1. Daily, Weekly & Monthly checks should be performed and recorded via log
book.
2. First Maintenance will be performed after 50hours or one month after initial
startup or commissioning.
3. Next Maintenance will be performed after every 250hours or 6months as per
Engine family via manufacturer recommendation.
4. Maintenance should be done via qualified or trained technician.
Periodic Maintenance
The tabular data that follows gives the recommended service intervals for a
generator set on Standby service. If the generator set will be subjected to Prime
usage or extreme operating conditions, the service intervals should be reduced
accordingly.
1|Page
Orient Energy Systems (Private) Limited
Some of the factors that can affect the maintenance schedule are:
Consult with an authorized distributor if the generator set will be subjected to any
extreme operating conditions and determine if extra protection or a reduction in
service intervals is needed.
Use the running time meter to keep an accurate log of all service performed for
warranty support. Perform all service at the time period indicated, or after the
number of operating hours indicated, whichever comes first.
Table 1 Periodic Maintenance Schedule
Perform maintenance tasks as specified using Daily or Hourly periods
– whichever occurs first
MAINTENANCE ITEMS
Daily or 8 Wkly or 6 M or 12 M or 12 M or 2000 2Yrs. or
Hours 50 Hrs. 250 Hrs. 250 Hrs. 1500 hrs. Hrs. 6000 Hrs.
Operator
Task Task Service Technician Task
Air Intake Maintenance Schedule
Check air cleaner restriction indicator
(where fitted): If the service indicator
shows red, replace air cleaner ■
elements and reset the air cleaner
service indicator.
Check air intake system for leaks:
Visually inspect the air intake system
for signs of wear or damage. Check
■
audibly when the generator set is
running. To replace, contact your
authorized distributor.
Clean air cleaner housing. ■
Control Maintenance Schedule
Check operation of Control Panel:
Check display (the system will perform
a control panel test on initial ■
activation). To replace, contact your
authorized distributor.
2|Page
Orient Energy Systems (Private) Limited
Check operation of Emergency Stop
Button: With the generator set
running, press the Emergency Stop ■
button. Check all systems, before
resetting the fault.
Cooling Maintenance Schedule
Check coolant level of radiator(s)
(water jacket & LTA): If low, top up to
coolant system specifications level, ■
with Cummins recommended coolant
mix.
Check cooling fan blades: Visually
inspect the fan blades through the
guarding for signs of wear or damage. ■
To replace, contact your authorized
distributor.
Check drive belt, condition and
tension: Visually check belt for
evidence of wear or slippage. To ■
replace, contact your authorized
distributor.
Check coolant lines and radiator hoses
for leaks, wear, and cracks: Visually
check for leaks, worn or damages ■ ■
hoses. To replace, contact your
authorized distributor.
Check radiator air flow: Visually inspect
the radiator through the guarding for
blockage, build up of debris, signs of ■
wear or damage. To clean or replace,
contact your authorized distributor.
Clean radiator cores. ■1 ■
Check aftercooler cores. ■
Check water pump. ■
Lubricate fan shaft bearings ■
Change coolant filter. ■
Check coolant heater. ■
Fan drive idler arm and fan belt
■
tensioner check.
Replace cooling system coolant. ■
■1 – Cleaning schedule may be reduced depending on operating conditions/environment. Contact your
authorized distributor.
ENGINE MAINTENANCE
Check fuel lines and hoses: Visually
check for leaks, worn or damages
■1
hoses. To replace, contact your
authorized distributor.
3|Page
Orient Energy Systems (Private) Limited
Check engine oil level: If low, top up to
engine specifications level, with ■
recommended oil.
Drain water from fuel system primary
filter/water separator: Drain one cup,
or more, of fuel to remove water and ■
sediment. See procedure in this
chapter.
Crankcase breather tube/collector.
Check for condensed oil. Drain and
■
dispose of in accordance with local
legislation.
Check charge alternator: Check visually
and audibly when the generator set is
■
running. To replace, contact your
authorized distributor.
Check engine oil make‐up system: If
low, top up to indicated level, with ■
Cummins recommended oil.
Check engine coolant heater: Check
coolant heater has power and is
■
running. To replace, contact your
authorized distributor.
Replace lubricating oil and filters. ■
Check engine ground. Clean as
■
necessary.
Replace water separator element. ■ ■
Replace fuel system secondary filter. ■ ■
Check engine mounts. ■
Check starting motor. ■
Check turbocharger. ■
Check Charging Alternator ■
Engine oil heater check. ■
Engine steam clean. ■
■1 – Check before starting and again with the generator set running.
Exhaust Maintenance Schedule
Check all exhaust components, and
hardware (fittings, clamps, fasteners,
etc.): Visually inspect the exhaust
system for signs of wear or damage. ■
Check audibly when the generator set
is running. To replace, contact your
authorized distributor.
Check exhaust condensation trap:
Drain condensation into a suitable
■
container. Dispose of fluids in
accordance with local legislation.
4|Page
Orient Energy Systems (Private) Limited
Table 2
Generator Set Maintenance Schedule
Perform maintenance tasks as specified using Daily or Hourly periods –
whichever occurs first
MAINTENANCE ITEMS
Daily or 8 Weekly or 6 Mths or 12 Mths or 12 Mths or 2000 2 Yrs. or
Hours 50 Hours 250 Hrs. 250 Hrs. 1500 Hrs. Hrs. 6000Hrs.
Operator
Task Service Technician Task
Task
Check fuel level in tank: If
low, add fuel (A full tank ■
reduces condensation.)
Check bedframe/enclosure
fluid containment (where
fitted): Drain as necessary.
Clean all contaminated ■
areas. Dispose of fluids in
accordance with local
legislation.
Inspect Engine/Alternator ■2
Flexible Rubber Coupling
Check generator set
Visually check enclosure (if
fitted), walk around
inspection of generator set.
Make sure no inlets/outlets
are covered/restricted,
■
service access doors are
operational and safety
systems are in place and
operational. To replace
damaged parts, contact
your authorized distributor.
Check batteries: Check
connections are secure and ■ ■
battery area is free from
tools and other items.
Check battery electrolyte
■1
level.
Check electrical
connections (battery,
■ ■
starter motor and
alternator connections).
■1 Lead acid battery's only ■2 For P80 Alternator regrease the alternator bearings every 1000 t0 1500 hours /
6 months
5|Page
Orient Energy Systems (Private) Limited
Table 3 ALTERNATOR SERVICE SCHEDULE
SERVICE ACTIVITY Type SERVICE LEVEL
30,000 hrs / 5 years
Alternator running
10,000 hrs / 2 years
250 hrs / 0.5 year
Post Commission
1000 hrs / 1 year
Commission
Replace
Inspect
Level 1
Level 2
Level 3
Clean
System
Test
X = required * = if necessary
for MV)
Insulation resistance of rotor, exciter and
X X X
PMG
Temperature sensors X X X X X X X
Customer settings for temperature sensors X X
Condition of bearings X X X
Grease exhaust X X X X X
Bearings
Grease in re‐greasable bearing(s) X X every 4000 to 4500 hours / 6 months
Sealed bearing(s) X every 4000 to 4500 hours
Re‐greasable & sealed bearing(s) X * X
Temperature sensors X X X X X X X
Customer settings for temperature sensors X X
All alternator/customer connections and
X X X X X
Ter. Box cabling
Initial AVR & PFC set up X X X
AVR & PFC settings X X X X X X
Controls X X X X X
Customer connection of auxiliaries
&
Function of auxiliaries X X X X X X
Auxiliari
es Synchronization settings X X
Synchronization X X X X X X X
Anti‐condensation heater X * X
6|Page
Orient Energy Systems (Private) Limited
Diodes and varistors X X X X X
Rectifier
Diodes and varistors X X
Air inlet temperature X X X X X X
Cooling Air flow (rate & direction) X X X
Condition of fan X X X X X X
* For stand‐alone alternator only.
Preventive maintenance
Because of the durability of diesel engines, most maintenance is preventive in nature.
A. General inspection
B. Lubrication Service
C. Cooling system Service
D. Fuel system Service
E. Air Intake System Service
F. Servicing and testing starting batteries
A. General inspection
When the generator set is running, operators need to be alert for mechanical problems that
could create unsafe or hazardous conditions. Following are several areas that should be
inspected frequently to maintain safe and reliable operation.
Exhaust system:
With the generator set operating, inspect the entire exhaust system including the exhaust
manifold, muffler and exhaust pipe. Check for leaks at all connections, welds, gaskets and
joints, and make sure that the exhaust pipes are not heating surrounding areas excessively.
Repair any leaks ASAP.
Monitor fluid levels, oil pressure and coolant temperatures frequently. Most engine problems
give an early warning. Look and listen for changes in engine performance, sound, or
appearance that will indicate that service or repair is needed.
For accurate readings on the engine’s dipstick, shut off the engine and wait approximately 10
minutes to allow the oil in the upper portions of the engine to drain back into the crankcase.
Keep the oil level as near as possible to the “full” mark on the dipstick by adding the same
quality and brand of oil.
Cummins Inc. recommends the use of a high quality, diesel oil such as Valvoline premium
blue or Valvoline premium blue extreme life.
7|Page
Orient Energy Systems (Private) Limited
By definition we think of cooling system has something that cools but actual has four functions
and must all work cohesiveness for the engine to survive
8|Page
Orient Energy Systems (Private) Limited
Let’s take a moment to talk about all the components that actual make that happened;
1. The heat absorbed by the coolant itself and this means coolant must have good heat
absorbing and heat transferring capabilities. Glycol or Antifreeze mixed with 50/50%
with pure water has much superior heat transferring characteristics, either pure water
or pure glycol.
2. Coolant is continuously circulating with in the cooling system and this function is
performed by water pump. Interestingly enough typical water pump can circulate
between 11 to 15000gallons of water /hour and it’s critical that this pump functions
flawlessly.
3. Heat is dissipated or radiated and this takes place in radiator. The efficiency and
effectiveness of radiator is critical.
4. Finally, the cooling system controls the heat and this is done by the thermostats,
again imperatively that thermostat operates flawlessly.
9|Page
Orient Energy Systems (Private) Limited
10 | P a g e
Orient Energy Systems (Private) Limited
OR
ES Compleat
It is already Mixed as per
required Ratios. (Complete
Mixture)
A good coolant has properties that inhabit
things like liner pitting, reduce or eliminates
scale or corrosion which can affect things
like radiator, water pumps and thermostat.
A good coolant also contains many other additives that protect specific engine component
based on their design and type of metal.
REAL™ Performance
Lifetime coolant with service interval at 150,000 mi, 250 km, 4000 hrs.
Provides antifreeze and antiboil protection
Best liner pitting and corrosion protection
Best aluminum and solder protection
Compatible with gaskets, elastomers and other non-metallic in the engine
Optimizes cooling system performance and water pump life
Contains proprietary scale inhibitors
Coolant Testing
Field Maintenance Tools for Engine Coolants
11 | P a g e
Orient Energy Systems (Private) Limited
12 | P a g e
Orient Energy Systems (Private) Limited
Fuel system service with the generator set operating; inspect the fuel supply
lines, return lines, filters and fittings for cracks or abrasions. Make sure the lines are
not rubbing against anything that could cause an eventual breakage. Repair any
leaks or alter line routing to eliminate wear immediately.
Diesel fuel is subject to contamination and deterioration over time, and one
reason for regular generator set exercise is to use up stored fuel over the
course of a year before it degrades. In additional to other fuel system service
recommended by the engine manufacturer, the fuel filters should be drained
at the interval. Water vapor accumulates and condenses in the fuel tank and
must also be periodically drained from the tank along with any sediment
present.
Don't Compromise on
Quality of Fuel
Cleaning of base tank & bulk storage tanks.
Additional Water separators(filter) installation
Periodic replacement of Fuel Filter its replacement also relates
to the quality of fuel
13 | P a g e
Orient Energy Systems (Private) Limited
Today we like to draw your attention to the reasons of early clogging of Fuel filter
which is not the fuel filter quality issue but the contaminated fuel. Contaminated
particles as small as 4microns which is 12 times smaller than human hair and these
Particles invisibles to the human eye, can premature wear fuel injector, is not only
decreased engine performance and higher fuel consumption but could also lead to
costly damage and down time.
Today diesel engines operator are facing many fuel related challenges and first,
which is fuel quality.
Worldwide fuel chartered has stated that 50% of the diesel fuel dispensed around
the world, does not meet the international standard organization or ISO code for
cleanliness. Add to the fact that fleets off & on highway are challenged with fuel that
is transported, loaded & offloaded some time, several times and its delivery to the
actual equipment fuel tank, each time adding to the possibility of contaminations.
Therefore today challenge are:
Fuel quality & cleanliness
Fuel delivery & transfer
Filter loading (filter actual loses efficiency overtime)
Fuel pressure surges
Filter vibration
All in all not a good combination for today engine therefore to overcome the situation,
Cummins recommends to install the additional Water separator between fuel tank
and engine. Please go through an article and at least solution.
Longer Life, Reduced Costs
All fuel filtration systems are engineered with precision to MEET customer demands for
longer life and improved performance. Fuel filters using proprietary StrataPore® multi-
layered media offer superior micron efficiencies, removing large particles, as well as the
14 | P a g e
Orient Energy Systems (Private) Limited
smallest debris. Each StrataPore layer offers unique properties to extend fuel filter life
and improve performance.
15 | P a g e
Orient Energy Systems (Private) Limited
With the best fuel processor available today to protect your valuable equipment.
Causation: Don’t fill diesel in base tanks while the Gen set or engine in
operation; it can mix all the sediments and water which can create wear & tear
in fuel pump, nozzles/injectors and symptom can be low frequency, low power
or early chocking of fuel filters. Therefore base tank or storage day tank
should be cleaned once in two year. Can be varied as per diesel quality
These contaminations can be from the supplier, means like dirty drums,
buckets or by diesel handler.
16 | P a g e
Orient Energy Systems (Private) Limited
D. Air Intake System:
The charge-air piping and hoses should be inspected daily for leaks, holes, cracks or loose
connections. Tighten the hose clamps as necessary. Also, inspect the charge-air cooler for dirt
and debris that may be blocking the fins. Check for cracks, holes or other damage.
The engine air intake components should be checked. The frequency of cleaning or replacing air
cleaner filter elements is primarily determined by the conditions in which the generator set
operates. Air cleaners typically contain a paper cartridge filter element which can be cleaned and
reused if not damaged.
Cleaning of Air filter Element with pressure Air is strictly prohibited.
For every gallon of fuel the typical diesel engine burns, it’s require about 1500gallons of air and that is
Clean Air.
Following are the air filter servicing guidelines will go long way to ensuring long engine life.
17 | P a g e
Orient Energy Systems (Private) Limited
Check for contact 100% of the gasket area, Appling a small amount of grease to the Gasket,
installing the filter and properly fastening all covers and then removing to inspect for square fit
can accomplish this.
When the old filter has been removed, inspect it for uneven dirt pattern that are indicators of
dust leakage or sealing problems.
Inspect all air system, duck works, especially between air filter and the engine. Insure that all
clamps and connections are tight and all piping is free of cracks and holes.
Always replace the air filter with correct part number cross. Air filter element is shorter by a
fraction of an inch may make a positive and seal impossible and allow dirt into the engine.
Use restriction indicator to term, when to change the air filter element. Otherwise change it at
the time of routine maintenance at 250~500 hours of operation. Never open air cleaner just to
look, don’t take chances and risk contamination the engine for frequent useless inspection.
Special note: Cummins Engine manufacturer & filtration discourage to clean the filter with pressurized
Air or any other means due to inadequate and incomplete process, non-availability of effective quality
measure to make sure filter is free of holes and leaks in both media and Gasket area.
E. Servicing and testing of Starting batteries
Weak or undercharged starting batteries are the most common cause of standby power system
failures. Even when kept fully charged and maintained, lead-acid starting batteries are subject to
deterioration over time and must be periodically replaced when they no longer hold a proper
charge. Only a regular schedule of inspection and testing under load can prevent generator
starting problems.
Cleaning batteries: Keep the batteries clean by wiping them with a damp cloth whenever dirt
appears excessive. If corrosion is present around the terminals, remove the battery cables
and wash the terminals with a solution of baking soda and water (1/4-pound baking soda to
one quart of water). Be careful to prevent the solution from entering the battery cells, and
flush the batteries with clean water when done. After replacing the connections, coat the
terminals with a light application of petroleum jelly.
Checking specific gravity: Use a battery hydrometer to check the specific gravity of the
electrolyte in each battery cell. A fully charged battery will have a specific gravity of 1.260.
Charge the battery if the specific gravity reading is below 1.215.
Recommended Method of Removal/Installation of Batteries: before removal always push
the emergency push button than remove or install the Batteries, at the time of removal always
remove the negative cable from Battery than positive cable. At the time of installation, always
put the positive cable than the negative cable.
Expected, Healthy Battery life is one year with Good Maintenance.
Notes:
1. These are General Instruction and for any of specific Maintenance, please consult relative
Operation & Maintenance Manual.
2. Being an Authorized distributor of Cummins diesel Engine & Generator Set
a. Genuine and legal parts, imported from Manufacturer the Cummins e.g., all
Consumables like Filters, Lube Oil (Valvoline premium blue, Only One Endorsed by
Cummins) & Grease etc. Engine Parts, Alternator Parts and Controller parts are
ready in our Stock.
b. We have qualified and Principal or Manufacturers certified Technicians for Service.
3. Non Genuine, Illegal, cheaper parts and service from unqualified persons will leads to heavy
cost in near future due to breakdown.
4. Here we like to recommend you, please have AMC contract with us which leads to trouble
free and smooth operation and long terms heavy cost will also be reduced. Peace of mind will
be there.
Waseem Iqbal
Assistant General Manager
Product Support Services +92 3018496079 waseem.iqbal@orient-power.com
1 KM Defense Road, Off Raiwind Road Lahore –Pakistan
18 | P a g e