Вы находитесь на странице: 1из 4

PROJECT : cGMPPharma

Column Stirrup Calculation

COLUMN ID Length (L) Width (B) Fck Fy Cover Ag Ak S

C1 600 500 30 500 40 300000 218400 100


C2 600 500 30 500 40 300000 218400 100
C3 600 230 30 500 40 138000 78000 75
C4 600 230 30 500 40 138000 78000 75
C5 600 230 30 500 40 138000 78000 75
C6 300 300 30 500 40 90000 48400 75
C7 300 300 30 500 40 90000 48400 100
C8 300 300 30 500 40 90000 48400 100
C9 600 750 30 500 40 450000 348400 100
C10 600 750 30 500 40 450000 348400 100
C11 600 750 30 500 40 450000 348400 100
C12 600 400 30 500 40 240000 166400 100
C13 600 400 30 500 40 240000 166400 100
C14 600 400 30 500 40 240000 166400 100
C15 600 400 30 500 40 240000 166400 100
C16 600 400 30 500 40 240000 166400 100

L -- Longer Dimension of column (mm)


B -- Shorter Dimension of column (mm)
Fck -- Characteristic Strength of Concrete in column (N/mm2)
Fck -- Grade of Steel used in Hoop Reinforcement (Not more than 415 N/mm 2)
Cover -- Concrete Cover taken as 40 mm from the face of ties
Ag -- Gross Area of Column Section (mm2)
Ak -- Area of confined Column core in rectangle hoop measured to its outer side dimensions (mm2)
Ash -- Area of bar cross section used for confinement (mm 2)
S -- Spacing of Hoop (mm)
h -- Longer Dimension of rectangular confining Hoop measured to its outer face (mm)
Along Length of the Column
h Ash Ash(pro) Dia of stirrups
Dia of bars nos Dia of bars Nos
80 32.28 50.24 8 ok 20 6 0 0
74 29.86 50.24 8 ok 25 6 0 0
118 73.52 78.5 10 ok 16 2 12 4
110 68.54 78.5 10 ok 20 2 16 4
100 62.31 78.5 10 ok 25 2 20 4
88 61.27 78.5 10 ok 16 2 12 1
80 74.26 78.5 10 ok 20 3 0 0
75 69.62 78.5 10 ok 25 2 20 1
111.6 35.15 50.24 8 ok 20 4 16 3
106 33.38 50.24 8 ok 25 4 20 3
104 32.75 50.24 8 ok 25 7 0 0
86.4 41.27 50.24 8 ok 16 4 12 2
83.2 39.74 50.24 8 ok 20 2 16 4
83.2 39.74 50.24 8 ok 20 4 12 2
76 36.30 50.24 8 ok 25 4 20 2
74 35.35 50.24 8 ok 25 6 0 0
g Length of the Column Along Width of the Column

Along LengthClear Spacing Dia of bars nos Dia of bars Nos Along WidthClear Spacing
80.00 20 5 0 0 80.00
74.00 25 5 0 0 73.75
88.00 16 2 0 0 118.00
83.20 20 2 0 0 110.00
78.00 25 2 0 0 100.00
88.00 16 2 12 1 88.00
80.00 20 3 0 0 80.00
75.00 25 2 20 1 75.00
65.33 20 4 16 2 111.60
60.00 25 4 20 2 106.00
57.50 25 6 0 0 104.00
86.40 16 4 0 0 85.33
83.20 20 2 16 2 82.67
83.20 20 4 0 0 80.00
76.00 25 4 0 0 73.33
74.00 25 4 0 0 73.33
D -- Diameter of column (mm)
Fck -- Characteristic Strength of Concrete in column (N/mm2)

Fck -- Grade of Steel used in Hoop Reinforcement (Not more than 415 N/mm 2)

Cover -- Concrete Cover taken as 40 mm from the face of ties


Ag -- Gross Area of Column Section (mm2)

Ak -- Area of Concrete core (mm2)

Ash -- Area of bar cross section used for confinement (mm 2)

S -- Pitch of spiral and Spacing of Hoop (mm)


Dk -- Diameter of core measured to the outside of spiral or hoop

DiameterFck Fy Cover Ag Ak S Dk Ash


600 35 500 40 282744 212372 100 150 31.31361
650 35 500 40 331831.5 255176 100 150 28.38781
300 30 415 40 70686 38013.36 100 220 123.023
300 25 415 40 70686 38013.36 100 220 102.5192
300 20 415 40 70686 38013.36 100 220 82.01533
900 40 415 40 636174 528103 100 820 145.5657
300 50 415 40 70686 38013.36 75 220 153.7788
230 50 415 40 41547.66 17671.5 75 150 164.8193