GEI-100667

GE Energy
Mark*VIe Serial Communications
IS220PSCAH1A - IS200SSCAH1A or IS200SSCAH2A Serial
Communications Additional Installation Instructions for
Connection to Devices Located in Class I, Div. 2 Hazardous
Locations
These instructions do not purport to cover all details or variations in equipment, nor
to provide for every possible contingency to be met during installation, operation,
and maintenance. The information is supplied for informational purposes only, and
GE makes no warranty as to the accuracy of the information included herein.
Changes, modifications, and/or improvements to equipment and specifications are
made periodically and these changes may or may not be reflected herein. It is
understood that GE may make changes, modifications, or improvements to the
equipment referenced herein or to the document itself at any time. This document is
intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this
document. The furnishing of this document does not provide any license whatsoever
to any of these patents.
This document contains proprietary information of General Electric Company, USA
and is furnished to its customer solely to assist that customer in the installation,
testing, operation, and/or maintenance of the equipment described. This document
shall not be reproduced in whole or in part nor shall its contents be disclosed to any
third party without the written approval of GE Energy.
GE provides the following document and the information included therein as is and
without warranty of any kind, expressed or implied, including but not limited to any
implied statutory warranty of merchantability or fitness for particular purpose.
If further assistance or technical information is desired, contact the nearest GE Sales
or Service Office, or an authorized GE Sales Representative.

© 2006 General Electric Company, USA. All rights reserved.

* Trademark of General Electric Company

g
National Electric Code is a registered trademark of the National Fire Protection
Association
Safety Symbol Legend

Indicates a procedure, practice, condition, or statement that, if


not strictly observed, could result in personal injury or death.

Indicates a procedure or condition that, if not strictly


observed, could result in damage to or destruction of
equipment.

Note Indicates an essential or important procedure or statement.

2 • Mark VIe Serial Communications GEI-100667


Applications
This document is in addition to the installation and operating instructions provided
for each system. It provides instructions that address additional considerations
necessary when this product is applied in locations covered by the requirements of
®
National Fire Protection Association (NFPA) 70, National Electrical Code (NEC),
Articles 500 through 504 - Hazardous (Classified) Locations, Class I, Division 2.

The installation and wiring of this product must be in accordance with NEC and all
local codes.

Do not connect or disconnect modules, connectors, cables, or


terminal board wiring while circuits are alive unless the area
is known to be non-hazardous.

Explosion Hazard – Substitution of components may impair


suitability for Class I, Division 2 applications.

Do not assume any cable or any circuitry to be without power


if one end of that cable could be connected to a power source.
To prevent accidental electrical shock, do not touch any
circuitry or bare wire without first ensuring that it does not
carry electricity. When testing for the presence of electricity
and when measuring any electrical circuit, use only the
equipment approved for contact with those voltage levels.

GEI-100667 Mark VIe Serial Communications • 3


Instructions
The external I/O connections to these cards meet the requirements of EN 50021:1999
Electrical apparatus for potentially explosive atmospheres – Type of protection nL,
and UL 1604 (IEC 60079-15) nonincendive for connection to devices suitable for
location in Class I, Division 2, or Zone 2 locations. Nonincendive field wiring must
be installed in accordance with the applicable sections of the NEC, including Article
501.4(B)(3), IEC60079-14, and all local codes. Selected nonincendive field wiring
apparatus must be installed in accordance with manufacturer’s control drawings and
must not be connected to an external power source.

IS200SSCAH1A or IS200SSCAH2A

Nonincendive Circuit Parameters:

SSCA terminals 1 through 48

Uo, Voc: 16 V dc; Co, Ca: 2.2 µF

Io, Isc ≤ 19 mA; Lo, La = 80 mH

Selected nonincendive field wiring apparatus must be simple apparatus or have


nonincendive circuit parameters such that Ui, Vmax ≥ Uo, Voc; Ii, Imax ≥ Io, Isc; Ci + Ccable ≤
Co, Ca; Li + Lcable ≤ Lo, La; Pi ≥ Po.

The remote terminal boards must be installed in an acceptable enclosure for the
location. All cables must be installed using suitable Division 2 or Zone 2 wiring
methods in accordance with Article 501.4(B)(1) of the NEC or EN 60079-14 and all
local codes including the following:

• These devices shall be properly grounded to protective earthing in the final


application.
• Supplied cables may not be cut and subsequently spliced or reterminated during
installation or maintenance.
• The molded connectors must not be used to pull the cables during installation,
and when installed there must be sufficient slack in the cable to remove strain
from the connectors.
• For ambient temperatures below -10°C (+14 °F) and above +60°C (+140 °F) use
field wiring suitable for both minimum and maximum ambient temperatures.

How to Get Help


If help is needed beyond the instructions provided in the documentation, contact the
nearest GE Sales or Service Office or an authorized GE Sales Representative.

g GE Energy
1501 Roanoke Blvd.
Salem, VA 24153-6492 USA

1 540 387 7000


www.geenergy.com
GEI-100667
060907