.1.d4.TCSSCBR1:1.ALARM B2 1.)I_O.2.c5.OR20:1.B3
O:68|T:2.5|I:0 2.)LED.1.a2.OR20:0.B2
TCSSCBR2_ALARM
1.)Supervision.1.d4.TCSSCBR2:2.ALARM

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
SUPERVISION PAGE 0 06/10/2018 EN 1/1
1 2 3 4 5 6 7 8

LOGIC PAGE
A Timer Logic for Overcurrent operate and Differential operate Logic for Low Voltage Side Circuit Breaker Opening Command A

OR6 OR
PHxPTOC_OPERATE_HVSIDE B1 O OC_OPERATE_PULSE TRPPTRC2_TRIP B1 O LV_CB_OPEN_COMMAND
1.)Protection.5.d3.OR6:22.O B2 DIFFERENTIAL_OPERATE_PULSE 1.)Protection.2.b7.TRPPTRC2:2.TRIP B2 1.)I_O.2.e6.
B3 O:126|T:2.5|I:15
PHxPTOC_OPERATE_LVSIDE B4
1.)Protection.5.d7.OR6:26.O B5
B6
EFxPTOC_OPERATE_LVSIDE
1.)Protection.6.c3.OR:7.O O:130|T:2.5|I:16

NSPTOC1_OPERATE
1.)Protection.7.b3.NSPTOC1:1.OPERATE
NSPTOC2_OPERATE
1.)Protection.7.b7.NSPTOC2:2.OPERATE
T2PTTRR1_OPERATE
1.)Protection.7.c3.T2PTTR1:1.OPERATE
B B

OR
TR2PTDF1_OPERATE B1 O
1.)Protection.7.d3.TR2PTDF1:1.OPERATE B2
O:131|T:2.5|I:18
HREFPNDF1_OPERATE
1.)Protection.6.b7.HREFPDIF1:1.OPERATE

Timer Logic for Voltage Protection Operate, Blackout, DC MCB Off Alarm
OR6
PHPTOV_OPERATE B1 O VOLTAGE_PROT_OPERATE_PULSE
1.)Protection.8.c7.OR:21.O B2 BLACKOUT_DCMCB_OFF_PULSE
B3
PHPTUV_OPERATE B4
C 1.)Protection.8.e3.OR:17.O
C
B5
B6
ROVPTOV_OPERATE
1.)Protection.8.c3.OR:5.O O:123|T:2.5|I:10

OR
B1 O
BLACKOUT_STATUS B2
1.)I_O.1.d7.AND20:0.O O:127|T:2.5|I:1

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
LOGIC PAGE 0 06/10/2018 EN 1/1
E
B
A

D
C

Rev:
1/1

Modification:
1
1

RDRE
RDRE1
PHIPTOC1_START C1 TRIGGERED DISTURB_RECORD_TRIGGERED
1.)Protection.5.b3.PHIPTOC1:1.START C2 1.)LED.1.a2.OR20:0.B1
C3
PHHPTOC1_START C4
1.)Protection.5.b3.PHHPTOC1:1.START C5

Rel. date:
C6
PHLPTOC1_START
C7
1.)Protection.5.c3.PHLPTOC1:1.START
C8
PHIPTOC2_START C9
1.)Protection.5.b7.PHIPTOC2:2.START C10
C11
PHHPTOC2_START C12
1.)Protection.5.b7.PHHPTOC2:2.START C13
C14
PHLPTOC2_START C15

Created by:
1.)Protection.5.c7.PHLPTOC2:2.START C16
C17
EFHPTOC2_START C18
1.)Protection.6.b3.EFHPTOC2:2.START C19
EFLPTOC2_START C20
1.)Protection.6.c3.EFLPTOC2:2.START C21

2
2

C22
NSPTOC1_START C23

Based on:
Replacing:
1.)Protection.7.b3.NSPTOC1:1.START C24
C25
NSPTOC2_START C26
1.)Protection.7.b7.NSPTOC2:2.START C27
C28
HREFPNDF1_START C29
1.)Protection.6.b7.HREFPDIF1:1.START C30

Project:
C31
T2PTTR1_START C32

Substation:
1.)Protection.7.c3.T2PTTR1:1.START C33
ROVPTOV1_START C34
1.)Protection.8.b3.ROVPTOV1:1.START C35
C36
ROVPTOV2_START C37
1.)Protection.8.b3.ROVPTOV2:2.START C38
C39
PHPTOV1_START C40
1.)Protection.8.b7.PHPTOV1:1.START C41
C42
PHPTOV2_START C43
1.)Protection.8.b7.PHPTOV2:2.START C44
C45
PHPTUV1_START
C46
1.)Protection.8.d3.PHPTUV1:1.START

3
3

C47
PHPTUV2_START C48
1.)Protection.8.d3.PHPTUV2:2.START C49
C50
PHLPTOC1_OPERATE C51
1.)Protection.5.c3.PHLPTOC1:1.OPERATE C52
C53
PHIPTOC1_OPERATE C54
1.)Protection.5.b3.PHIPTOC1:1.OPERATE C55

LUELCO
C56
PHHPTOC1_OPERATE C57
1.)Protection.5.b3.PHHPTOC1:1.OPERATE C58
C59
PHLPTOC2_OPERATE
C60
1.)Protection.5.c7.PHLPTOC2:2.OPERATE
C61
PHIPTOC2_OPERATE C62
1.)Protection.5.b7.PHIPTOC2:2.OPERATE C63
C64
PHHPTOC2_OPERATE O:97|T:2.5|I:1

15/18.75MVA AGOO SUBSTATION


1.)Protection.5.b7.PHHPTOC2:2.OPERATE
EFLPTOC2_OPERATE
1.)Protection.6.c3.EFLPTOC2:2.OPERATE
EFHPTOC2_OPERATE
1.)Protection.6.b3.EFHPTOC2:2.OPERATE

4
4

NSPTOC1_OPERATE
1.)Protection.7.b3.NSPTOC1:1.OPERATE
NSPTOC2_OPERATE
1.)Protection.7.b7.NSPTOC2:2.OPERATE
ROVPTOV1_OPERATE
1.)Protection.8.b3.ROVPTOV1:1.OPERATE

ABB Ltd.
ROVPTOV2_OPERATE
1.)Protection.8.b3.ROVPTOV2:2.OPERATE
PHPTOV1_OPERATE
1.)Protection.8.b7.PHPTOV1:1.OPERATE
PHPTOV2_OPERATE
1.)Protection.8.b7.PHPTOV2:2.OPERATE

Responsible Department:
PHPTUV1_OPERATE
1.)Protection.8.d3.PHPTUV1:1.OPERATE
PHPTUV2_OPERATE
1.)Protection.8.d3.PHPTUV2:2.OPERATE
TR2PTDF1_OPERATE
1.)Protection.7.d3.TR2PTDF1:1.OPERATE

5
5

TR2PTDF1_OPR_LS
1.)Protection.7.d3.TR2PTDF1:1.OPR_LS
DISTURBANCE RECORDER PAGE

TR2PTDF1_OPR_HS
1.)Protection.7.d3.TR2PTDF1:1.OPR_HS
HREFPNDF1_OPERATE
1.)Protection.6.b7.HREFPDIF1:1.OPERATE
T2PTTR1_OPERATE
1.)Protection.7.c3.T2PTTR1:1.OPERATE

Created by:
T2PTTR1_ALARM

Approved by:
1.)Protection.7.c3.T2PTTR1:1.ALARM
Technical Reference:

Title:
6
6

RET615
Document Kind:

DISTURBANCE RECORDER
Graphical Application Configuration
7
7

0
Rev.:
Document I.D.:
Doc. Designation:
AA1J1Q01A1

Rel. Date:
EN06/10/2018
8
8

Lang.
1/1
Sheet No.:
E
B
A

D
C
1 2 3 4 5 6 7 8

LED PAGE
A GENERAL ALARM NEGATIVE SEQUENCE PROT. TRIP A
LED1 LED5
OR20 OR
OK OK
DISTURB_RECORD_TRIGGERED B1 O ALARM NSPTOC1_OPERATE B1 O ALARM
1.)Disturbance_Recorder.1.b5.RDRE:1.TRIGGERED B2 RESET 1.)Protection.7.b3.NSPTOC1:1.OPERATE B2 RESET
B3 O:132|T:2.5|I:1 O:109|T:2.5|I:2 O:110|T:2.5|I:5
TCSSCBR_ALARM B4 NSPTOC2_OPERATE
1.)Supervision.1.e3.OR:11.O B5 1.)Protection.7.b7.NSPTOC2:2.OPERATE
B6
SSCBR1_ALARMS LED_RESET
B7
1.)Supervision.1.b7.OR:25.O 1.)LED.2.b5.AND6:3.O
B8
CCBRBRF1_CB_FAULT_AL B9 VOLTAGE PROT. TRIP
1.)Protection.9.b6.CCBRBRF1:1.CB_FAULT_AL B10
B11 LED6
CCBRBRF1_TRRET B12 OR6
1.)Protection.9.b6.CCBRBRF1:1.CB_FAULT_AL B13 OK
B14 PHPTOV_OPERATE B1 O ALARM
CCBRBRF1_TRBU B15 1.)Protection.8.c7.OR:21.O B2 RESET
1.)Protection.9.b6.CCBRBRF1:1.TRBU B16 B3
B O:117|T:2.5|I:6 B
B17 PHPTUV_OPERATE B4
SEQRFUF1_FUSEF-3PH B18 1.)Protection.8.e3.OR:17.O
1.)Supervision.2.b3.SEQRFUF1:1.FUSEF_3PH B5
B19 B6
B20 ROVTOV_OPERATE
SEQRFUF1_FUSEF-U 1.)Protection.8.c3.OR:5.O
1.)Supervision.2.b3.SEQRFUF1:1.FUSEF_U O:98|T:2.5|I:0
LED_RESET
BLACKOUT_STATUS 1.)LED.2.b5.AND6:3.O
1.)I_O.1.d7.AND20:0.O
HV ES STATUS
X110_BI3_HV_CB_FAIL
1.)I_O.1.c3.OR:20.O LED7
X130_BI1_HV_VT_MCB_OPEN HV_ES_OPENED OK
1.)I_O.1.b3 1.)I_O.1.d4.NOT:7.OUT ALARM
X130_BI4_EXT_OC_BLOCKING RESET
X110_BI6_HV_ES_CLOSED
1.)I_O.3.c3 O:138|T:2.5|I:7
1.)I_O.1.d4.OR:3.O
LED_RESET
1.)LED.2.a6.AND:7.O HV DS STATUS
C DIFFERENTIAL PROT. TRIP C
LED8
LED2 X110_BI5_HV_DS_OPENED OK
OR6 1.)I_O.1.d4.OR:4.O ALARM
OK
TR2PTDF1_OPR_HS B1 O ALARM RESET
HV_DS_CLOSED
1.)Protection.7.d3.TR2PTDF1:1.OPR_HS B2 RESET O:140|T:2.5|I:8
1.)I_O.1.d4.NOT:6.OUT
B3 O:108|T:2.5|I:2
TR2PTDF1_OPR_LS B4
1.)Protection.7.d3.TR2PTDF1:1.OPR_LS B5 HV CB STATUS
B6
HREFPNDF1_OPERATE
1.)Protection.6.b7.HREFPDIF1:1.OPERATE O:107|T:2.5|I:20 LED9
LED_RESET X110_BI4_HV_CB_OPENED OK
1.)LED.2.b5.AND6:3.O 1.)I_O.1.c4.OR:14.O ALARM
RESET
HV_CB_CLOSED
OVERCURRENT HV-SIDE PROT. TRIP 1.)I_O.1.c4.NOT:10.OUT
O:143|T:2.5|I:9

LED3
OK LV CB1 STATUS
PHxPTOC_OPERATE_HVSIDE ALARM
D 1.)Protection.5.d3.OR6:22.O RESET LED10 D
O:112|T:2.5|I:3 LV_CB1_OPENED OK
LED_RESET
1.)LED.2.b5.AND6:3.O 1.)I_O.1.e4.NOT:8.OUT ALARM
RESET
X110_BI7_LV_CB1_CLOSED
OVERCURRENT LV-SIDE PROT. TRIP 1.)I_O.1.d4.OR:26.O
O:142|T:2.5|I:10

LED4
OR LV CB2 STATUS
OK
PHxPTOC_OPERATE_LVSIDE B1 O ALARM
1.)Protection.5.d7.OR6:26.O B2 RESET LED11
O:120|T:2.5|I:33 O:121|T:2.5|I:4 LV_CB2_OPENED OK
EFxPTOC_OPERATE_LVSIDE
1.)Protection.6.c3.OR:7.O 1.)I_O.1.e4.NOT:9.OUT ALARM
RESET
LED_RESET X110_BI8_LV_CB2_CLOSED
O:135|T:2.5|I:11
1.)LED.2.b5.AND6:3.O 1.)I_O.1.e4.OR:8.O

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
LED PAGE 0 06/10/2018 EN 1/2
1 2 3 4 5 6 7 8

LED PAGE
A A
FAULT / LED ALARM RESET
NOT AND LEDPTRC1
TRPPTRC1_TRIP IN OUT B1 O RESET OUT_START
1.)Protection.1.b7.TRPPTRC1:1.TRIP O:103|T:2.5|I:14 B2 OUT_OPERATE
O:104|T:2.5|I:5 OUT_ST_A
OUT_OPR_A
OUT_ST_B
NOT OUT_OPR_B
OUT_ST_C
TRPPTRC2_TRIP IN OUT OUT_OPR_C
1.)Protection.2.b7.TRPPTRC2:2.TRIP O:102|T:2.5|I:15 OUT_ST_NEUT
OUT_OPR_NEUT
O:140|T:2.5|I:1

NOT AND6
B GENERAL_START IN OUT B1 O LED_RESET B
1.)Protection.4.b4.OR6:0.O O:97|T:2.5|I:12 B2 1.)LED.1.b3.LED1:1.RESET
B3 2.)LED.1.c3.LED2:2.RESET
B4 3.)LED.1.d3.LED3:3.RESET
B5 4.)LED.1.e3.LED4:4.RESET
NOT B6 5.)LED.1.b7.LED5:5.RESET
6.)LED.1.c7.LED6:6.RESET
GENERAL_OPERATE IN OUT
1.)Protection.4.c4.OR6:12.O O:96|T:2.5|I:13

C C

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
LED PAGE 0 06/10/2018 EN 2/2
1 2 3 4 5 6 7 8

MEASUREMENT PAGE
A
Three Phase Current Measurement (HV Side) Three Phase Voltage Measurement (HV Side) Three Phase Power and Energy Measurement A
CMMXU1 VMMXU1 PEMMXU1
BLOCK HIGH_ALARM BLOCK HIGH_ALARM RSTACM
HIGH_WARN CMMXU1_HIGH_WARN HIGH_WARN O:278|T:5|I:1
LOW_WARN 1.)I_O.1.e6.AND6:2.B3 LOW_WARN
LOW_ALARM CMMXU1_LOW_ALARM LOW_ALARM VMMXU1_LOW_ALARM
O:240|T:5|I:1 1.)I_O.1.d6.AND20:0.B5 O:196|T:5|I:1 1.)I_O.1.d6.AND20:0.B7 Data Monitoring
Three Phase Current Measurement (LV Side) Sequence Voltage Measurement (HV Side) FLTMSTA1
BLOCK
CMMXU2 VSMSQI1 CB_CLRD
O:185|T:2.5|I:1
BLOCK HIGH_ALARM O:209|T:5|I:1
HIGH_WARN CMMXU2_HIGH_WARN
LOW_WARN
LOW_ALARM
1.)I_O.1.e6.AND6:2.B4
CMMXU2_LOW_ALARM Residual Voltage Measurement (HV Side) Load Record Profile
O:267|T:5|I:2 1.)I_O.1.d6.AND20:0.B6 LDPMSTA1
RESVMMXU1
B
Sequence Current Measurement (HV Side) BLOCK HIGH_ALARM
RSTMEM MEM_WARM
MEM_ALARM
B
HIGH_WARN O:266|T:5|I:1
CSMSQI1 O:221|T:5|I:1

O:213|T:5|I:1

Residual Current Measurement (LV Side)


RESCMMXU2
BLOCK HIGH_ALARM
HIGH_WARN
O:347|T:5|I:2

C C

D D

E E

1 2 3 4 5 6 7 8
Project: Responsible Department: Technical Reference: Document Kind: Doc. Designation:
LUELCO ABB Ltd. Graphical Application Configuration AA1J1Q01A1
Replacing: Substation: Created by: Title: Document I.D.:

RET615
15/18.75MVA AGOO SUBSTATION Approved by: Rev.: Rel. Date: Lang. Sheet No.:
Rev: Modification: Rel. date: Created by: Based on:
MEASUREMENT PAGE 0 06/10/2018 EN 1/1
RET615 Programmable LED Configuration:

LatchedAck-F-S

Project: Responsible Department: Technical Ref.: Document Kind: Doc. Designation:

LUELCO AGOO Substation ABB Ltd. RET615 AGOO AA1J1Q01A1


Created by: Title: Document I.D.:

Replacing Programmable LED


15/18.75MVA, 67kV Bay1 Approved by: Configuration Rev.: Rel. Date: Lan. Sheet
No.:
Rel. Created Based 0 06/10/2018 EN 1/1
Rev: Modification: Date: By: On:
RET615 Measurement Configuration:

Project: Responsible Department: Technical Ref.: Document Kind: Doc. Designation:

LUELCO AGOO Substation ABB Ltd. RET615 AGOO AA1J1Q01A1


Created by: Title: Document I.D.:

Replacing Measurement
15/18.75MVA, 67kV Bay1 Approved by: Configuration Rev.: Rel. Date: Lan. Sheet
No.:
Rel. Created Based 0 06/10/2018 EN 1/1
Rev: Modification: Date: By: On: