Вы находитесь на странице: 1из 11

EM_3VA53601 - Ladder Diagram Page 1

WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:00


Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Wyeth Nutritional (China)

Function: EM_3VA53601

Version: 1.00
Created by: Charles Zha
Last updated date: 2009-09-01
Version:1.30
Updated by: Wilber Shou
Last updated date: 2009-10-20
Note:
Updated after Function FAT
---

0 NOP

*** Equipment Module ***

EM_3VA53601 - Contrate Valves

1 NOP

*** Equipment Module ***

Module Start
Switch concentrate EM_3VA53601 Start
to balance tank Request
EVAP_CONC_BTD_SWITCH EM_3VA53601.CMD_Start
2
Switch concentrate
to outlet
EVAP_CONC_OUTLET_SWITCH

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 2
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:03
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
InBatch. RUNNING

PHASE START Command from InBatch


(Put Running Logic in this section)
EP_3EV53600ESD Phase
EM_3VA53601 Running Run status
EM_3VA53601.STS_Running EP_3EV53600ESD.STS_Run
3 / MCR

Running Logic

4 NOP

*** Phase step sequence ***

Step 1
Swtich valve to tank
Step Number Switch concentrate Step Number
EM_3VA53601 FAT Force Bit to balance tank EM_3VA53601
EQU FAT_CCVL_Force[0] EVAP_CONC_BTD_SWITCH MOV
5 Equal Move
Source A EM_3VA53601_StepN Source 1
33
Source B 0 Dest EM_3VA53601_StepN
33

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 3
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Step 3
Concentrate to Balance Tank
Step Number 3TA-53605-VA-0002 Step Number
EM_3VA53601 FAT Force Bit Closed Status EM_3VA53601
EQU FAT_CCVL_Force[1] CM_3TA53605_VA0002.STS_Cls MOV
6 Equal Move
Source A EM_3VA53601_StepN Source 3
33
Source B 1 Dest EM_3VA53601_StepN
33

Step Number 3TA-53605-VA-0003


EM_3VA53601 FAT Force Bit Closed Status
EQU FAT_CCVL_Force[2] CM_3TA53605_VA0003.STS_Cls
Equal
Source A EM_3VA53601_StepN
33
Source B 25

Step 4
Switch valve to forward flow
Step Number Switch concentrate Step Number
EM_3VA53601 FAT Force Bit valve to drain EM_3VA53601
EQU FAT_CCVL_Force[3] EVAP_CONC_VALVE_DRAIN MOV
7 Equal Move
Source A EM_3VA53601_StepN Source 4
33
Source B 3 Dest EM_3VA53601_StepN
33

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 4
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Step 14
Switch valve drain to outlet
Step Number Switch concentrate Step Number
EM_3VA53601 FAT Force Bit to outlet EM_3VA53601
EQU FAT_CCVL_Force[4] EVAP_CONC_OUTLET_SWITCH MOV
8 Equal Move
Source A EM_3VA53601_StepN Source 14
33
Source B 3 Dest EM_3VA53601_StepN
33

Step 15
Switch valve to forward flow
Step Number 3TA-53605-VA-0003 Step Number
EM_3VA53601 FAT Force Bit Open Status EM_3VA53601
EQU FAT_CCVL_Force[5] CM_3TA53605_VA0003.STS_Opn MOV
9 Equal Move
Source A EM_3VA53601_StepN Source 15
33
Source B 14 Dest EM_3VA53601_StepN
33

Step 24
Swtich valve to tank
Step Number Switch concentrate Step Number
EM_3VA53601 FAT Force Bit to balance tank EM_3VA53601
EQU FAT_CCVL_Force[6] EVAP_CONC_BTD_SWITCH MOV
10 Equal Move
Source A EM_3VA53601_StepN Source 24
33
Source B 33 Dest EM_3VA53601_StepN
33

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 5
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Step 25
Switch valve to drain
Step Number 3TA-53605-VA-0002 Step Number
EM_3VA53601 FAT Force Bit Closed Status EM_3VA53601
EQU FAT_CCVL_Force[7] CM_3TA53605_VA0002.STS_Cls MOV
11 Equal Move
Source A EM_3VA53601_StepN Source 25
33
Source B 24 Dest EM_3VA53601_StepN
33

Step 33
Concentrate to outlet
Step Number 3TA-53605-VA-0002 Step Number
EM_3VA53601 FAT Force Bit Open Status EM_3VA53601
EQU FAT_CCVL_Force[10] CM_3TA53605_VA0002.STS_Opn MOV
12 Equal Move
Source A EM_3VA53601_StepN Source 33
33
Source B 15 Dest EM_3VA53601_StepN
33

Step 34
Switch valve to drain
Step Number Switch concentrate Step Number
EM_3VA53601 FAT Force Bit valve to drain EM_3VA53601
EQU FAT_CCVL_Force[11] EVAP_CONC_VALVE_DRAIN MOV
13 Equal Move
Source A EM_3VA53601_StepN Source 34
33
Source B 33 Dest EM_3VA53601_StepN
33

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 6
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Step 0
Concentrate to drain
Step Number 3TA-53605-VA-0002 Step Number
EM_3VA53601 FAT Force Bit Open Status EM_3VA53601
EQU FAT_CCVL_Force[12] CM_3TA53605_VA0002.STS_Opn MOV
14 Equal Move
Source A EM_3VA53601_StepN Source 0
33
Source B 4 Dest EM_3VA53601_StepN
33

Step Number 3TA-53605-VA-0003 EM_3VA53601 State


EM_3VA53601 FAT Force Bit Closed Status Complete Request
EQU FAT_CCVL_Force[13] CM_3TA53605_VA0003.STS_Cls EM_3VA53601.CMD_StateCmplt
Equal L
Source A EM_3VA53601_StepN
33
Source B 34

Copy StepNumber to EM AutoStep


EM_3VA53601
Requested Auto Step
Number
MOV
15 Move
Source EM_3VA53601_StepN
33
Dest EM_3VA53601.SET_AutoStep
33

Reset Signal

Concentrate Concentrate
to balance tank to outlet
EVAP_CONC_BTD EVAP_CONC_OUTLET
16 U U

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 7
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
*** Activation of control modules ***

CM_3TA53605_VA0002
Step Number 3TA-53605-VA-0002
EM_3VA53601 Auto Close Request
EQU CM_3TA53605_VA0002.CMD_AutoCls
17 Equal L
Source A EM_3VA53601_StepN
33
Source B 1

Step Number
EM_3VA53601
EQU
Equal
Source A EM_3VA53601_StepN
33
Source B 24

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 8
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
*** Activation of control modules ***

CM_3TA53605_VA0002
Step Number 3TA-53605-VA-0002
EM_3VA53601 Auto Open Request
EQU CM_3TA53605_VA0002.CMD_AutoOpn
18 Equal L
Source A EM_3VA53601_StepN
33
Source B 4

Step Number
EM_3VA53601
EQU
Equal
Source A EM_3VA53601_StepN
33
Source B 15

CM_3TA53605_VA0003
Step Number 3TA-53605-VA-0003
EM_3VA53601 Auto Open Request
EQU CM_3TA53605_VA0003.CMD_AutoOpn
19 Equal L
Source A EM_3VA53601_StepN
33
Source B 14

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 9
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
CM_3TA53605_VA0003
Step Number 3TA-53605-VA-0003
EM_3VA53601 Auto Close Request
EQU CM_3TA53605_VA0003.CMD_AutoCls
20 Equal L
Source A EM_3VA53601_StepN
33
Source B 25

Step Number
EM_3VA53601
EQU
Equal
Source A EM_3VA53601_StepN
33
Source B 34

Step 3 - Activations
Step Number Concentrate
EM_3VA53601 to balance tank
EQU EVAP_CONC_BTD
21 Equal L
Source A EM_3VA53601_StepN
33
Source B 3

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 10
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:04
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Step 33 - Activations

Step Number Concentrate


EM_3VA53601 to outlet
EQU EVAP_CONC_OUTLET
22 Equal L
Source A EM_3VA53601_StepN
33
Source B 33

Master Control Reset

23 MCR

Step 0 - Activations
Step Number Concentrate
EM_3VA53601 to drain
EQU EVAP_CONC_DRAIN
24 Equal
Source A EM_3VA53601_StepN
33
Source B 0

RSLogix 5000
EM_3VA53601 - Ladder Diagram Page 11
WNC_PLC04:MainTask:U_3EV53600 10/22/2009 16:38:05
Total number of rungs in routine: 27 C:\Documents and Settings\cnshouw\Desktop\Suzhou Wyeth Project PLC\Ver16\WNC_PLC04_1_3_20091022_1113.ACD

[CCVL]
Concentrate Valves
Emergency Shutdown
EP_3EV53600ESD Phase Step Number EM_3VA53601 State
run step buffer EM_3VA53601 Complete Request
EQU MOV EM_3VA53601.CMD_StateCmplt
25 Equal Move L
Source A EP_3EV53600ESD.STS_SI Source 0
0
Source B 2 Dest EM_3VA53601_StepN
33

Concentrate Concentrate
to balance tank to outlet
EVAP_CONC_BTD EVAP_CONC_OUTLET
U U

Procedure Complete
EM_3VA53601 Running EM_3VA53601 Reset
Complete Request
EM_3VA53601.STS_Complete EM_3VA53601.CMD_Reset
26

(End)

RSLogix 5000