Вы находитесь на странице: 1из 16

General Cam switches 0

Complete products 10 A

The range of K10 cam switches (10 A rating) comprises only complete switches.
These products are more specifically designed for process control applications:
b compact size,
b easy to integrate with other Ø 16 and Ø 22 mm units,
b selection functions.

Complete products Front mounting switches

b OFF-ON switches
b stepping selector switches
b changeover switches

0
2
0
1

1
3

Single Ø 16.3 or Ø 22.3 mm hole fixing

Mounting method Single Ø 16 or Ø 22 hole fixing

0
2
1

Locking/unlocking of the body-head assembly by means of a lug

Single Ø 16 hole fixing Single Ø 22 hole fixing

Characteristics : References : Dimensions :


page 30051/3 pages 30051/4 to 30051/8 page 30051/9

30051_Ver2.00-EN.fm/2 Schneider Electric


Characteristics Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

Environment
Conforming to standards IEC/EN 60947-3

Approvals c UL us

Protective treatment Standard version: “TC”

Ambient air temperature Operation: - 20…+ 55 °C

Storage: - 40…+ 70 °C

Electric shock protection Class II, conforming to IEC 60536

Degree of protection IP 65 conforming to IEC 60529 (operating head)


IP 20 (contact block)

Mechanical durability 1 million operating cycles

Contact block characteristics


Rated operational characteristics AC-15, A300 – 240 V 3A
120 V 6A
AC-21A, AC-1 – 400 V 10 A
UL/Canada 3-phase 110/120 V 0.75 HP
Heavy Duty 220/240 V 1 HP
A300
Single-phase 110/120 V 0.33 HP
220/240 V 0.75 HP
AC-23A 3-phase 220/240 V 1.8 kW
Single-phase 110/120 V 0.37 kW
220/240 V 0.75 kW
d.c. current Ie 1 contact 24 V 10 A
resistive load 110 V 0.7 A
220 V 0.3 A
Short-circuit protection Cartridge fuse 10 A gG

Conventional thermal current (Ith) 10 A

Rated insulation voltage (Ui) 440 V, degree of pollution 3 conforming to IEC 60947-1

Contact operation Slow break

Terminal referencing Conforming to CENELEC EN 50013

Rated impulse withstand voltage (U imp) 4 kV conforming to IEC 60947-1

Electrical reliability Failure rate < 1 failure, for 100 million operating cycles (c 24 V PLC inputs)

Cabling Screw and captive cable clamp terminals


Clamping capacity: 2 x 1.5 mm2

Dimensions : References : Dimensions :


page 30051/2 pages 30051/4 to 30051/8 page 30051/9

Schneider Electric 30051_Ver2.00-EN.fm/3


References Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

OFF-ON switches
Wiring scheme Marking Number Reference Weight
and & switch of
switching scheme position poles kg
55257

12 34 0 1 K10-A001ACH 0.030
1
1
2
3
4
5
6 2 K10-B002ACH 0.035
K10-B002ACH 7 0
8 60

0 60 3 K10-C003ACH 0.045
1-pole 1
2
2-pole 3
4
3-pole 5
6
4-pole 7
8 4 K10-D004ACH 0.045

Stepping switches, single-pole, with “O” position


Wiring scheme Marking Number Reference Weight
and & switch of
switching scheme position poles kg

L1 1 2 2 K10-B002QCH 0.035
1 0
2
3
4
1 2

330 30
270 330 30
1 270
2
3
4

L1 2 3 K10-C003QCH 0.045
1 3
1 0
2
3
4
5
6
12 3 0
315 45
270
270 315 0 45
1
2
3
4
5
6

L1 2 34 4 K10-D004QCH 0.045
1
550258

0
1
2
3
4
5
6
7 330 0 30
K10-D004QCH 8 300
270
1234

270 300 330 0 30


1
2
3
4
5
6
7
8

Dimensions : Characteristics : Dimensions :


page 30051/2 page 30051/3 page 30051/9

30051_Ver2.00-EN.fm/4 Schneider Electric


References (continued) Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

Stepping switches, 2-pole, with “O” position


Wiring scheme Marking Number Reference Weight
and & switch of
switching scheme position poles kg

L1 L2 2 K10-D012QCH 0.045
550259

1 2
1
2 0
3
4
5
6
7
8
330 30
K10-D012QCH 1 2
270
270 330 30
1
2
3
4
5
6
7
8

L1 L2
1 1
2
3 3 K10-F013QCH 0.055
2 0
3
4
5
6
7
8
9 0
315 45
10
11 270
12
1 2 3
270 315 0 45
1
2
3
4
5
6
7
8
9
10
11
12

Stepping switches, single-pole, without “O” position


L1 2 3 3 K10-C003NCH 0.045
1 1
2
3
4
5
6 330 30
12 3 270
270 330 30
1
2
3
4
5
6

L1 2 3 4 K10-D004NCH 0.045
1 1 4
2
3
4
5
6
7 330 30
8
270 90
12 34
270 330 30 90
1
2
3
4
5
6
7
8

Dimensions : Characteristics : Dimensions :


page 30051/2 page 30051/3 pages 30051/9

Schneider Electric 30051_Ver2.00-EN.fm/5


References (continued) Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

Stepping switches, 2-pole, without “O” position


Wiring scheme Marking Number Reference Weight
and & switch of
switching scheme position poles kg
1 L1 L2
2
3 2 3 3 K10-F013NCH 0.055
4
5 1
6
7
8
9
10
11
12 1 2 3
330 30
270330 30
1
2 270
3
4
5
6
7
8
9
10
11
12

Changeover switch with spring return


Wiring scheme Marking Number Reference Weight
and & switch of
switching scheme position poles kg

1 L1 L4
1 K10-B006TCH 0.035
550260

2 1 0 2
3
4

1 2

K10-B006TCH 330 0 30
330 0 30
1
2
3
4

Changeover switches with “O” position


L/1 2 3 4
1
2 1
0
2
1 K10-B001UCH 0.035
3
4
5
6
7
8
9 0 2 K10-D002UCH 0.045
10
11 300 60
12
13
550261

14
15
16 1 2
3 K10-F003UCH 0.055
300 0 60
1
2
1-pole 3
4
K10-F003UCH 5
6
2-pole 7
8
9 4 K10-H004UCH 0.065
10
3-pole 11
12
13
14
4-pole 15
16

Changeover switches without “O” position


L/1 2 3 4
1
2 1 2 1 K10-B011UCH 0.035
3
4
5
6
7
8
9
10 2 K10-D012UCH 0.045
11 330 30
12
13
14
15
16 1 2
330 30 3 K10-F013UCH 0.055
1
2
1-pole 3
4
5
6
2-pole 7
8
9 4 K10-H014UCH 0.065
10
3-pole 11
12
13
14
4-pole 15
16

Dimensions : Characteristics : Dimensions :


page 30051/2 page 30051/3 pages 30051/9

30051_Ver2.00-EN.fm/6 Schneider Electric


References (continued) Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

Voltmeter switches
For measurement between phases and between phase and neutral
Wiring scheme Marking Reference Weight
and & switch
switching scheme position kg

L1 L2 L3 N
550262

L1-L2 0 L1-N
K10-F027MCH 0.055
1 L2-L3 L2-N
L3-L1 L3-N
2
3
4
5
6
K10-F027MCH 7
8 315
0
45
9
10 270 90
11 225 135
12
V

270 300 330 0 30 60 90


1
2
3
4
5
6
7
8
9
10
11
12

For measurement between phases, with “O” position

L1 L2 L3 L1-L2
L2-L3
L3-L1 K10-D024MCH 0.045
1 0
2
3
4
5
6
7 315
0
45
8
V 270

270 315 0 45
1
2
3
4
5
6
7
8

Ammeter switches
3 measurement points, with neutral position
550263

L1 0 K10-F003MCH 0.055
L2
L3 3 1
PE 2
1
2
K10-F003MCH 3
0
4
5 A
6 270 90
7
8 180
9
10
11
12

0 90 180 270
1
2
3
4
5
6
7
8
9
10
11
12

Dimensions : Characteristics : Dimensions :


page : 30051/2 page 30051/3 pages 30051/9

Schneider Electric 30051_Ver2.00-EN.fm/7


References Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate
Accessories
540016

Legend holders
Description Sold Unit Weight
in reference
lots of kg

For Ø 22 mm hole fixing With metallic 25 Z227N 0.060


finish legend

Z227N
501646_1

Accessories
Description Colour Sold Unit Weight
in reference
lots of kg
Z33
Blanking plug Black 10 Z33 0.060
501647_1

Nut wrench – 5 Z201 0.020

Z201

Dimensions : Characteristics : Dimensions :


page 30051/2 page 30051/3 page 30051/9

30051_Ver2.00-EN.fm/8 Schneider Electric


Dimensions Cam switches 0

Complete products, 10 A
Front mounting, single Ø 16 or Ø 22 mm hole fixing
With 30 x 30 mm front plate

Cam switches 10 A
30

28
25 e
a

a
K10-A, B 51
K10-C, D 63
K10-F 75
K10-H 87

e : thickness of support 0.5 to 5.5 mm.

Single Ø 16 or Ø 22 mm hole fixing

1,7 3,2
12,7
9,8

16,2 22,3

Contact functions: how to understand the conventions used


Link positions (factory mounted) Graphic representation of switching positions and spring return to “O” position

L1 L2 L3
315 0 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10 Contact number (position)

UVW
Contact closed

Contact closed in 2 positions and maintained between


the 2 positions

Angular position of switch


Sealed assembly for auto-maintain control

0
315 45
Overlapping contacts

Dimensions : Characteristics : References :


page 30051/2 page 30051/3 pages 30051/4 to 30051/8

Schneider Electric 30051_Ver2.00-EN.fm/9


General Cam switches 0

Complete switches, 32 to 150 A

The range of K30 to K150 cam switches (32 to 150 A ratings) comprises only
complete switches.
These products are more specifically designed for direct control of simple machines.

Complete switches Front mounting

# OFF-ON switches
# starter switches
# changeover switches

By 4 holes By 4 holes
with 64 x 64 mm front plate with 88 x 88 mm front plate
32 to 63 A ratings 115 to 150 A ratings
K30, K50 and K63 K115 and K150

"Multifixing" mounting method Rear mounting

By 4 holes By 4 holes
32 to 63 A ratings 115 to 150 A ratings
K30, K50 and K63 K115 and K150

Characteristics : References : Dimensions :


page 30052/3 pages 30052/4 to 30052/8 page 30052/9

30052_Ver1.10-EN.fm/2 Schneider Electric


Characteristics Cam switches 0

Complete switches, 32 to 150 A

Type K30 K50 K63 K115 K150


Environment
Conforming to standards IEC/EN 60947-3

Approvals UL, CSA 120 V- 1-phase 2 hp 3 hp 3 hp 5 hp 7.5 hp


240 V- 1-phase 5 hp 7.5 hp 7.5 hp 10 hp 15 hp
240 V- 3-phase 5 ph 7.5 ph 10 hp 20 hp 25 hp
480 V- 3-phase 20 hp 25 hp 25 hp 30 hp 40 hp

Protective treatment Standard version: “TC”

Ambient air temperature Operation - 25…+ 55 °C


Storage - 40…+ 70 °C

Electric shock protection Class II, conforming to IEC 536 and NF C 20-030
Degree of protection
conforming to IEC 529 and NF C 20-010 IP 40
Mechanical durability 300 000 operating cycles

Contact block characteristics


Rated insulation voltage Ui = 690 V conforming to IEC/EN 60947-1 - Degree of pollution 3

Conventional Screw clamp connections In open air Ith = 32 A Ith = 50 A Ith = 63 A Ith = 115 A Ith = 150 A
thermal current
Rated operational characteristics
to IEC/EN 60947-5-1 " AC-15 220…240 V 14 A 16 A – – –
380…440 V 6 A 7A – – –
to IEC/EN 60947-3 " AC-3 3-phase 220…240 V 5.5 KW 7.5 KW 11 KW 15 KW 22 KW

3-pole 380…440 V 11 KW 15 KW 18.5 KW 30 KW 37 KW


660…690 V 11 KW 15 KW 18.5 KW 30 KW 37 KW
1-phase 110 V 2.2 KW 2.5 KW 3 KW 3.7 KW 5.5 KW
2-pole 220…240 V 4 KW 5.5 KW 6 KW 7.5 KW 11 KW
380…440 V 5.5 KW 7.5 KW 11 KW 13 KW 18.5 KW
" AC-23 A 3-phase 220…240 V 7.5 KW 11 KW 15 KW 30 KW 37 KW
3-pole 380…440 V 15 KW 22 KW 30 KW 45 KW 75 KW
660…690 V 15 KW 22 KW 55 KW 65 KW 65 KW
1-phase 110 V 2.2 KW 2.5 KW 4 KW 5.5 KW 11 KW
2-pole 220…240 V 4 KW 5.5 KW 10 KW 15 KW 22 KW
380…440 V 7.5 KW 11 KW 18.5 KW 22 KW 37 KW
" AC-21 A 32 A 40 A 63 A 100 A 150 A

Rated conditional Power: kA 5 5 10 15 25


short-circuit current
Short-circuit protection gG cartridge fuse, 50 63 80 125 200
A
Rated impulse withstand voltage U imp = 6 kV conforming to IEC/EN 947-1

Contact operation Slow break (with positive opening operation)

Cabling Screw and captive cable clamp terminals (For 2 x 2.8 x 0.8 mm push-on connectors, please
consult your Regional Sales Office)
Solid cable 2 x 6 mm2 2 x 10 mm2 2 x 16 mm2 1 x 35 mm2 1 x 70 mm2
Flexible cable with or without 2 x 4 mm2 2 x 6 mm2 2 x 10 mm2 1 x 25 mm2 1 x 50 mm2
cable end
Tightening torque 1.2 N.m 2 N.m 2.5 N.m 2.5 N.m 2.5 N.m

Switching capacity $ Number of contacts in series 1 2 3


Resistive load V 24 48 70 32 A 50 A 63 A 115 A 150 A
T ≤ 1 ms 48 95 140 32 A 40 A 63 A 100 A 150 A
60 120 180 23 A 37 A 30 A – –
110 220 330 6.5 A – – – –
220 440 660 1.2 A – – – –
440 660 – 0.4 A – – – –
Inductive load V 24 48 70 32 A 40 A 63 A 100 A 150 A
T = 50 ms 30 60 90 25 A 30 A 55 A 33 A 50 A
48 95 140 16 A 20 A 20 A – –
60 120 180 11 A 15 A – – –
110 220 330 3.2 A 3.5 A – – –

General : References : Dimensions :


page 30052/2 pages 30052/4 to 30052/8 page 30052/9

Schneider Electric 30052_Ver1.10-EN.fm/3


References Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (ratings 32 to 63 A)
and 88 x 88 mm front plate (ratings 115 and 150 A)

OFF-ON switches
Front mounting
Connection scheme Marking & Number Thermal Reference Weight
and switch of current
switching scheme position poles (Ith)
A kg
103521

1 32 K30-A001AP 0.130
Input 1 Input 2 0
1
L1 L2L3 N L1L2
1 50 K50-A001AP 0.175
2
3
4
5 0
6 60 2 32 K30-B002AP 0.170
7
K30-C003AP 8
9
10
11 50 K50-B002AP 0.215
12
U V WN U V
Output 1 Output 2 3 32 K30-C003AP 0.224
0 60
1-pole 1
103522

2
2-pole 3 50 K50-C003AP 0.275
4
3-pole 5
6
4-pole 7
8
9
10 63 K63-C003AP 0.345
6-pole 11
12

115 K115-C003AP 0.680


K50-C003AP

150 K150-C003AP 0.790

4 32 K30-D004AP 0.250

50 K50-D004AP 0.305

63 K63-D004AP 0.390

115 K115-D004AP 0.745

150 K150-D004AP 0.880

6 32 K30-F006AP 0.425

50 K50-F006AP 0.530

63 K63-F006AP 0.590

General : Characteristics : Dimensions :


pages 30052/2 page 30052/3 page 30052/9

30052_Ver1.10-EN.fm/4 Schneider Electric


References (continued) Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (32 to 63 A ratings)
and 88 x 88 mm front plate (115 and 150 A ratings)

ON-OFF switches
Front mounting
Connection scheme Marking & Number Thermal Reference Weight
and switch of current
switching scheme position poles (Ith)
A kg
501179

Input OFF 3 32 K30-C003HP 0.224


L1 L2L3 N ON
1
2 50 K50-C003HP 0.275
3
4
5 0
6
7 90
K63-C003HP 8 63 K63-C003HP 0.345
UV WN

Output
115 K115-C003HP 0.680

0 90
1
501178

2
3
4
150 K150-C003HP 0.790
3-pole 5
6
4-pole 7
8
4 32 K30-D004HP 0.250

50 K50-D004HP 0.305

63 K63-D004HP 0.390
K150-D004HP

115 K115-D004HP 0.745

150 K150-D004HP 0.880

Rear mounting

Input OFF 3 32 K30-C503HP 0.250


L1 L2L3 N ON
1
2 50 K50-C503HP 0.300
3
4
5 0
6
7 90
8 63 K63-C503HP 0.370
UV WN
Output
115 K115-C503HP 0.720

0 90
1
2
3 150 K150-C503HP 0.830
4
3-pole 5
6
4-pole 7
8
4 32 K30-D504HP 0.280

50 K50-D504HP 0.350

63 K63-D504HP 0.440

115 K115-D504HP 0.790

150 K150-D504HP 0.930

General : Characteristics : Dimensions :


page 30052/2 page 30052/3 page 30052/9

Schneider Electric 30052_Ver1.10-EN.fm/5


References (continued) Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (32 to 63 A ratings )
and 88 x 88 mm front plate (115 and 150 A ratings )

Changeover switches with “O” position


Front mounting
Connection scheme Marking & Number Thermal Reference Weight
and switch of current
switching scheme position poles (Ith)
A kg
Input 1 Input 2
103522

0 1 32 K30-B001UP 0.170
L1 L2L3 N L1L2L3 N 1 2
1
2 50 K50-B001UP 0.215
3
4
5
6 2 32 K30-D002UP 0.250
7
8 0
9 300 60 50 K50-D002UP 0.305
10
K50-B001UP 11
12
13 3 32 K30-F003UP 0.425
14
15 50 K50-F003UP 0.530
16 UV WN 63 K63-F003UP 0.590
115 K115-F003UP 0.645
300 0 60
1
2
150 K150-F003UP 0.760
1-pole 3
4
5
6 4 32 K30-H004UP 0.485
2-pole 7
8
9 50 K50-H004UP 0.610
10
3-pole 11
12
63 K63-H004UP 0.680
13
14 115 K115-H004UP 0.750
4-pole 15
16 150 K150-H004UP 0.880

Changeover switches without “O” position


Front mounting
Input 1 Input 2
1 2 3 32 K30-F013UP 0.425
L1 L2L3 L1L2L3
1
2
3
4 50 K50-F013UP 0.530
5 330 30
6
501179

7
8
9 63 K63-F013UP 0.590
10
11
12
UVW
115 K115-F013UP 0.645
330 30
1
2
3
4
K63-F013UP 5
6
7
8 150 K150-F013UP 0.760
9
10
11
12

Input 1 Input 2
1 2 4 32 K30-H014UP 0.485

330 30 50 K50-H014UP 0.610

63 K63-H014UP 0.680

330 30
1
2 115 K115-H014UP 0.750
3
4
5
6
7
8
9
10
11
12 150 K150-H014UP 0.880
13
14
15
16

General : Characteristics : Dimensions :


page 30052/2 page 30052/3 page 30052/9

30052_Ver1.10-EN.fm/6 Schneider Electric


References (continued) Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (32 to 63 A ratings)
and 88 x 88 mm front plate (115 and 150 A ratings)

Star-delta switches
Front mounting
Connection scheme Marking & Number Thermal Reference Weight
and switch of current
switching scheme position poles (Ith)
A kg
103522

L1 L2L3
3 32 K30-H001YP 0.485
1 0
2
3
4
5
6
7 50 K50-H001YP 0.610
8
9
10 0
300 60
11
K50-H001YP 12
13
14 63 K63-H001YP 0.680
15 W2 U1
16
W1 U2

V2 V1

115 K115-H001YP 0.750

300 0 60
1
2
3
4
5
6
7
150 K150-H001YP 0.880
8
9
10
11
12
13
14
15
16

Reversing star-delta switches


Front mounting

L1 L2 L3
501177

0 3 32 K30-K006YP 0.560
1
2
3
4
5
6
7 50 K50-K006YP 0.690
8
9 00
10 315 45
300 60
11 270 90
12
13
14 L1L2L3 N 63 K63-K006YP 0.770
15
16
17 W2 U1
K115-K006YP 18
19 W1 U2
20
V2 V1 115 K115-K006YP 0.880

290 315 0 45 90
1
2
3
4 150 K150-K006YP 0.990
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

General : Characteristics : Dimensions :


page 30052/2 page 30052/3 page 30052/9

Schneider Electric 30052_Ver1.10-EN.fm/7


References (continued) Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (32 to 63 A ratings)
and 88 x 88 mm front plate (115 and 150 A ratings)
Accessories

Pole change switches for 2-speed motors


(for motors with tapped "Dahlander" windings)
Front mounting
Connection scheme Marking & Number Thermal Reference Weight
switch of current
L1 L2L3
position poles A kg
501179

1
2
3 3 32 K30-H004PP 0.485
4
5
6
7
8
9 1U
10
11 0
12 2V 2U 300 60
13 50 K50-H004PP 0.610
K63-H004PP 14
15
16 1W 2W 1V

300 0 60
1
2
3
4
5
6
7
8 63 K63-H004PP 0.680
9
10
11
12
13
14
15
16

Reversing switches with “O” position


Front mounting
Connection scheme Marking & Number Thermal Reference Weight
switch of current
position poles A kg
501178

L1 N
1 2 32 K30-D002WP 0.250
2
3
4 50 K50-D002WP 0.305
5 U V
6
7
8 M 63 K63-D002WP 0.390
0
300 60
300 0 60
1 115 K115-D002WP 0.745
2
3
4
5
6 150 K150-D002WP 0.880
7
8
K150-D002WP
L1 L2 L3 0
1 1 2 3 32 K30-E003WP 0.385
2
3
4 50 K50-E003WP 0.485
5
6
7
8 0 63 K63-E003WP 0.540
9 300 60
10 U V W
11 115 K115-E003WP 0.590
12
M
300 0 60
150 K150-E003WP 0.710
1
2
3
4
5
6
7
8
9
10
11
12

Accessories
Description For use Colour Sold in Unit Weight
with lots of reference kg
Legend holders Square heads – 5 KZN-15 0.020
With blank legend, 64 x 64 mm
Square heads – 5 KZN-103 0.040
88 x 88 mm
Blank legends Square heads Metallic 5 KZ-77N 0.025
for legend holder Square heads Metallic 5 KZ-100N 0.040
Blank legends for 64 x 64 5 KZN-21 0.035
metallic finish front plate 88 x 88 5 KZN-24 0.045

General : Characteristics : Dimensions :


page 30052/2 page 30052/3 page 30052/9

30052_Ver1.10-EN.fm/8 Schneider Electric


Dimensions Cam switches 0

Complete switches, 32 to 150 A


With 64 x 64 mm front plate (32 to 63 A ratings)
and 88 x 88 mm front plate (115 and 150 A ratings)

Cam switches from 32 to 150 A


Front mounting Rear mounting

D1

b
e
G1 34 X a a1
34 a

K30-A K30-C K30-E K30-H K30-K K50-A K50-C, K50-E K50-H K50-K K63-A K63-C K63-E K63-H K63-K
K30-B K30-D K30-F K50-B K50-D K50-F K63-B K63-D K63-F
a *41 *53.7 *66.4 79.1 *104.5 *45.8 63.3 80.8 *98.3 *133.3 *49.8 *71.3 *92.8 114.3 *157.3
a1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
b 58 58 58 58 58 60 60 60 60 60 66 66 66 66 66
 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
D1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 5.4 5.4 5.4 5.4 5.4
G1 – 48 – – – – 48 – – – – 48 – – –
X – 78 to 97 – – – – 78 to 97 – – – – 78 to 97 – – –
K115-A K115-C K115-E K115-H K115-K K150-A K150-C K150-E K150-H K150-K
K115-B K115-D K115-F K150-B K150-D K150-F
a *61.5 *88 *114.5 *141 *194 *67.5 *100 *132.5 *165 *230
a1 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9
b 84 84 84 84 84 88 88 88 88 88
 88 88 88 88 88 88 88 88 88 88
D1 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4
G1 – 68 – – – – 68 – – –
X – 12...150 – – – – 12...150 – – –
e: thickness of support 0.5 to 5.5 mm.

Support drilling

D3 D2
G2

K30/K50/K63 K115/K150
D2 4.5 6
D3 10 13
G2 G2 48 68

Contact functions: how to understand the conventions used


Link positions (factory mounted) Graphic representation of switching positions and spring return to “O” position

L1 L2 L3
315 0 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10 Contact number (position)

UVW
Contact closed

Contact closed in 2 positions and maintained between


the 2 positions

Angular position of switch


Sealed assembly for auto-maintain control

0
315 45
Overlapping contacts

General : Characteristics : References :


page 30052/2 page 30052/3 pages 30052/4 to 30052/8

Schneider Electric 30052_Ver1.10-EN.fm/9

Вам также может понравиться