Академический Документы
Профессиональный Документы
Культура Документы
334:1999
Incorporating
Amendment No. 1
ICS 23.060.40
National foreword
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 59 and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
This British Standard, having Sidelining in this document indicates the most recent changes by amendment.
been prepared under the
direction of the Engineering
Sector Committee, was
published under the authority
of the Standards
Committee and comes
into effect on Amendments issued since publication
15 November 1999
Amd. No. Date Comments
© BSI 05-2001
13001 May 2001 Indicated by a sideline
ICS 23.060.40
English version
CEN
European Committee for Standardization
Comité Européen de Normalisation
Europäisches Komitee für Normung
© 1999 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national
Members.
Ref. No. EN 334:1999 + A1:2000 E
EN 334:1999
This European Standard has been prepared by of the following countries are bound to implement
Technical Committee CEN/TC 235, Gas pressure this European Standard: Austria, Belgium,
regulators and associated safety shut-off devices for Czech Republic, Denmark, Finland, France,
use in gas transmission and distribution, the Germany, Greece, Iceland, Ireland, Italy,
Secretariat of which is held by UNI. Luxembourg, Netherlands, Norway, Portugal,
At the time of drafting, it has not been decided Spain, Sweden, Switzerland and the United
whether the pressure regulators within the scope of Kingdom.
this European Standard will fall under the Pressure
Equipment Directive 97/23/EC and also there was Contents
no network of Notified Bodies under the provisions Page
of the directive itself. Therefore it was decided to Foreword 2
establish the evaluation of conformity according to
the CEN, Guidelines for Technical Committees — 1 Scope 5
Requirements in European Standards concerning 2 Normative references 5
the evaluation of conformity 1993-01. 3 Definitions and symbols 7
When it is confirmed that pressure regulators 3.1 Terminology 7
within the scope of this European Standard fall 3.1.1 Gas pressure regulator 7
under the Pressure Equipment Directive, the
3.1.2 Main components 9
Standard will be revised to ensure that it’s clauses
conform with the essential requirements and 3.1.3 Accessories 10
conformity assessments of the Directive. 3.2 Control variables 10
NOTE Referring to 4.2.2 of this European Standard it should 3.2.1 Reference values 10
be noted that at the discussion during its elaboration within
WG 1, it was pointed out that in some member countries there is 3.2.2 Variables in the controlling process 11
legislation limiting the application of some materials listed in 3.2.3 Possible values of all variables 12
Table 5.
3.2.4 Terms pertinent to the controlled
This European Standard shall be given the status of variable 12
a national standard, either by publication of an
3.3 Operating features in stable conditions 12
identical text or by endorsement, at the latest by
November 1999, and conflicting national standards 3.3.1 Stable conditions 12
shall be withdrawn at the latest by November 1999. 3.3.2 Performance curve 13
According to the CEN/CENELEC Internal 3.3.3 Hysteresis band 13
Regulations, the national standards organizations 3.3.4 Family of performance curves 14
of the following countries are bound to implement
this European Standard: Austria, Belgium, 3.3.5 Features pertinent to accuracy 14
Czech Republic, Denmark, Finland, France, 3.3.6 Features pertinent to lock-up behaviour 14
Germany, Greece, Iceland, Ireland, Italy, 3.4 Further functional terminology 17
Luxembourg, Netherlands, Norway, Portugal, 3.4.1 Pressures pertinent to design of
Spain, Sweden, Switzerland and the United
gas pressure regulator 17
Kingdom.
3.4.2 Nominal pressure 17
Foreword to amendment A1 3.4.3 Operating temperature range 18
This amendment EN 334:1999/A1:2000 to the 4 Construction requirements 18
EN 334:1999 has been prepared by Technical 4.1 General requirements 18
Committee CEN/TC 235, Gas pressure regulators 4.1.1 Operational requirements 18
and associated safety shut-off devices for use in gas
transmission and distribution, the Secretariat of 4.1.2 Gas pressure regulators with
which is held by UNI. built-in safety devices 18
This amendment to the European Standard 4.1.3 End connections 18
EN 334:1999 shall be given the status of a national 4.1.4 Nominal pressures 18
standard, either by publication of an identical text 4.1.5 Nominal sizes and face-to-face
or by endorsement, at the latest by March 2001, and dimensions 19
conflicting national standards shall be withdrawn 4.2 Materials 20
at the latest by March 2001.
2 © BSI 05-2001
EN 334:1999
Page Page
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
www.bzfxw.com
5.3.2 Lock-up behaviour 28 surveillance 45
5.3.3 Stable conditions 29 8.3.2 Surveillance report 45
6 Gas pressure regulator sizing 29 9 Marking 46
6.1 Flow behaviour 29 9.1 General requirements 46
6.2 Sizing equations for the calculation 9.2 Markings for the various connections 46
of volumetric flow rates of a gas 9.3 Marking of built-in safety devices 46
pressure regulator with its control
Annex A (informative) Use of allowable
member in its mechanically fully
pressure pzul 47
open position 29
Annex B (informative) Alternative methods
6.2.1 Normal calculations 29 for the determination of the accuracy class,
6.2.2 Practical calculations 30 the lock-up pressure class, the maximum
6.2.3 Simplified calculations 30 accuracy flow rate, the flow coefficients
6.3 Calculation of the maximum and the verification of the hysteresis band 47
accuracy flow rate 30 B.1 General 47
6.4 Inherent flow characteristics 31 B.2 Test methods 47
6.5 Calculation of volumetric flow B.2.1 Direct acting gas pressure regulator 47
rates for partially open gas B.2.2 Pilot controlled gas pressure regulators 48
pressure regulators 31 B.3 Determination of flow coefficients
7 Testing 31 for larger capacity regulators 49
7.1 Types of tests 31 Annex C (informative) Inspection certificate 54
7.1.1 General 31 Annex D (informative) Acceptance test 56
7.1.2 Type test 32 Annex E (informative) Conformity evaluation 56
7.1.3 Selection of test samples 33 E.1 General 56
7.1.4 Manufacturer’s test 33 E.2 Manufacturer’s conformity evaluation 56
7.1.5 Surveillance 33 E.3 Third party conformity evaluation 57
7.2 Test and verification methods 33 E.3.1 Introduction 57
7.2.1 Dimensional check and visual E.3.2 Procedure 57
inspection 33 E.4 Issue of the certificate of conformity 57
© BSI 05-2001 3
EN 334:1999
Page Page
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
E.3.3 Selection of test samples 57 Figure B.2 — Graph of the outlet pressure
Annex F (informative) Seat leakage 57 plotted against different positions of
the control member in a unbalanced
Annex G (informative) Order specification 58
direct acting regulator 50
G.1 Minimum specifications 58 Figure B.3 — Functional diagram of
G.1.1 Details of construction 58 a pilot controlled regulator 51
G.1.2 Dimensions 58 Figure B.4 — Various graphs relating to
G.1.3 Performance 58 the tests detailed in B.2 for a balanced
G.2 Optional specifications 58 pilot controlled regulator 52
Figure B.5 — Various graphs relating to
Annex H (informative) A-deviations 59
the tests detailed in B.2 for an unbalanced
Annex J (informative) Bibliography 59 pilot controlled regulator 53
Figure 1 — Example of a direct Figure B.6 — Graph of Cg values plotted
acting regulator 7 against different positions of
Figure 2 — Example of a pilot the control member 54
controlled regulator 8 Table 1 — Recommended face-to-face
Figure 3 — Performance curve dimensions for flanged regulators 19
(pas constant, pe constant) 13 Table 2 — Alternative face-to-face
Figure 4 — Family of performance curves dimensions for flanged regulators 19
(pas constant) 14 Table 3 — Face-to-face dimensions
Figure 5 — Family of performance curves for flangeless regulators 20
indicating maximum accuracy flow rates Table 4 — Face-to-face dimensions
and minimum flow rates (pas constant, for flangeless regulators 20
www.bzfxw.com
stable conditions) 15
Table 5 — Materials for pressure
Figure 6 — Performance curve indicating containing parts 21
lock-up pressure zone (stable condition) 16
Table 5a — Non-destructive testing 23
Figure 7 — Points of measurement
for sound pressure level 27 Table 5b — Minimun inspection sample 24
Figure 8 — Flow behaviour of a regulator Table 6 — Minimum values of safety factor 26
with the control member in a fixed position 29 Table 7 — Accuracy classes 28
Figure 9 — Three examples of Table 8 — Lock-up pressure classes 28
inherent flow characteristics 31 Table 9 — Lock-up pressure zone classes 28
Figure 10 — Graphical representation Table 10 — Summary of types of tests and
of the tests detailed in 7.2.6.3 38 relevant test methods and requirements 32
Figure 11 — Graphical representation Table 11 — Pressure values for the shell
of 7.2.6.4.3 40 strength test 35
Figure 12 — Graphical example of 7.2.6.4.4 41 Table 12 — Pressure values in the external
Figure 13 — Recommended pressure tapping 43 leakage test 35
Figure 14 — Test rig requirements 44 Table 13 — Maximum external and internal
Figure B.1 — Graph of the outlet pressure leakage rates 35
plotted against different positions of the control
member in a balanced direct acting regulator 49
4 © BSI 05-2001
EN 334:1999
1 Scope
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
This European Standard specifies constructional and functional requirements, regulator sizing, testing,
documentation and marking of gas pressure regulators:
— for inlet pressures up to 100 bar and nominal diameter up to DN 400;
— used at an operating temperature range from –20 °C to +60 °C;
which operate with fuel gases of the 1st and of the 2nd family in accordance with EN 437 in transmission
and distribution networks and also in industrial installations.
“Gas pressure regulators” hereafter will be called “regulators” except in the titles.
This European Standard considers the following classes of regulators:
— class 1: operating temperature range from –10 °C to 60 °C;
— class 2: operating temperature range from –20 °C to 60 °C.
For inlet pressure higher than 100 bar and/or operating temperatures outside the range from –20 °C to
60 °C and/or nominal diameter DN > 400, this European Standard may be used as a “guideline”.
This European Standard applies to regulators which use the pipeline gas as a source of control energy
unassisted by any external power source. These regulators have no continuous discharge of gas into the
atmosphere but temporary discharges from safety devices can occur.
The regulators complying with the requirements of this European Standard may be declared as “in
conformity with EN 334”.
This European Standard does not apply to:
— regulators upstream from/on/in domestic gas-consuming appliances which are installed downstream
of domestic gas meters;
www.bzfxw.com
— regulators that comply with both of the following characteristics:
— volumetric flow rate k 100 m3/h at standard conditions;
— inlet pressure k 5 bar;
— regulators for which a specific European Standard exists (e.g. EN 88, etc.);
— industrial process control valves in accordance with prEN 1349.
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other publications.
These normative references are cited at the appropriate places in the text and the publications are listed
hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply
to this European Standard only when incorporated in it by amendment or revision. For undated references
the latest edition of the publication referred to applies.
BS 437, Test gases — Test pressures — Appliance categories.
EN 287-1, Approval testing of welders — Fusion welding — Part 1: Steels.
EN 287-2, Approval testing of welders — Fusion welding — Part 2: Aluminium and aluminium alloys.
EN 288-1, Specification and qualification of welding procedures for metallic materials — Part 1: General
rules for fusion welding.
EN 288-2, Specification and qualification of welding procedures for metallic materials — Part 2: Welding
procedure specification for arc welding.
EN 288-3, Specification and qualification of welding procedures for metallic materials — Part 3: Welding
procedure tests for the arc welding of steels.
EN 970, Non-destructive examination of fusion welds — Visual examination.
prEN 1349, Industrial process control valves.
EN 1418, Welding personnel — Approval testing of welding operators for fusion welding and resistance weld
setters for fully mechanized and automatic welding of metallic materials.
EN 10045-1, Metallic materials — Charpy impact test — Part 1: Test method.
EN 10204, Metallic products — Types of inspection documents.
© BSI 05-2001 5
EN 334:1999
prEN 13787:2000, Elastomers for gas pressure regulators and associated safety devices for inlet pressures
up to 100 bar.
EN 20898-1, Mechanical properties of fasteners — Part 1: Bolts, screws and studs.
(ISO 898-1:1988)
EN 45011, General criteria for certification bodies operating product certification.
EN 45014, General criteria for supplier’s declaration of conformity.
EN 45020, General terms and their definitions concerning standardization and related activities.
EN 60534-1, Industrial-process control valves — Part 1: Control valve terminology and general
considerations.
(IEC 534-1:1987)
EN 60534-2-2, Industrial-process control valves — Part 2: Flow capacity — Section 2: Sizing equations for
compressible fluid flow under installed conditions.
(IEC 534-2-2:1980)
EN 60534-2-3, Industrial-process control valves — Part 2: Flow capacity — Section 3: Test procedures.
(IEC 534-2-3:1983)
EN 60651:1994, Sound level meters.
(IEC 651:1979)
EN ISO 898-1, Mechanical properties of fasteners made of carbon steel and alloy steel — Part 1: Bolts, screws
and studs.
(ISO 898-1:1999)
www.bzfxw.com
EN ISO 6708, Pipework components — Definition and selection of DN (nominal size).
(ISO 6708:1995)
EN ISO 9000-1, Quality-management and quality assurance standards — Part 1: Guidelines for selection
and use.
(ISO 9000-1:1994)
EN ISO 9001, Quality systems — Model for quality assurance in design/development, production,
installation and servicing.
(ISO 9001:1994)
EN ISO 9002, Quality systems — Model for quality assurance in production, installation and servicing.
(ISO 9002:1994)
EN ISO 9003, Quality systems — Model for quality assurance in final inspection and test.
(ISO 9003:1994)
EN ISO 9004-1, Quality management and quality system elements — Part 1: Guidelines.
(ISO 9004-1:1994)
ISO 7-1, Pipe threads where pressure-tight joints are made on the threads — Part 1: Dimensions, tolerances
and designation.
ISO 3419, Non-alloy and alloy steel butt-welding fittings.
ISO 5752, Metal valves for use in flanged pipe systems — Face-to-face and centre-to-face dimensions.
ISO 6761, Steel tubes — Preparation of ends of tubes and fittings for welding.
ISO 7005, Metallic flanges.
IEC 534-3:1976, Industrial-process control valves — Part 3: Dimensions — Section 1: Face-to-face
dimensions for flanged, two-way, globe-type control valves.
IEC 534-3-2:1984, Industrial-process control valves — Part 3: Dimensions — Section 2: Face-to-face
dimensions for flangeless control valves except wafer butterfly valves.
ASME B 16.34:1996, Valves — Flanged, threaded and welding end.
ASME VIII div. 1:1995, Rules for construction of pressure vessels.
MSS SP 55 — 1985, Quality standard for steel castings for valves, flanges and fittings and other piping
components (Visual method).
6 © BSI 05-2001
EN 334:1999
For the purposes of this European Standard, the definitions given in EN 60534-1 and the following specific
definitions apply.
3.1 Terminology
3.1.1
gas pressure regulator
device whose function is to maintain the value of the controlled variable (see 3.2.2.1) within its tolerance
field irrespective of disturbance variables
3.1.1.1
direct acting gas pressure regulator
regulator in which the net force required to move the control member is supplied directly by the controlled
variable (see example in Figure 1)
www.bzfxw.com
© BSI 05-2001 7
EN 334:1999
3.1.1.2
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
www.bzfxw.com
Figure 2 — Example of a pilot controlled regulator
3.1.1.3
monitor
second regulator normally installed in series with an active regulator which has the task of maintaining
the controlled variable within allowable limits in the event of the failure of the active regulator
3.1.1.4
series of regulators
regulators with the same design concept but differing only in size
3.1.1.5
fail open regulator
regulator whose control member automatically tends to open when the main diaphragm fails or when the
energy required to move the control member fails
NOTE The definition in this clause covers typical main failure modes. There are other failure modes that may be considered.
3.1.1.6
fail close regulator
regulator whose control member automatically tends to close when the main diaphragm fails or when the
energy required to move the control member fails
NOTE The definition in this clause covers typical main failure modes. There are other failure modes that may be considered.
3.1.1.7
integral strength regulator
regulator in which the pressure containing parts have a design pressure pd not less than the allowable
pressure pzul
8 © BSI 05-2001
EN 334:1999
3.1.1.8
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001 9
EN 334:1999
3.1.2.8
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
pilot
device which included:
— a setting element to obtain the set value of the controlled variable;
— a detector element for the controlled variable;
— a unit which compares the set value of the controlled variable with its feedback value;
— a system which provides the motorization energy for the actuator.
3.1.2.9
main diaphragm
diaphragm, the function of which is to detect the feedback of the controlled variable and/or the diaphragm
which provides the thrust to move the control member
3.1.2.10
pressure controlling parts
parts intended to control or regulate the movement of pressurized fuel gas, such as the control member,
the actuator etc.
3.1.2.11
pressure containing parts
parts whose failure to function as intended would result in a release of the retained fuel gas to the
atmosphere
these include bodies, bonnets, the casing of the actuator and blind flanges
3.1.3
accessories
parts or minor devices connected to the regulator
3.1.3.1
sensing and process lines
lines which connect impulse points to the regulator
sensing and process lines may be integrated into the regulator or external to the regulator
those lines with no internal flow are termed “sensing lines”; those with internal flow are termed “process
lines”
3.1.3.2
breather line
connection line between the controller and/or pilot and atmosphere to equalize the pressure on the detector
element when it changes its position in normal operating conditions
in the event of a fault in the detector element this line may become an exhaust line
3.1.3.3
exhaust line
connection line between the regulator or its fixtures and atmosphere for the safe exhausting of gas in the
event of failure of any part
3.1.3.4
fixtures
functional devices connected to the main components of the regulator (see 3.1.2)
3.2 Control variables
3.2.1 Reference values
3.2.1.1
pressure
NOTE All pressures specified in this European Standard are static gauge pressures. They are measured in bar1).
10 © BSI 05-2001
EN 334:1999
3.2.1.1.1
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
inlet pressure, pe
gas pressure at the inlet of the regulator
3.2.1.1.2
outlet pressure, pa
gas pressure at the outlet of the regulator
3.2.1.1.3
differential pressure, p
difference between two values of pressure measured at two different points
3.2.1.1.4
motorization pressure, pm
gas pressure in the motorization chamber
3.2.1.1.5
pilot feeding pressure, pep
gas pressure at the inlet of the pilot
3.2.1.2 Flow conditions
3.2.1.2.1
normal conditions
absolute pressure of 1,013 25 bar and temperature of 0 °C (273,15 K)
NOTE For calculation purposes a value of 273 K is used in this European Standard.
3.2.1.2.2
gas volume
volume of gas at normal conditions
it is expressed in m3
3.2.1.2.3
volumetric flow rate, Q
volume of gas which flows through the regulator in unit time
it is expressed in m3/h at normal conditions
3.2.1.3
sound pressure level, LpA
sound pressure frequency weightings A in accordance with EN 60651:1994
3.2.2 Variables in the controlling process
3.2.2.1
controlled variable, X
variable which is monitored by the controlling process
this controlled variable in regulators may be:
— inlet pressure, pe;
— outlet pressure, pa;
— differential pressure, p;
in this European Standard, only the outlet pressure “pa” is considered as the controlled variable.
© BSI 05-2001 11
EN 334:1999
3.2.2.2
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
disturbance variable, Z
variables acting from outside on the controlling process
in the case of regulators with the outlet pressure as the controlled variable, the disturbance variables are
essentially:
— fluctuations in the inlet pressure, pe;
— changes in the volumetric flow rate, Q.
3.2.3 Possible values of all variables
3.2.3.1
actual value
instantaneous value of any variable at any instant
it is specified by the index “i” added to the symbol of the variable
3.2.3.2
maximum value
the highest value:
— to which any variable can be adjusted or to which it is limited;
— any variable may reach during a series of measurements or during a certain time period;
it is specified by the subscript “max” added to the symbol of the variable.
3.2.3.3
minimum value
the lowest value:
— to which any variable can be adjusted or to which it is limited;
— any variable may reach during a series of measurements or during a certain time period;
it is specified by the index “min” added to the symbol of the variable.
3.2.4 Terms pertinent to the controlled variable
3.2.4.1
set point, pas
nominal value of the controlled variable
NOTE The set point is not directly measurable but determined as shown in Figure 5.
3.2.4.2
set range, Wh
whole range of set points which can be obtained from a regulator by adjustment and/or the replacement of
some components (i.e. replacement of the valve seat or adjustment element e.g. spring)
3.2.4.3
specific set range, Wa
whole range of set points which can be obtained in a regulator by adjustment and with no replacement of
its components
3.2.4.4
control deviation, Xw
difference between the actual value of the controlled variable and the set point
3.2.4.5
regulation change
control deviation, Xw expressed as a percentage of the set point
3.3 Operating features in stable conditions
3.3.1
stable conditions
conditions when the controlled variable settles to a stable value after a disturbance has occurred
12 © BSI 05-2001
EN 334:1999
3.3.2
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
performance curve
graphic representation of the controlled variable as a function of the volumetric flow rate
this curve is determined by increasing and then decreasing the volumetric flow rate with constant inlet
pressure and set point (see Figure 3)
3.3.3
hysteresis band
difference between the two values of outlet pressure for a given volumetric flow rate (see Figure 3)
© BSI 05-2001 13
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
3.3.4
family of performance curves
set of the performance curves for each value of inlet pressure determined for a given set point (see Figure 4)
3.3.5 Features pertinent to accuracy
3.3.5.1
accuracy
average, expressed as a percentage of the set point, of the absolute maximum values of the positive and
negative control deviation within the operating range
3.3.5.2
accuracy class, AC
maximum permissible value of the accuracy
3.3.5.3
inlet pressure range, bpe
range of the inlet pressure for which the regulator ensures a given accuracy class
the inlet pressure range is characterized by its limit values pemax and pemin
3.3.5.4
maximum accuracy flow rate
the lowest value of the maximum volumetric flow rate up to which, for a given set point and within the
ambient temperature range specified, a given accuracy class is ensured:
14 © BSI 05-2001
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure 5 — Family of performance curves indicating maximum accuracy flow rates and
minimum flow rates (pas constant, stable conditions)
3.3.6.2
lock-up pressure, pf
pressure that occurs at the measuring point of the controlled variable when the control member is in the
closed position
the lock-up pressure corresponds to the outlet pressure at the volumetric flow rate Q = 0 in the performance
curve (see Figure 3)
it results when the time taken for a change in volumetric flow rate from Q to zero is greater than the
lock-up time of the regulator
3.3.6.3
lock-up pressure class, SG
maximum permissible positive difference between the actual lock-up pressure and the set point expressed
as a percentage of the set point e.g:
P f – P as
SG = --------------------- ´ 100 (1)
P as
© BSI 05-2001 15
EN 334:1999
3.3.6.4
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
3.3.6.5
lock-up pressure zone
zone between the volumetric flow rate Q = 0 and the minimum flow rate Qmin,pe for each corresponding
inlet pressure and set point (see Figure 6)
3.3.6.6
class of lock-up pressure zone, SZ
maximum permissible lock-up pressure zone for specified:
— inlet pressure pe or inlet pressure range bpe;
— set point pas or specific set range Wa or set range Wh;
it is expressed as the percentage of Qmin,pe to Qmax,pe, i.e:
Q min,pe
SZ = -------------------- ´ 100 (2)
Q max,pe
NOTE The values of pe referred to in Qmin and Qmax are not necessarily the same.
16 © BSI 05-2001
EN 334:1999
3.4.1.4
test pressure, pt
pressure applied to a section of the regulator for a limited period of time in order to prove certain
characteristics
3.4.1.5
design pressure, pd
pressure used in the strength calculations for the body and other parts of the housing taking into account
the safety factors required by this European Standard
3.4.1.6
limit pressure, pl
pressure at which yielding or failure becomes apparent in any component of the regulator or its fixtures
3.4.1.7
safety factor
ratio of the value of the limit pressure pl to the value of the design pressure pd applied to:
— the regulator body: Sb;
— the other pressure containing parts of the regulator: S.
3.4.1.8
permissible inlet pressure, pemax
the highest inlet pressure at which the regulator can continuously operate within specified conditions
3.4.1.9
permissible outlet pressure, pamax
the highest outlet pressure at which the regulator can continuously operate within specified conditions
3.4.1.10
minimum operating differential pressure, pmin
minimum operating differential pressure between the inlet and outlet pressures below which the regulator
will no longer function correctly within specified conditions
3.4.2
nominal pressure, PN
numerical designation relating to pressure that is a convenient round number for reference purposes
for the specific purpose of this European Standard it applies to flanges
© BSI 05-2001 17
EN 334:1999
3.4.3
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
3) On this subject CEN/TC 235 is preparing the draft European Standard, Safety devices for gas pressure regulating stations and
installations — Part 1: Gas safety shut-off devices for operating pressures up to 100 bar (W.I. 00235002).
4) The nominal pressure designations PN 20, PN 50 and PN 110 are equivalent to class ratings 150, 300 and 600 respectively.
18 © BSI 05-2001
EN 334:1999
For all regulators with flange connections with the same nominal size at inlet and outlet, the nominal sizes
and the face-to-face dimensions given in Table 1 are recommended.
Alternatively, the nominal sizes and the face-to-face dimensions may be taken from Table 2.
Flangeless regulators (regulators that have no line flanges but are intended to be installed by clamping
between pipes flanges) are permitted as an alternative. In this case regulators should have the same
nominal size at inlet and outlet and face-to-face dimensions should be taken from Table 3 or Table 4.
The following regulators are permitted:
— those with different nominal inlet and outlet diameters;
— those with face-to-face dimensions differing from those given in Table 1 and Table 2;
— angle pattern bodies in accordance with ISO 5752.
For regulators with DN > 400, face-to-face dimensions are not specified.
Table 1 — Recommended face-to-face dimensions for flanged regulators
Nominal size Nominal pressure Limit deviations for
PN 10/16/20a PN 25/40/50 PN 110 face-to-face
DN Face-to-face dimensions in mm Dimensions in mm
25 184 197 210
40 222 235 251
50 254 267 286 ±1,5
65 276 292 311
80 298 317 337
100 352 368 394
150 451 473 508 ±2,5
200 543 568 610
250 673 708 752
300 737 775 819
±3,5
350 889 927 972
400 1 016 1 057 1 108
Source: Table 1 of IEC 534-3:1976 (nominal pressure in accordance with ISO 7005).
a In some countries the group PN 10/16/20 includes also PN 6.
© BSI 05-2001 19
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
4.2 Materials
4.2.1 Chemical resistance requirements
The materials used in the construction of a regulator shall be chemically resistant to the fuel gases listed
in clause 1 and to the additive substances normally used for odorization and conditioning of gases.
Furthermore, the materials shall be resistant to the permissible impurities in the gas.
20 © BSI 05-2001
EN 334:1999
where
A = elongation after fracture in accordance with EN ISO 898-1.
For pzul k 16 bar and DN k 50 fasteners with properties class 12.9 in accordance with
EN ISO 898-1 may be used.
b) compression fittings
For these parts the materials shall have a percentage of elongation greater than or equal to 8 % after
fracture at an ambient temperature, in accordance with the relevant standard.
The internal components of regulators not subjected to differential pressure, may be constructed of either
the materials given in Table 5, without taking into account the restrictions for pressures and nominal sizes,
or of different materials provided they comply with the requirements of this European Standard.
Table 5 — Materials for pressure containing parts
Material Properties of Restrictions
material
Amina Maximum allowable (pzul·DN b)max DNbmax
pressure
pzulmax
% bar bar · mm mm
Rolled and forged steel 16 100 — —
Cast steel 15 100 — —
Spheroidal graphite cast 7 20 1 500 1 000
iron 15 50 5 000 300
Malleable cast iron 6 20 1 000 100
Grey cast iron c 10 1 500 1 000
Copper-zinc wrought alloys 15 100 — 25
Copper-tin and 5 20 1 000 100
copper-zinc cast alloys 15 100 — 25
Aluminium wrought alloys 4 20 — 50
7 50 50
7 100 25
Aluminium cast alloys 1,5 10 250 150
4 20 1 600 1 000
NOTE Some countries or purchasers may restrict the use of some of the materials listed above.
a A = percentage elongation after fracture (according to the applicable standard relevant to the chosen material).
b For the bodies of pilots or fixtures this term shall refer to their inlet connections.
c Minimum tensile strength 200 N/mm2.
© BSI 05-2001 21
EN 334:1999
4.2.2.2 With minimum operating temperature down to –20 °C and allowable pressure pzul > 25 bar
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
In addition to the requirements of 4.2.2.1, the following supplementary requirements with respect to
resilient properties in accordance with EN 10045-1 shall be applied to bodies, bonnets, casings of actuators
and blind flanges made of rolled, forged and cast steel or spheroidal cast iron:
— for carbon steel the Charpy-V strength shall be at least:
— 27 J as an average of three test pieces; and
— 20 J as minimum individual value;
at a temperature of p20 °C; or:
— 17,6 J as an average of three test pieces; and
— 13,6 J as minimum individual value;
at a temperature not higher than p45 °C;
— for spheroidal cast iron the Charpy-V strength shall be at least:
— 12 J as an average of three test pieces; and
— 9 J as minimum individual value;
at a temperature of p20 °C.
The above data may be obtained in two ways:
— actual test in accordance with EN 10045-1; or
— technical data sheet for the material (relevant standard or test certificate from the manufacturer or
test laboratory).
Wrought and cast aluminium alloys may be used if the ultimate tensile strength is less than or equal
to 350 N/mm2.
The above supplementary requirements do not apply to austenitic stainless steel, copper-zinc and
copper-tin-alloys.
For pzul k 25 bar the above supplementary requirements may be included in the order specification.
Additional requirements with respect to resilient properties for bolts, screws and studs may be included in
the order specification.
Additional requirements with respect to resilient properties for bodies, bonnets, casings of actuators and
blind flanges at p20 °C or p45 °C may be included in the order specification.
4.2.2.3 Manufacturing
Materials used in the construction of a regulator shall conform to the requirements of the relevant
standards for manufacturing, chemical composition, heat treatment and mechanical properties. The
manufacturer shall select standards for these materials that meet the requirements of this European
Standard and state them in the relevant documentation (see clause 8).
Fabrication welds in all pressure containing parts shall be made using qualified procedures, carried out by
qualified welders or welding operators according to EN 288-1, EN 288-2, EN 288-3, EN 287-1, EN 287-2
and EN 1418 respectively.
In addition, for fabrication welds to make bodies (including blind flanges, bonnets and actuator casings):
— only full penetration welds shall be used;
— weld fabrication and heat-treatment shall comply with the ASME Boiler and Pressure Vessel Code,
Section VIII, division I (If equivalent national standards exist that cover all relevant aspects they may
be used instead. Where equivalent ISO or EN standards are available that cover all relevant aspects they
shall be applied).
These additional requirements are not applicable to seal or attachment welds or welds in accessories.
4.2.2.4 Non-destructive testing (NDT)
Steel bodies shall be non-destructively tested in accordance with Table 5a and Table 5b.
Additional non-destructive testing may be specified in the order specification.
22 © BSI 05-2001
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001
Table 5a — Non-destructive testing
23
EN 334:1999
EN 334:1999
In the case of random inspection, if a casting, forging or weld does not conform to the acceptance criteria,
a further inspection sample of twice the original sample size from the production batch shall be examined.
If one of these castings, forgings or welds fails, the examination shall be extended to all castings, forgings
or welds in the production batch.
Any casting, forging or weld that does not conform to the acceptance criteria shall be repaired according to
an applicable procedure and then re-examined.
24 © BSI 05-2001
EN 334:1999
Parts in which there is no specific safety device to prevent a pressure increase up to pemax shall comply
with 4.3.2.1.
For markings see clause 9.
4.3.3 Minimum values of safety factor
The values listed in Table 6 shall be used to limit the stresses in the walls of pressure containing parts at
the design pressure.
© BSI 05-2001 25
EN 334:1999
5 Functional requirements
5.1 General
5.1.1 Mounting position
The regulator shall be capable of meeting the performance requirements of this European Standard in all
of the mounting positions specified by the manufacturer.
5.1.2 Sound emission
On request in the order specification, the sound pressure level LpA of the regulator shall be given for the
operating conditions for which it has been ordered if the expected LpA of the regulator exceeds 70 dB.
The operating conditions are directly related to:
— the inlet pressure;
— the outlet pressure;
— the volumetric flow rate;
— the type of gas.
On request in the order specification, the manufacturer shall also supply the following information for
specified operating conditions:
— the likely spectral octave band of the noise level with centre frequencies of 500 Hz through
to 8 000 Hz;
— sound pressure level below 70 dB.
With reference to the wide variety of different operating conditions and data, it may be appropriate to
determine the noise level by calculation.
— Measured sound pressure level: the declared LpA shall be measured in accordance with 7.2.6.4.6 and
shall be related to the points of measurement indicated in Figure 7 at the same height as the regulator;
— Calculated sound pressure level: the declared LpA shall be calculated using a method established by
the manufacturer.
The accuracy of the sound pressure measurement or the calculated sound pressure level shall be given and
shall not exceed 5 dB.
26 © BSI 05-2001
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
where
I0 is the distance between any two points on a pressure containing part before applying the test
pressure;
I is the distance between the same points after releasing the test pressure.
5.2.2 External tightness
The pressure containing parts and all connecting joints shall be leak-proof in accordance with Table 13
when tested in accordance with 7.2.5.
The tightness of pressure containing parts including those of measuring and test points, which may be
dismantled for servicing, adjustment or conversion shall be achieved by mechanical means (e.g. metal to
metal joints, o-rings, gaskets, etc.). All jointing compounds, such as liquids and pastes, shall not be used.
Jointing compounds, however, may be used for permanent assemblies and shall remain effective under
normal operating conditions.
Pressure containing parts not intended to be dismantled during servicing, adjustment or conversion shall
be sealed by means which will show evidence of interference (e.g. lacquer).
5.2.3 Internal sealing
The control member in its closed position shall seal in accordance with the appropriate requirements of
7.2.6.3 or 7.2.6.4.3.
Internal walls and connecting joints which are subjected to inlet pressure shall have a tightness in
accordance with the appropriate requirements of 7.2.6.3 or 7.2.6.4.3.
© BSI 05-2001 27
EN 334:1999
The same type of regulator may have different accuracy classes depending on the set range Wh and/or the
inlet pressure range bpe.
5.3.1.2 Hysteresis
The hysteresis is included in the accuracy class and shall be declared by the manufacturer if requested in
the order specification.
5.3.2 Lock-up behaviour
5.3.2.1 Lock-up pressure classes
Regulators shall conform to lock-up pressure requirements relevant to the declared class(es) chosen from
Table 8.
Table 8 — Lock-up pressure classes
Lock-up pressure class Permissible positive regulation change within the lock-up pressure
zone
SG 2,5 2,5 %a
SG 5 5 %a
SG 10 10 %
SG 20 20 %
SG 30 30 %
SG 50 50 %
a but not lower than 1 mbar.
The same type of regulator may have different lock-up pressure classes depending on the specified set
range Wh and/or the inlet pressure range bpe.
5.3.2.2 Classes of lock-up pressure zone
Regulators shall conform to lock-up pressure zone requirements relevant to the declared class(es) chosen
from Table 9.
Table 9 — Lock-up pressure zone classes
Class of lock-up pressure zone Limit value of the lock-up pressure zone as a percentage
of Qmin,pe to Qmax,pe
SZ 2,5 2,5 %
SZ 5 5%
SZ 10 10 %
SZ 20 20 %
Within the lock-up pressure zone the regulator need not comply with 5.3.3.
28 © BSI 05-2001
EN 334:1999
The same type of regulator may have different classes of the lock-up pressure zone depending on the set
range Wh and/or the inlet range bpe.
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure 8 — Flow behaviour of a regulator with the control member in a fixed position
6.2 Sizing equations for the calculation of volumetric flow rates of a gas pressure regulator with its control
member in its mechanically fully open position
6.2.1 Normal calculations
Volumetric flow rates should be calculated using the sizing equations of EN 60534-2-2.
© BSI 05-2001 29
EN 334:1999
6,79 pe – pa
Q = ---------------------------------- C g ( p e + p b )sin K 1 ------------------ (3)
d ( t e + 273 ) p e + pb deg
6,79
Q = ---------------------------------- C g ( p e + p b ) (4)
d ( t e + 273 )
where
Cg = flow coefficient;
d = relative density (air = 1, non dimensional value);
K1 = body shape factor;
pb = ambient atmospheric pressure in bar (absolute value);
te = gas temperature at the inlet of the regulator under test in °C.
13,57
Q = ---------------------------------- C g ( p a + p b ) ( p e – p a ) (5)
d ( t e + 273 )
b) critical flow behaviour, where (pe – pa) > 0,5 (pe + pb):
6,79
Q = ---------------------------------- C g ( p e + p b ) (6)
d ( t e + 273 )
Conversion of the flow coefficients may be carried out by making reference to EN 60534-2-2.
13,57 -
NOTE the expression ---------------------------------- C is also known as KG.
d t e + 273 g
30 © BSI 05-2001
EN 334:1999
The relationship between flow coefficient and the position of the control member is usually represented
diagrammatically (see Figure 9). Flow coefficients are usually expressed as a percentage of the flow
coefficient at fully open position and the position of the control member as a percentage of the maximum
travel (limit imposed by a mechanical stop). Figure 9 gives examples of the inherent flow characteristics of
three different types of regulator.
6.5 Calculation of volumetric flow rates for partially open gas pressure regulators
Volumetric flow rates for regulator positions between closed and fully open shall be calculated using the
equations given in 6.2, but by using the percentage of the flow coefficient at fully open position associated
with a given percentage of the valve travel as detailed in 6.4.
7 Testing
7.1 Types of tests
7.1.1 General
Table 10 gives an overview of the different types of tests that are described in this chapter and correlates
them to the test methods and various requirements detailed in 7.2.
© BSI 05-2001 31
EN 334:1999
Table 10 — Summary of types of tests and relevant test methods and requirements
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
32 © BSI 05-2001
EN 334:1999
The number and types of a series of regulators to be subjected to a type test shall be selected according to
the following requirements:
— one regulator for each type of fixture and/or pilot;
— two sizes from a series of up to six sizes and three sizes from series greater than six in number;
— one regulator for each accuracy class AC, if necessary;
— if the series of regulators includes sizes of regulators with more than one valve seat diameter, the test
sample shall have the largest valve seat installed.
The check in accordance with 7.2.6.4.5 shall only be carried out on one test sample.
7.1.4 Manufacturer’s tests
The following tests and verifications shall be carried out by the manufacturer on each regulator during the
manufacturing process:
— shell strength test in accordance with 7.2.4;
— external tightness test in accordance with 7.2.5;
— check of internal sealing, setting and lock-up pressure in accordance with 7.2.6.3.
The tests or verifications shall also confirm that the materials, dimensions and the external conditions of
each regulator remain in conformity with the results of the type test.
7.1.5 Surveillance
These tests and verifications shall be carried out under the responsibility of the interested party or parties
in order to confirm continuing conformity.
The tests and verifications shall include:
— verification of the manufacturer’s test records;
— verification of drawings and material certificates;
— verification of markings;
— dimensional check and visual inspection in accordance with 7.2.1;
— material check in accordance with 7.2.2;
— shell strength in accordance with 7.2.4;
— external tightness test in accordance with 7.2.5;
— check of internal sealing, lock-up pressure class and simplified test procedure for accuracy class in
accordance with 7.2.6.3.
7.2 Test and verification methods
7.2.1 Dimensional check and visual inspection
These are the actions to assess:
— the dimensional conformity of pressure containing parts with the applicable drawings;
— the compliance of the regulator construction with the pertinent assembly drawing and the
construction requirements of this European Standard.
7.2.2 Materials check
These are the actions to assess the compliance of the materials used or prescribed in 4.2:
— the verification of the materials used shall be carried out by the review of the material certificates;
— the verification of the materials prescribed shall be carried out by the review of the materials bill.
© BSI 05-2001 33
EN 334:1999
Verification is made by proving the compliance of the actual safety factors with those specified in 4.3.3 and
the compliance of thicknesses shown in drawings with values specified in the strength calculations.
Actual safety factors are obtained through one of the following three ways:
— strength calculation report according to applicable standards;
— hydrostatic pressure test applied until the first sign of yielding or failure becomes apparent in any
component and verification that the limit pressure pl at which the first sign of yielding or failure becomes
apparent is:
— pl U pd × Sb for the regulator body only;
— pl U pd × S for other components;
— hydrostatic pressure test and verification that permanent deformations do not exceed the values
stated in 5.2.1 up to the following test pressures:
— 0,9 pd × Sb for the regulator body only;
— 0,9 pd × S for other components.
The test is carried out in such a manner that deformations of the test sample in all directions are possible.
There shall be no additional stresses due to bending and/or torque and/or tension.
Forces from fastening systems shall be of the same nature as those experienced under normal installation
conditions.
Regulator bodies and pressure containing parts manufactured from different materials may be pressure
tested separately.
Special high strength clamping bolts and nuts may be used for hydrostatic testing.
Diaphragms used as pressure containing parts in chambers subjected, or that can be subjected to, a
maximum differential pressure pmax shall withstand a test pressure (in bar) of at least:
— 0,3 if pmax < 0,15;
— 2 pmax if 0,15 k pmax < 5;
— 1,5 pmax but at least 10, if pmax U 5.
7.2.4 Shell strength test
Pressure containing parts and the ones that become pressure containing parts in case of a diaphragm or
differential pressure seal failure shall be pressure tested. The test is carried out with water at ambient
temperature at a pressure according to the values in Table 11 for three minutes. The criteria of 5.2.1 shall
be met.
The test is carried out in such a manner that deformations of the test sample in all directions are possible.
There shall be no additional stresses due to bending and/or torque and/or tension.
Forces from fastening systems shall be of the same nature as those experienced under normal installation
conditions at least during the type test.
The test may be carried out without trim (i.e. the internal parts that are in flowing contact with the gases).
The test may also be carried out with air or nitrogen, if the necessary safety measures are taken.
Chambers separated by diaphragms are pressurized on both sides of the diaphragm at equal pressure.
34 © BSI 05-2001
EN 334:1999
Chambers subjected or that can be subjected to gas Chambers safeguarded in accordance with 4.3.2.2
pressure subjected, or that can be subjected, to a gas pressure
Test pressures
1,5 pzul 1,5 pmax
but at least pzul + 2 bar but at least pmax + 2 bar
© BSI 05-2001 35
EN 334:1999
Q d ( t e + 273 )
C g = --------------------------------------- (7)
6,79 ( p e + p b )
The Cg flow coefficient shall be assumed to be equal to the arithmetic mean of the three values.
The shape factor K1 shall be determined for at least three different operating conditions in the sub-critical
flow behaviour with:
Q d ( t e + 273 )
arcsin -------------------------------------------
6,79C g ( p e + p b )
deg (8)
K 1 = --------------------------------------------------------------------------
pe – pa
------------------
pe + pb
The shape factor K1 shall be assumed to be equal to the arithmetic mean of the three values.
For Cg and K1 values a tolerance of ±10 % is permitted.
The behaviour shall be assumed to be critical when:
pe + pb K12
------------------
- ³ --------------------------
- (9)
p a + pb K 2 – 8100
1
In the equations (7) and (8) Q is the volumetric flow rate at normal conditions of the test fluid as measured
by the flow meter 9 in Figure 14. The measured values shall be converted into values related to the normal
conditions specified in 3.2.1.2.1. The calculation of Q shall be carried out using the following equation:
pM + pb
Q = 269, 43 ----------------------- Q M (10)
t M + 273
36 © BSI 05-2001
EN 334:1999
where
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001 37
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
38 © BSI 05-2001
EN 334:1999
The compliance with performance requirements shall be checked against only three families of
performance curves for three different values of outlet pressure chosen within the set range Wh in
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
p amax – p amin
p aint = p amin + ------------------------------------
-
3
For each family of performance curves three values of inlet pressure shall be chosen within the inlet
pressure range bpe in accordance with the following criteria:
pemin
pemax
p emin + p emax
p eav = ------------------------------------
- (rounded to the nearest whole number)
2
The regulator shall be kept pressurized throughout the whole process with no interruption of this condition
until the determination of the families of performance curves is completed.
7.2.6.4.2 Determination of a performance curve and verification of the hysteresis band
With the understanding that the “actual set point” cannot be determined at the outset of this process,
the setting of the regulator shall be adjusted at:
— an inlet pressure equal to peav;
— the volumetric flow rate recommended by the manufacturer.
Changes to the setting prior to the completion of the whole process for the determination of a single
performance curve, or families of performance curves, are not permitted. The flow rate regulating valve 8
(Figure 14) shall be used to vary the volumetric flow rates. The operating time of the valve shall not be
less than the response time of the regulator as specified by the manufacturer. Volumetric flow rates
measured by the flow meter 9 (Figure 14) shall be recalculated to refer to:
— normal conditions (see 3.2.1.2.1);
— air at the reference temperature of 15 °C at the inlet of the regulator under test.
To this end the following equation shall be used:
pM + pb
Q = 15,88 ----------------------- Q M d ( t e + 273 ) (11)
t M + 273
where
pM = gas pressure at the flow meter;
QM = volumetric flow rate measured at the flow meter;
te = gas temperature in °C at the inlet of regulator under test;
tM = gas temperature at the flow meter in °C.
At least 11 different measurements conveniently distributed over the full range of values between Qmin and
Qmax (5 with volumetric flow rates increasing, 4 with volumetric flow rates decreasing, an additional
measurement at zero volumetric flow rate and one at the start setting) shall be taken for each pair of pe
and pas values.
Figure 3 is an example of a chart showing the relevant details such as the start setting, the measured
results and the performance curve for the controlled variable related to a single pair of pe and pas values.
© BSI 05-2001 39
EN 334:1999
7.2.6.4.3 Determination of the lock-up pressure and verification of the internal sealing
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
The lock-up pressure shall be determined in connection with tests carried out to determine the performance
curve of the controlled variable. The time required to reduce the volumetric flow rate to zero shall not be
less than the lock-up time of the regulator. This condition is deemed to be satisfied when the lock-up
pressure is found to be independent of the time needed to reduce the volumetric flow rate to zero
(see Figure 11).
The lock-up pressure pf shall be measured twice, after 1 min and 2 min from the regulator closure.
When the inlet pressure is greater than 16 bar the second measurement shall be taken after 5 min.
Any lock-up pressure value that can be affected by temperature variations of the fluid contained in the
volume between the regulator under test and the flow rate regulating valve, shall be recalculated and
related to the initial temperature by using the following formula:
t + 273
p f = -------------------- ( p fi + p b ) – p b (12)
t i + 273
where
pb = absolute ambient atmospheric pressure;
pfi = lock-up pressure related to the second measurement;
t = gas temperature in °C related to the first measurement;
ti = gas temperature in °C related to the second measurement.
The regulator shall be deemed leaktight if the last two lock-up pressures, corrected for the initial
temperature, are comparable (taking account of the accuracy of the measuring system) or comply with the
internal leakage rate requirements given in:
— Table 13; or
— prEN 1349 if specified in the order specification (see Annex F and Annex G).
The lock-up pressure of the regulator shall be assumed to be equal to the average of the last two measured
pressures. For lock-up pressure measurements the outlet pipework of the test rig shall have a minimum
length as specified in Figure 14.
40 © BSI 05-2001
EN 334:1999
7.2.6.4.4 Determination of the accuracy class, the lock-up pressure class, the class of lock-up pressure zone,
the maximum accuracy flow rate and the minimum flow rate related to a given range of inlet pressures
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
The determination is based on optimal enveloping of each family of performance curves with the vertical
and horizontal limit lines as shown in Figure 5. An example of an optimal enveloping procedure is shown
in Figure 12 and is described as follows:
— plot the performance curves of a family in a semilog diagram with volumetric flow rates on the decimal
scale of the abscissa and outlet pressure on the logarithmic scale of the ordinate;
— locate on this diagram, in an optimized manner, three horizontal lines spaced as shown in Figure 12;
the optimization of the location of these lines is reached when the greatest possible number of
performance requirements are met;
— identify the actual set point where the dashed horizontal line intersects the ordinate;
— ensure that Qmax,peav, Qmax,pemin, Qmax,pemax, Qmin,pemax, Qmin,peav, Qmin,pemin, AC and pf are within
the established limits.
Other equivalent optimal enveloping methods may be used.
If the performance data listed by the manufacturer are not met, the test report shall detail the actual
performance data taken from the type tests.
© BSI 05-2001 41
EN 334:1999
42 © BSI 05-2001
EN 334:1999
The connections between the regulator and the test rig pipework shall be made using concentric reducers
according to ISO 3419 or equivalent. The pressure tapping diameter b shown in Figure 13 shall be at
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
least 3 mm and shall be no larger than 12 mm or one-tenth of the nominal pipe diameter, whichever is the
lesser. The tapping shall be circular and its edge shall be clean and sharp or slightly rounded and free from
burrs or other irregularities. Any suitable method of making a physical connection is acceptable provided
the above recommendations are followed. However, fittings shall not protrude inside the pipework.
The lock-up pressure tests shall always be carried out on a test rig in which the downstream pipework has
the minimum specified length; for these tests an additional downstream volume is not permitted. The flow
meter shall be installed in accordance with the instructions of the manufacturer.
NOTE For alternative test methods under the conditions of 7.2.6.4.1 see also Annex B.
© BSI 05-2001 43
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
44
EN 334:1999
© BSI 05-2001
EN 334:1999
8 Documentation
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001 45
EN 334:1999
9 Marking
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
46 © BSI 05-2001
EN 334:1999
Annex A (informative)
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Annex B (informative)
Alternative methods for the determination of the accuracy class, the lock-up
pressure class, the maximum accuracy flow rate, the flow coefficients and the
verification of the hysteresis band
B.1 General
The following alternative test methods may be used to establish the performance classification of a
regulator or a series of regulators. The detailed procedure should be agreed with the manufacturer.
B.2 Test methods
B.2.1 Direct acting gas pressure regulator
In this type of regulator it is necessary to vary the pressure on one side of the detector element in order to
move the control member from the open position to the closed position.
The test method comprises the following steps:
— set the regulator at the minimum value of the set range Wh following the manufacturer’s instructions;
— increase the pressure in the casing of the actuator from an external source until the control member
reaches its closed position and verify the internal sealing at the minimum and maximum inlet pressures
(internally impulsed regulators may have to be modified);
— vent the pressure from the body;
— slowly reduce the pressure in the casing of the actuator until the control member reaches the required
open position (i.e the one relevant to the expected maximum accuracy flow rate) and measure the
pressure against each 10 % increase in the valve travel;
— slowly increase the pressure in the casing of the actuator until the control member reaches the lock-up
position and measure the pressure against each 10 % decrease in the valve travel;
— establish the closed position by the verification of internal sealing;
— calculate for each position of the control member the volumetric flow rate Q using the method detailed
in 6.5.
With balanced moving parts (i.e. no variation in the thrust on the moving parts against changes in inlet
pressure pe) all measured values of the pressure, except that for the closed position, should be within the
expected accuracy class AC.
The measured value of the lock-up pressure pf should be within the expected lock-up pressure class SG.
The hysteresis can be verified by measuring the maximum difference in pressure for the same position of
the control member.
The calculated value of maximum accuracy flow rate should be greater than or equal to that specified by
the manufacturer (see Figure B.1).
With unbalanced moving parts the same method should be used, with account taken of the unbalanced
thrust (see Figure B.2).
© BSI 05-2001 47
EN 334:1999
With this type of regulator it is necessary to vary the motorization pressure in the motorization chamber
in order to move the control member from the closed position to an open position and vice versa. The thrust
created by the motorization pressure is normally balanced by the load of a spring. The motorization
pressure is supplied by the pilot. The pilot controls the supply of the motorization gas according to the value
of the control deviation in such a way as to keep the outlet pressure as close as possible to its set point.
Therefore, in both a regulator and pilot with moving parts balanced (i.e. no variation in the thrust on
the moving parts with changes in inlet pressure) it is possible to classify the performance of the system
i.e. the regulator with its pilot, by measuring the variation in outlet pressure against the position of the
control member from the closed position to a specific valve travel. The test method should be established
in detail according to the specific design of the regulator.
In the following test method reference should be made to the functional diagram given in Figure B.3.
Figure B.4 shows the relationship between the valve travel, motorization pressure pm and the flow through
the process line Qf and the outlet pressure of the system pa including the regulator and its pilot.
The test method comprises the following steps:
a) set the pilot at the minimum value of the set range Wh following the manufacturer’s instructions;
b) feed the pilot from an external source using the applicable fixture at minimum inlet pressure pemin
and exhaust the gas from the chamber where both process and sensing lines are connected;
c) keep the regulator in the closed position using upstream inlet pressure. The inlet and outlet end
connections may be sealed by using blind flanges;
d) verify internal sealing of the regulator with Qf = 0 at minimum and maximum inlet pressure pe;
e) regulate the inlet pressure at pemin;
f) increase the flow Qf until the first internal flow occurs in the regulator and measure the outlet pressure
pa in the chamber where both process and sensing lines are connected (at this stage the inlet and outlet
pressures in the regulator body are balanced, because there is zero flow through the regulator);
g) by increasing the flow Qf, open the regulator until 100 % of the valve travel relevant to the maximum
accuracy flow rate Qmax,pemin has occurred and measure the outlet pressure pa against each 10 %
increase in the valve travel;
h) by decreasing the flow Qf, bring the regulator to the closed position and measure the outlet pressure
pa against each 10 % decrease in the valve travel. The closed position is verified by an internal sealing
test;
i) regulate the inlet pressure at pemax;
j) repeat the tests explained above from f) to h);
k) calculate, for each position of the control member, the volumetric flow rate Q using the method
detailed in 6.5.
With balanced moving parts (i.e. no variation in the thrust on the moving parts with changes in the inlet
pressure pe) all measured values of:
— outlet pressure pa should be within the expected accuracy class AC. The hysteresis can be verified by
measuring the maximum difference in outlet pressures pa for the same position of the control member;
— lock-up pressure pf should be within the lock-up pressure class SG and the calculated value of the
maximum accuracy flow rate should be greater than or equal to that specified by the manufacturer
(see Figure B.4).
With unbalanced moving parts the same method should be used, with account taken of the unbalanced
thrust (see Figure B.5).
48 © BSI 05-2001
EN 334:1999
For larger capacity regulators if the available volumetric flow rates do not permit the use of the method
detailed in 7.2.6.2, the following procedure may be followed:
— firstly, determine the flow coefficient for a partially open position that is compatible with the available
volumetric flow rate by using equation (7) of 7.2.6.2;
— determine the shape factor K1 applicable to the same partially open position by using equation (8)
of 7.2.6.2;
— determine the function shown in Figure B.6 at sub-critical conditions calculating Cg,x by using the
following equation:
Q d ( t e + 273 )
C g,x = -----------------------------------------------------------------------------------------
pe – pa (B.1)
6,79 ( p e + p b )sin K 1 ------------------
pe + pb
deg
These calculations should be made for three different opening positions of the control member; extrapolate
the value of Cg taken from the graph given in Figure B.6 by starting from the point in the x co-ordinate
of 100 % control member travel.
Where there is sufficient flow the previous extrapolation can be avoided by carrying out the test detailed
in the third indent with the control member at full open position.
To convert Q to normal conditions see 7.2.6.2.
For Cg and K1 values limit deviations of ±10 % are permitted.
Figure B.1 — Graph of the outlet pressure plotted against different positions of
the control member in a balanced direct acting regulator
© BSI 05-2001 49
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure B.2 — Graph of the outlet pressure plotted against different positions of
the control member in an unbalanced direct acting regulator
50 © BSI 05-2001
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001
Figure B.3 — Functional diagram of a pilot controlled regulator
51
EN 334:1999
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure B.4 — Various graphs relating to the tests detailed in B.2 for a balanced
pilot controlled regulator
52 © BSI 05-2001
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure B.5 — Various graphs relating to the tests detailed in B.2 for an unbalanced
pilot controlled regulator
© BSI 05-2001 53
EN 334:1999
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Figure B.6 — Graph of Cg values plotted against different positions of the control member
Annex C (informative)
Inspection certificate
Where an inspection certificate and declaration of conformity is provided, the following gives an example
of the format which may be used.
NOTE Inspection certificate 3.1.B according to EN 10204; Declaration of conformity according to EN 45014.
54 © BSI 05-2001
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
© BSI 05-2001
55
EN 334:1999
EN 334:1999
Annex D (informative)
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Acceptance test
This annex gives an example of a typical acceptance test which may be used if specified in the order
specification.
The tests and verifications should be carried out on the finished regulators by the manufacturer in the
presence of the purchaser’s inspector prior to shipping.
The tests are:
— dimensional check and visual inspection in accordance with 7.2.1;
— material check in accordance with 7.2.2;
— external leakage test in accordance with 7.2.5.1;
— check of internal sealing, setting and lock-up pressure class in accordance with 7.2.6.3.
Unless otherwise specified, the number of regulators selected for an acceptance test should be as follows:
— 2 regulators for batches of 2 to 4 pieces;
— 3 regulators for batches of 5 to 8 pieces;
— 4 regulators for batches of 9 to 20 pieces;
— 5 regulators for batches of 21 to 30 pieces;
— 6 regulators for batches of 31 to 60 pieces;
— 10 %5) for batches > 60 pieces.
Additional tests, if required, may be specified in the order specification.
Annex E (informative)
Conformity evaluation6)
This annex gives guidance on the procedure that may be used if third party (or in some cases second party)
certification is required.
E.1 General
The main purpose of conformity evaluation is to give the customer the necessary confidence in the
conformity of a regulator or a series of regulators with this European Standard.
For the regulators certified as in conformity with this European Standard, the manufacturer should carry
out the conformity evaluation in accordance with E.2.
For these regulators the manufacturer should also commission the conformity evaluation by a third party
in accordance with E.3.
When there is no conformity evaluation by a third party, the manufacturer may agree upon, in addition to
his evaluation, the conformity evaluation by a second party on the basis of the methods explained in E.3.
E.2 Manufacturer’s conformity evaluation
For each series of regulators the manufacturer should carry out:
— the tests as detailed in clause 7; the test samples should be selected at least as specified in E.3.3;
— a permanent internal control of production by a quality system based on the relevant standard of the
EN ISO 9000 series; the quality system should be certified by a third party.
Further, the manufacturer should retain and file:
— the material certificates for all pressure containing parts;
— the NDT reports and the inspection certificate;
for a period of at least ten years from the delivery of the regulator.
A copy of these certificates should be made available to the purchaser if requested in the purchase order.
56 © BSI 05-2001
EN 334:1999
E.3.1 Introduction
The certification body should meet the requirements of EN 45011 and establish a certification scheme for
regulators.
The certification scheme should meet the requirements of this European Standard and establish:
— if the surveillance in accordance with 7.1.5 may be carried out by the body that has certified the
quality system of the manufacturer;
— a guideline to be followed when any non-conformities are discovered during the surveillance as
detailed in 7.1.5;
— the form of the certificate of conformity.
E.3.2 Procedure
The evaluation of conformity should include:
— the type test in accordance with 7.1.2; the tests samples should be selected as detailed in E.3.3;
— a surveillance as detailed in 7.1.5 every five years; the test samples should include two regulators for
each certified series and they should be selected at random from the production population present at the
time of the surveillance visit to manufacturer’s premises.
The surveillance may be carried out by the body that has certified the quality system of manufacturer, if it
is provided for in the certification scheme for regulators.
Any other verification pertinent to the quality system of the manufacturer should be carried out by the body
that has certified the quality system.
E.3.3 Selection of test samples
The number and types of a series of regulators to be subjected to a type test should be selected according
to the following criteria:
— one regulator for each type of fixture and/or pilot;
— two sizes from a series of up to six sizes and three sizes from series greater than six in number;
— one regulator for each accuracy class AC, if necessary;
— if the series of regulators includes sizes of regulators with more than one valve seat diameter, the test
sample should have the largest valve seat installed.
The check in accordance with 7.2.6.4.5 may be carried out on only one test sample.
E.4 Issue of the certificate of conformity
If the series of regulators complies with this European Standard the third party should issue a
“certificate of conformity”.
Annex F (informative)
Seat leakage
This annex establishes a series of seat leakage classes related to the specific internal sealing requirements.
If requested in the order specification the internal sealing requirements may be in accordance with
prEN 1349. The leakage class will be included:
— on the nameplate;
— on the inspection certificate.
© BSI 05-2001 57
EN 334:1999
Annex G (informative)
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Order specification
This annex gives guidelines on the form that an order specification should take.
The ordering of gas pressure regulators, particularly for larger sizes, depends on the site conditions, other
regulators already in the grid, interchangeability and other factors. Therefore, in addition to the minimum
specifications in tenders, offers and orders other specifications as detailed in G.2 may also be required.
G.1 Minimum specifications
G.1.1 Details of construction
— direct acting/pilot controlled;
— fail open/fail close;
— integral strength/differential strength;
— built-in safety devices;
— built-in monitor;
— additional features;
— type of end connections.
G.1.2 Dimensions
— regulator size (see 3.1.1.9);
— nominal pressure PN;
— face-to-face dimensions.
G.1.3 Performance
— inlet pressure range bpe;
— allowable pressure pzul;
— set range or set point Wh/Wa/pas;
— maximum accuracy flow rate and minimum flow rate (at stable conditions and specified inlet
pressures) Qmax,pemin/Qmin,pemax;
— operating temperature range (class 1 or class 2).
G.2 Optional specifications
— prescribed/permitted materials and/or specific requirements regarding chemical resistance;
— lifting facilities;
— minimum values of flow coefficients and factors;
— accuracy class AC;
— maximum hysteresis band;
— lock-up class/lock-up pressure zone SG/SZ;
— minimum operating differential pressure pmin;
— internal sealing requirements in accordance with prEN 1349;
— sound pressure level LpA;
— likely spectral octave band;
— additional documentation;
— acceptance test in accordance with Annex D;
— copy(ies) of various certificates;
— full tests using a test rig in accordance with 7.2.6.4.7 instead of any alternative methods;
— alternative test methods in accordance with Annex B instead of those detailed in 7.2.6.4.5;
— Charpy-V strength for bolts, screws and studs under specified conditions;
— Charpy-V strength for pressure containing parts in accordance with 4.2.2.2 for pzul k 25 bar;
58 © BSI 05-2001
EN 334:1999
— Charpy-V strength for bodies, bonnets, casings of actuators and blind flanges at p20 °C or p45 °C;
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
Annex H (informative)
A-deviations
A-deviation: National deviation due to regulations, the alteration of which is for the time being outside
the competence of the CEN/CENELEC member.
This European Standard does not fall under any Directive of the EC.
In the relevant CEN/CENELEC countries these A-deviations will supersede the provisions of the
European Standard until they have been removed.
For Sweden a deviation from clauses 4.2.2.1, 4.2.2.2 and 4.2.2.3 is required, to comply with the
prescriptions of the “Ordinance AFS 1994:39 — chapter 3 — section 1”. It should be noted that the design
of pressure equipment and selection of materials must be made in accordance with the Swedish Piping
Code 1978 and Swedish Pressure Vessel Code 1987, which together with the Nordic Group for Steel
regulation (NGS-sheet) and the Swedish Material Data Sheets (SMDS-sheets) list the materials whose
evaluation, documentation and properties have been carried out in accordance with recognized (Swedish)
procedures for establishing them as pressure vessel materials. All these documents are part of the Swedish
regulatory system.
Annex J (informative)
Bibliography
EN 88, Pressure governors for gas appliances for inlet pressures up to 200 mbar.
EN 12186, Gas supply systems — Gas pressure regulating stations for transport and distribution —
Functional requirements.
© BSI 05-2001 59
BS EN
334:1999
BSI — British Standards Institution
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
Licensed Copy: sheffieldun sheffieldun, na, Sat Nov 04 01:57:11 GMT+00:00 2006, Uncontrolled Copy, (c) BSI
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
Standards are also available from the BSI website at http://www.bsi-global.com.
Information on standards
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.