Академический Документы
Профессиональный Документы
Культура Документы
quality factors
affecting transformers
Application Note
Commercial buildings commonly within acceptable limits. Trans- • Compare actual load kVA to
have a 208/120 V transformer in formers are also critical to the nameplate kVA rating to deter-
a delta-wye configuration to integrity of the grounding system. mine % loading.
feed receptacles. Single-phase,
non-linear loads connected to Factors When using a single phase
the receptacles produce triplen analyzer on a balanced load, a
harmonics, which add up in the 1. Transformer loading (kVA) single measurement is sufficient.
neutral. When this neutral cur- Start by measuring kVA and Transformers loaded at less than
rent reaches the transformer, it is determine wether the transformer 50 % are generally safe from
reflected into the delta primary load is balanced. overheating. However, as loads
increase, measurements should
winding where it causes over- • Connect voltage probes on be made periodically. At some
heating and transformer failures. Phase 1 and Neutral and
Another transformer problem clamp current probe on same point the transformer may require
results from core loss and copper phase. Repeat for Phase 2 and derating.
loss. Transformers are normally 3.
rated for a 60 Hz phase current • Use a single phase power
load only. Higher frequency har- quality analyzer to read kVA of
monic currents cause increased each phase and sum all three
core loss due to eddy currents for total transformer kVA.
and hysteresis, resulting in more • Or, connect all four current
heating than would occur at the clamps and all five test leads
same 60 Hz current. for the three phase power
Transformers supplying non- quality analyzer to read kVA
linear loads should be checked for each phase and the total.
periodically to verify operation
ø1
Red Figure 2. Harmonic spectrum.
kVA1
2. Harmonic spectrum
The harmonic spectrum of the
secondary (load) current will give
ø2
us an idea of the harmonic orders
Red
kVA2 and amplitudes present:
• In a transformer feeding sin-
gle-phase loads, the principal
harmonic of concern is the
Black Black
N 3rd. The 3rd will add arith-
Black
metically in the neutral and
circulate in the delta primary
ø3 of a delta-wye transformer.
Red
The good news is that the
delta-wye tends to isolate the
kVA3
rest of the system from the 3rd
Unbalanced load: (though not the 5th, 7th or
kVATOTAL = kVA1 + kVA2 + kVA3
other non-triplen harmonics).
The bad news is that the
transformer pays the price
Figure 1. Measuring transformer load (unbalanced) using a single phase power quality analyzer. with additional heat.
208 Y/120 V
Neutral
like eddy current losses, are Some facilities managers use a 100