Easergy P3
Network Protection Relays
General Contents
PM106568
Range description 6
Easergy P3 Standard 28
Easergy P3 Advanced 48
Ordering 102
It helps you::
• Translate data into actionable intelligence and better business decisions
• Make informed decisions to secure uptime and operational efficiency thanks to
Efficient asset real-time control platforms
management
• Get visibility into your electrical distribution by measuring, collecting,
Boost your efficiency and
reduce downtime using aggregating, and communicating data
predictive maintenance tools.
EcoStruxure Platform
Cloud and/or
On Premise
End-to-End
Edge control
Connected products
• Simple selection and ordering with • Simpler operation and maintenance • Embedded arc protection
EcoReal MV with the Easergy SmartApp • Built-in virtual injection testing
• Simplified configuration with the new • 9 communication protocols in one • Compliant with international
eSetup Easergy Pro setting tool box, including IEC 61850 standards (i.e. IEC 60255-1)
• Faster delivery with on-the-shelf • Increased number of inputs and
availability of standard configurations outputs for more possibilities
Range overview
DM105528
T U L L F U
G G U U U U U U M
T U L L G U M M
Selection guide 9
Communication
21
Examples of network architectures
Voltage - - -
P3F30
with directional
Feeder -
P3L30
line diff. & distance
P3U30
P3U10 P3U20 with directional O/C P3T32
Transformer -
with voltage protection with directional
P3M32
Motor P3M30 with directional
P3G32
Generator P3G30 with directional
Characteristics
Phase current 1/5A CT (x3) 1/5A CT (x3) 1/5A CT (x6)
1/5A CT & 1A CT 1/5ACT (x2) & 1A CT
Measuring inputs Residual current 1/5A CT or 0.2/1A CT or or
1A CT & 0.2A CT 1/5A CT & 1A CT & 0.2A CT
Voltage VT (x1) VT (x4) VT (x4) VT (x4)
Arc-flash sensor input - 0 to 4 point sensor (1) (2) 0 to 4 point sensor (1)
Input 2 10 16 6 to 36 6 to 16
Digital
Output 5 + SF 5 + SF 8 + SF 10 to 21 + SF 10 to 13 + SF
Input - 0 or 4 (1) 0 or 4 (1)
Analogue
Output - 0 or 4 (1) 0 or 4 (1)
Temperature sensor input - 0 or 8 or 12 (1) 0 or 8 or 12 (1)
Front port USB USB
Nominal power supply 24V dc or 48-230V ac/dc 24 to 48V dc or 110-240V ac/dc
Ambient temperature, in service -40 to 60°C (-40 to 140°F) -40 to 60°C (-40 to 140°F)
Communication
Rear ports
-
RS232, IRIG/B, RS485, Ethernet
IEC61850 ed1 & ed2 -
IEC 60870-5-101 & 103 -
DNP3 over Ethernet -
DNP3 serial -
Modbus serial -
Protocols
Modbus over Ethernet -
Ethernet IP -
DeviceNet -
Profibus DP -
SPAbus -
Redundancy protocols (RSTP/PRP) -
Others
1 object 6 controlled + 6 controlled +
Control
mimic 2 monitored objects mimic 2 monitored objects mimic
Logic (Matrix + Logic equation)
Withdrawable CT connector with shorting -
Remote HMI -
Hardware dimensions (W/H/D) 171 x 176 x 214(3) mm / 6.73 x 6.93 x 8.43 in 264 x 177 x 208 mm / 10.39 x 6.97 x 8.19 in
(1) Depends on optional module
(2) Arc flash protection option not available on Easergy P3L30
(3) 226 mm (8.90 in) with ring-lug connectors
DM105536
P3F30 P3F30
P3G30 P3G30
P3T32 P3T32
P3G32 P3G32
P3F30 P3M30
P3T32 P3M32
• Up to 4 light point sensors to monitor the busbar • Up to 4 light point sensors in each relay
• Transmission of light detection signals via digital I/O or
IEC 61850 GOOSE messages
Zone 1
light detection signal
signal sent to upstream relay for tripping
P3F30
P3G30 • Light detection in zone 2:
P3T32
P3G32 incomer Easergy P3 trips, if fault confirmed by overcurrent
Zone 1
• Light detection in zone 3:
corresponding outgoing Easergy P3 trips, if fault confirmed by
Zone 2 overcurrent
P3F30 P3M30
P3T32 P3M32
Outgoing protection
• Feeder overcurrent protection
• Feeder overload protection
Protection of low-capacitance feeders in Protection of high-capacitance feeders Protection of feeders with metering
impedance-earthed or solidly-earthed in impedance-earthed or compensated
neutral systems or isolated neutral systems
DM105538
DM105539
DM105540
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
• Feeder earth-fault overcurrent • Directional earth-fault overcurrent • Power and energy measurement
• Transient intermittent earth-fault • Min and max demand values over the last
31 days and 12 months
Incomer protection
• Busbar overcurrent protection
Incomer protection without voltage monitoring Incomer protection with voltage and
frequency monitoring
DM105541
DM105542
DM105543
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
DM105545
P3U30 P3F30
• Voltage and frequency min and max values • Directional phase overcurrent
• Voltage harmonic values and THD • Directional earth-fault overcurrent
• Voltage sags and swells
Line protection
• Overcurrent and earth-fault protection (directional and non-directional)
• Feeder overload protection
Overhead line protection Incomer protection with fault locator Line protection with line differential
and distance functions
DM105546
DM105547
DM105548
P3F30
P3U30 P3F30
P3L30
P3L30
Motor protection
• Motor overcurrent and earth-fault overcurrent
• Thermal overload
• Motor start-up supervision
• Motor restart inhibition
Motor protection without voltage Motor protection with voltage Motor protection with differential
monitoring monitoring function
DM105549
DM105550
DM105551
P3U20 P3M30
P3U30 P3U30 P3M30 P3M32
RTD
module
DM105553
P3U30 P3M30
P3M32
26
26 63
63 49T
49T
RTD
module
DM105555
DM105556
P3U10
P3U20 P3U30 P3F30
P3U20 P3F30 P3F30
P3U30
P3U30
26 26 26
63 63 63
49T 49T
RTD
module
• Directional earth-fault overcurrent for • Temperature measurement (ambient, oil) • Over and undervoltage protection
impedance earthed or compensated
neutral systems
Transformer feeder protection with additional current measurement Transformer feeder protection with
differential function
DM105559
DM105558
DM105557
26 26 26
63 63 63
49T 49T 49T
DM105561
DM105562
P3U10 P3U10
P3U20 P3F30 P3U20 P3F30 P3U30 P3F30
P3U30 P3U30
• Transformer earth-fault overcurrent • Earth-fault overcurrent for transformer • Over and undervoltage protection
and back-up protection • Power and energy measurement
• Min and max demand values over the last
31 days and 12 months
DM105564
P3T32
DM105566
DM105565
26
26
63
63
49T
49T
P3U30 P3G30
P3U30 P3G30
• Earth-fault overcurrent protection of the supplied network • Earth-fault overcurrent protection of the generator
Note: monitoring of generator insulation must be ensured by • Earth-fault overcurrent protection of the supplied network
another device
26
26
63
63
49T
49T
P3G30
P3U30 P3G30
• Earth-fault overcurrent protection of the transformer • Earth-fault overcurrent protection of the generator and the
• Neutral voltage displacement to detect transformer earth-fault transformer
when CB is open • Neutral voltage displacement to detect transformer earth-fault
• Synchro-check when CB is open
Note: monitoring of generator insulation must be ensured by • Synchro-check
another device
DM105570
DM105571
26
63
49T
• Earth-fault overcurrent protection of the • Stator earth-fault detection • Stator earth-fault detection
generator when coupled • Differential protection • Differential protection
• Neutral voltage displacement to detect • Restricted earth-fault protection
generator earth-fault when CB is open
• Synchro-check
DM105573
DM105574
P3U10
P3U20
P3U30 P3U30
P3F30
P3U10
P3U20
P3U30
HMI/
SCADA
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
communication.
Serial Daisy chain
link
Available protocols:
• Modbus RTU
• IEC 60870-5-101
• IEC 60870-5-103
Relay 1 Relay 2 Relay n (n max= 32)
• DNP3
• DeviceNet
• Profibus
• SPAbus
HMI/
SCADA
This architecture allows you to connect a set of Easergy protection relays directly to
an Ethernet network.
Available protocols:
• IEC 61850
• IEC 60870-5-101
Ethernet
Network • DNP3
• Modbus
Ethernet Ethernet
switch switch • EtherNet/IP
Note: It is possible to mix on the same Ethernet network the IEC 61850 protocol
with any of the 4 other protocols.
This allows you to use the GOOSE messages between relays together with another
protocol for communication to SCADA.
Sub-
Network It is also possible to connect an Easergy relay to 2 different control systems, using
the same Ethernet communication port and IEC 61850 protocol for one of them and
any available protocol for the other one.
The Easergy P3 relay handles the IEC 61850 station bus, in compliance with
standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Ed.1 or Ed.2, according to
configuration.
Architecture example 1
DM102975
Panel Ethernet
switch Easergy
HMI Pro
Switchboard internal network
This architecture allows fast GOOSE communication between Easergy protection
Ethernet
relays of the switchboard, thus avoiding costly wiring. Typical uses are logic
discrimination, load shedding, etc.
GOOSE GOOSE
messages messages
In addition, a panel HMI featuring a web browser can be used to monitor and
control the entire switchboard.
A spare connection on the panel Ethernet switch can also be provided for
connecting the Easergy Pro.
Architecture example 2
DM105575
HMI/
SCADA
Connection to SCADA using serial lines and legacy protocols
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
Daisy chain
Serial
link
communication protocols such as Modbus-RTU, DNP3, or IEC 61870-5-103.
The RS485 serial communication port of the Easergy protection relay enables
simple daisy chaining wiring thanks to its 2 RJ45 connectors, suited for 2-wire or
4-wire cabling. A termination module is plugged into the last connection. As an
alternative, the fiber optic serial communication port can be used.
Relay 1 Relay 2 Relay n (n max= 32)
Architecture example 3
DM105576
HMI/
SCADA
Sub-
Network
HMI/
SCADA
RSTP (Rapid Spanning Tree Protocol)
DM105577
The principle of RSTP is to virtually cut all links that are not necessary at a given
time, changing the meshed topology into a tree topology.
The main advantage of RSTP is that it is widespread and works on any network
Ethernet Ethernet
switch switch topology. On the other hand, RSTP takes milliseconds or seconds to reconfigure the
network in case of network interruption.
Ethernet Ethernet
switch switch
HMI/
SCADA
Network A Network B
The receiving device is in charge of eliminating the redundant frame if it is
received.
PRP features a 0 ms recovery time in case of failure.
PRP is supported by Easergy P3 relays.
Ethernet ports
Protocol IEC 61850 Ethernet/IP FTP
Real-time data
Measurement -
Alarms and status -
Controls -
Time-stamped events -
Historical data
Disturbance records -
Setting management
Setting group change -
Serial Ports
Protocol IEC 60870-5-103 DeviceNet Profibus SPAbus
Real time data
Measurement
Alarms and status
Controls
Time-stamped events
Historical data
Disturbance records - - -
Setting management
Setting group change
Settings - - -
Engineering system
DM105579
Easergy web-HMI
In addition to eSetup Easergy Pro, most of the resources of the relay can be
Safe Repository and
Schneider Electric web accessed with a standard web browser, using the web pages embedded into the
relay.
System
.icd file configurator
.icd file
Safe Repository and When the configuration of an Easergy protection relay is done, setting tool can
Schneider Electric web
generate IED capability file. This file can be used by the system configurator.
ZONE 1
= Arc Sensor
ZONE 2
ZONE 3
Presentation 30
Functional view 32
Communication protocols 41
Programmable stages 42
Connection diagram 44
Model selection 47
The Easergy P3 Standard protection relay has been developed to meet your standard protection needs
for building, distribution utilities, and industrial applications. Thanks to its optimized and flexible design,
the Easergy P3 Standard provides an excellent solution for various protection applications.
Robust
• Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays
• Strong tests performed in international laboratories
• Compliant to IEC electro-mechanical standards
Easergy P3 is designed to cover all the standard applications with only one device: the
Universal Protection.
DM105529
U
Feeder
U
U U U U
M
Capacitor Motor Feeder Transformer
eSetup
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A
0 Local Port
ON I3: 0.0A Service
LED A P : 0.0W LED B
V : 0.0V
1 LED C LED D
LED E LED F
Control buttons LED G LED H
Programmable Logic
Setting groups:4
H2/H5
SOTF
79 74 86 60 99
CLPU
48
37 51LR 66
59C
50BF
59N
50 67NI
51
67N
51C
50N
49 50G X3 Connector
DI1 DI2
51N
46 51G SF T1 T2 T3 T4 A1
I1 / I2 / I3 Io V/V0
Analog measurement card Power Supply
Current input Voltage input
I1 I2 I3 Io - V1 - - -
eSetup
DM105584
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A Comm. interface - X4
0 Local Port
ON I3: 0.0A Service
Redundancy Protocols
LED A P : 0.0W LED B • RSTP • IEC 61850
V : 0.0V • PRP • Modbus
1 LED C LED D
• DNP3.0
LED E LED F Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
Control buttons LED G LED H
Comm. interface - X4
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF
59N Protocols
Modbus
Protocols
Modbus
Protocols
DeviceNet
DNP3.0 DNP3.0
IEC-103 IEC-103
50 67NI SPAbus
RS485 RS485
51 X4 Connector Serial
67N Serial network
DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
51C
OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G X3 Connector Tx
51N Rx
I1 I2 I3 Io - V1 - - - RTD CH06
mA In4
RTD CH06
eSetup
DM105585
Easergy Pro
REL52822
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A Comm. interface - X4
0 Local Port
ON I3: 0.0A Service
Redundancy Protocols
LED A P : 0.0W LED B • RSTP • IEC 61850
V : 0.0V • PRP • Modbus
1 LED C LED D
• DNP3.0
LED E LED F Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
Control buttons LED G LED H
Comm. interface - X4
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF X5 Connector
DI13 DI16
59N Protocols
Modbus
Protocols
Modbus
Protocols
DeviceNet
RS485 RS485
81R
51 X4 Connector Serial
67N 25
Serial network
81 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
51C 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G 59 X3 Connector Tx
51N Rx
I1 I2 I3 Io V1 V2 V3 V0 RTD CH06
mA In4
RTD CH06
PM106501
PM106338
Easergy P3U10 Easergy P3U20 Easergy P3U30
Withdrawable connectors
PM106500
DM105587
DM105588
Dimensions
DM105589
171
6.73
176
6.93
A B
With screw connector 214 mm / 8.43’’ 192 mm / 7.6’’
With ring-lug connector 226 mm / 8.90’’ 204 mm / 8.0’’
13.5
0.53
144.5 6
DM105590
5.69 12 6
4.9
9.25 5.0
0.36 0.2
28.5
1.12
2 E a s e rg
y
9.5
0.37
120
139 4.72
5.47
OK
F2
F1
Weight (maximum)
O
Analog inputs
Measuring Input Consump- Rated 1-second 10-second
range Impedance tion thermal overload overload
withstand
Phase Current Input 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 1 to 10A (Continuously)
Residual Current Input (I0) 5A CT 0.015 – 50 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 0.1 to 10A (Continuously)
Residual Current Input (I0) 1A CT 0.003 – 10 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Configurable for CT secondaries 0.1 to 10.0A (Continuously)
Residual Current Input (I0) 0.2A CSH sensor 0.0006 – 2 A 0.02 Ohm 0.02 VA 0.8 A 20 A 4A
Configurable for CT secondaries 0.1 to 10.0A (Continuously)
Voltage Input 0.5 – 190 V n.a. < 0.5 VA 100 V 250V 600 V
Configurable for VT secondaries 50 to 120V (100 V / 110 V) (Continuously)
Digital Input
Nominal operation voltage DI1 to DI16 24 to 230 V ac/dc 110 to 230 V ac/dc 220 to 230 V ac/dc
Typical switching threshold 12 V dc 75 V dc 155 V dc
At state 1 ≥ 19.2 V dc ≥ 88 V dc ≥ 176 V dc
Input limit voltage
At state 0 < 10.0 V dc < 60 V dc < 140 V dc
Frequency 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Typical consumption <4 mA (typical approx. 3 mA)
Voltage withstand 255 V ac/dc
Digital Output
Type of contact Control and Trip contact, Tx Signal contact, A1 Signal Contact, SF
Rated Voltage 250 V ac/dc 250 V ac/dc 250 V ac/dc
Continuous current 5A 5A 5A
AC 2.000 VA 2.000 VA 2.000 VA
Breaking at 48 V dc 1.15 A 1A 1A
DC
capacity at 110 V dc 0.5 A 0.3 A 0.3 A
(L/R=40ms)
at 220 V dc 0.25 A 0.15 A 0.15 A
< 0.5 s 30 A 30 A -
Making capacity
< 3.0 s 15 A 15 A -
Minimum making capacity 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc
Typical operation time <8 ms - -
Contact material AgNi 90/10 AgNi 0.15 gold plated AgNi 0.15 gold plated
Power supply
Nominal Voltage 48 to 230 Vac/dc 24 Vdc
Range -20% / +10% (40 to 253 Vac/dc) -20% / +20% (19.2 to 28.8 Vdc)
25 A with time constant of 1000 µs
Inrush current (DC) 25 A with time constant of 750 µs
15 A with time constant of 500 µs
Normal conditions <15 W (<30 VA)
Power consumption
Output relays activated <25 W (<50 VA)
Acceptable momentary outages <50 ms (110 V dc)
(1) 78,750 in
Electromagnetic
compatibility
Standard and test class/level Test value
Emission tests IEC/EN 60255-26 (ed3)
Conducted EN 55022, Class A / CISPR 22 0.15 – 30 MHz
Emitted EN 55011, Class A / CISPR 11 30 – 1000 MHz
Immunity IEC/EN 60255-26 (ed3)
1 Mhz damped oscillatory wave IEC/EN 61000-4-18 ±2.5kVp CM
±2.5kVp DM
Static discharge (ESD) IEC/EN 61000-4-2 Level 4 ±8 kV contact
±15 kV air
Emitted HF field IEC/EN 61000-4-3 Level 3 80 - 2700 MHz, 10 V/m
Fast transients (EFT) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
Surge IEC/EN 61000-4-5 Level 3 ±2 kV, 1.2/50 µs, CM
±1 kV, 1.2/50 µs, DM
Conducted HF field IEC/EN 61000-4-6 Level 3 0.15 - 80 MHz, 10 Vrms
Power-frequency magnetic field IEC/EN 61000-4-8 300 A/m (continuous) 1000 A/m 1 – 3s
Pulse magnetic field IEC/EN 61000-4-9 Level 5 1000A/m, 1.2/50 µs
ac and dc voltage dips IEC/EN 61000-4-29, IEC/EN 61000-4-11 0% of rated voltage
• ac: ≥ 0.5 cycle
• dc: ≥ 10 ms 40% of rated voltage
• ac: 10 cycles
• dc: 200 ms 70% of rated voltage
• ac: 25 cycles
• dc: 500 ms
ac and dc voltage interruptions IEC/EN 61000-4-29, IEC/EN 61000-4-11 100% interruption
• ac: 250 cycles
• dc: 5 s
Voltage alternative component IEC/EN 61000-4-17 15% of operating voltage (dc) / 10 min
Mechanical
robustness
Standard and test class/level Test value
In operation
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 1 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 10 Gn / 11 ms
Seismic IEC 60255-21-3 Method A, Class II 2G horizontal / 1G vertical , 1–35 Hz
De-energized
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 2 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 30 Gn / 11 ms
Bump IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 20 Gn / 16 ms
Environment tests
Standard and test class/level Test value
In operation
Dry heat EN / IEC 60068-2-2, Bd 70°C (158°F)
Cold EN / IEC 60068-2-1, Ad -40°C (-40°F)
Damp heat, cyclic EN / IEC 60068-2-30, Db From 25°C (77°F) to 55°C (131°F)
From 93% RH to 98% RH
Testing duration: 6 days
Damp heat, static EN / IEC 60068-2-78, Cab 40°C (104°F)
93% RH
Testing duration: 10 days
Change of temperature IEC / EN 60068-2-14, Nb Lower temp -40°C (-40°F)
Upper temp 70°C (158°F)
5 cycles
In storage
Dry heat EN / IEC 60068-2-2, Bb 70°C (158°F)
Cold EN / IEC 60068-2-1, Ab -40°C (-40°F)
Environmental
conditions
Safety
Standard and test class/level Test value
Electrical safety tests
Impulse voltage withstand IEC/EN 60255-27 5 kV, 1.2/50 µs, 0.5 J
1 kV, 1.2/50 µs, 0.5 J Communication
Dielectric test IEC/EN 60255-27 2 kV, 50 Hz
0.5 kV, 50 Hz Communication
Insulation resistance IEC/EN 60255-27
Protective bonding resistance IEC/EN 60255-27
Clearance and creepage distance Design criteria for distances as per IEC 60255-27 Annex C
(pollution degree 2, overvoltage category 3)
Power supply burden IEC 60255-1
SPA-Bus (*)
Comm. interface - X4
Ethernet protocols - Protocols RS232 + IRIG-B
RJ45 / LC port • IEC 61850
• Modbus Two protocols
Easergy • DNP3.0 at the same time
SmartApp. IEC61850 ed1 & ed2 • IEC-101
• Ethernet/IP WebServer
Modbus TCP Comm. interface - X4
Protocols
DNP3.0 • Modbus
• DNP3.0 RS485
• IEC-103
• SPAbus
IEC60870-5-101
When the devices are connecting in Ethernet link and demand for higher availability,
Easergy P3 Standard can use Rapid Spanning Tree Protocol (RSTP) or Parallel
Redundancy Protocol (PRP) to recover from a network failure.
Easergy P3 web-HMI
A webserver is available in Easergy P3 Standard to get information from the device
to monitor all data, send commands, and change protection settings.
Easergy web-HMI
MV network
DM105591
HMI interface
Function key F1 Mimic Diagram F2
I1: 0.0A
LED F1 LED F2 USB
I2: 0.0A
CT 0 Local Port
ON I3: 0.0A Service
LED A P : 0.0W LED B
V : 0.0V
I LED C LED D
LED E LED F
Control buttons LED G LED H
Nominal voltage
Alarm contact
Trip Circuit for Trip circuit
Supervision failure
Latching contact Trip control
ANSI 86 Order contact
A1
DI 2 DI 1
T3
This electrical schematic
can facilitate the IEC
61850 implementation 0
52a 52b
because all the logics
are determined by the 1
protection unit that will
Open/Close
make the decisions and Mechanical CLOSE OPEN
if necessary can send command COIL COIL
Circuit Breaker
GOOSE messages to
other units.
1
0
3 20
DI1 V1
4 19
5 USB 18
Local Port V2 17
DI2
6 16
17 V3 15
T1
16
T5 14
15
T2
13
14
X3 T6 12
13 T3
11
12
11 X5 T7 10
T4
10 9
8
8 DI16 7
9 A1
DI15 6
7 Easergy DI14 5
19
20
SF P3U30 4
DI13 3
18
DI12 2
X1 DI11 1
1
CAUTION: hazard of electric
shock, electric arc or burns 2 I1 14
- only qualified personnel 3 DI10 13
should install this 4 I2 DI9 12
equipment. Such work 5 11
should be performed only I3 DI8
6 10
after reading this entire set
of instructions. DI7 9
7 8
- NEVER work alone.
8 5A DI6
- turn off all power 7
supplying this equipment 9 OR Io X4 6
before working on or inside 1A DI5
OR 10 5
it. Consider all sources of
power, including the 4
possibility of backfeeding. DI4
1 3
- always use a properly 2
V4
rated voltage sensing 2 DI3
device to confirm that all 1
3
power is off. X2
4
- start by connecting the
device to the protective
earth and to the functional X4
earth.
COM
- screw tight all terminals,
even those not in use.
Failure to follow these
instructions will result in
death or serious injury. Serial communication port
1
0
3 20
DI1 V1
4 19
5 USB 18
Local Port V2 17
DI2
6 16
17 V3 15
T1
16
T5 14
15
T2
13
14
X3 T6 12
13 T3
11
12
11 X5 T7 10
T4
10 9
8
8 DI16 7
9 A1
DI15 6
7 Easergy DI14 5
19
20
SF P3U30 4
DI13 3
18
DI12 2
X1 DI11 1
1
CAUTION: hazard of electric
shock, electric arc or burns 2 I1 14
- only qualified personnel 3 DI10 13
should install this 4 I2 DI9 12
equipment. Such work 5 11
should be performed only I3 DI8
6 10
after reading this entire set
of instructions. DI7 9
7 8
- NEVER work alone.
8 5A DI6
- turn off all power 7
supplying this equipment 9 OR Io X4 6
before working on or inside 1A DI5
OR 10 5
it. Consider all sources of
power, including the 4
possibility of backfeeding. DI4
1 3
- always use a properly 2
V4
rated voltage sensing 2 DI3
device to confirm that all 1
3
power is off. X2
4
- start by connecting the
device to the protective
earth and to the functional X4
earth.
- screw tight all terminals,
even those not in use.
Failure to follow these
instructions will result in
death or serious injury. Redundant Ethernet Network - RSTP or PRP
1
0
PM106367
P3U10
Page 106
Standard application
PM106367
P3U20
Page 107
Standard application
PM106367
P3U30
Page 108
Standard application
Go to web configurator
Presentation 50
Functional view 52
Communication 69
Communication protocols 69
Programmable stages 70
Connection diagrams 73
Model selection 76
The Easergy P3 Advanced protection relay has been developed to cover demanding protection needs
for building, distribution utilities, and industrial applications. Thanks to its wide scope of functionalities,
the Easergy P3 Advanced range provides an excellent solution for your high-end protection
applications.
efficiency with rapid ordering, • All communication protocols embedded on serial and Ethernet links,
including IEC 61850 ed.1 and ed. 2
configuration, and operations for an
• Increased number of inputs and outputs
unparalleled digital experience provided
with Easergy P3.
Robust
• Best-in class reliability based on 100+ years of experience in Sepam,
MiCOM and Vamp relays
• Strong tests performed in international laboratories
• Compliant with IEC electro-mechanical standards
DM105530
Line Differential
& Distance G
Generator
L G Differential
U M T
Feeder
M Motor
Differential
Transformer
Differential
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18
59N Protocols
Modbus
Protocols
Modbus
Protocols
DeviceNet
DNP3.0 DNP3.0
50 T14 T15 T16 T17 IEC-103 IEC-103
67NI SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
51C 81 T6 T7 T8 T13
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card 1 - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
27 T2 T3 T4 T5
RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18
59N Protocols
Modbus
Protocols
Modbus
Protocols
DeviceNet
DNP3.0 DNP3.0
50 T14 T15 T16 T17 IEC-103 IEC-103
SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
51C 81 T6 T7 T8 T13
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card 1 - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
27 T2 T3 T4 T5
RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
M RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Current input
59N Protocols Protocols Protocols
50 I’1/I’2/I’3 DNP3.0
IEC-103
DNP3.0
IEC-103
SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
51C 81 T6 T7 T8 T13
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card 1 - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
27 T2 T3 T4 T5
RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
M RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF 64ref I/O card 3 - Current input
59N Protocols Protocols Protocols
50 I’1/I’2/I’3 DNP3.0
IEC-103
DNP3.0
IEC-103
SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
81 T6 T7 T8 T13
81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card 1 - Slot 2
59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
46 51G 27
RTD CH01
Tx
RTD CH01
Io1 T2 T3 T4 T5
27P RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Slot 4
59N DI13 DI14 DI15 DI16 DI17 DI18 Protocols Protocols Protocols
Modbus Modbus DeviceNet
DNP3.0 DNP3.0
50 67NI T14 T15 T16 T17 IEC-103 IEC-103
SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
51C 81 T6 T7 T8 T13
81U OR REL52825 REL52826
27 T2 T3 T4 T5
RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
OR
Circuit Breaker control
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Slot 4
DI13 DI14 DI15 DI16 DI17 DI18
59N Protocols
Modbus
Protocols
Modbus
Protocols
DeviceNet
DNP3.0 DNP3.0
50 T14 T15 T16 T17 IEC-103 IEC-103
SPAbus
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
27N 81 T6 T7 T8 T13
64G 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G I/O card 1 - Slot 2
51V 59 Tx
PTC
DI1 DI2 DI3 DI4 DI5 D6 Fiber
51N Rx
46 51G 40 27
RTD CH01
Tx
RTD CH01
T2 T3 T4 T5
32Q 27P RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
G RTD CH12
OR
RTD CH12
eSetup
Easergy Pro
REL52822
HMI interface ON Service
Mimic Diagram
LED A LED B
I 0 LED C LED D USB
LED E I1: 0.0A LED F Local Port Comm. interface - Slot 9
Control buttons LED G I2: 0.0A LED H Redundancy Protocols
• RSTP • IEC 61850
LED I I3: 0.0A LED J
• PRP • Modbus
LED K P : 0.0W LED L • DNP3.0
Two protocols • IEC-101
LED M LED N
F1 V : 0.0V F2 at the same time WebServer • Ethernet/IP
Function key
LED F1 LED F2
Comm. interface - Slot 9
Programmable Logic
Programmable Logic Redundancy LC LC Protocols
• RSTP • IEC 61850
• PRP • Modbus
Inputs AND TIMER OR COUNTER XOR Output • DNP3.0
Two protocols • IEC-101
at the same time WebServer • Ethernet/IP
RS232
RS232
50BF I/O card 3 - Current input
59N Protocols Protocols Protocols
RS485 RS485
81R
51 I/O card 2 - Slot 3 Serial
67N 25 DI7 DI8 DI9 DI10 DI11 DI12 Serial network
27N 81 T6 T7 T8 T13
64G 81U OR REL52812 REL52813
REL52814
50N RS485 RS485
Rx
49 50G 51V 59 I/O card 1 - Slot 2 Tx
PTC
46 51G 40 27
RTD CH01
Tx
RTD CH01
T2 T3 T4 T5
32Q 27P RTD CH02 RTD CH02
I1 / I2 / I3 Io/I’o V / V0 V4 mA In1
RTD CH03 RTD CH03
Analog measurement card - Slot 8 Power Supply - Slot 1 mA In2
RTD CH04 RTD CH04
Current input Voltage input T9 T10 T11 T12 mA In3
RTD CH05 RTD CH05
G RTD CH12
OR
RTD CH12
DM102188
Easergy P3 Advanced measures fault
current, and with arc protection, also
Arc flash sensors
measures light via arc sensor channels that
1
provide monitoring for the whole switchgear.
PM106502
Should an arc fault occur in the switchgear,
the arc protection system provides
extremely fast tripping of the circuit breaker.
The fault will be prevented from spreading 2
and quickly isolated, which may save
valuable assets.
Easergy P3 Advanced
Easergy P3 Advanced relays can connect
up to four arc flash sensors, including 3 4
continuous self-supervision to check the
sensor status.
Example of application
The four arc flash sensors can be installed in specific
parts of the switchgear:
1. Busbars compartment
2. Circuit breaker compartment IEC 61850 (GOOSE)
or by wire
3. Current/voltage transformers compartment 4
Cable
1
DM105582
BB
CB CB
2 2
Cable Cable
3 3
Mimic Diagram
operation
All the data you require for a local equipment operation can be displayed on
I1: 0.0A demand:
I2: 0.0A • Display the single line diagram and freely assignable analog values
I3: 0.0A • Display of all measurements
• Display of operation and alarm messages
P : 0.0W • Display and setting of all parameters
V : 0.0V • Password entry to protect parameter and protection settings
Slot 1 2 3 4&5 6 8 9
PM106503
Slot 1 2 3 4&5 6 8 9
PM106342
Easergy P3L30
PM106504
P3x30 units
This mounting technique allows for a lighter door because the relay’s frame is
installed in the back of the secondary compartment. Communication, DI, and DO
cabling is easier, too, as the door movement does not need to be considered.
In this case, only the communication between IED base and display has to be
wired.
DM105604
Ea se rg y
Conventional HMI mm
DM105605
208
in 264 8.18
10.37
183
Easergy 7.20
177 150
6.97 5.91
Remote HMI
DM105606
247
9.72
180 29 199
7.09 1.12 7.81
199
7.83 150
180 5.91
7.09
Weight (maximum)
Easergy P3 Advanced 4.2 Kg (9.272 Ib) or higher (depends of options)
DM105607
In case the depth dimension behind the compartment
door is limited, the IED can be equipped with a frame
around the collar. This arrangement reduces the depth
inside the compartment by 45 mm (1.77 in).
Wall mounting
DM105608
210
8.27
Ø5
mm
100
in
3.94
18
0.71
11.5
0.45
20 34
0.79 1.34 Eas erg y
180
7.09
Ø7
0.28
180
7.09
Analog inputs
Rated phase Measuring Input Rated thermal 1-second 10-second
Consumption
current range Impedance withstand overload overload
Phase Current Input (I) 1 A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 8 5 A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Residual Current Input (I0)
Slot 8 - 5 A CT 0.015 – 50 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Configurable for CT secondaries 0.1 to 10A
Residual Current Input (I0’)
Slot 8 - 1 A CT 0.003 – 10 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Configurable for CT secondaries 0.1 to 10.0A
Residual Current Input (I0’)
Slot 8 - 0.2 A CSH sensor 0.0006 – 2 A 0.02 Ohm 0.02 VA 0.8 A 20 A 4A
Configurable for CT secondaries 0.1 to 10.0A
Phase Current Input - (I’) 1A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 4 (Only for device with
differential overcurrent) 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Residual Current Input (I0’’) 1A CT 0.02 – 50 A 0.02 Ohm 0.02 VA 4A 100 A 20 A
Slot 4 (Only for device with
differential overcurrent) 5A CT 0.05 – 250 A 0.003 Ohm 0.075 VA 20 A 500 A 100 A
Voltage Input 0.5 – 190 V 250 V
n.a. < 0.5 VA 100 V 600 V
Configurable for VT secondaries 50 to 120 V (100V / 110 V) (Continuously)
Maximum current 20 mA
Digital Input
Nominal operation voltage DI1 to DI16 24 to 230 Vac/dc 110 to 230 Vac/dc 220 to 230 Vac/dc
Typical switching threshold 12 Vdc 75 Vdc 155 Vdc
Input limit voltage At state 1 ≥ 19.2 Vdc ≥ 88 Vdc ≥ 176 Vdc
At state 0 < 10.0 Vdc < 60 Vdc < 140 Vdc
Frequency 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Typical consumption <4 mA (typical approx. 3 mA)
Voltage withstand 255 V ac/dc
Digital Output
Type of contact Control and Trip contact, Tx Signal contact, A1 Signal Contact, SF
Rated Voltage 250 Vac/dc 250 Vac/dc 250 Vac/dc
Continuous current 5A 5A 5A
Breaking AC 2.000 VA 2.000 VA 2.000 VA
capacity DC at 48 V dc 1.15 A 1A 1A
(L/R=40ms) at 110 V dc 0.5 A 0.3 A 0.3 A
at 220 V dc 0.25 A 0.15 A 0.15 A
Making capacity < 0.5 s 30 A 30 A -
< 3.0 s 15 A 15 A -
Minimum making capacity 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc 100 mA @ 24 Vac/dc
Typical operation time <8 ms - -
Contact material AgNi 90/10 AgNi 0.15 gold plated AgNi 0.15 gold plated
Power supply
Nominal Voltage 110-240 V ac/dc 24-48 Vdc
Range -20% / +10% (88 to 264 Vac/dc) -20% / +20% (19.2 to 57.6 Vdc)
Inrush current (DC) 25 A with time constant of 1000 µs
25 A with time constant of 750 µs
15 A with time constant of 500 µs
Power consumption Power consumption increases when more I/O or optional I/O or communication cards are used
Max. 50 W
Acceptable momentary outages <50 ms (110 Vdc)
(1) 78,740 in
Disturbance tests
Standard and test class/level Test value
Emission IEC/EN 60255-26 (ed3)
Conducted EN 55022, Class A / CISPR 22 0.15 – 30 MHz
Emitted EN 55011, Class A / CISPR 11 30 – 1000 MHz
Immunity IEC/EN 60255-26 (ed3)
1 Mhz damped oscillatory wave IEC/EN 61000-4-18 ±2.5kVp CM
±2.5kVp DM
Static discharge (ESD) IEC/EN 61000-4-2 Level 4 ±8 kV contact
±15 kV air
Emitted HF field IEC/EN 61000-4-3 Level 3 80 - 2700 MHz, 10 V/m
Fast transients (EFT) IEC/EN 61000-4-4 Level 4 ±4 kV, 5/50 ns, 5 kHz
Surge IEC/EN 61000-4-5 Level 4 ±4 kV, 1.2/50 µs, CM
±2 kV, 1.2/50 µs, DM
Conducted HF field IEC/EN 61000-4-6 Level 3 0.15 - 80 MHz, 10 Vrms
Power-frequency magnetic field IEC/EN 61000-4-8 300A/m (continuous) 1000 A/m 1 – 3 s
Pulse magnetic field IEC/EN 61000-4-9 Level 5 1000A/m, 1.2/50 µs
ac and dc voltage dips IEC/EN 61000-4-29, IEC/EN 61000-4-11 0% of rated voltage
• ac: ≥ 0.5 cycle
• dc: ≥ 10 ms 40% of rated voltage
• ac: 10 cycles
• dc: 200 ms 70% of rated voltage
• ac: 25 cycles
• dc: 500 ms
ac and dc voltage interruptions IEC/EN 61000-4-29, IEC/EN 61000-4-11 100% interruption
• ac: 250 cycles
• dc: 5 s
Voltage alternative component IEC/EN 61000-4-17 15% of operating voltage (dc) / 10 min
Mechanical
robustness
Standard and test class/level Test value
In operation
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 1 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 10 Gn / 11 ms
Seismic IEC 60255-21-3 Method A, Class II 2G horizontal / 1G vertical , 1–35 Hz
De-energized
Vibrations IEC 60255-21-1, Class II / IEC 60068-2-6, Fc 2 Gn, 10 Hz – 150 Hz
Shocks IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 30 Gn / 11 ms
Bump IEC 60255-21-2, Class II / IEC 60068-2-27, Ea 20 Gn / 16 ms
Electrical safety
Standard and test class/level Test value
In operation
Impulse voltage withstand IEC/EN 60255-27 5 kV, 1.2/50 µs, 0.5 J
1 kV, 1.2/50 µs, 0.5 J Communication
Dielectric test IEC/EN 60255-27 2 kV, 50 Hz
0.5 kV, 50 Hz Communication
Insulation resistance IEC/EN 60255-27
Protective bonding resistance IEC/EN 60255-27
Clearance and creepage distance Design criteria for distances as per IEC 60255-27 Annex C
(pollution degree 2, overvoltage category 3)
Power supply burden IEC 60255-1
Environmental tests
Standard and test class/level Test value
In operation
Dry heat EN / IEC 60068-2-2, Bd 70°C (158°F)
Cold EN / IEC 60068-2-1, Ad -40°C (-40°F)
Damp heat, cyclic EN / IEC 60068-2-30, Db From 25°C (77°F) to 55°C (131°F)
From 93% RH to 98% RH
Testing duration: 6 days
Damp heat, static EN / IEC 60068-2-78, Cab 40°C (104°F)
93% RH
Testing duration: 10 days
Change of temperature IEC / EN 60068-2-14, Nb Lower temp -40°C (-40°F)
Upper temp 70°C (158°F)
5 cycles
In storage
Dry heat EN / IEC 60068-2-2, Bb 70°C (158°F)
Cold EN / IEC 60068-2-1, Ab -40°C (-40°F)
Environmental
conditions
(1) with 1 x raising frame -> maximum ambient temperature 55°C (+131°F)
with 2 x raising frame -> maximum ambient temperature 50°C (+122°F)
When the devices are connecting in Ethernet link and demand for higher availability,
Easergy P3 Advanced can use Rapid Spanning Tree Protocol (RSTP) or Parallel
Redundancy Protocol (PRP) to recover from a network failure.
Easergy P3 web-HMI
A webserver is available in all Easergy P3 Advanced to get information from the
device to monitoring all data, send command and change protection setting.
Easergy P3 web-HMI
MV network
DM105592
Nominal voltage
Alarm contact
Trip Circuit for Trip circuit
Supervision failure
This electrical schematic Latching contact Trip control
can facilitate the IEC 61850 ANSI 86 Order contact
implementation because all
the logics are done by the
protection unit that will make A1
the decisions and, if necessary,
T2 T1 Digital Input 2 Digital Input 1
send GOOSE messages to Trip circuit Trip circuit Trip circuit
other units. supervision supervision failure alarm
Close contact
Order contact
DI 2 DI 1
T3
0
52a 52b
1
Open/Close
Mechanical CLOSE OPEN
command COIL COIL
Circuit Breaker
Power quality
DM105651
DM105609
1
0
Arc Flash
Sensor
1 1
DI1 V1
2 2
3
2 USB 3
Local Port V2 4
DI2
4 5
5 V3 6
DI3
6 8
7
8
DI4 3
9 4
1
DI5
DI7
5
10 1
2
DI13
11
DI6
Easergy 3 2
1
12 P3x30 DI8
4
3 DI19
2
T2 DI14
13 5 4 3
14 DI9 5 DI20
T3 6 DI15 4
15 7
16 6
5
DI10 7
T4 8 DI21
17
9 DI16 6
8
18 DI11 7
19 T5 10 DI22
DI17
11 8
10
20 DI12 11 DI23
12
DI18 10
1 T6 13 12
11
2 I1 T14 13
14 DI24
3 12
T7 15 14
4 I2 T18 13
T15 15
5 16
T8 17 14
6 I3 16
T19 15
Arc Flash T16 17
8 18
Sensor 7
T13 19 18 16
8 5A Io T20 17
20 T17 19
9 18
20
10 1 A Io T21 19
CAUTION: hazard of electric
20
shock, electric arc or burns 11
12 V4
- only qualified personnel
should install this
equipment. Such work 20
A Arc T12
should be performed only 1
after reading this entire set A Arc
2
19
6 18
of instructions. A Arc
T11
3 T1, T9, T10,
Arc Flash 17
- NEVER work alone. Sensor A Arc T11 and T12:
4 T10 16
- turn off all power 5 heavy duty
15 trip relay for
supplying this equipment
T9 14 arc protection
before working on or inside
it. Consider all sources of 13
12
power, including the T1
possibility of backfeeding. 11
A1 10
- always use a properly 9
rated voltage sensing 8
device to confirm that all SF 7
6
power is off. 5
1 2
- start by connecting the 1
device to the protective
earth and to the functional
earth.
9
- screw tight all terminals,
even those not in use.
Failure to follow these
instructions will result in
death or serious injury.
Redundant Ethernet Network - RSTP or PRP
DM105610
Arc Flash Sensor
1
0
Arc Flash
Sensor
1 1
DI1 V1
2 2
3
2 USB 3
Local Port V2 4
DI2
4 5
5 V3 6
DI3
6 8
7
8
DI4 3
9 1
DI5
DI7
10 2
11
DI6
Easergy 3
12 P3x32 DI8
4
T2
13 5
14 DI9
T3 6
15 7
16
DI10
17 T4 8
9
18 DI11
19 T5 10
11
20 DI12
12
1 T6 13
2 I1 14
Arc Flash 3 T7 15
Sensor I2
4
5 16
T8 17
6 I3
18
7 8
T13 19
CAUTION: hazard of electric 8 5A Io
20
shock, electric arc or burns 9
DM105611
1
0
1 1
DI1 V1
2 2
3
2 USB 3
Local Port V2 4
DI2
4 5
5 V3 6
DI3
6 8
7
8
DI4 3
9 4
1
DI5
DI7
5
10 1
2
DI13
11
DI6
Easergy 3 2
1
12 P3L30 DI8
4
3 DI19
2
T2 DI14
13 5 4 3
14 DI9 5 DI20
T3 6 DI15 4
15 7
16 6
5
DI10 7
T4 8 DI21
17
9 DI16 6
8
18 DI11 7
19 T5 10 DI22
DI17
11 8
10
20 DI12 11 DI23
12
DI18 10
1 T6 13 12
11
I1 T14 13
2 14 DI24
3 12
T7 15 14
I2 T18 13
4 T15 15
5 16
T8 17 14
6 I3 16 15
T19
T16 17
18
7 8 16
T13 19 18
T20 17
8 5A Io T17 19
20
9 18
20
CAUTION: hazard of electric T21 19
10 1 A Io
shock, electric arc or burns 20
11
- only qualified personnel 12 V4
should install this
equipment. Such work
should be performed only T12 20
after reading this entire set 19
of instructions. T11 18
RX A1 10
9
rated voltage sensing
Card
8
device to confirm that all SF 7
power is off. TX 6
5
- start by connecting the 1 2
device to the protective 1
P3F30
Page 109
Feeder application
PM106371
P3L30
Page 110
Line application
P3M30
Page 111
Motor application
P3G30
Page 112
Generator application
P3T32 Transformer
PM106371
Page 113
with differiential application
P3M32 Motor
Page 114
with differential application
P3G32 Generator
Page 115
with differrential application
Go to web configurator
Easergy P3 software 80
Presentation 80
Easergy web-HMI 85
Easergy SmartApp 86
DM105614
DM105613
eSetup
DM105612
eSetup eSetup
Easergy Pro Easergy Pro Easergy Pro
Use eSetup Easergy Pro in standalone Connect the PC running eSetup Easergy Connect the PC running eSetup Easergy
mode during engineering to prepare the Pro to the USB port of the Easergy Pro to the Ethernet network during
configuration. protection relay during commissioning to operation to retrieve data from the relays
adjust the settings and test the relay. and update the system.
Com
mi
ss
g
io
rin
nin
Enginee
O p e r at i o n
• Create the configuration of the Easergy P3 relay: select the appropriate options
and receive the order code
• Set the characteristics of the CTs, VTs, or sensors connected to the relay, and
select the protection functions that will be activated and their settings
• Build a specific logic, if required, using a graphic editor
• Map the digital inputs of the relay and different internal signals to the relevant
functions, LEDs, and digital outputs, using a straightforward matrix format.
• Draw the single-line diagram that will appear on the front display of the relay for
switchgear control and select the measurements that will be displayed. If any,
build the interlocking logic using a matrix format
• For IEC 61850 protocol, configure the data set and the report control blocks that
will be published and select the GOOSE data to which you want to subscribe
• Complete the setting of additional functions (disturbance recorder, event logging
system, clock synchronization, etc.).
EM106160
EM106161
EM106162
• Connect to the front panel of one single relay or access several relays by
connecting to Ethernet
• Open the Digital Inputs menu to check the status of inputs. Reverse the polarity
or add a filtering delay if necessary
• Open the Relays menu and force the status change of the output relays in order
to check the wiring.
• Open the Phasor Diagram menu to see in real time the phasor of injected
currents and voltages and the value
• Use virtual injection for testing protection settings and circuit breaker tripping
and for checking LEDs and connected outputs
• Open the Logic or the Matrix menu if the logic needs to be tested. The active
signals appear in a different color and are updated in real time. Changes in the
logic or in the matrix can be made and applied to the relay smoothly.
EM106163
EM106164
EM106165
• Connect to the front panel of a single relay or gain access to several relays by
connecting to Ethernet
• During normal operation, get the most of the metering capabilities of the
Easergy protection relay:
–– Open the different Measurements menus to access the power monitoring
and power quality data.
–– Open the disturbance recorder menu to get a waveform capture or program
the recording of a power trend.
• After a trip, use eSetup Easergy Pro to understand the fault:
–– Check the fault log of the protection that has tripped the circuit breaker
–– Download the disturbance record from the Easergy P3 and display it with a
disturbance recorder evaluation tool, eg. Wavewin.
EM106166
EM106167
EM106168
Safety
The Easergy SmartApp improves safety by allowing the operator to stay away from
the circuit-breaker during operations.
Simplicity
The Easergy SmartApp provides easy access to device status, control, and
monitoring of the circuit breaker, measurements, settings, events and other
functions, through the mirror HMI or a simplified view.
• Mirror HMI: Duplicate the device display in the Easergy SmartApp to perform
actions more easily and safely.
• Simplified view: The Easergy SmartApp gives you an organized view of all
the device’s functionalities for simpler access to the data. You benefit from a
clearer overview of the switchgear’s health, faster issue resolution, and safer
operations.
Easergy SmartApp
screens example
(1) Wi-Fi is not embedded in Easergy P3, a separate Wi-Fi router connected to an Ethernet port of
the device is required.
Communication modules 92
REL52825
DM105616
A remote port is available when a REL52825 cable is used. The cable contains a
connector for the RS-232 interface of the Easergy P3 Standard and a D9-
connector for the external option module.
REL52827
DM105617
The cable contains a connector for the RS-232 interface of the Easergy P3
Standard and a D9-connector for the REL52815 Profibus interface module.
An extension port is available for the REL52827 in Easergy P3 Standard.
REL52826
synchronization, when the REL52826 cable is used. The REL52826 cable contains
a connector for the RS-232 interface of the Easergy P3 Standard and a 3-piece
D9-connector for the external option module and IRIG-B.
REL52823
REL52824
DM105620
The cable contains a connector for the RS232 interface of Easergy P3 Advanced
and D9-connector for the REL52815 Profibus interface module. An extension port
is available for the REL52824 in Easergy P3 Advanced.
Characteristics
Distance (maximum) 200 m (7,874.02 in)
Devices (maximum) 32
Type of fiber optic connector PIN (3)
Type of RS232 connector 9-pin DSUB connector
RS485 type 2-wire
Serial protocols Modbus, DNP3.0, IEC870-5-103 and SpaBus
Power supply From RS232 port or external – 12Vdc
Characteristics
Distance (maximum) 200 m (7,874.02 in)
Devices (maximum) 32
Type of output connector PIN
Type of RS232 connector 9-pin DSUB connector
Serial protocols DeviceNet
Power supply Need power feed from both RS232 port and
external 24 Vdc
To connect the interface with:
Easergy P3 Standard devices, use REL52825 cable
Easergy P3 Advanced devices, no additional cable required
Characteristics
Interface 9-pin DSUB connector (Female)
Transfer method RS485, Half-duplex
Transfer cable Twisted pair (1 pair and shield)
Electrical isolation 500 Vdc
Serial protocols Profibus DP
Baud rate 9.6 kBaud to 12 Mbaud
Power supply
Easergy P3 Standard: External – 12Vdc
Easergy P3 Advanced: From RS232 port or external – 12Vdc
To connect the interface with:
Easergy P3 Standard devices, use REL52827 cable
Easergy P3 Advanced devices, use REL52824 cable
Tx Tx Tx
PTC
Fiber
Rx
Sensors description
DM105632
REL52804
REL52801
REL52810
REL52808
REL52806
REL52803
Characteristics
Sensitivity area
DM105637
plate for sensor L-shape), or it can be mounted in
customer drilled holes.
Before
DM105633
Mounting plate
for sensor L-shape
After
DM105634
REL52828 dimensions
DM105637
Mounting plate
for sensor Z-shape
Install
Life Cycle Services
Life cycle services
We help you install efficient, reliable, and safe solutions based on your plans:
DM408843
• Project management:
Plan Designed to help you complete your projects on time and within budget
What are my options?
• Commissioning:
Ensure your actual performance versus design, through on-site testing and
commissioning, tools, and procedures
Install
How do I install and commission?
Operate
We help you maximize your installation uptime and control your capital
Operate expenditures through our service offering:
How do I operate and maintain?
• Asset operation solutions
• Advantage service plans
Optimize • On-site maintenance services
How do I optimize? • Spare parts management
• Technical training
Renew
How do I renew my solution? Optimize
We provide recommendations to improve your safety, availability, reliability, and
quality:
• MP4 electrical assessment:
When it comes to your electrical Define your improvement and risk management program
distribution installation, we can
help you:
• Increase productivity, reliability, and safety
• Mitigate risk and limit downtime
Renew
• Keep equipment up to date and extend its
We extend the life of your system while providing upgrades and offers to take full
lifespan
responsibility for the end-of-life processing of old electrical equipment:
• Cut costs and increase savings
• Improve your return on investment • Retrofit:
Keep up to date and improve the performance of your electrical installations
CONTACT US! (LV, MV, Protection Relays, etc.)
www.schneider-electric.com/ • MV product end of life:
electricaldistributionservices Recycle and recover your outdated equipment with end-of-life services
Discover what we
mean by green ….
Over 75% of
our manufactured products
Check your products! have been awarded the
Green Premium ecolabel
Accessories 116
Easergy P3 Standard
For more configuration or options, please use our web configurator or see:
page 106 for Easergy P3U10
page 107 for Easergy P3U20
Page 108 for Easergy P3U30
Go to web configurator
Easergy P3 Advanced
REL52103 P3F30-CGGGI-DAECA-B2 Power C 110-230 V 110-230 Vac/dc 4 28 DI / 17 DO 4 Arc sensors RS232 + RJ45
REL52109 P3F30-CGIAA-AAECA-B1 Power C 110-230 V 24-230 Vac/dc 4 16 DI / 9 DO 4 Arc sensors RS232 + RJ45
For more configuration or options, please use our web configurator or see:
page 109 for Easergy P3F30 page 112 for Easergy P3M32
page 110 for Easergy P3L20 page 113 for Easergy P3T32
Page 111 for Easergy P3M30 page 114 for Easergy P3G30
page 115 for Easergy P3G32
Go to web configurator
U10 Application
U10 Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Phase currents and voltage input
X1
5 1 A/ 5 A & 1U (100/110 V), pluggable screw
6 1 A / 5 A & 1U (100/110 V), pluggable ring
Earth-fault current input
X1
A 1A/5A
B 0,2 A / 1 A
Nominal power supply voltage [V]
X2
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
B Power B 24 V (range: 18 ... 36 Vdc)
A Future option
X3
A None
Digital input voltage range
X4
1 24 to 230 Vac/dc
2 110 to 230 Vac/dc
3 220 to 230 Vac/dc
A Product version
X7
A Version 2.1
Easergy P3 U10 A A A A
Slot numbers X1 X1 X2 X3 X4 X5 X6 X7
U20 Application
U20 Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Phase currents and voltage input
X1
5 1 A/ 5 A & 1U (100/110 V), pluggable screw
6 1 A / 5 A & 1U (100/110 V), pluggable ring
Earth-fault current input
X1
A 1A/5A
B 0,2 A / 1 A
Nominal power supply voltage [V]
X2
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
B Power B 24 V (range: 18 ... 36 Vdc)
A Future option
X3
A None
Digital input voltage range
X4
1 24 to 230 Vac/dc
2 110 to 230 Vac/dc
3 220 to 230 Vac/dc
A Product version
X7
A Version 2.1
Easergy P3 U20 A A A
Slot numbers X1 X1 X2 X3 X4 X5 X6 X7
U30 Application
U30 Feeder & Motor, 4xI, 1xU. 2DI, 5DO
Phase currents and voltage input
X1
5 1 A/ 5 A & 1U (100/110 V), pluggable screw
6 1 A / 5 A & 1U (100/110 V), pluggable ring
Earth-fault current input
X1
A 1A/5A
B 0,2 A / 1 A
Nominal power supply voltage [V]
X2
A Power A 48 - 230 V (range: 40 ... 265 Vac/dc)
B Power B 24 V (range: 18 ... 36 Vdc)
A Future option
X3
A None
Digital Input voltage range
X4
1 24 to 230 Vac/dc
2 110 to 230 Vac/dc
3 220 to 230 Vac/dc
A Product version
X7
A Version 2.1
Easergy P3 U30 A B A
Slot numbers X1 X1 X2 X3 X4 X5 X7 X7
Application
F30
F30 Feeder protection relay
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
5 I/O Card IV
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
1. Choose your option B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
2. Report your choice on the case
Easergy P3 F30 G - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
L30
L30 Feeder protection relay with Line differential and distance protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
5 I/O Card IV
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None, Distance protection included
D Line diff and distance FW with integrated optical diff comms. Card
Line diff and distance FW with RS232 for external diff comms.
K
converter
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
1. Choose your option
B 110 to 230 V ac/dc, with conformal coating
2. Report your choice on the case C 220 to 230 V ac/dc, with conformal coating
Easergy P3 L30 G - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
M30
M30 Motor protection relay
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
5 I/O Card IV
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
1. Choose your option B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
2. Report your choice on the case
Easergy P3 M30 G - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
M32
M32 Motor protection relay with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
I/O Card III
4 T
T 3xI (5/1A) + Io (5/1A) for motor differential protection
I/O Card IV
5 A
A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
Easergy P3 M32 G T A - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
T32
T32 Transformer protection relay with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
I/O Card III
4 T
T 3xI (5/1A) + Io (5/1A) for transformer differential protection
I/O Card IV
5 A
A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
Easergy P3 T32 G T A - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
G30
G30 Generator protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
4 I/O Card III
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
5 I/O Card IV
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
1. Choose your option B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
2. Report your choice on the case
Easergy P3 G30 G - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
Application
G32
G32 Generator protection with differential protection
1 Nominal Supply Voltage [V]
C Power C 110 - 230 V (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)
D Power D 24 - 48 V (18 .. 60 Vdc, 5 x DO heavy duty, A1, SF)
I/O Card I
2 G
G 6DI+4DO (6 x DI, 4 x DO)
3 I/O Card II
A None
G 6DI+4DO (6 x DI, 4 x DO)
H 6DI+4DO (6 x DI, 4 x DO(NC))
I 10DI (10 x DI)
I/O Card III
4 T
T 3xI (5/1A) + Io (5/1A) for generator differential protection
I/O Card IV
5 A
A None
6 Option card I
A None
D 4Arc (4 x Arc sensor)
K RS232 (RS232)
Future option
7 A
A None
8 Analog measurement card (See application)
E 3L(5 A)+4U+2Io (5/1A+1/0,2 A)
F 3L(1 A)+4U+2Io (5/1A+1/0.2 A)
9 Communication interface I
A None
B RS232 (RS232, IRIG-B)
C RS232+RJ (RS232, IRIG-B + Ethernet RJ-45 100 Mbs)
D RS232+LC (RS232, IRIG-B + Ethernet LC 100 Mbs)
N 2xRJ (Ethernet RJ 100 Mbs, RSTP, PRP)
O 2xLC (Ethernet LC 100 Mbs, RSTP, PRP)
P PP (Plastic / Plastic serial fibre)
R GG (Glass / Glass serial fibre)
Product version
10 A
A Version 2.1
11 Display type
B 128x128 (128 x 128 LCD matrix)
C 128x128Ext (128 x 128 LCD matrix, detachable) (1
12 Voltage range of Digital Input
A 24 to 230 V ac/dc, with conformal coating
B 110 to 230 V ac/dc, with conformal coating
C 220 to 230 V ac/dc, with conformal coating
Easergy P3 G32 G T A - A A -
Slot numbers 1 2 3 4 5 - 6 7 8 9 10 11 12
www.schneider-electric.com
9 th November, 2017
NRJCAT17764EN_v12