Академический Документы
Профессиональный Документы
Культура Документы
Car
l
9
sol o Gav
es rela id sta azzi
8 seri y ra te
er 3 ange nge
Findrelay r
9-1
Selection guide
Electromechanical relays - control type
Control relays
Cat. No. Description Page Ref.
ACS-CS 7 / CSS 7 Control relays and accessories / Safety control relays 9 - 4 to 9 - 10
CS 1A / CS 1C Plug-in heavy-duty control relay 9 - 11 to 9 - 13
Step relays
26.01 Step relay screw terminal 1 N/O 10 A 9 - 21
26.02 Step relay screw terminal 2 N/O 10 A 9 - 21
26.03 Step relay screw terminal 1 N/O + 1 N/C 10 A 9 - 21
20.22 Step relay screw terminal (DIN rail) 2 N/O 16 A 9 - 21
20.23 Step relay screw terminal (DIN rail) 1 N/O + 1 N/C 16 A 9 - 21
9-2
Selection guide
Electromechanical relays - general purpose
Accessories
Relay bases, LED and diode modules and mounting clips, 9 - 30 to 9 - 34
Relay dimensions
Relay and relay base dimensions 9 - 35 to 9 - 37
9-3
Refer catalogue ACS-2
ACS control relay CS 7
Heavy-duty – 690 volt
Features
■ Complies with IEC 60947
■ High contact reliability
■ Basic 4 pole relay can be increased to 6, 8 or 12 pole by using optional clip-on contacts
■ Choice of front mount or side mount additional clip-on contacts
■ Electronic compatible contacts
■ Mechanically linked contacts
A1 13 21 33 43
10 6 20 3 1 CS 7-31E...V
K1
A2 14 22 34 44
A1 13 23 33 43
10 6 20 4 0 CS 7-40E...V
K1
A2 14 24 34 44
A1 11 21 31 41
10 6 20 CS 7-04E...V
K1
A2 12 22 32 42
CS 7-40E
Control relay CS 7C with DC control 2)
A1 11 21 31 41
10 6 20 0 4 CS 7C-04E…V
K1
A2 12 22 32 42
10 6 20 1 3 CS 7C-13E…V
A1 13 21 31 43
10 6 20 2 2 CS 7C-22E…V
K1
A2 14 22 32 44
13 21 33 43
10 6 20 A1
3 1 CS 7C-31E…V
K1
A2 14 22 34 44
CS 7C-22E 10 6 20 A1 13 21 31 43
4 0 CS 7C-40E…V
K1
A2 14 22 32 44
9
53 61
1 1 11 CS 7-PV-11
54 62
Auxiliary contact 51 61
2 pole top mount 0 2 02 CS 7-PV-02
52 62
53 63
2 0 20 CS 7-PV-20
54 64
53 61 71 83
1+1E 1+1L L22 CS 7-PV-L22
54 62 72 84
53 61 73 83
3 1 31 CS 7-PV-31
54 62 74 84
53 63 73 83
4 0 40 CS 7-PV-40
54 64 74 84
Auxiliary contact
4 pole top mount 1
Notes: )Add coil voltage, standard voltages AC 24, 32, 110, 240, 415 V 50 Hz.
2
)Add coil voltage, standard voltages DC 24, 36, 48, 110 and 240 V DC.
3
)Other contact blocks type CA 7-P can be used providing terminal numbers are acceptable
(refer CA 7 contactor auxiliaries Section 1).
Price Schedule ‘AA’ 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
Features
■ AC/DC control
■ Mechanically linked contacts according to IEC 947-5-1
■ Fixed coupling of relay and auxiliary contact block
■ Protection against unintended actuation
■ Auxiliary contacts are electronic compatible according to DIN 19240
■ High contact reliability
■ Red contact housing for easy identification
Available in AC and DC control voltages, the Sprecher + Schuh CSS 7 range of safety relays are ideal for use
in feedback circuits found in today's modern applications. The safety relays have a distinctive red
coloured housing which is permanently fixed to the front of the relay to prevent manual operation. It also
features N/C mechanically linked contacts which ensure that N/O and N/C contacts cannot occupy the
same state simultaneously - even in the event of welded contacts. This is a crucial safety requirement to
protect equipment and personnel. Replacement coil is same as CA7 9/12/16.
3 3 3 10 5 3 CSS 7-53EC…VAC
3 3 3 10 3 5 CSS 7-35EC…VAC
3 3 3 10 4 4 CSS 7D-44EC…VDC
1
Notes: ) Auxiliary contact ratings only. For base relay ratings refer to CS 7 rating on page 9-4.
2
) Add coil voltage, standard voltages 24, 110, 240 V 50 Hz.
3
) Add coil voltage, standard voltage 24 V DC. Other voltages available on request.
240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038:2000.
13
1 0 44
10 CA 7-PA-10
14
43
11 21
0 2 32 42
02 CA 7-PA-02
12 22
31 41
Auxiliary contact 13 21
13 23
2 0 34 44
20 CA 7-PA-20
14 24
33 43
17 25
E1 L1 36 48
L11 CA 7-PA-L11
18 26
35 47
A1
Time range 1…30 s CRZE 7-30
A2
9
A0 B2
ZA
Interlock only CM 7
21 21
Interlock with CM 7-02
CM 7 mechanical interlock
with 2 x N/C contacts 22 22 2 x N/C contacts
1
Notes: ) Can be fitted to either side of relay or to both sides - 1 level only.
2
) Accessories are also suitable for all CA 7 contactors.
3
) Other contact blocks type CA 7-P can be used providing terminal numbers are acceptable
(refer CA 7 contactor auxiliaries Section 1).
Price Schedule ‘AA’ 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
Mechanical Latch
Function/Description Cat. No. Price $
1
Mechanical latch. Clips onto top of CS 7 relays. Latch includes N/O CV 7-11…V )
and N/C contact. Suggested circuit shows on and off button with
interlock circuit. The contactor stays latched ‘on’ until electrically
released by the stop button. Eg. contact stays closed without power
to the coil.
L1~/L+
0
I
CV 7 mechanical latch 57 65 13
K1R K1M
58 66 14
A1 E1
K1M
K1R
N~/L- A2 E2
Interface (electronic). Clips onto CS 7 coil. Ideal for PLC interface. CRI 7E
18...30 V DC (10 mA...15 mA) input. 200 VA switching capacity.
Suitable for coil voltage 110...240 V AC. Includes
in-built suppressor and LED status indicator.
L
– +
A1
CRI 7E interface
A2
L
E1
A1
Suppressor module R-C (resistor capacitor) for limiting switching overvoltages of the coil circuit.
Clips onto all CS 7 relay coils
Coil voltage range 24...48 V 50/60 Hz CRC 7-48
Coil voltage range 110...280 V 50/60 Hz CRC 7-280
Coil voltage range 380...480 V 50/60 Hz CRC 7-480
Suppressor module Suppressor module - varistor for limiting switching overvoltages of the coil circuit (surge protection).
Clips onto CS 7 relay for AC or DC coil circuits.
0 mm spacing CA 7-S0
Dovetail adaptors
9 mm spacing CA 7-S9
1
Notes: ) Add standard voltage 24, 110, 240 V 50/60 Hz (other voltages available).
240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
Note: 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
9-8
Refer catalogue ACS-2
ACS control relay CS 7
Technical information (Cont’d)
Maximum altitude
IEC 68-2-30 and DIN 50 016, 56
2000 m NN, to IEC 947-4
9
Protection class IP 2LX (IEC 529 and DIN 40050)
In connected condition
Protection against contact Finger and back of hand to VDE 0106, Part 100
Note: 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
9-9
Refer catalogue ACS-2
ACS control relay CS 7
Dimensions in mm
CS 7 (AC) CS 7C (DC)
Relay
Type 2) a b c c1 c2 ød d1 d2
CS 7 (AC) 45 81 80.5 75.5 6 4.5 60 35
Accessories
Contactor with [mm]
Front mounting auxiliary contact 2 or 4 pole c/c1+39
Side mounting auxiliary contact 1 or 2 pole a+9
Pneumatic timing module c/c1+58
Electronic timing module Coil mounting b+24
Mechanical interlock Mounts between contactors a+9
c/c1+61
Interface Coil mounting b+9
Suppressor Coil mounting b+3
With inscriptions Labels +0
9 1
Label support system V 7 +5.5
Mounting position
25
°
5°
11
11
5°
5°
11
9 - 10
Refer catalogue 2500
Plug-in heavy-duty control relay
AC type CS 1A - DC type CS 1C
Bases
Three types of connection socket are available-types K, U and F.
CS 1C relay - DC operated
K With screw terminals for front wiring, has a foot. The free space thus
provided behind the terminals, serves as a cable channel.
U With screw terminals, front or rear wiring (Panel mounting).
9
F With double prongs for 6.3 x 0.8 mm spade connectors or solder
connections, front or rear wiring.
1
Notes: ) Standard voltages 24, 32, 110, 240 and 415 V AC, 24, 48, 110, 220
and 240 V DC.
2
) CS 1 relays have 6 contact positions. If less than 6 contacts are required order
blank elements.
3
) For alternative contacts refer next page.
240/415 V rated coils are suitable for use on 230/400 V in accordance with
AS 60038 : 2000.
CS 1 contact element
Components
Contact elements 1) Cat. No. Price $
Early make N/O 10 amp CS1-3
Late break N/C 10 amp CS1-4
Light current N/O 2 amp gold CS1-6G
Light current N/C 2 amp gold CS1-7G
CS 1 contact element
Early make N/O 2 amp CS1-8
Late break N/C 2 amp CS1-9
Complete operating mechanism AC (less coil) CS1A
Complete operating mechanism DC (less coil) CS1C
DC coil 1
Notes: )Contacts are normally supplied in packets of 10.
2 amp elements are recommended where normal current is less than 2 amps
(refer technical catalogue 2500).
2
) AC 24, 32, 110, 240, 250 and 415 V 50 Hz.
DC 24, 32, 48, 110, 220 and 240 V.
For dimensions and Illustrated list of components, refer page 9 - 13.
9 240/415 V rated coils are suitable for use on 230/400 V in accordance with AS 60038 : 2000.
CS 1-RP
Control contact
25
12
18.6
9 - 13
The power
in relays since
1954
SCR
DIN rail mount TERMEWLESS
INAL
S
■ Interface module with 34 series relay
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC/DC 24, 110, 240
DC 6 , 12, 48 , 60
Rated power AC/DC (50/60 Hz) AC/DC (0.2…0.9)W
DC 0.3W
Operation range (50/60 Hz) AC/DC (0.83…1.1) UN
DC (0.83…1.2) UN
Holding voltage AC/DC 0.6 UN/0.6 UN
Must drop-out voltage AC/DC 0.1 UN/0.1 UN
Technical data
Mechanical life AC/DC -/10.106
Electrical life @ rated load AC 1 60.103
Insulation between coil and contacts 6 kV
11
A1 A2
Contact specifications
Contact configuration 1 C/O
Rated current 6A
Rated voltage 250 V AC
Rated load in AC 1 1,500 VA
Rated load in AC 15 (230 V AC) 300 VA
Breaking capacity in DC 1 : 30/110/220 V 6/0.2/0.15 A
Maximum peak current 10 A
Maximum switching voltage 400 V AC
Minimum switching load 500 mW
Coil specifications
Nominal voltage (UN) 125 V (50/60 Hz) AC/DC 240 V (50/60 Hz) AC
Rated power (UN) 1W 0.5 W
Operation range 94 V min - 138 V max (AC/DC) 184 V min - 264 V max (AC)
Holding voltage 0.6 UN (AC/DC) 0.6 UN (AC)
Must drop-out voltage 44 (AC/DC) 92 (AC)
Technical data
Mechanical life AC/DC -/10.106
Electrical life @ rated load AC 1 60.103
Insulation between coil and contacts 6 kV
Ambient temperature range -40 °C…+55 °C
Protection rating IP 20
Connection diagram 12 14
11
9
A1 A2
Note: The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
9 22 24 14 12
21 11
A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
9
operate the contacts. Releasing the button will return contacts
to normal state.
Option 2: To use as a lockable test button first remove (break/cut-off) the
plastic pip. Once removed, simply push and rotate the button
anti-clockwise to lock the test button in place. The contacts
will remain latched in the operation mode until the test
button is rotated back to its normal position.
Note: In both cases test button actuation should be swift and decisive.
Coil specifications 1) 2)
Nominal voltage (UN) (50/60 Hz) AC 12, 24, 32, 48, 110, 240 12, 24, 32, 48, 110, 240
DC 12, 24, 48, 110 12, 24, 32, 48, 110
Rated power AC/DC 1.5 VA/1W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.5 UN
Must drop-out voltage AC/DC 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 20.106/50.106 cycles
Electrical life @ rated load AC 1 200.103 cycles 150.103 cycles
Insulation between coil and contacts 3.6 kV 2.5 kV
A1 A2 A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
2
) Please contact NHP for other voltages.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
Coil specifications 1)
Nominal voltage (UN) 2) (50/60 Hz) AC 12, 24, 48, 110, 240 12 , 24, 48 ,110, 240
DC 6 , 12, 24, 48, 110 V 6 ,12, 24, 48 ,110
Rated power AC/DC 1.5 VA/1 W 2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.6 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 20.106/50.106 cycles
Electrical life @ rated load AC 1 3
200.10 cycles 150.103 cycles
Insulation between coil and contacts 4 kV
Ambient temperature range -40 °C…+70 °C
Protection rating
Connection diagram 3 1 4 2
IP 50
5 1 6 2 7 3 8 4
9
Note: New DC relays are non-polarised *
9 10 11 12
5 6
(+) (–)
13 14
* Polarity for DC supply when using plug-in 7 8
A1 A2
LED/diode modules. A1 A2
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 6, 12, 24, 32, 48, 60 , 110, 240 6, 12, 24, 32, 48, 110, 240
DC 6, 12, 24, 32, 48, 60 , 110 6, 12, 24, 32, 48, 110
Rated power AC/DC 2.2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.5 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 20.106/50.106 cycles
Electrical life @ rated load AC 1 200.103 cycles
Insulation between coil and contacts 3.6 kV
Ambient temperature range -40 °C…+70 °C
9 Protection rating
Connection diagram
IP 50
20 series
■ One module wide (17.5 mm)
■ Integral ID label
■ Test button with mechanical indicator
26 series Cat. No. 1) Price $ Cat. No. 1) Price $
■ Screw terminal connection 20.22…V AC 26.01…V AC
■ Panel mountable 20.22…V DC 26.02…V AC
■ Silent operation 20.21.110 V AC 26.03…V AC
20.23…V AC
20.23…V DC
Contact specifications
Contact configuration 2 N/O 1 N/O + 1 N/C 1 N/O 2 N/O 1 N/O + 1 N/C
Rated current 16 A 10 A
Rated voltage 250 V AC
Rated load in AC 1 4,000 VA 2,500 VA
Rated load in AC 15 (230 V AC) 750 VA 500 VA
Nominal lamp rating: incandescent (230 V) 2,000 W 800 W
Compensated fluorescent (230 V) 750 W 360 W
Uncompensated fluorescent (230 V) 1,000 W 500 W
Halogen lamps (230 V) 2,000 W 800 W
Maximum peak current 30 A 20 A
Maximum switching voltage 400 V AC
Minimum switching load 1,000 mW
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 24, 110, 240 12 , 24, 48 , 110 , 240
DC 12 , 24 –
Rated power AC/DC 5.5 VA/5 W 4.5 VA
Operation range (50 Hz) AC (0.85…1.1) UN (0.8…1.1) UN
DC (0.9…1.1) UN –
Maximum pulse duration (EN 60669) 1 hour
Technical data
Mechanical life AC/DC 300.103 cycles 300.103 cycles
Electrical life @ rated load AC 1 100.103 cycles 100.103 cycles
Insulation between coil and contacts
Ambient temperature range
4 kV
-40 °C…+40 °C
4 kV
-40 °C…+40 °C 9
Protection rating IP 20 IP 20
Connection diagram
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
■ Space saving
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 24, 110, 240 24, 110, 240
DC 24 12, 24, 48
Rated power AC/DC 2.2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.6 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 10.106/30.106 cycles
Electrical life @ rated load AC 1 100.103 cycles
Insulation between coil and contacts 6 kV
A1 A2 A1 A2
1
Note: ) Add coil voltage to Cat. No. when ordering.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
■ Flange mounted
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 6 , 12, 24, 48, 60 , 110, 240 24, 110, 230, 240
DC 6 , 12, 24, 48, 60 , 110 12 , 24 , 48 , 125
Rated power AC/DC 2.2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.85…1.1) UN
Holding voltage AC/DC 0.8 UN/0.6 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 10.106/30.106 cycles
Electrical life @ rated load AC 1 80.103 cycles 50.103 cycles
Insulation between coil and contacts 4 kV
Ambient temperature range
Protection rating
-40 °C…+50 °C
IP 50 9
Connection diagram
A1 A2 A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 6 , 12 , 24, 48 ,110, 240 6 , 12, 24, 48 , 110, 240
DC 6 , 12 , 24, 48 , 110 6 , 12, 24, 48 , 110
Rated power AC/DC 2.2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.6 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 10.106/30.106 cycles
Electrical life @ rated load AC 1 100.103 cycles
A B A B
A1 A2 A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) AC 240 6 , 12 , 24 , 48 , 110, 240
DC 12 , 24 , 110 12 , 24 , 110
Rated power AC/DC 2.2 VA/1.3 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.8…1.1) UN
Holding voltage AC/DC 0.8 UN/0.6 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 10.106/30.106 cycles
Electrical life @ rated load AC 1 100.103 cycles
Insulation between coil and contacts
Ambient temperature range
6 kV
-40 °C…+70 °C
9
Protection rating IP 50
Connection diagram
A B A B
A1 A2 A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
30 series
■ Able to switch low signals
■ IP 67 protection rating
34 series
■ Ultra slim, 5 mm wide
■ Sensitive DC coil
Cat. No. Price $ Cat. No. Price $
■ Replacement relay for 38 series
30.22…V DC 34.51…V DC
Contact specifications
Contact configuration 2 C/O 1 C/O
Rated current 1.25 A 6A
Rated voltage 125 V AC 250 V AC
Rated load in AC 1 125 VA 1,500 VA
Rated load in AC 15 (230 V AC) 25 VA 300 VA
Breaking capacity in DC 1 : 30/110/220 V 2/0.3/– A 6/0.2/0.12 A
Maximum peak current 2A 10 A
Maximum switching voltage 250 V AC 400 V AC
Minimum switching load 10 mW 500 mW
Coil specifications
Nominal voltage (UN) DC 12, 24 6 ,12, 24, 60
Rated power DC 0.2 W 0.17 W
Operation range DC (0.7…1.9) UN (0.7…2) UN
Holding voltage DC 0.35 UN 0.4 UN
Must drop-out voltage DC 0.05 UN 0.05 UN
Technical data
Mechanical life AC/DC –/10.106 cycles –/10.106 cycles
3
Electrical life @ rated load AC 1 100.10 cycles 60.103 cycles
Insulation between coil and contacts 1.5 kV 6 kV
Ambient temperature range -40 °C…+70 °C -40 °C…+85 °C
Protection rating IP 67 IP 50
9 Connection diagram
A1 A2 A1 A2
1
Notes: ) Add coil voltage to Cat. No. when ordering.
Available on indent only.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
Contact specifications
Contact configuration 1 C/O 2 C/O
Rated current/maximum peak current A 16/25 8/15
Rated voltage/maximum switching voltage V AC 250/440
Rated load AC 1 VA 4000 2000
Rated load AC 15 (230 V AC) VA 750 350
Single phase motor rating (230 V AC) kW 0.55 0.37
Breaking capacity DC 1: 30/110/220 VA 12/0.5/0.15 6/0.5/0.15
Minimum switching load mW (V/mA) 300 (5/5)
Coil specifications 1)
Nominal voltage (UN) (50/60 Hz) V AC 12, 24, 48, 110, 240
V DC 12, 24, 48, 110
Rated power VA/W 1.2/0.5
Operation range AC (0.8…1.1) UN
DC (0.73…1.1) UN
Holding voltage AC/DC 0.8 UN/0.4 UN
Must drop-out voltage AC/DC 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC cycles 10.106
Electrical life at rated load AC 1 cycles 100.103
Operate/release time ms 10/3
Insulation between coil and contacts (1.2/50µs) 6 kV (8 mm)
Ambient temperature range
Protection rating
-40…+70ºC
IP 50 9
Connection Diagram
Note: DC relays are non-polarised
1
Notes: ) Add coil voltage to Cat. No. when ordering.
The equipment on this page is rated 230/400 V and is suitable for use on 240/415 V systems as per AS 60038:2000.
■ Compact
■ PCB or plug-in
Cat. No. 1) Price $ Cat. No. 1) Price $
■ 5 mm pinning
40.51 240 V AC 40.52 240 V AC
40.51…V AC 40.52…V AC
40.51…V DC 40.52…V DC
Contact specifications
Contact configuration 1 C/O 2 C/O
Rated current 10 A 8A
Rated voltage 250 V AC
Rated load in AC 1 2,500 VA
Rated load in AC 15 (230 V AC) 500 VA
Single phase motor rating (230 V AC) 0.37 kW
Breaking capacity in DC 1 : 30/110/220 V 10/0.3/0.12 A
Maximum peak current 20 A 15 A
Maximum switching voltage 400 V AC 250 V AC
Minimum switching load 300 mW
Coil specifications 1)
Nominal voltage (UN) AC 12, 24, 110, 240 12, 24, 110, 240
DC 6, 12, 24, 48 6, 12, 24, 48 , 110
Rated power AC/DC 1.2 VA/0.65 W
Operation range (50 Hz) AC (0.8…1.1) UN
DC (0.73…1.5) UN
Holding voltage AC/DC 0.8 UN/0.4 UN
Must drop-out voltage 0.2 UN/0.1 UN
Technical data
Mechanical life AC/DC 10.106 /20.106 cycles
Electrical life @ rated load AC 1 200.103 cycles 100.103 cycles
Insulation between coil and contacts 6 kV
Ambient temperature range -40 °C…+85 °C
9 Protection rating
Connection diagram
IP 50
A1 A2 A1 A2