Annexure- 6.

E&I Design Consideration (Solar Power Plant) - Maihar (M.P.)

S.No. Description
1 Project Capacity (AC)
2 Project Capacity (DC)
3 Technology
4 PV Cell rating
5 PV module efficiecy
6 Performance Ratio (PR)
7 Type of mounting
8 PV module mounting structure
9 PV module tilt angle
10 Array junction box
11 Solar Inverter
a) Type of Inverter
b) Inverter efficiency
c) Losses in Inverter due to efficiency
d) Inverter losses on sleep mode
e) Number of Modules in a String
f) Strings per Inverter
g) String Power Capacity
12 Evacuation Voltage
13 DC to AC ratio (DC : AC)
14 ACDB panel
15 ACDB outgoing MCCB rating
16 Connectors
17 Lightning arrestor
18 DC cable
19 Average Power Generation per Year
20 Low Voltage Power Cables
a) Rated Voltage
b) Service Voltage
c) Conductor Material
d) Cross Section of Conductors
e) Type of Insulation
f) Screening of Cable
g) Inner & Outer Sheath
h) Cable Loading
i) Derating Factors
j) Cables Trays filling
21 High Voltage Power Cables
a) Rated Voltage
b) Service Voltage
c) System (UE / E)
d) Conductor Material
e) Maximum Cross Section of Conductors
f) Insulation Material
g) Screening of Cable
h) Temperature protection of winding
i) Moisture protection
j) Loading
k) Derating Factors
22 Generator Transformer
a) Capacity (kVA)
b) Winding Material
c) Primary Voltage
d) Secondary Voltage
e) Tapping step and Range
f) Impedance Voltage
g) Vector Group
h) Accessories and Fittings
i) Class of Insulation
j) Protection

k) Protection Devices

l) Max Allowablw Temp of Winding


m) Max Allowablw Temp of Oil
n) Neutral Terminal
o) Type of Earthing

p) Monitoring Indication

q) DCS Interface

23 Distribution Transformer
a) Capacity (kVA)
b) Winding Material
c) Primary Voltage
d) Secondary Voltage
e) Tapping step and Range
f) Impedance Voltage
g) Vector Group
h) Accessories and Fittings
i) Class of Insulation
j) Protection

k) Protection Devices

l) Max Allowablw Temp of Winding


m) Max Allowablw Temp of Oil
n) Neutral Terminal
o) Type of Earthing

p) Monitoring Indication

q) DCS Interface

24 Medium Voltage Switchboard


a) Type
b) Rated voltage
c) Rated current of Busbar at given Ambient
d) Rated Short Circuit Breaking Capacity
e) Rated Short Circuit Making Capacity
f) Busbar Material
g) Maximum Current Density

h) Protection

i) Metering

j) Earthing
k) Spare Feeders
l) Earthing Trucks
m) Maintenance Trolley
25 Low Voltage Distribution Board
a) Rated voltage
b) Rated symmetrical shortcircuit capacity
c) Control Voltage
d) Control System Voltage
e) Flexibility of Board
f) Type of Module
g) Busbar Material
h) Maximum Current Density
i) Protection
j) Metering

k) Spare Feeders
l) Protection Class (minimum)
m) Double front MCC
n) Earthing Trucks
o) Maintenance Trolley

26 Grounding & Lighting Protection

a) Foundation Grounding Type Network


b) Earthing Material

c) Min Cross Section Area of main earthing mat

d) Min Cross Section Area for branch network


e) Lightening Earthing Electorde
f) Grounding of Neutral

g) Value of Earth Resistance for Power System

h) Value of Earth system for DCS system


27 SCADA Monitoring Features
Level and kind of Monitoring (Required String
a)
Level)
b) Monitoring of PV Module
c) Monitoring of electrical equipments like Inverter
d) Electrical Parameters
e) Protection System
f) Alarming
Inverter start up, shut off and disconnection
g)
sequence
h) Over / Under voltage and frequency protection
i) Anti iislanding protection
j) Power tracker to match inverter to the array
Adjustment of delay periods to custoize system
k)
shutdown sequence
Graphical user interface for real time
l)
communication, monitoring and control

m) Optional remotr monitoring via internet modem


n) Fault notification via internet modem
o) Data acquisition and Logging
p) Web connectivity for remote monitoring
28 System Losses
a) At Full Load
b) At 75% Load
c) At 50% Load
d) At No Load
29 Voltage
a) High Voltage
b) Low Voltage
c) Lighting, plug-sockets etc.
d) DC Voltage
30 Auxiliary Control Voltage
a) PCC
b) Automation Control
c) UPS
31 Fire extinguisher
RRECL, SLDC, Electricity Board, CEIG
32
approval for the Solar Power Plant
Annexure- 6.1

on (Solar Power Plant) - Maihar (M.P.)

Requirement Bidder Remarks


10 MW 10 MW
Supplier to specify
Poly-Crystalline PV Modules
Supplier to specify
> 16%
>= 80%
Ground Mounted
Galvanized mild steel
Manual Adjustable Tilt
IP 65, if any

String Inverters / Central Inverter


> 97%
kW
kW
Nos
Nos
kWp
11 kV
1.25 : 1 (max)
Yes
Supplier to specify
Yes
Yes
Yes
kWh

1.1 kV
0.415 kV
Alumnium
sqmm (max)
XLPE
Individually Screened
PVC
80%
As per IEC
70%

11 Kv(UE)
11 kV
UE
Alumnium
AS per IEC
XLPE
Individually Screened
NA
NA
80%
As per IEC

1x100% with 80% loading


Copper Material
0.440 kV
11 kV
2.5% steps & 7.5%
5% (As per IS)
Ynyoyo
As per IEC Standard
A
50/50N, 51/51N, 63, 64T, 51NT
Buchholz, Winding Temp, Oil Temp, Oil Level,
Surge Protection, Over Prussure Protection etc.
95 deg C
85 deg C
To be provided on Star Winding
Solidly Earthed
Magnetic Level Guage, Winding Temp Indicator, Oil
Temp Indicator
Potential Free Interface with DCS for Alarm and
Tripping Parameters

1x100% with 80% loading


Copper Material
11 kV
0.440 kV
2.5% steps & 7.5%
5% (As per IS)
Dyn11
As per IEC Standard
A
50/50N, 51/51N, 63, 64T, 51NT
Buchholz, Winding Temp, Oil Temp, Oil Level,
Surge Protection, Over Prussure Protection etc.
95 deg C
85 deg C
To be provided on Star Winding
Solidly Earthed
Magnetic Level Guage, Winding Temp Indicator, Oil
Temp Indicator
Potential Free Interface with DCS for Alarm and
Tripping Parameters

VCB
11 kV
630 A
40 kA (3s)
80 kA
Copper Material
As per Type TC
Microprocessor Relay with Profibus communication
and remote programming terminal (50, 51, 80, 86,
94, 95)
Multifunction digital energy meters with Profibus
communication and remote load management
system
GI Material
1 no.
1 set
1 set

0.415 kV
50 kA
110V AC
110 V AC, 50 Hz
Extendible on either side
Drawout Type
Aluminium
As per OEM type test certificates
Microprocessor Relay
Multifunction digital energy meters with Profibus
communication and remote load management
system
20% each type but Min one
IP 42
Double Front Compartmentalized
NA
One Set for each Station

Yes
GI / Copper

As per earthing design minimum 65x8 sqmm

As per requirement
Shall be provided separate
Shall be provided separate

1 Ohm (Max)

0.5 Ohm (Max)

String level Monitoring


Yes
Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes

Yes

Yes

Yes
Yes
Yes
Yes

During detail Engg


During detail Engg
During detail Engg
During detail Engg

11 kV, 50 Hz
3P+N, 0.415 kV(+/-)10%, 50Hz(+/-) 5%
220 VAC, 50Hz, 1P+N
Supplier to specify as per PV module

220 VAC, 50 Hz
110 V AC, 50 Hz
Output 220V / Input 415 VAC, 3 Ph, 50 Hz
Portable

Fee & Duteis by RCC