Refrigeration Dryers
SECOTEC®
Flow rate 0.6 to 14.3 m³/min
www.kaeser.com
SECOTEC ®
Energy savings all day, every day
Image: SECOTEC TB 19
2 3
www.kaeser.com
SECOTEC ®
Quality counts
4 5
www.kaeser.com
SECOTEC ®
Quality engineered
Image:
TE 61 internal view
6 7
www.kaeser.com
SECOTEC ®
Easy to maintain
8 9
www.kaeser.com
100 % – 43°C –
Additional energy-saving
ambient temperature
Designed for use in
potential (for use at summer 40°C –
90 % –
temperatures, e.g. ambient 35°C –
temperature 40 °C)
80 % – 30°C –
25°C –
70 % –
20 % –
10 % – Midday break
10 11
www.kaeser.com
Operating panel
Equipped with dew point trend gauge,
emergency stop switch, LEDs to
indicate “Thermal mass active” and
“Refrigerant compressor ON”.
Installation example 2
LEDs for “High dew point” and “ECO-
DRAIN alarm” are fitted as standard on
TE models and upwards. TF models
and upwards feature two operating For heavily fluctuating air demand, the
hours counters. SECOTEC dryer is located between
the compressor, centrifugal separator
with condensate drain and air receiver.
General design
Example: TE series
Compressed
air outlet Compressed air
Air/air heat exchanger
inlet
Air/refrigerant heat exchanger
with thermal mass
12 13
www.kaeser.com
m³/min bar kW kW Kg
kg mm G G/DN kg t
230 V / 779
630 x 484 x
TA 8 0.85 0.14 0.27 0.15 80 ¾ G¼ 1 Ph / 0.22 0.3 •
779
50 Hz
230 V /
764 x 660 x DN 10 963
TC 36 3.90 0.16 0.88 0.48 170 1¼ 1 Ph / 0.97 1.4 •
1009 ¼
50 Hz
400 V /
TE 121 12.70 0.18 1.45 0.80 660 1520 x 1060 x 2xDN 10 2.10 3.0 •
2 3 Ph /
1513 ¼
50 Hz
660 774
TE 141 14.30 0.24 1.60 0.88 660 2.10 3.0 •
TD series
*) Suitable for ambient temperatures from +3 to +43 °C. Max. compressed air intake temperature +55 °C; Gauge pressure min./max. 3 to 16 bar
Performance characteristics at reference conditions to ISO 7183 Option A1: Operating pressure 7 bar, ambient temperature +25 °C, compressed air inlet temperature +35 °C,
pressure dew point +3 °C. The flow rate changes for deviating operating conditions. Contains fluorinated greenhouse gas R-134a (GWP = 1,430).
Correction factors for deviating operating conditions (flow rates in m³/min x k...)
1187
Deviating working pressure p at dryer inlet
Modell
Model ppbar
bar(ü)
(g) 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TA-TF
TA-TE kp 0.75 0.84 0.90 0.95 1.00 1.04 1.07 1.10 1.12 1.15 1.17 1.19 1.21 1.23 759 1125
Modell
Model TTie(°C)
(°C) 30 35 40 45 50 55 Modell
Model TTau (°C) 25 30 35 40 43 TE series
TA-TF
TA-TE kTeTi 1.20 1.00 0.83 0.72 0.60 0.49 TA-TF
TA-TE kTu
Ta
1.00 0.99 0.97 0.94 0.92
Calculation of flow rate under deviating operating conditions: Selected refrigeration dryer: TB 19 with 2.1 m³/min (VReference)
Example: 1513
Working pressure: 10 bar (g) ▹ Table ▹ kp = 1.10 Vmax. operation = VReference x kp x kTi x kTa
Compressed air inlet temperature: 40 °C ▹ Table ▹ kTi = 0.83 Vmax. operation = 2.1 m³/min x 1.1 x 0.83 x 0.99 = 1.9 m³/min
Ambient temperature: 30 °C ▹ Table ▹ kTa = 0.99 1060 1520
14 15
www.kaeser.com
Choose the required grade of treatment according to your field of application: Explanation
Application examples: Selection of treatment classes to ISO 8573-1 (2010) ACT Activated carbon adsorber
AQUAMAT AQUAMAT
Air treatment with refrigeration dryer Installation for
DD Desiccant dryer
fluctuating air demand
DHS Air-main charging system
Solids Water
1
Oil 2
AR Air receiver
DHS KE
Pure air and clean room ECD ECO-DRAIN
technology, dairies, 1 4 1
KA Activated carbon filter, adsorption
breweries
DHS KD ACT KE Optional KB Coalescence filter, Basic
Food and beverage AR filtration RD ZK KBE Extra combination
production, ultra-clean 2 4 1
conveying air, KD Particulate filter, dust
chemical plants KE Coalescence filter, Extra
KEA Carbon combination
RD Refrigeration dryer
THNF Bag filter
DHS KEA AR ZK Centrifugal separator
Pharmaceuticals industry,
weaving machines, photo 1 4 1 Compressed air quality classes to ISO 8573-1(2010):
labs
RD ED Compressor THNF
Solid particles/dust
Max. particle count per m³ *
Class of a particle size d in [μm]
Paint spraying, powder DHS KE
coating packing, control 1 4 2 0.1 ≤ d ≤ 0.5 0.5 ≤ d ≤ 1.0 1.0 ≤ d ≤ 5.0
and instrument air
Please consult KAESER
0 regarding specific requirements
AQUAMAT 1 > 20,000 ≤ 400 ≤ 10
DHS
General factory air, 2 ≤ 400,000 ≤ 6,000 ≤ 100
high-grade sand blasting 4 4 3
3 Not defined ≤ 90,000 ≤ 1,000
DHS KB 4 Not defined Not defined ≤ 10,000
Shot-blasting 5 Not defined Not defined ≤ 100,000
4 7 3
Class Particle concentration Cp in mg/m³ *
6 0 < Cp ≤ 5
Conveying air for waste- With KAESER rotary screw compressors 7 5 < Cp ≤ 10
water systems, no quality X Cp > 10
specifications 6 7-X 4
Water
Class Pressure dew point, in °C
KAESER KOMPRESSOREN SE
P.O. Box 2143 – 96410 Coburg – GERMANY – Tel +49 9561 640-0 – Fax +49 9561 640130