Вы находитесь на странице: 1из 2

Site Test Report: 01BBA01 Report No: LTP-BIB3-ELE-TR-022

Hi-Pot Test Record of 6.6KV Power Cable


Feeder Description: P30_Line 2 PT with Incomer Cables Date: 29-May-18

Cable Size: 1C: 500sqmm Cu


No. of Runs: 4 Nos per Phase

1. Insulation Resistance Test (Before/After Hi-Pot Test)


Applied Voltage: 5000V DC Duration: 60 secs
Measured Value
Phase Measured Between Remarks
Before Hi-Pot Test After Hi-Pot Test
R1-E 94 GΩ 263 GΩ
R2-E 144 GΩ 240 GΩ
R
R3-E 132 GΩ 261 GΩ
R4-E 119 GΩ 243 GΩ
Y1-E 25.4 GΩ 80.2 GΩ
Y2-E 391 GΩ 562 GΩ
Y
Y3-E 346 GΩ 384 GΩ
Y4-E 85.7 GΩ 97.2 GΩ
B1-E 21.6 GΩ 47.6 GΩ
B2-E 145 GΩ 223 GΩ
B
B3-E 179 GΩ 210.5 GΩ
B4-E 43 GΩ 129 GΩ

2. Hi-Pot Test Duration: 60 Secs


FAT Voltage: 22KV AC for 5min Previous Test Voltage & Duration (After FAT): N.A.
Applied Voltage: If AC: Minimum of {(0.8XPrevious Test Voltage), (2V+1) i.e. 14.2KV}

If DC: 1.2 X Minimum of {(0.8XPrevious Test Voltage), (2V+1) i.e. 14.2KV}

Leakage Current (mA)


Phase Connection Applied Voltage Remarks
Start End
R1-E 17KV DC 0.03 0.01 Withstood
R2-E 17KV DC 0.03 0.01 Withstood
R
R3-E 17KV DC 0.03 0.01 Withstood
R4-E 17KV DC 0.03 0.01 Withstood
Y1-E 17KV DC 0.06 0.05 Withstood
Y2-E 17KV DC 0.06 0.05 Withstood
Y
Y3-E 17KV DC 0.06 0.05 Withstood
Y4-E 17KV DC 0.06 0.05 Withstood
B1-E 17KV DC 0.07 0.04 Withstood
B2-E 17KV DC 0.07 0.04 Withstood
B
B3-E 17KV DC 0.07 0.04 Withstood
B4-E 17KV DC 0.07 0.04 Withstood

iBMS L&T Power Marubeni BPDB/Consultant


Signature
Name
Designation
Date
L&T Power Page 1 of 2
Format No.: LTPCCC-BIB3-PRO-FOR-025, Rev.-0, Eff. Date: 23 -01-2018
Site Test Report: 01BBA01 Report No: LTP-BIB3-ELE-TR-022
Hi-Pot Test Record of 6.6KV Power Cable
Feeder Description: P30_Line 2 PT with Incomer Cables Date: 29-May-18

Remarks/Comment (If any)


 Incomer Busbars, HV test performed along with Cable HV test.
 Incomer Busbars IR Measurement Before & After HV Test
Applied Voltage: 5000V DC Duration: 60 secs
Measured Value
Measured Between Remarks
Before Hi-Pot Test After Hi-Pot Test
R-E 94 GΩ 263 GΩ
Y-E 25.4 GΩ 80.2 GΩ
B-E 21.6 GΩ 47.6 GΩ

 HV Test
Leakage Current (mA)
Phase Connection Applied Voltage Remarks
Start End
R R- (Y+B+E) 17KV DC 0.03 0.01 Withstood
Y Y- (R+B+E) 17KV DC 0.06 0.05 Withstood
B B- (R+Y+E) 17KV DC 0.07 0.04 Withstood

iBMS L&T Power Marubeni BPDB/Consultant


Signature
Name
Designation
Date
L&T Power Page 2 of 2
Format No.: LTPCCC-BIB3-PRO-FOR-025, Rev.-0, Eff. Date: 23 -01-2018