LARSEN & TOUBRO LIMITED

400 MW Bibiyana III Gas Based Combined Cycle Power Plant


Project
Bangladesh Power Development Board

Site Test Report: GT Control Oil Pump # A Motor (01MBV03AN102-M01)


Client: Bangladesh Power Development Board Report No: xxxxxxxxxxxxxxxxxxxxxxx

EPC Contractor: Marubeni Corporation Report Date: 16-Jul-18

Equipment Details

Make: TOSHIBA Serial No.64086922


Rated Power: 15KW (20HP) Duty: S1
Phase: 3 Insulation Class: F
Rated Voltage: 415 V Frame Size: 250L
Rated Frequency: 50 Hz Enclosure: IP55
Rated Speed: 2940 rpm Bearing (DE): 6310ZZC3
Rated Current: 27.8 A (Delta Connected winding) Bearing (NDE): 6208ZZC3
Locked Rotor Current: 545.4 A Referred Standard: IEC60034-1
Starting Duty: Cold-3/Hot-2 S.F.: 1
Power Factor: 0.835 Type: TKKH3
Efficiency: 92.2% Weight: 505 Kg
Temp. Rise: 70K Date: 2016.10

Reference Drawing:

Description Drawing No. & Rev


GA
Feeder Schematic LCF – WM1

Signing Authorities:

Performing Agency iBMS Technology Limited, Bangladesh


Verified By L&T Power, India
Marubeni Corporation, Japan
Reviewed /Witnessed By
BPDB/ Owner’s Consultant (JV – NOFEAR & MEPC)

iBMS L&T Power Marubeni BPDB/Consultant


Signature
Name
Designation
Date
L&T Power Page 1 of 3
Format No.: LTPCCC-BIB3-PRO-FOR-0015, Rev.-0, Eff. Date: 23 -01-2018
Site Test Report: 01MBX01AP101-M01 Report No: xxxxxxxxxxxxxxxxxx
Motor Test Report
Source: GT 415V Normal MCC Feeder No.: LCF122

Insulation Resistance (IR) Date: 15-Jul-18


Applied Voltage: 500V DC Duration: 60 Sec
Measured IR Value in MΩ across
For R-E Y-E B-E R-Y Y-B R-B
Motor >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ
Power Cable >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ
Acceptance Criteria: IR> 2 MΩ or as per OEM recommendation

Winding Resistance
Motor Winding resistance in Ω
R-R’ Y-Y’ B-B’ R-Y Y-B B-R
1.11Ω 1.11Ω 1.02Ω 0.484Ω 0.478Ω 0.481Ω
Acceptance Criteria: As per factory test report data/ type test data

Motor Space Heater Available: Yes/No


Test on Motor Space Heater
1. Insulation Resistance
Applied Voltage: 500V DC Duration: 60 Sec
Across IR Value in MΩ
Ph-E NA
Acceptance Criteria: IR> 2 MΩ
2. Heater Resistance & Current
Load Current (Rated Power: 110W, Voltage:230V AC)
Measured Resistance
Applied Voltage Measured Current
NA NA NA
Acceptance Criteria: As per data sheet

Remarks/Comment (If any)

Instrument Details:
Model Rating/ Due Date of
Description Make Serial No
No Range Calibration
Motor Checker MCM Instrument EMC-28 1267 As per Selection 08-Jun-19
Digital Insulation
Kyoritsu KEW3125A E0018942 5000V 16-Sep-18
Tester
Multi Meter Hioki 2013 131231094 As per Selection 27-Aug-18
AC Clamp Meter Hioki 2013 131231094 As per Selection 27-Aug-18
Fluke-62-
Temp. Gun Fluke 38751605WS -30˚C TO 650˚C 25-Nov-18
MAX+ESPR
Vibration Meter Baseline 2050 0912-2114 As per Selection 29-Dec-18
Tachometer Lutron DT2234B Q633625 As per Selection 12-Apr-19

iBMS L&T Power Marubeni BPDB/Consultant


Signature
Name
Designation
Date
L&T Power Page 2 of 3
Format No.: LTPCCC-BIB3-PRO-FOR-0015, Rev.-0, Eff. Date: 23 -01-2018
Site Test Report: 01MBX01AP101-M01 Report No: xxxxxxxxxxxxxxxxxx
Motor Test Report
Source: GT 415V Normal MCC Feeder No.: LCF122

Operation Checks before No Load Trial Date: 15-Jul-18


Sl. No. Activity Remarks
1 Feeder Start Operation from Field verified Yes/No/NA
2 Feeder Stop operation from EPB verified Yes/No/NA
3 Feeder Start/stop operation from Remote (DCS/PLC) verified Yes/No/NA
Motor Thermal Overload Relay (OLR) Setting (100% of FLC)
4 Yes (84 A)
verified
5 Motor & LPBS body proper earth connection verified Yes/No
6 Motor space heater auto cut-off verified Yes/No/N.A.
(Clockwise/Anticlockwise
6 Motor direction of rotation (DOR) verified as per pump DOR
from motor NDE)

Motor No Load Trial ISTART: 256 Amp Start Time: 16:45hr


Motor Motor
Motor
Time Voltage (Volts) Current (Amps) BRG DE BRG NDE
Body (0C)
(HH:MM) (0C) (0C)
RY YB BR R Y B
00:00 420 420 420 25.50 24.27 24.45
00:30
01:00
01:30
02:00
02:30
03:00
03:30
04:00

Time Motor DE Vibration (mm/sec) Motor NDE Vibration (mm/sec) Speed Ambient
(HH:MM) A V H A V H RPM Temp (0C)
00:00
00:30
01:00
01:30
02:00
02:30
03:00
03:30
04:00

Remarks/Comment (If any)


1. Motor IR with cable connected before no load trial, R/Y/B – E: >1GΩ
2. MHPS document is attached for No Load trial details.
iBMS L&T Power Marubeni BPDB/Consultant
Signature
Name
Designation
Date
L&T Power Page 3 of 3
Format No.: LTPCCC-BIB3-PRO-FOR-0015, Rev.-0, Eff. Date: 23 -01-2018