Академический Документы
Профессиональный Документы
Культура Документы
T.S . Sidhu, Senior Member, IEEE D.S.Ghotra, Student Member, IEEE M. S.Sachdev, Fellow, IEEE
Power System Research Group
University of Saskatchewan
Saskatoon, Saskatchewan
CANADA S7N SA9
Abstract: This paper describes the design of a distance relay that uses occurrence of a fault and initiate the filtering process.
adaptive data window filters to provide high speed tripping. The Starting from the fault detection, the data window size is
relay uses a fault detector to detect the inception of a fault. Starting progressively increased to one cycle of the fundamental
from the fault detection, the data window size is progressively frequency. Using the filters of appropriate lengths at
increased as new fault samples become available until the window different sampling instants, the transient response of the
size becomes one cycle of the fundamental frequency. At each
instant, a suitable filter is used for estimating voltage and current relay becomes faster. This allows faster convergence of the
phasors. This procedure improves the transient response of the relay seen impedance and, therefore, reduces the trip time. The
and allows faster convergence of the impedance estimates and, relay was tested using the fault simulations on a part of
therefore, reduces the trip time. The proposed relay was tested by 138/230 kV power system of SaskPower Corporation
using fault simulations on a sample power system. Results indicate modeled using the EMTDWSCAD software. Some results
that the proposed relay design reduces the trip times. are included in the paper.
Keywords: Transmission line protection, Distance relay, Adaptive
data window filters II. THE PROPOSED TECHNIQUE
A. Overview
1. INTRODUCTION
The acquired voltage and current signals are filtered
Protective relays are a vital control component of a power through a low pass anti-aliasing filter. The filtered signals
system. They detect faults and issue trip commands to are used for fault detection, computations of voltage and
appropriate circuit breakers for isolating the faulted portion of current phasors, and apparent impedance calculations.
the power system from the rest of the system. Distance relays
are generally used for transmission line protection. Most Once a fault detector indicates a fault, the digital filters are
distance protection relays now marketed are microprocessor- initiated for phasor computations. The filtering is started
based systems [1,2,3]. The trip times of these relays are with a data window size of ten samples, therefore, the
similar to those of electromechanical and solid-state coefficients of the 10* order orthogonal filters are used to
counterparts. compute the fundamental frequency phasors. Starting from
the isstant of fault detection, the immediately preceding ten
Several distance relays being sold today estimate samples of the input signal form the first data window as
fundamental frequency phasors from the quantized values of shown in Figure 1. This ten-sample window may include
voltage and current samples [4]. As a fault occurs on a pre- and post-fault samples. The data window is advanced by
transmission line, the acquired signals may include high one sample as a new sample becomes available. This means
frequency damped oscillations, exponential components, that the most recent sample is included in the data window
harmonic components, etc., in addition to the fundamental and the oldest sample is discarded, which keeps the length of
frequency signal. Therefore, suitable filters are required to the data window to ten samples. The advancement of ten-
extract the fundamental frequency component. The higher sample window is continued until four sampling instants
frequency components are eliminated by using an analog anti- after the fault detection as shown in Figure 1. After this, the
aliasing filter of appropriate cut-off frequency. There can be data window size is progressively increased by one
some low frequency, dc and dc-decaying components, present
in the signals after filtering through the anti-aliasing filter.
Most distance relays use filters that use fixed data windows
of one cycle of the nominal frequency to estimate the
fundamental frequency phasors [4]. As a new sample is
acquired, the data window advances by including a new
sample and discarding the oldest sample. This keeps the
length of the data window constant. Therefore, the transient
response of the filter is about one cycle and the impedance
estimates do not converge before this time. However, it is
possible to use different lengths of data windows at different
stages of a disturbance 131.
This paper describes the use of digital filters of different
data window lengths in a distance relay to provide faster
tripping. This technique requires a fault detector to detect the Figure 1.Adaptive data windows
BG
CG + 3kb
where,
A, B and C denote the three phasors,
G denotes the ground.
V, and I, are the voltage and current signals used by the relay elements.
V. Vb and V, are the voltages of a, b and c phases with respect to
ground respectively.
I,, I* and are the cunents in a b and c phases respectively,
k = (Za- Z N 5 .
& and Zl are the zero and positive sequence line impedances
respectively, and
b is the zero sequence current. Genemtor < .
,.,
@ L4,3.184kms L,,78.592 kms 1'
and CG relay elements are used for detecting three-phase to A
ground, two-phase to ground, and phase to ground faults. 6 L6, 6.208 k m s 7
Operating characteristics, shown in Figure 2, are identical for V
- "
all relay elements. The seen impedance is estimated by each circuit line
FTFg2-
relay element separately and is used to identify the location of
the fault. If the seen impedance estimated by any relay
element lies inside the characteristics, a trip command is
150
T I & TMVA
2
230/13.8/138 kV ''2
.?fUL
- 13.8kV Double
circuit line
at /Line
eo-
80-
data window approach
B eo-
3
m-
$50-
I
604-30-20-10 0 10 20 3l 40 50 % 40-
Resistance(Ohms) 2 30.
Figure 4. Trajectories of the seen impedances for a phase 'a' to ground 20-
fault. 10 -
0 -
Figure 5 shows the fault trajectories when the generation
level is minimum and a phase 'b' to phase 'c' fault is Resistance ( o h s )
experienced on the line, L1,at a distance of 140 kms from the
Figure 6. Trajectories of the seen impedvlces for n three-phase
relay location. This figure depicts the impedances as seen by to ground fault.
the BC relay element when adaptive and fmed data window
approaches are used. It is observed that when the adaptive
Figure 7 shows the fault trajectories when the generation
window approach is used, the seen impedance enters the
level is minimum and a three-phase to ground fault is
operating zone of the relay fourteen samples after the
experienced cm the line, L,,at a distance of 185 kms from
occurrence of the fault. Whereas, when the fixed window
the relay location, which is outside the protection zone.
approach is used, the seen impedance enters the operating
Wher. the adaptive and the fixed window approaches are
zone twenty-three samples after the occurrence of the fault.
used, the seen impedance does not enter the operating zone
Therefore, the transient response of the proposed technique is of the relay. Therefore, no trip command is issued.
faster, and thus, a lower trip time is obtained.
(11.1031,76.1013)
** I b m p l e after the
fatdl usingthe fixed
data window approach
(11.1031,76.1013)
10 -
60-100-30-2o-io o i o 10 30 m n l
U)
I . . . . . 1
Resistance (ohms) dO403(HQ10 0 1020304050
Figure 5. Trajectoriesof the seen impedances for a phase 'b Resistance (ohms)
phase 'c' fault. Figure 7. Trajectories of the seen impedances for a three-phase
to ground fault outside the zone.
Figure 6 shows the fault trajectories when the generation
level is maximum and a three-phase to ground fault is B. Trip Times
experienced on the line. L1,at a distance of 20 kms from the
relay location. It is observed that when the adaptive window Trip times of the relays using the adaptive and fixed data
approach is used, the convergence of the impedance as seen window approaches were compared for various faults on
by the AG relay element is faster as compared to that by the different lines; and at different distances from the relay
Faullsat 20 kma
0.m51
-1
0 . m
0.0167
I
f 0,0126
CI
F 0".
figure 9.Comparison of trip times for faults at 100 kms 0.W
line length when generation is minimum.
.bco .bc .b bc Ca .bo baa a-9 ag bg cg
0.0251 Faults a1 140 kma
-D
v)
0.0'87
Figures 14 and 15 show the comparison of trip times when
0.0126
a
Q
faults are simulated at maximum generation level by
E 00083 including the fault resistance of 10 ohms and 20 ohms,
respectively. It can be seen that by including the fault
0.- resistance, the trip times -€orall the faults are lower when the
relay uses adaptive data window approach.
Falltsat140kma
Hgurc 10. Comparisonof trip times for faults at 140 kms
line length when generation is minimum.
BIOGRAPHIES
Tarlochan S. Sidhu received the B.E. (Hons.) degree from the Punjabi
University, Patiala, India in 1979 and the M.Sc. and Ph.D.degrees from the
University 0 1 Saskatchewan, Saskatoon, Canada in 1985 and 1989
respectively. He worked for the Regional Computer Center, Chandigarh.
India from 1979 to 1980 and developed software for computer-based
systems. He rdso worked for Punjab State Electricity Board, lndia from
1980 to 1983 in distribution system operation and thermal generating station
design. After obtaining the Ph.D. degree. he joined Bell-Northern Research
Fault and their distances @us)
Ltd.. Ottawa, Canada and worked on a software development project for
Rgure 15. Comparison of trip times wben fault resistance is 20 ohms about one year. He joined, in 1990, the University of Saskatchewan where
he is pmently Professor in the Department of Electrical Engineering and
Graduate Chaiuman of the. Department of Electrical Engineering. He is a
IV.CONCLUSI0NS senior member of the IEEE. a Registered Professional Engineer in the
Province of Saskatchewan and a ChWrCd Engineer in the UK. His areas of
The paper describes the design of a distance relay using the interest includt: power system protection. monitoring and control.
adaptive data window filters for transmission line protection.
The relay elements used for estimating the seen impedance Daljit S. Ghoitra received the B.E. degree in electronics engineering from
and the design of the fault detector are also discussed. The Marathwada lrtstitute of Engineering and Tcchnology.Aurangabad, lndia in
1995. He wokrd for Jnnotech Madceting as an engineer From 1995 to 1997.
signal compositions selected for the design of various LES He joined University of Saskatchewan, Saskatoon. Canada in 1998. where
filters using different data window lengths are also described. he is cumntl:y pursuing the M.Sc. degree in electrical engineering. His
research inmert includes power system protection, monitoring & control. '