Existing AHU
Existing AHU AEB AEB Calc. Fan operating AEB Air Fan operating AEB Air Fan operating AEB Calculated
at AHU Heat Load CALC TSP At 100% TSP At TSP At 40% Fan Pulley/
AHU Quantity Design ESP Calculated Air flow rate Point within flow rate at Point within flow rate at Point within Existing Design AEB Calculated AHU Existing Cooling Difference w/r to
AHU
Diversified Peak Diversified PEAK AEB 60% AEB AEB Motor Pulley Cooling Coil analysis as per Fitout
S.No. Tower Ref# Level Type Level Ref# AHU Ref# Including Considering ESP at 100% Recommended 60% Recommended 40% Recommended Chilled Water Chilled Water Cooling Capacity (Fitout existing Cooling Any other modifications / Conclusion
Load with Base with Base Build Diversified Diversified Diversified to be changed Design
Typical Floors Induction VAV considering PI Diversified Region of Fan Diversified Region of Fan Diversified Region of Fan Flow Rate (l/s) Flow Rate (l/s) Capacity (Kw) Cooling Capacity
Build +2% Duct Leakage Load (Pa) Load (Pa) Load (Pa) (Y/N)
(Pa) VAV (Pa) Load Curve Load Curve Load Curve Capacity) (Kw)
(l/s) (L/s)
The required total cooling Existing fan and motor can operate at
2 T-1 Prayer L2 AHU-T1-07A 1 1992 2024 -2 464 341 123 292 2024 633 ✔ 1214 228 ✔ 810 101 X 1.03 0.86 38 31.9 6.1 Yes load can be met with existing @ 100% & 60% air flow as per fitout
coil design.