Вы находитесь на странице: 1из 24

H

SR.NO DESCRIPTION

[A] HVAC System HIGH SIDE

1.0 EQUIPMENTS
Supply of Ceiling Suspended Chilled Water Fan Coil Type Units, complete with 3/4 Row Chilled Water Coils wit
coils to be tested for 21 bar max, dynamically balanced low noise type centrifugal section, multi speed single p
capacitor, automatic thermal protector with standard opening on the winding, resilient mounts , washable typ
of 60% or EU-1 filter levels. Unit casing shall be of Galvanized corrosion resistant / powder coated with interna
foam, External insulation of 3mm thick insulating foam, 4 way diffusion with adjustable blades. Fresh air intak
dia with self adjusting damper module, inbuilt condensate drain pump, insulated drain tray with injected poly
1.2 etc. Units shall be factory fitted with valve package comprising of 2/3 way motorized valve Siemens (Landis &
equivalent make with Cooling Thermostat, ball valve with 'Y' strainer at inlet & ball valve at outlet and necessa
connections. Unit capacities are as mentioned below.

1.5 TR / 600 cfm


Supply of Variable Refrigerant Volume Inverter driven type air-conditioning system with wide range of indoor a
actual and total piping length and with high external static pressure. The system consists of multiple indoor un
fancoil, ducted type, etc.. connected to a single or multiple modular type outdoor units with individual controller
1.3 piping, control cabling and also centralized controller. The specifications and details are as below:

Supply, Installation, Testing & Commissioning of Variable Refrigerant Volume / Flow (VRV/VRF) modular type o
which consists of Inverter compressors, condenser fan, motor & condenser coils, control panel it should
pressure switch, fuses, fusible plug for condensing unit in accordance with the approved shop drawings
The vendor can select their configuration based on the models available and their unit performance
capacity of the outdoor unit should be in line with the specification and concept briefed in the tender docum
also include outdoor connecting kit and power cable from isolator provided by others to out door unit. The Ve
equipment as per Thane condition. The VRV unit should be compatible with third
party BMS system through Bacnet output protocal.

a 32 HP - Top Discharge

b 8 HP - Side Discharge
1.4 Supply and installation of MS Structure for ODU's with non-corrosive paint
Supply, Installation, Testing & Commissioning of following VRV Indoor unit with evaporation coil expansion val
1.5 in accordance with the approved shop drawings and technical specifications.
a 8.0 TR High Static Ductable Unit
b 4.0TR Ductable Unit - For Server Room
c 2.6TR Ductable Unit
d 2.0TR Ductable Unit - For UPS Room
f 2.0 TR Slim Duct FCU
g 1.5 TR Slim Duct FCU
h 1.3 TR Slim Duct FCU
i 0.8 TR Slim Duct FCU
j 0.6 TR Slim Duct FCU
1.6 SITC of corded remote / thermostat for Indoor Units
1.7 Additional Charge of gas and oil for VRF units
1.8 Central Remote controller for VRV Units.
1.9 Sequential Controller for AC unit to programme the run hours of compressor.
a For Server & UPS Room

TOTAL OF HIGH SIDE


HVAC HIGH SIDE

DESCRIPTION

Chilled Water Fan Coil Type Units, complete with 3/4 Row Chilled Water Coils with max working pressure of 8 Bar,
ax, dynamically balanced low noise type centrifugal section, multi speed single phase fan motor with permanent
protector with standard opening on the winding, resilient mounts , washable type filters with filtering efficiency
nit casing shall be of Galvanized corrosion resistant / powder coated with internal insulation of 10mm insulating
mm thick insulating foam, 4 way diffusion with adjustable blades. Fresh air intake opening of minimum 100mm
r module, inbuilt condensate drain pump, insulated drain tray with injected polystyrene for leakage prevention
ed with valve package comprising of 2/3 way motorized valve Siemens (Landis & Staefa), Sauter, Belimo, make or
Thermostat, ball valve with 'Y' strainer at inlet & ball valve at outlet and necessary copper coil piping
re as mentioned below.

Volume Inverter driven type air-conditioning system with wide range of indoor and outdoor units, with longer
and with high external static pressure. The system consists of multiple indoor units ranging from high wall,
nected to a single or multiple modular type outdoor units with individual controllers to each indoor unit, refrigerant
o centralized controller. The specifications and details are as below:

Commissioning of Variable Refrigerant Volume / Flow (VRV/VRF) modular type outdoor air-conditioning system
ompressors, condenser fan, motor & condenser coils, control panel it should also include high & lower
plug for condensing unit in accordance with the approved shop drawings and technical specifications.
eir configuration based on the models available and their unit performance. However, the selection
should be in line with the specification and concept briefed in the tender document/drawing. The quote should
ng kit and power cable from isolator provided by others to out door unit. The Vendor should select the
dition. The VRV unit should be compatible with third
cnet output protocal.

Structure for ODU's with non-corrosive paint


Commissioning of following VRV Indoor unit with evaporation coil expansion valve and corded / cordless remote
ved shop drawings and technical specifications.
Unit
ver Room

S Room

mostat for Indoor Units


oil for VRF units
VRV Units.
nit to programme the run hours of compressor.

TOTAL OF HIGH SIDE


UNIT QTY RATE AMOUNT

Nos. 1 39500 39500

Nos. 1 401600 401600

Nos. 2 160000 320000


Nos. 3 8000 24000

Nos. -
Nos. 2 43200 86400
Nos. -
Nos. 2 31100 62200
Nos. 7 31100 217700
Nos. 4 28000 112000
Nos. 1 28000 28000
Nos. 15 26500 397500
Nos. RO
Nos. 31 3500 108500
Lot 1 146400 146400
Nos. -

Nos. 2 14300 28600

1972400
HV

SR.NO DESCRIPTION

1.10 INLINE FANS:


The inline fans shall be complete with centrifugal fan, unit casing access door, electrical connections canopy fa
a include
2000 cfmalland
accessories for installation
25mm static - Fresh air of
faninline fan.
b 800 cfm and 20mm static - Toilet Exhaust
1.11 Battery Room Exhaust Fan
Supply, Installation, Testing & commissioning of Ceiling Suspended DIDW Cabinet type fans shall be complete
belt, electrical connections , elect. Panel fan shall be suitable for indoor installation A/C contractor to include al

Local BMS compatible Control Panel for UPS / battery Room Exhaust fan with DOL Starter & 24Hrs Digital pr
a Relays for 25MM
150 CFM, Fire system
static,& Hydrogen Sensor system to be included
1.12 300 mm dia. Propeller fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

a Supply, installation, testing and commissioning of cubicle type fully compartmentalized totally sheet steel encl
LT panel suitable for 415V, 50 Hz.
(i) Panel for Ceiling Suspended CSUs with star/ delta starter complete with cabling upto CSU motor
Supply and laying of Necessary Cabling from panel to AHU,
Unless specified the voltage grade of all LT Power and Control cables shall be rated for 1100 Volts.
Vendor
Vendor shall
shallconsider
considernecessary clamping andglands.Terminating
Double compression tagging of cables asLugs
part of cable layinglugs
- Aluminum work.
forThe cable laying
aluminum conds
cables and copper lugs for copper conductor cables.
XLPE Insulated, steel round / flat armored, copper conductor cables - multi core
b 4C x 4 Sq.mm
c End Termination - Supply & Installation
d 3C x 2.5 Sq.mm
e End Termination - Supply & Installation

f Supply and Laying of 150 mm wide Ladder Type cable trays for Laying of cables / Earthling (1.6 mm thick)

g Supply and Laying of 25 x 3 Earthing strip


h Supply and Laying of 8SWG Earthling wire copper
2 CHILLED WATER PIPING WITH VALVES & ACCESSORIES
Supply & erection of the following factory rolled MS 'C' class pipes with specified wall thickness cut to require
Providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flange joints. With
2.1 installing.

100mm dia.
80mm dia.
65mm dia.
50mm dia.
40mm dia.
32mm dia.
25mm dia.
2.2 Chilled Water Piping Insulation: ( Nitrile Rubber)
Supply, installation, testing & commissioning of insulation for chilled water piping. 25mm thick Nitrile Rubber co
Mechanical & UV Protection as per specifications.
100mm dia.
80mm dia.
65mm dia.
50mm dia.
40mm dia.
32mm dia.
25mm dia.
2.3 Supply, installation, testing & commissioning of following sizes of butterfly valve with lug type construction, bo
supports
50mm dia.complete with insulation covered with woven Glass Fibre Covering for Mechanical Protection as per
40mm dia. (Ball valve)
25mm dia. (Ball valve)
2.4 Supply, installation, testing & commissioning of following sizes of Double regulating valve / Balancing Valve wi
matching
50mm dia.flanges, bolts, supports complete with insulation covered with woven Glass Fibre Covering for Mech
40mm dia.
25mm dia.
Supply, installation, testing & commissioning of following sizes of Motorized 2/3 way motorized modulating co
2.5 accessories including matching flanges, bolts, supports complete with insulation covered with woven Glass Fib
specifications etc.
43.2 GPM (18.0 TR)
24.0 GPM (10 TR)
6.0 GPM (2.5 TR)
2.6 Supply, installation, testing & commissioning of following sizes of Y strainer with matching flanges, bolts, supp
complete
50mm dia.with insulation covered with woven Glass Fibre Covering for Mechanical Protection as per specificati
40mm dia.
25mm dia.
2.7 Providing and fitting Auto Vent Valves.
1 " dia.
3/4 " dia.
2.8 Necessary pressure gauges and thermometers
Pressure gauges with Brass/SS syphon and petcock
Thermometers
Thermowells
BTP- Binders test point
Drain cock 25mm dia
3 REFRIGERANT PIPING AND CONTROL CABLING
Supply and laying of copper piping with necessary imported fittings, Y-joints and headers etc.,
3.1 FOR VRV UNITS
Interconnecting copper refrigerant pipe work duly insulated with elastomeric nitrile rubber type tubular insula
shop drawing and technical specifications . All piping inside the room shall be properly supported with hanger
The copper piping should be align properly when running in the ceiling. The quote should also includes the pr
joints and headers etc.

3.1.1 41.3mm OD (insulation = 19mm thick)


34.9mm OD (Insulation = 19mm thick)
28.6mm OD (insulation = 19mm thick)
22.2mm OD (insulation = 19mm thick)
19.1mm OD (insulation = 19mm thick)
15.9mm OD (insulation = 19mm thick)
12.7mm OD (insulation = 19mm thick)
9.5mm OD (insulation = 19mm thick)

22.2mm OD (insulation = 13mm thick)


19.1mm OD (insulation = 13mm thick)
15.9mm OD (insulation = 13mm thick)
12.7mm OD (insulation = 13mm thick)
9.5mm OD (insulation = 13mm thick)
6.4mm OD (insulation = 13mm thick)
3.1.2 SITC of refnet joints for above units & distribution
3.2 Control cabling with necessary conduiting between VRV indoor and outdoor units.
3.3 Supply, installation, testing and commissioning of Protective layer for exposed copper piping. Self adhesive Wo
and shall be wrapped around copper piping tubular insulation by using UV paint.

3.4 Provide adequate size enclosed GI cable tray to cover and protect the exposed refrigerant pipes and cabling fo
3.5 Supply wire between VRV indoor unit to the socket
3.6 Three pin tops for VRV indoor units
3.7 Supply cable between individual outdoor unit to the isolators, near outdoor units along with termination usin
3.8 armouredDistribution
Electrical copper cable laid for
Panel in GI trays units. IP-55 protection suitable for outdoor installation for VRV outdo
outdoor
adjustable thermal for outdoor HP. Outgoing: 3 Nos. upto 63A pole MCB+ELCB, sensitivity 100mA,MCB rated a
Final rating for MCB shall be as per unit HP.
Note: Outdoor panel shall be design as per incoming power and outgoing to nos of outdoor unit based on the
consulatant before execution.

3.9 Supply, laying and connection of copper earthing of following sizes:


50 x 10 mm GI Strip
25 x 3 mm GI strip
8 SWG copper wire
10 SWG copper wire
12 SWG copper wire
3.10 INSULATED DRAIN PIPING
SITC of drain piping complete with PVC, fitting, accessories, bends, elbows, tees, flanges, tappings, wall sleev
a tubular
25mm dia9 mm nitrile rubber.The piping shall be connected to the nearest drain pipe at site.
b 32mm dia
c 40mm dia
d 50mm dia
4.0 AIR DISTRIBUTION
4.1 Supply, Fabrication, installation, testing & commissioning of Factory fabricated GSS ducting complete with spli
b etc.GasGIper
24 approved drawings Ducting to be as per SMACNA standards. Galvanizing shall be class VII-light coati
Ducting
c quality
22 G GIprime material.
Ducting
d 20 G GI Ducting
4.2 FACTORY FABRICATED FLAT OVAL DUCTING
Supply, installation, testing and balancing of factory fabricated OVAL ducts using GI Sheets. The price shall incl
supports (factory fabricated Wire Rope Hangers & Supports (Gripple / Tie rod Supports) complete with end fix
joints shall be 100% leak proof. The duct should be factory fabricated & painted with 2 coats powder coated fr
proper covering. Colour shall be confirmed later by architect. The color shade shall be approved by architect.
a Upto 600mm- 24 G Ducting
b 600mm-1200mm- 22 G Ducting
c 1200mm and above 20 G Ducting
4.3 DAMPERS
Supply, Installation, testing Commissioning and Balancing of UL listed and CBRI approved fire dampers with fu
shall be made out of high quality galvanized sheet with spring holder, steel springs, suitable links, with UL liste
4.3.1

a Dampers
b Fusible Link
4.3.2 Supply, Installation, testing Commissioning and Balancing of UL listed and CBRI approved fire dampers with m
a dampers
Dampers shall be made out of high quality galvanized sheet with spring holder, steel springs, suitable links, wit
b Motorized Actuator
Supply, installation, testing and commissioning of multi blade opposed blade GSS dampers for ducts to be pro
4.3.3 manual control of volume of air flow and for proper balancing of the air distribution system.
Supply, installation, testing and balancing of GSS Volume Control Oval shape Dampers with operating handle f
4.3.4 Supply air duct branches in accordance with the approved shop drawings and specifications as per the sizes m
Supply , installation and testing commissioning of black multi blade type box dampers of Al. construction for du
blades, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distrib
4.3.5

4.3.6.1 SITC of Fire retardant Flexible canvass/Reksin connections for above CSU, Ductable
4.3.6.2 SITC of Fire retardant Flexible canvass/Reksin connections for FCU equipment
4.3.7 SITC of Fresh air cowl connection with bird screen and volume control dampers
4.3.8 Supply, Installation, testing & commissioning of Gravity louvered damper (back draft damper).
4.4 GRILLS / DIFFUSERS
Supply, installation ,testing and balancing of tiled square supply air diffusers as per the approved shop drawing
with fixed air distribution grid, removable core for proper balancing of air distribution system a.Powder coate
4.4.1 and shade of size 600mm x 600mm suitable for installation in modular ceiling with sizes of active sections give
active portions blanked Off from above.All diffusers to look alike when viewed from below irrespective of the

a 450 x 450
b 375 x 375
c 300 x 300
d 225 x 225
Supply, installation ,testing and balancing of tiled square return air diffusers without collar dampers as per the
diffuser shall be equipped with fixed air distribution grid removable core for proper balancing of air. a.Powder
4.4.2 colour and shade of size 600mm x 600mm suitable for installation in modular ceiling with sizes of active sectio
non- active portions blanked Off from above.All diffusers to look alike when viewed from below irrespective o

a 450 x 450
b 375 x 375
c 300 x 300
d 225 x 225
Supply, installation, testing and commissioning of Spill Air Plenum / Mixing boxes made of 24G G.I sheet with
fixing flexible duct and suitable collar for connecting to various neck diffuser. The box should be internally ins
4.4.3 necessary chains for
supporting and anchor fasten in accordance with the approved shop drawings and technical specifications of

a 450 x 450
b 375 x 375
c 300 x 300
d 225 x 225
4.4.4 Supply, installation ,testing and balancing of Extruded Aluminium powder coated circular supply air diffusers w
a specifications.
300mm dia Each diffuser shall be equipped with fixed air distribution grid, removable core for proper balan
b 250mm dia
Supply, installation ,testing and balancing of Extruded Aluminium powder coated circular return air diffusers w
4.4.5 and specifications. Each diffuser shall be equipped with fixed air distribution grid, removable core for proper b

a 300mm dia
b 250mm dia
4.4.6 Supply, testing, commissionig and balancing of one way blow Aluminium extruded powder coated continuous
a Linear
100 mm grilles
widefor supply and return air with 4 side flanges and as per approved colour shade by the architect.
b 150 mm wide
c 200 mm wide
4.4.7 Supply, testing, commissionig and balancing of one way blow Aluminium extruded powder coated Curved Line
a grilles
100 mm to wide
suitewith
the oval duct as per shop drawings for supply air with 4 side flanges and as per approved colou
dampers
b 150 mm wide with dampers
4.4.8 Supply, Installation, testing and commissioning of multi slot supply air diffuser complete with flanges. Diffuser
a adjustment.
3 slot, 20 mmThe slotpattern controllers
(With Hit shall dampers
& miss collar be positive
forpositioning
Supply Air)when providing a horizontal air path. Constan
under all positions of pattern adjustment.Diffusers shall be suitable for positive screw type installation to prov
b 3 slot, 20
costing formm
hit slot (Without
& miss collar
dampers anddampers)
supply air plenum box as per specifications
4.4.9 Supply, testing, commissionig and balancing of Aluminium extruded powder coated grilles for exhaust air with
a the
150 architect.
x 150 with collar damper
4.5 Insulated Flexible duct connection to supply air diffuser of plenums. Flexible ducts to be made of aluminium fo
helix (UL 181 class1).
a 150 mm dia
b 200 mm dia
c 250 mm dia
d 300 mm dia
e 350 mm dia
4.6 Factory fabricated Z type Cross Talk Silencer (area calculation : (400x300) Supply and Fixing of Cross T
internal 25mm thick fiberglass Twiga insulation.
4.7 Supply, Installation, Testing and Commissioning of the Air Volume Flow Limiter of approved make suitable for
installation
0- 50 cfm at any orientation and to be precise to +/- 10% to regulate the airflow relative to the specified max
5 INSULATION
5.1 Supply, Installation, testing and Commissioning of Acoustic lining of duct work with 25mm thick bitumen fibe
mechanically
Supply fastened,
Installation, covered
Testing with RP tissue and
and commissioning 30G aluminum
of Supply perforated
Duct insulation 9mmsheet
thick as per specs.
closed Acoustic lini
cell elastomeric nit
5.2 specifications. (For Outside Duct Insulation)
Supply Installation, Testing and commissioning of Supply Duct insulation 9mm thick closed cell elastomeric nit
5.3 specifications. (The duct should be internally insulated)
HVAC LOW SIDE

RIPTION UNIT QTY RATE

ctrical connections canopy fan shall be suitable for installation A/C contractor to
Nos. 1 28750
Nos. 1 21500

type fans shall be complete with centrifugal fan, frame work, EEF Class 1motor,
n A/C contractor to include all accessories

OL Starter & 24Hrs Digital programmable timer & 24V Transformer with PLA
Nos. RO
. Nos. RO

alized totally sheet steel enclosed


g upto CSU motor Nos. 2 79100

d for 1100 Volts.


ying work.
m lugs forThe cable laying
aluminum shall be on cable trays as the case may be.
conductor
core
Rmt RO
Nos. RO
Rmt 30 230
Nos. 6 235

Earthling (1.6 mm thick) Rmt 20 485

Rmt 25 115
Rmt 25 116

wall thickness cut to required lengths and installed with all welded joints,
rs, mating flange joints. With 2 Coats of primer & one coat of enamel paint before

Rmt 5 1600
Rmt 20 1250
Rmt 15 1000
Rmt 60 810
Rmt 25 575
Rmt 5 485
Rmt 30 395

25mm thick Nitrile Rubber covered with Woven Glass Fibre Covering for

Rmt 5 525
Rmt 20 405
Rmt 15 335
Rmt 60 264
Rmt 25 203
Rmt 5 165
Rmt 30 132
with lug type construction, bolts,
echanical Protection as per specifications etc. Nos. 4 2680
Nos. 4 2100
Nos. 8 1050
ng valve / Balancing Valve with
lass Fibre Covering for Mechanical Protection as per specifications etc. Nos. 1 8740
Nos. 1 6300
Nos. 2 3975
way motorized modulating control valve with actuator, thermostat & other
overed with woven Glass Fibre Covering for Mechanical Protection as per

Nos. 1 20900
Nos. 1 19950
Nos. 1 17800
matching flanges, bolts, supports
Protection as per specifications etc. Nos. 1 4285
Nos. 1 3200
Nos. 1 2415

Nos. 2 895
Nos. 5 850

Nos. 2 2245
Nos. 2 2245
Nos. 10 1830
Nos. 10 370
Nos. 8 830

headers etc.,

le rubber type tubular insulation between indoor & outdoor units as per approved
perly supported with hanger and all external piping shall run in covered cable tray.
e should also includes the pressure testing of copper pipe & necessary fittings, Y-

RMT 5 1345
RMT 25 1270
RMT 10 1040
RMT 45 775
RMT 50 745
RMT 20 670
RMT 10 550
RMT 30 480

RMT 5 750
RMT 25 720
RMT 10 715
RMT 50 530
RMT 20 460
RMT 40 345
Nos. 35 5900
RMT 200 160
per piping. Self adhesive Woven fibre glass cloth shall be 7mm thick and 200 gsm 265
RMT 25

frigerant pipes and cabling for all the VRF/DX Split units.. RMT 25 710
RMT 62 160
NOS. 31 140
along with termination using RMT 20 575
or installation for VRV outdoor units. incomer : 160A TP+NL MCCB 25ka O/C + S/C
nsitivity 100mA,MCB rated at 10kA with terminals and wiring upto cable alley.
Nos. 1 164000
of outdoor unit based on the system design and shall be approved by the

RMT 5 245
RMT 15 115
RMT 15 110
RMT -
RMT -

flanges, tappings, wall sleeves, hangers, supports, anchors and insulation using
at site. RMT 15 150
RMT 90 190
RMT 35 265
RMT 20 340

S ducting complete with splitter dampers, turning vanes, access doors, supports,
ng shall be class VII-light coating of zinc,nominal 120 gm/sq.m and lock forming Sqm 85 1000
Sqm 40 1150
Sqm 10 1325

GI Sheets. The price shall include T-joints(Branch piece) flanges, turning vanes,
pports) complete with end fixing), sealent (neoprene gasket), hangers etc. The
ith 2 coats powder coated from factory itself. Ducts should brought to site with
ll be approved by architect.
Sqm 130 1200
Sqm 55 1350
Sqm 30 1620

pproved fire dampers with fusible link for atleast 120 mins rating. The dampers
s, suitable links, with UL listed fusible links as per approved shop drawings.

Sqm 1 8745
Nos. 4 1490
pproved fire dampers with motorized actuator for atleast 120 mins rating. The
el springs, suitable links, with UL listed actuator as per approved shop drawings. Sqm RO
Nos. RO
dampers for ducts to be provided with suitable links, levers and quadrants for 6680
system. Sqm 1

pers with operating handle for 8325


ecifications as per the sizes mentioned in drawings. Sqm 3

pers of Al. construction for ducts collars to be provided with suitable links, vertical 4245
er balancing of the air distributions system. Sqm 1

ble Nos. 3 3510


Nos. 28 1840
Sqm 1 11140
aft damper). Sqm 1 11600

r the approved shop drawing and specifications. Each diffuser shall be equipped
ution system a.Powder coated extruded aluminium diffusers of approved colour
h sizes of active sections given below. The diffusers to be full tile with the non-
m below irrespective of the sizes.

Nos. 2 2490
Nos. 3 2025
Nos. 3 1725
Nos. 1 1570
ut collar dampers as per the approved shop drawing and specifications. Each
er balancing of air. a.Powder coated extruded aluminium diffusers of approved
ng with sizes of active sections given below. The diffusers to be full tile with the
ed from below irrespective of the sizes.

Nos. 2 1565
Nos. 3 1435
Nos. 3 1350
Nos. 1 1275
made of 24G G.I sheet with necessary spigot connection & Spigot damper for
box should be internally insulated with 6mm thick nitrile rubber. And with

d technical specifications of following sizes.

Nos. 2 1015
Nos. 3 925
Nos. 3 835
Nos. 1 835
circular supply air diffusers with damper as per the approved shop drawings and
movable core for proper balancing of air distribution system Nos. 1 1685
Nos. 1 1592
circular return air diffusers without damper as per the approved shop drawings
removable core for proper balancing of air distribution system

Nos. 1 1310
Nos. 1 1190
d powder coated continuous
our shade by the architect. Rmt 130 455
Rmt 10 635
Rmt 10 815
d powder coated Curved Linear
s and as per approved colour shade by the architect. Rmt. 30 545
Rmt. 10 1000
mplete with flanges. Diffusers shall be provided with adjustable pattern
horizontal air path. Constant static pressure shall be maintained at a fixed volume Rmt 2 1685
rew type installation to provide a blemish free appearance. Vendor to include
Rmt 5 1470
ed grilles for exhaust air with 4 side flanges and as per approved colour shade by
Nos. 12 280
s to be made of aluminium foil both inside and outside encapsulating a steel wire

Rmt 5 440
Rmt 15 455
Rmt 10 500
Rmt 10 540
Rmt 5 560
pply and Fixing of Cross Talk silencer fabricated using 22G GI Sheets with Nos. RO

approved make suitable for duct


relative to the specified maximum air flow. Nos. 25 2400

h 25mm thick bitumen fiberglass stick using shalikote primer hot and Sqmtrs 40 885
et as
ck per specs.
closed Acoustic lining
cell elastomeric nitrileshall
foamberubber
rigid board.
insulation class O stuck to duct as per 460
Sqmtrs 110
ck closed cell elastomeric nitrile foam rubber insulation class O stuck to duct as per 455
Sqmtrs 200

TOTAL OF LOW SIDE


AMOUNT

28750
21500

158200

6900
1410

9700

2875
2900

8000
25000
15000
48600
14375
2425
11850

2625
8100
5025
15840
5075
825
3960

10720
8400
8400

8740
6300
7950

20900
19950
17800

4285
3200
2415

1790
4250

4490
4490
18300
3700
6640

6725
31750
10400
34875
37250
13400
5500
14400

3750
18000
7150
26500
9200
13800
206500
32000
6625

17750
9920
4340
11500
164000

1225
1725
1650

2250
17100
9275
6800

85000
46000
13250

156000
74250
48600

8745
5960

6680

24975

4245

10530
51520
11140
11600

4980
6075
5175
1570

3130
4305
4050
1275

2030
2775
2505
835

1685
1592

1310
1190

59150
6350
8150

16350
10000

3370
7350

3360

2200
6825
5000
5400
2800

60000

35400
50600

91000

2263297
AHU
SR.NO DESCRIPTION

1.0 EQUIPMENTS

Supply, installation, testing & commissioning of DOUBLE SKIN, CEILING SUSPENDED AHU, with supply air alumi
draw through type air handling unit (AHU) of 0.8mm thk GI sheet metal cabinet type (outer skin) & 0.8 mm thk
equipped with 50 mm thick, 40 kg/cum polyurethane foam sandwiched between panels complete with pre filt
microns with Fan section with DIDW centrifugal forward / backward curved fan of non-overloading charactersti
1.1 10% volts, 50 cycles, 3 phase AC supply, Multi Row coil section with copper header, removable type Cooling co
wall construction with 13 mm thick nitrile foam insulation.
NOTE : THE UNIT NOISE LEVEL SHOULD NOT EXCEED 55 DB.

EACH UNIT SHOULD BE PROVIDED WITH THE GI TRAY BOTTOM OF THE UNIT, COVERING VAL

Contractor shall design the chilled water coil according to the following conditions:
a. ADP - 13 +/- 1.0 deg C
b. Chilled water temperature entering 7.5 deg C/ 45.5 deg F

CFM TR Ex.SP TYPE


a) 7000 cfm, 18TR 25mm (Ceiling Suspended)
b) 1000 cfm 2.5TR 15mm (Ceiling Suspended)
c) 4000 cfm 10 TR 25mm (Ceiling Suspended)

Note: Fan Outlet Velocity 8 m/sec


Coil face velocity 2.5 m/sec
Filter velocity 2 m/sec
AHU
DESCRIPTION

ommissioning of DOUBLE SKIN, CEILING SUSPENDED AHU, with supply air aluminium damper, sectionalized construction,
unit (AHU) of 0.8mm thk GI sheet metal cabinet type (outer skin) & 0.8 mm thk GI PLAIN (inner skin) and imported fans
kg/cum polyurethane foam sandwiched between panels complete with pre filter of MERV 8-90% efficiency down to 10
DIDW centrifugal forward / backward curved fan of non-overloading characterstics & Motor (IE2) shall be suitable for 415 +
C supply, Multi Row coil section with copper header, removable type Cooling coil section, insulated SS drain pan of double
hick nitrile foam insulation.
SHOULD NOT EXCEED 55 DB.

ROVIDED WITH THE GI TRAY BOTTOM OF THE UNIT, COVERING VALVES & DRAIN OUTLET

ed water coil according to the following conditions:

tering 7.5 deg C/ 45.5 deg F

Ex.SP TYPE
25mm (Ceiling Suspended)
15mm (Ceiling Suspended)
25mm (Ceiling Suspended)

sec
2.5 m/sec
/sec

TOTAL OF AHU
UNIT QTY RATE AMOUNT

alized construction,
and imported fans
ciency down to 10
l be suitable for 415 +
drain pan of double

ET

Nos. 1 265000 265000


Nos. 1 60000 60000
Nos. 1 140000 140000

TOTAL OF AHU 465000