Innovative Controls (P) Limited

P-150, 8th Main, XII Sector, LIC Colony, 1


Jeevan Bima Nagar, Bangalore - 560075

TEST REPORT

TEST REPORT FOR POTENTIAL TRANSFORMER

Plant M/s JSW Energy ltd,


Toranagallu, Bellary(Dist.)
Location MSDS 6 ( LV-2 ,33 KV )
System BUS PT . P NO 5

Specification
Nomenclature Potential Transformer
Make Electrical controls & system
R - Phase 06/006030
Sl.No Y – Phase 06/006043
B – Phase 06/006031

Core No Ratio Burden in VA Class


1 33KV/V3/110/V3 45 VA 0.2
2 33KV/V3/110/V3 50 VA 3P
3 33KV/V3/110/V3 50 VA 3P

 Insulation Resistance Test:

Particulars Megger Used R – Phase Y – Phase B – Phase


Pri –Earth 5000V 826 GΩ 579 GΩ 916 GΩ
Pri-Sec-1 5000V >1 TΩ 763 GΩ >1 TΩ
Pri -Sec-2 5000V 934 GΩ 325 GΩ >1 TΩ
Sec.1-Earth 500V >1 GΩ >1 GΩ >1 GΩ
Sec.2-Earth 500V >1 GΩ >1 GΩ >1 GΩ
Sec.1-Sec.2 500V >1 GΩ >1 GΩ >1 GΩ

Tested By Witnessed by JSW For Innovative Controls (P) Limited

Authorized Signatory
Innovative Controls (P) Limited
P-150, 8th Main, XII Sector, LIC Colony, 2
Jeevan Bima Nagar, Bangalore - 560075

TEST REPORT

Polarity test:

A given to +ve, N given to –ve

Meter showing positive Deflection at a1 is +ve & n1 is –ve

Polarity Ok as per marking on PTs in all Three phases.


Winding Resistance:( in ohm )

Secondary Winding Resistance in ohms

Phase
1a-1n 2a1-2a2 2a1-2n

R 0.3 Ω 0.6 Ω 0.7 Ω

Y 0.3 Ω 0.5 Ω 0.7 Ω

B 0.3 Ω 0.6 Ω 0.7 Ω

 Ratio Test (33kV/√3/110V/√3/110V/√3V-(110/3V-110/√3V) :

Applied Primary Measured Secondary Voltage in Volts


Voltage in Volts Core-1 Core-2

R-Y =413 r-y =1.38 r-n =0.75 0.08

Y-B =414 y-b =1.39 y-n =0.76

B-R =414 b-r =1.38 b-n=0.75

In Open Delta connection the voltage measured core was Zero.

 Remarks: Test Results found satisfactory.

Tested By Witnessed by JSW For Innovative Controls (P) Limited

Authorized Signatory