Вы находитесь на странице: 1из 6

Common power

quality factors
affecting transformers
Application Note

Commercial buildings commonly within acceptable limits. Trans- • Compare actual load kVA to
have a 208/120 V transformer in formers are also critical to the nameplate kVA rating to deter-
a delta-wye configuration to integrity of the grounding system. mine % loading.
feed receptacles. Single-phase,
non-linear loads connected to Factors When using a single phase
the receptacles produce triplen analyzer on a balanced load, a
harmonics, which add up in the 1. Transformer loading (kVA) single measurement is sufficient.
neutral. When this neutral cur- Start by measuring kVA and Transformers loaded at less than
rent reaches the transformer, it is determine wether the transformer 50 % are generally safe from
reflected into the delta primary load is balanced. overheating. However, as loads
increase, measurements should
winding where it causes over- • Connect voltage probes on be made periodically. At some
heating and transformer failures. Phase 1 and Neutral and
Another transformer problem clamp current probe on same point the transformer may require
results from core loss and copper phase. Repeat for Phase 2 and derating.
loss. Transformers are normally 3.
rated for a 60 Hz phase current • Use a single phase power
load only. Higher frequency har- quality analyzer to read kVA of
monic currents cause increased each phase and sum all three
core loss due to eddy currents for total transformer kVA.
and hysteresis, resulting in more • Or, connect all four current
heating than would occur at the clamps and all five test leads
same 60 Hz current. for the three phase power
Transformers supplying non- quality analyzer to read kVA
linear loads should be checked for each phase and the total.
periodically to verify operation

ø1
Red Figure 2. Harmonic spectrum.
kVA1

2. Harmonic spectrum
The harmonic spectrum of the
secondary (load) current will give
ø2
us an idea of the harmonic orders
Red
kVA2 and amplitudes present:
• In a transformer feeding sin-
gle-phase loads, the principal
harmonic of concern is the
Black Black
N 3rd. The 3rd will add arith-
Black
metically in the neutral and
circulate in the delta primary
ø3 of a delta-wye transformer.
Red
The good news is that the
delta-wye tends to isolate the
kVA3
rest of the system from the 3rd
Unbalanced load: (though not the 5th, 7th or
kVATOTAL = kVA1 + kVA2 + kVA3
other non-triplen harmonics).
The bad news is that the
transformer pays the price
Figure 1. Measuring transformer load (unbalanced) using a single phase power quality analyzer. with additional heat.

From the Fluke Digital Library @ www.fluke.com/library


Table 1: Measurements at the distribution transformer 3. Total Harmonic Distortion
Measurement Look for Check for THD of both voltage
1. kVA Transformer loading. If loading exceeds 50 %, check for harmonics and current:
and possible need for derating. • For voltage, THD should not
2. Harmonic • Harmonic orders/amplitudes present: exceed 5 %
spectrum 3rd harmonic (single-phase loads)
5th, 7th (primarily three-phase loads)
• For current, THD should not
exceed 5-20 % (see Odd
• Resonance of higher order harmonics
• Effectiveness of harmonic trap filters Harmonics table)
3. THD Harmonic loading within limits: IEEE 519 sets limits for har-
Voltage %THD < 5 %
Current %THD < 5-20 % (Table 2)
monics at the PCC (Point of
Common Coupling) between the
4. K-factor Heating effect on transformer from harmonic loads
utility and customer (EN50160 is
5. Ground currents • Objectionable ground currents are not quantified but are
the European standard). IEEE 519
prohibited by the NEC
• Neutral-ground bond in place is based on THD measurements
• ESG (Electrical Safety Ground) connector to ground electrode taken at the PCC. Technically, the
(typically building steel) in place
PCC is the primary of the utility
supply transformer (although
there are cases where the PCC is
condition at that frequency. If at the secondary if the secondary
• In a transformer feeding three-
such a condition is detected, feeds a number of customers). In
phase loads which include
drives or UPS systems with 6- be sure to take readings at practice, these measurements are
pulse converters, the 5th and capacitor banks to see if the often made at the secondary of
7th harmonic will tend to pre- caps are experiencing overcur- the customer’s main transformer,
dominate. Excessive 5th is of rent/overvoltage conditions. since that is the point most easily
particular concern because it is • Before-and-after harmonic accessible to all parties (and also
negative sequence. It will tend spectrum measurement is since that is generally a Low
to produce counter-torque and extremely valuable to deter- Voltage measurement).
overheating in polyphase mine if harmonic mitigation Some PQ practitioners have
motors. techniques, like trap filters, broadened the concept of PCC to
which are tuned to specific include points inside the facility,
• Harmonic amplitudes normally
frequencies, are sized properly such as on the feeder system,
decrease as the frequency
goes up. If one frequency is and are working as expected. where harmonic currents being
significantly higher in ampli- • Different harmonic frequencies generated from one set of loads
tude than lower frequencies, affect equipment in different could affect another set of loads
we can suspect a resonant ways (see below). by causing significant voltage
distortion. The emphasis is on
improving in-plant PQ, rather
than on simply not affecting util-
Harmonic Sequences ity PQ.
Name F 2nd 3rd 4th 5th 6th 7th 8th 9th
Frequency 60 120 180 240 300 360 420 480 540
3a. Voltage THD
THD has a long history in the
Sequence + — 0 + — 0 + — 0
industry. The underlying concept
Rule: If waveforms are symmetrical, even harmonics disappear. is that harmonic currents gener-
ated by loads will cause voltage
Effects of Harmonic Sequences distortion (E=IZ) as they travel
Sequence Rotation Effects (from skin effect, eddy currents, etc.) through the system impedance.
Positive Forward Heating of conductors, circuit breakers, etc. This voltage distortion then
Negative Reverse Heating as above + motor problems becomes the carrier of harmonics
Zero None Heating, + add in neutral of 3-phase, 4-wire system system-wide: if, for example, the
distorted voltage serves a linear
Harmonics are classified as follows:
1. Order or number: Multiple of fundamental, hence, 3rd is three times the fundamental, or load like a motor, it will then cre-
180 Hz. ate harmonic currents in that
2. Odd or even order: Odd harmonics are generated during normal operation of nonlinear linear load. By setting maximum
loads. Even harmonics only appear when there is dc in the system. In power circuits, this
only tends to occur when a solid state component(s), such as a diode or SCR, fails in a
limits for voltage distortion, we
converter circuit. set limits for the system-wide
3. Sequence: impact of harmonics.
• Positive sequence. Main effect is overheating.
• Negative sequence. Create counter-torque in motors, i.e., will tend to make motors go
backwards, thus causing motor overheating. Mainly 5th harmonic.
• Zero sequence. Add in neutral of 3-phase, 4-wire system. Mainly 3rd harmonic.

2 Fluke Corporation Common power quality factors affecting transformers


Table 2: IEEE 519 limits for harmonic currents at the point of The SCR (Short Circuit Ratio) is
common coupling (All percentages are % of IL, maximum demand load current) a measure of the electrical size of
Odd Harmonics the customer in relation to the
SCR=Isc/IL <11 11-17 17-23 23-35 >35 TDD utility source. The smaller the
<20 4.0 % 2.0 % 1.5 % 0.6 % 0.3 % 5.0 % customer (higher SCR), the less
20-50 7.0 % 3.5 % 2.5 % 1.0 % 0.5 % 8.0 %
the potential impact on the utility
50-100 10.0 % 4.5 % 4.0 % 1.5 % 0.7 % 12.0 %
source and the more generous
the harmonic limits. The larger
100-1000 12.0 % 5.5 % 5.0 % 2.0 % 1.0 % 15.0 %
the customer (smaller SCR), the
>1000 15.0 % 7.0 % 6.0 % 2.5 % 1.4 % 20.0 %
more stringent the limits on har-
SCR = Short circuit ratio (Isc/IL) monic currents.
Isc = Available short circuit current at PCC
IL = Maximum demand load current (rms amps) 3c. TDD and THD
TDD = Total demand distortion
TDD (Total Demand Distortion) is
Note: IEEE allows these limits to be exceeded for up to one hour per day, while IEC allows
them to be exceeded for up to 5 % of the time.
the ratio of the current harmonics
The concept of IL, maximum demand load current, is key to using Table 2. For existing facili-
to the maximum load (IL). It dif-
ties, IL is calculated by averaging the maximum demand current for 12 consecutive months fers from THD in that THD is the
(information available in billing records). For new installations, IL must be estimated. ratio of harmonics to the instan-
Transformer rating could be used and would be the most conservative estimate (i.e., it would taneous load. Why TDD instead
result in the lowest SCR), since it assumes that the transformer would be used at full capacity.
of THD? Suppose you were run-
ning a light load (using a small
fraction of system capacity), but
Voltage distortion, however, For equipment manufacturers, those loads were nonlinear. THD
depends on source impedance, IEC 1000-3-2, published in 1995, would be relatively high, but the
i.e., on system capacity. It was is the applicable standard. It harmonic currents actually being
quite possible for the first (or sec- specifies maximum current levels generated would be low, and the
ond or third) customer to inject out to the 40th harmonic. Its effect on the supply system
significant harmonic currents into expected effective date is pro- would in fact be negligible. So
the system and not cause voltage jected to be early 2001. To certify who cares? TDD acknowledges
THD to exceed 5 %. The entire for CE, a requirement for the this, and allows harmonic load to
responsibility for harmonic miti- European market, manufacturers be referenced to the maximum
gation could fall on the last will have to meet this standard. load: if harmonic load is high at
customers unlucky enough to This edict will have a major effect maximum load, then we have to
push V-THD over 5 %, even if on power supply design. watch out for the effect on the
their particular harmonic load For the facility, IEEE 519 is the supply source. So where does
was relatively small-literally the standard (EN 50160 in Europe). that leave current THD as a useful
straw that broke the camel’s The limits set in IEEE 519 for measurement. The closer the cur-
back. harmonic currents depend on the rent THD reading(s) is taken to
size of the customer relative to the conditions of maximum load, the
3b. Current THD
system capacity. (See Table 2.) closer it approximates TDD.
To restore some fairness to this
situation, standards for maximum
current harmonics were added,
since current harmonics were Table 3
under the control of the local Inspection of Transformer Ground Explanation
facility and equipment manufac- Check for N-G bond. A high impedance N-G bond will cause
turer (remember, harmonic voltage fluctuation.
“loads” act as “generators” of har- Check for grounding conductor and Fault currents will return to the source via
integrity of connection to building steel these connections, so they should be as low
monics). This emphasis on the (exothermic weld). impedance as possible.
mitigation of current harmonics at Check for tightness of all If the conduit is not itself grounded, it
the load, including the not-too- conduit connections. will tend to act as a “choke” for higher
distant requirement that the load frequencies and limit fault current
generate virtually no harmonics, (remember that fault currents are not just
at 60 Hz but have high-f components).
has become the prevailing regu-
Measure for ground currents on the Ideally there should be none, but there will
latory philosophy. It puts the grounding conductor. always be some ground current due to
burden of responsibility on the normal operation or leakage of protective
local site and on the equipment components (MOVs, etc.) connected from
phase or neutral to ground. However,
manufacturers. anything above an amp should be cause
for suspicion (there is no hard and fast rule,
but experienced PQ troubleshooters develop
a feel for possible problems).

3 Fluke Corporation Common power quality factors affecting transformers


A final word on measuring standard trade sizes of K-4, K-13, Transformer grounding
THD: the one place not to apply K-20, K-30, etc. K-13 is a com- The proper grounding of the
the specs is at the individual har- mon rating for a transformer transformer is critical. (Table 3.3.)
monic-generating load. This will supplying office loads. The higher NEC Article 250 in general and
always be a worst-case distortion ratings tend to be packaged into 250-26 in particular address the
and a misleading reading. This is PDUs (Power Distribution Units) grounding requirements of the
because as harmonics travel which are specially designed to SDS.
upstream, a certain amount of supply computer and other PQ- • A ground reference is estab-
cancellation takes place (due to sensitive installations. lished by a grounding
phase relationships which, for connection, typically to build-
5. Ground currents
practical purposes, are unpre- ing steel (which, in turn, is
Two prime suspects for excessive
dictable). Measure at a PCC, or at required to be bonded to all
ground current are illegal N-G
the source transformer. cold water pipe, as well as
bonds (in subpanels, receptacles
any and all earth grounding
4. K-factor or even in equipment) and so-
electrodes). Bonding should be
K-factor is a specific measure of called isolated ground rods:
by exothermic weld, not
the heating effect of harmonics in • Subpanel N-G bonds create a clamps that can loosen over
general and on transformers in parallel path for normal return
time. The “grounding electrode
particular. It differs from the THD current to return via the
conductor” itself should have
calculation in that it emphasizes grounding conductor. If the
as low a high-frequency
the frequency as well as the neutral ever becomes open, the
impedance as possible (not
amplitude of the harmonic order. equipment safety ground
least because fault current has
This is because heating effects becomes the only return path;
high frequency components).
increase as the square of the fre- if this return path is high
Wide, flat conductors are pre-
quency. impedance, dangerous voltages
ferred to round ones because
A K-4 reading would mean could develop.
they have less inductive reac-
that the stray loss heating effects • Separate isolated ground rods tance at higher frequencies.
are four times normal. A standard almost always create two
For the same reason, the dis-
transformer is, in effect, a K-1 ground references at different
tance between the “grounding
transformer. As with THD, it is potentials, which in turn
electrode conductor connection
misleading to make a K-factor causes a “ground loop” current
to the system” (i.e., N-G bond
reading at the load or receptacle to circulate in an attempt to
at the transformer) and the
because there will be a certain equalize those potentials. A
grounding electrode (building
amount of upstream cancellation; safety and equipment hazard is
steel) should be as short as
transformer K-factor is what also created: in the case of
possible: in the words of the
counts. Once the K-factor is lightning strikes, surge currents
Code, “as near as practicable
determined, choose the next travelling to ground at different
to and preferably in the same
higher trade size. K-factor rated earth potentials will create
area...”
transformers are available in hazardous potential differences.
• The neutral and ground should
be connected at a point on the
480 V
transformer neutral bus.
Although permitted, it is not
advisable to make the N-G
bond at the main panel, in
order to maintain the segrega-
tion of normal return currents
and any ground currents. This
point at the transformer is the
only point on the system
where N-G should be bonded.

Grounding electrode nearby,


preferably structural metal

208 Y/120 V

Neutral

Figure 3. Transformer grounding.

4 Fluke Corporation Common power quality factors affecting transformers


Solutions

There are a number of solutions • A new ground reference is


for transformer-related PQ established. Part of the defini-
problems: tion of the SDS is that it “has
• Install additional distribution no direct electrical connection,
transformers (Separately including a solidly connected
Derived Systems) grounded circuit conductor, to
• Derate transformers supply conductors originating
• Install K-rated transformers in another system.” (NEC 100)
• Used forced air cooling The opportunity exists to seg-
1. Separately Derived System regate the subsystem served
(SDS) by the SDS from ground loops
The distribution transformer is and ground noise upstream
the supply for a Separately from the SDS, and vice versa.
Derived System (SDS), a term 2. K-rated transformers
which is defined in the NEC
(Article 100). The key idea is that
the secondary of this transformer
is the new source of power for all
its downstream loads: this is a
powerful concept in developing a
PQ distribution system. The SDS
accomplishes several important
objectives, all beneficial for PQ:
frequency. For example, a 3rd
• It establishes a new voltage harmonic current will have
reference. Transformers have
nine times the heating effect
taps which allow the second-
as the same current at the fun-
ary voltage to be stepped up
damental.
or down to compensate for
any voltage drop on the feed- • Skin effect. As frequency
Figure 4. Typical K-factor in commercial increases, electrons migrate to
ers.
building. the outer surface of the con-
• It lowers source impedance by ductor. More electrons are
decreasing, sometimes drasti- Harmonics cause heating in using less space, so the effec-
cally, the distance between transformers, at a greater rate tive impedance of the
the load and the source. The than the equivalent fundamental conductor has increased; at
potential for voltage distur- currents would. This is because the higher frequency, the con-
bances, notably sags, is of their higher frequency. There ductor behaves as if it were a
minimized. are three heating effects in trans- lower gauge, lower ampacity,
• It achieves isolation. Since formers that increase with higher impedance wire.
there is no electrical connec- frequency:
tion, only magnetic coupling, The industry has responded
between the primary and sec-
• Hysteresis. When steel is with two general solutions to the
magnetized, magnetic dipoles
ondary, the SDS isolates its effects of harmonics on trans-
all line up, so that the North
loads from the rest of the elec- formers: install a K-factor rated
poles all point one way, the
trical system. To extend this transformer or derate a standard
South poles the other. These
isolation to high frequency dis- transformer. Let’s look at pros
poles switch with the polarity
turbances, specially and cons of the K-factor approach
of the applied current. The
constructed “isolation trans- first. K-factor is a calculation
higher the frequency, the more
formers” provide a shield based on the rms value, %HD
often the switching occurs,
between the primary and sec- (harmonic distortion) of the har-
and, in a process analogous to
ondary to shunt RF (radio monic currents, and the square of
the effects of friction, heat
frequency) noise to ground. the harmonic order (number). It is
losses increase.
Otherwise, the capacitive cou- not necessary to actually perform
pling between primary and
• Eddy currents. Alternating the calculation because a har-
magnetic fields create localized
secondary would tend to pass monic analyzer will do that for
whirlpools of current that cre-
these high-frequency signals you. The important thing to
ate heat loss. This effect
right through. understand is that the harmonic
increases as a square of the

5 Fluke Corporation Common power quality factors affecting transformers


order is squared in the equation 3. Derating standard Transformer Capacity (%)
and that is precisely where the transformers After Derating for
high- frequency heating effects, Electronic Load

like eddy current losses, are Some facilities managers use a 100

taken into account. 50 % derating as a rule-of-thumb 80


K-rated transformers are for their transformers serving 60
designed to minimize and accom- single-phase, predominantly
40
modate the heating effects of nonlinear loads. This means that
20
harmonics. K-rated transformers a 150 kVA transformer would
do not eliminate harmonics only supply 75 kVA of load. The 0
0 20 40 60 80 100
(unless additional elements like derating curve, taken from IEEE Switched-Mode Power Supply Load (% of Overall Load)
filters are added). They accom- 1100-1992 (Emerald Book),
modate harmonics with shows that a transformer with
techniques such as the use of a 60 % of its loads consisting of Figure 5. Transformer derating curve (IEEE 1100-1992)
number of smaller, parallel wind- SMPS (switched-mode power
ings instead of a single large supplies), which is certainly
possible in a commercial office the higher the CF. If the CF were
winding: this gives more skin for 2.0, then the xHDF=1.414 / 2
the electrons to travel on. The building, should in fact be
derated by 50 %. =.71. A CF=3 gives us an xHDF
primary delta winding is up-sized =.47. A wave with CF=3 is about
to tolerate the circulating third The following is an accepted
method for calculating trans- as badly distorted a current
harmonic currents without over- waveform as you can expect to
heating. The neutral on the former derating for single-phase
loads only. It is based on the very see on a single-phase distribution
secondary is also up-sized for transformer.
third harmonics (typically sized atreasonable assumption that in Caution: This method does not apply to
twice the phase ampacity). single-phase circuits, the third transformers feeding three-phase loads,
harmonic will predominate and where harmonics other than the third tend to
cause the distorted current wave- predominate and CF is not useful as a simple
Application issues with predictor of the amount of distortion. A calcu-
K-factor transformers form to look predictably peaked. lation for three-phase loads is available in
Use a true-rms meter to make ANSI/IEEE C57.110. However, there is some
K-rated transformers have been these current measurements: controversy about this calculation since it
widely applied, but there are cer- 1. Measure rms and peak current may underestimate the mechanical resonant
vibrations that harmonics can cause, and that
tain issues with them. Many of each secondary phase. accelerate transformer wear above and
consultants do not see the need (Peak refers to the instanta- beyond the effects of heat alone.
for using transformers with a rat- neous peak, not to the inrush
ing higher than K-13 although or “peak load” rms current). 4. Forced air cooling
K-20 and higher might be sup- 2. Find the arithmetic average of
the three rms readings and the If heat is the problem, cooling is
plied as part of an integrated
three peak currents and use the solution. Break out the fan,
Power Distribution Unit (PDU).
this average in step 3 (if the turn it on the transformer and use
Also, early applications some-
load is essentially balanced, forced air cooling. Some experi-
times overlooked the fact that
this step is not necessary). enced hands figure that’s worth
K-rated transformers necessarily
20-30 % on the up side. In any
have a lower internal impedance. 3. Calculate Xformer Harmonic
Derating Factor: case, it can only help.
Whereas a standard transformer
has an impedance typically in the xHDF = (1.414 * IRMS) / IPEAK
4. Or, since the ratio of
5-6 % range, K-rated transform-
Peak/RMS is defined as Crest
ers can go as low as 2-3 % Factor, this equation can be
(lower as the K-rating increases). rewritten as: Fluke. Keeping your world
In retrofit situations, where a xHDF = 1.414 / CF up and running.
standard transformer is being If your test instrument has the
replaced by a K-rated transformer capability, measure the CF of
of equivalent kVA, this may each phase directly. If the load Fluke Corporation
require new short circuit calcula- is unbalanced, find the aver- PO Box 9090, Everett, WA USA 98206
tions and re-sizing of the age of the three phases and Fluke Europe B.V.
secondary overcurrent protective PO Box 1186, 5602 BD
use the average in the above Eindhoven, The Netherlands
devices. formula.
For more information call:
Since a sine wave current In the U.S.A. (800) 443-5853 or
waveform has a CF=1.414, it will Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
have an xHDF=1; there will be Fax (31 40) 2 675 222
no derating. The more the 3rd In Canada (800) 36-FLUKE or
harmonic, the higher the peak, Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 10/2004 2403202 A-US-N Rev A
6 Fluke Corporation Common power quality factors affecting transformers

Вам также может понравиться