Академический Документы
Профессиональный Документы
Культура Документы
Definition: The Scott-T Connection is the method of connecting two single phase
transformer to perform the 3-phase to 2-phase conversion and vice-versa. The two
transformers are connected electrically but not magnetically. One of the transformers is called
the main transformer, and the other is called the auxiliary or teaser transformer.
The figure below shows the Scott-T transformer connection. The main transformer is centre
tapped at D and is connected to the line B and C of the 3-phase side. It has primary BC and
secondary a a . The teaser transformer is connected to the line terminal A and the centre
1 2
The identical,
interchangeable transformers are used for Scott-T connection in which each transformer has a
primary winding of T turns and is provided with tapping at 0.289T , 0.5T and 0.866 T .
p p p p
The line voltages of the 3-phase system V , V , and V which are balanced are shown in the
AB BC CA
figure below. The same voltage is shown as a closed equilateral triangle. The figure below
shows the primary windings of the main and the teaser transformer.
The D divides the primary BC of the main transformers into two halves and hence the
number of turns in portion BD = the number of turns in portion DC = T /2.The voltage V and
p BD
The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage
ratings of the main transformer. Voltage V is applied to the primary of the teaser transformer
AD
and therefore the secondary of the voltage V of the teaser transformer will lead the secondary
2t
terminal voltage V of the main transformer by 90º as shown in the figure below.
2m
Then,
For keeping the voltage per turn same in the primary of the main transformer and the primary
of the teaser transformer, the number of turns in the primary of the teaser transformer should
be equal to √3/2T . p
Thus, the secondary’s of both transformers should have equal voltage ratings. The V and
2t
V are equal in magnitude and 90º apart in time; they result in the balanced 2-phase system.
2m
The primary of the two transformers may have a four wire connection to a 3-phase supply if
the tapping N is provided on the primary of the teaser transformer such that
The same voltage turn in portion AN, ND and AD are shown by the equations,
The equation above shows that the neutral point N divides the primary of the teaser
transformer in ratio.
AN : ND = 2 : 1
2. It is used to supply the single phase loads such as electric train which are so scheduled
as to keep the load on the three phase system as nearly as possible.
3. The Scott-T connection is used to link a 3-phase system with a two–phase system
with the flow of power in either direction.
The Scott-T connection permits conversions of a 3-phase system to a two-phase system and
vice versa. But since 2-phase generators are not available, the converters from two phases to
three phases are not used in practice.