Академический Документы
Профессиональный Документы
Культура Документы
Extra coats shall be applied to achieve even paint finish as per Architect's
instructions.
ELECTRICAL
1. DISTRIBUTION TRANSFORMERS
85
Complete with Certified Laboratory Test reports from manufacturer which includes the
following:
1. Turns ratio test
2. Polarization Index
3. No Load (excitation) loss test
4. Load loss test
5. Winding resistance test
6. Insulation resistance test
7. Impedance test
8. Oil dielectric test
9. Dissolve gas analysis
10. Insulation Power Factor Test
11. Winding excitation test
1.2. The main transformer tank and attached components shall be designed to withstand
pressure 25% greater than required operating design value without permanent
deformation.
All seams and jointsshall be continuously welded.
1.3. Installation shall be in accordance with manufacturer’s instruction.
1.4. Install transformer with clearances (minimum 1-meter) for proper ventilation. Provide
flexible busbar connectors on both the primary and secondary sides.
1.5. Potential transformer for the primary metering should be secluded (provide separate
enclosure) from the Vacuum Circuit Breaker (VCB) enclosure
1 -
1 GENSET 1 1-4000 1-4000 100 (10sets(250mm²
+30 mm²(G))
2 -
2 LVSG1 1-4000 1-4000 100 (10sets(250mm²
+30 mm²(G))
3 COPPER BUSBAR 1-4000A
86
2.1.6. Mounting :Structural Stee Skid Base supports the engine,
alternator and radiator with anti-vibration (vibration
eliminator)
2.1.7. NFPA 110 :Generator Sets accepts full rated load in a single step.
2.1.8. Diesel Tank :12 hours @ 100% load. Provide storage tank that can
accommodate 12 hours operation for each
Generatot set.
2.1.9. Emergency Power Supply :Can accept load within ten (10) seconds
(either single or synchronized unit)
2.1.10. Application Standard :ISO 8528, ISO 3046, IEC 6034, AS2789, DIN
6271, BS 5514, NEMA, NEC, NFPA, IEEE, ANSI, OSHA, UL
2.1.11. General Application :general purpose (lighting & electrical loads),
induction motors, compressors, Variable speed
drives, PC and telecommunication equipment.
2.1.12. Complete with certified factory and commissioning tests:
2.1.12.1. Insulation resistance testing.
2.1.12.2. Starting and Stopping Test.
2.1.12.3. Load test.
2.1.12.4. Governor test.
2.1.12.5. Load characteristic test.
2.1.12.6. Frequency alteration test.
2.1.12.7. Voltage alteration test.
2.1.12.8. Protective device test among others.
Note: The complete system shall designed, assembled, tested and shipped by one
manufacturer so that there is only one source of supply and responsibility
on all components with the system.
87
2.2.8. Exhaust system : Residential-grade exhaust silencer (unless otherwise
specified)
2.2.9. Exhaust Manifold Type :Dry
2.2.10. Air System : Turbocharged and low temperature after-cooled.
2.2.11. Governor : Electronic type.
2.2.12. Starting motor : 24V DC dual electric starting motor (unless otherwise
specified)
2.2.13. Emissions Compliance : Comply with EPA (Environmental Protection
Agency) emissions requirements for
stationaryapplications (is an advantage).
Superior voltage waveform from two-thirds (2/3) pitch windings and skewed stator.
88
2.4.2. Power Supply : 24V DC (unless otherwise specified)
2.4.3. Humidity Range : 5% to 95% noncondensing
2.4.4. Operating Temperature : -40°C to + 70°C
2.4.5. Standards :
• NFPA99
• NFPA 110, Level 1
• UL 508
2.4.6. User Interface Controls and Components :
Emergency stop switch with IEC yellow ring identification. Lockout
key switch.
Auto/ Manual Button
Alarm horn indicates generator set shut down and warning faults.
Status lamps
Breaker Control Buttons
Digital Display Menu
Key Pad
Communication Ports
• Two (2) RS-485 connector for Modbus or Lonworks interfaces.
• One (1) RS-232 connector for PC(optional software required)
91
3.5. MANUFACTURERS
The low voltage air circuit breaker switchgear assembly shall be bolt on type or
by means of bus bar interconnection as manufactured from an approved manufacturer
and shall have a maximum rating of 5000 AT from either of the following.
• ABB
• Eaton
• General Electric
• Siemens
• Square D
• And other approved equivalent
3.6. PROTECTION •
Overload
• Ground Fault
• Phase unbalance
• Over voltage
• Voltage
• Residual Voltage
• Reverse Power
3.8. SUBMITTALS
Submit shop drawings and product information in the quantities listed
according to the Conditions of the Contract.
• Shop Drawings- 3D generated drawings indicating the overall
dimensions, front, rear & side sections.
• Single line diagram.
• Nameplate schedule
• Component and accessories list and data including ratings and voltage
• Circuit breaker type, interrupting capacity and trip setting
• Routine test and design test
• Equipment layout showing clearances of equipment from wall and from
other equipment.
• Equipment base construction details
• Metering equipment, connections and mounting details
For Final Acceptance the following information shall be submitted for record purposes:
• Final as-built drawings and information for items listed and shall
incorporate all changes made during the manufacturing process.
• Wiring diagrams
• Certified production test reports
• Istallation informations
• Operation and maintenance manuals- including all product specifications.
• Warranty Certificates
92
• Tools and Keys.
93
4.3.1. VCB Type : Fixed
4.3.2. Operation : Via motor charged energy spring mechanism
and in emergency individual manual handle.
4.3.3. Tripping Control Voltage : 48VDC
4.3.4. VCB Components : Three vacuum interrupters seoarately mounted, self
contained and self aligning pole unit.
4.3.5. Approved Brands : AREVA, GE, ABB, EATON-CH,SIEMENS,
SCHNEIDER or approved equivalent.
4.5. ACCESSORIES
The switchgear shall contain the following accessories needed to complete the
switchgear:
3 pcs Bushing type current transformer rated as shown in the drawings.
3 pcs Potential transformer rated as shown in the drawings.
94
*Note: Accuracy ratings shall be equal to or higher than ANSI standard requirements.
The thermal and mechanical ratings shall be coordinated with the Vacuum CB, power meter
and protective relay.
3 pcs Metal Oxide Station Type Lightning Arresters
2 pcs LED Type Indicating Lights
1 pc CBCS
1 set Industrial type batteries, 48Vdc, 18Ah shall be furnished together with the regulated
battery charger, 240V, 60Hz input, 48Vdc output equipped with automatic switchover
float/boost charge. The battery charger shall be enclosed complete with DC voltmeter
and DC ammeter.
4.6. MANUFACTURERS
The high voltage vacuum circuit breaker switchgear assembly shall be bolt on
type or by means of bus bar interconnection as manufactured from an approved
manufacturer and shall have a maximum rating of 5000 AT from either of the following.
• ABB
• Eaton
• General Electric
• Siemens
• Square D
• And other approved equivalent
4.8. SUBMITTALS
Submit shop drawings and product information in the quantities listed
according to the Conditions of the Contract.
• Shop Drawings- indicating the overall dimensions, front view and side
section view.
• Single line diagram.
• Schematic diagram
• Nameplate schedule
• Component and accessories list and data including ratings and voltage
• Circuit breaker type, interrupting capacity and trip setting
• Routine test and design test
• Equipment layout showing clearances of equipment from wall and from
other equipment.
• Equipment base construction details
• Metering equipment, connections and mounting details
95
For Final Acceptance the following information shall be submitted for record purposes:
• Final as-built drawings and information for items listed and shall
incorporate all changes made during the manufacturing process.
• Wiring diagrams
• Certified production test reports
• Istallation informations
• Operation and maintenance manuals- including all product specifications.
• Warranty Certificates
• Tools and Keys.
5. XLPE
6. LIGHTNING PROTECTION
96
NEC.
10.2. PURPOSE
• The purpose of this document is to ensure that pipes, conduits and ducts
are labeled to identify:
1. Identify the contents and the direction of flow and additional pipe/ duct
information.
2. Ensure uniformity and consistent methodology; and
3. Lessen the chances of error, confusion or inaction especially in times
of emergency.
10.3. SCOPE
• This procedure shall provide a common information to assist in the proper
labeling of piping and ducting system. This shall cover only the labeling
the pipes, conduits and ducts and does not cover pipes buried in the
ground.
97
means of identification is the color code of the band or the color of the
pipe or conduit. Identification by colored stenciled or lettered legends with
colored bands shall be placed at frequent intervals on straight pipe runs,
close to all valves, and adjacent to all shange-in-directions, or where pipes
pass through walls and floors. If desired, the entire length of the piping
system may be painted with the color.
PIPE MARKING GUIDE
TYPE OF PIPE USED LEGEND PIPE/BAND COLOR FONT TEXT COLOR SAMPLE
98
11. AUTOMATIC METER READING (AMR)
11.1. SINGLE PHASE KWH
11.1.1. Shall be able to provide the following functionalities:
• Time of Use (TOU)
• Active Energy
• Meter Number
• Time and Date
99
• Number of Daily Profiles (4 daily profiles)
• Maximum Demand (4 tariffs)
11.5. RATING
• System (1P, 3P-3W, 3P-4W)
• CLASS 1 Accuracy
• IEC 62052-11 Standard
• Reference Voltage: (110V; 220V; 240V; 400V; 480V)
• Reference Frequency: 50/60 Hz
100
100
100
17. WIRING DEVICES
a. Wall Switches: Quiet type, spring operated. The type of switch shall be of tumbler
operation. Rating as shown in the plan.
b. General Purpose Receptacles: Flush mounting, type and rating as shown in the plan.
c. General Purpose Wall Plates: Type, color, plating and appearance of device plates shall
be as selected by the CONSULTANT. Appropriate samples shall be submitted prior to
the purchase of the faceplates.
d. Brands : Philips, G.E., Panasonic, Bticino
101
101
101
18.17. Where indicated, provide neutral bus bar of the same material as the phase
bus bars and a continuous current rating 200 percent of the phase bus
bars. Provide at least one terminal lug for each branch circuit. 18.18.
Minimum Short-Circuit Rating: 25,000 amps rms symmetrical (for
Distribution panelboards) and 22,000 amps rms symmetrical (for branch
circuit panelboards) unless shown otherwise on the Drawings.
102
102
102
18.21. Feeder cables should have separate conduit from the load conduits.
18.22. Protection during construction: Store all products in a dry location. Following
installation, protect products from the effects of moisture, corrosion, and
physical damage during construction.
18.23. Mount panelboards securely where indicated, in-line, and square with walls.
Unless otherwise indicated, mount panelboard with top of its cabinet
approximately 6-1/2 feet above the floor, panelboard with main
breaker/disconnect at the top: the height between the main disconnect device
and the floor shall not exceed more than 5-1/2 feet maximum.
18.24. Color: ANSI 61 Gray
18.25. Finish: Powdered Coated
103
103
103
18.26. Enclosure Thickness Lighting Panels/Power Panels: Gauge 16 for main
enclosure and dead front cover. Main Distribution Panelboards &
ECB(500AT/AF & higher):Gauge 14
18.27. Clearances: as per PEC
a) SCOPE
• This guideline established the basic specifications for fire detection and
alarm system based on commercial requirement set forth by the following
Codes and Standards.
o RA 9514 – Fire Alam Codes of the Philippines; [Div.6; Section
10.2.6.4] o RA 6541- Building Codes of the Philippines; [Chapter 2, Section
2.02] o NFPA 72 – National Fire Alarm Codes
[2007]
b) Specification
2. Initiating Devices
104
104
104
in a specific area and shall be compatible with the panel
with a programmable sensitivity of three level. each smoke
detector shall be addressable plug-in type or conventional
for semi-addressable system, shall
have a manual dip switches for addressing and shall be UL
listed.
2.3 Beam Type Smoke Detector : Beam type shall be used for areas with a clear
ceiling height and there is no obstruction in between the
effective line of sight with an operational range of eight
meter to 100 meters, monitoring area of 1,40,
maximum height of 40 meters and an adjusting angle of
-6° to + 6° (line of sight). Shall have electronic addressing
and shall be reflective infrared beam obstruction, with
reflectors, combination of emitting and receiving parts.
3. Notification Devices
3.1 Sounder and Strobe Light : Shall be UL listed with a sound level output of
84 dBA to 95 dBA at 3 meters and a beacon light
frequency of 20 to 180 times. It should also have
a programmable alarm/sound (e.g. for evacuate
mode or alarm mode) and shall have a manual
addressing dip switches.
4. System Accessories
4.1 Secondary Power Supply : A secondary power supply for indoor use with a
105
105
105
power input of 220/230 volts, maximum standby
capacity of DC24V/24Ah, output capacity of
DC24V/6A-8A and has a sealed lead acid battery.
It should also be addressable (can be fully
monitored FCP), dully monitored with self-test
facilities, display AC input voltage, DC output
voltage and DC load and with built-in battery
charger.
4.2 Wires /Cables : shall have a voltage rating and tempeture rating of
300V and 75°C respectively.
4.3 Pipes, Fittings, and : Pipes shall be EMT/IMC with hot-zinc galvanized
Accessories coating (interior or exterior) or equivalent. Pipes
shall be painted RED, whole or part that will serve
as an indication of fire alarm circuits. Lock nut,
Bushing, Connectors, clamps, TEE and LB conduit
shall be specified in the materials list, including the
octagonal boxes and square boxes (with boxes).
2.2.1 Horizontal cable: Horizontal cable shall be 100Ω, 4 pairs, Category 6, Unshielded
Twisted Pair (UTP), 0.51mm (AWG 24), solid bare copper wire, polyethylene
insulated, PVC jacketed, and CMR flame rated. Cable shall have the following
transmission characteristics:
106
106
106
2.2.2 WORK STATION OUTLET
Workstation outlet shall be Category 6, UTP, 568A, RJ45, with the following
electrical characteristics at 200MHz.
a. NEXT - ≥ 48dB
b. FEXT - 37dB; and
c. Attenuation - 0.2dB.
Constructed from high impact, flame retardant thermoplastic with color- coded snap-
in identification
The distribution frame shall link the horizontal system & backbone system together. Shall
be composed of floor mounted rack, patch panels, terminal block, cross connection wires,
patch cord, and cable management system.
2.3.1 Cable Management Rack
Cable management rack shall be standard EIA 19” X 7 ft floor mounted rack. Rack
shall include vertical cable managers mounted on the channels with removable
covers that can handle large quantities of cables and patch cords.
Path panel shall have Category 6 electrical performance. Path panel shall be made
of black anodized aluminum 24/48 ports, TIA 568A configuration.
Terminal block shall be rack mounted with number pair as indicated on the plans.
Terminal block shall be color coded to TIA 568B.2-1.
107
107
107
Pitch - 3.81 mm
NEXT - better than –53dB @ 100 MHz Attenuation -
<0.001 dB @ 100 MHz
Termination type - Gas-Tight insulation displacement Resistance
Insulation - 500 megaohms Termination -
<0.5 milliohms
Cross connection wire and patch cord shall meet or exceed the same category rating
of connecting hardware.
1. The system shall be capable of capturing all camera pictures and shall
provide a multi-screen camera display.
2. The Network Video Recorder (NVR) provided shall operate the
recording process when the system is on the machine command mode.
3. System operation and programming shall be accomplished using a
full function keyboard.
4. Permanent record of system status shall always be available showing time
and dated of changes such as: incoming alarms, acknowledgement of
alarms, loading of sequences, user log-on to keyboard and a power-up
reset message.
5. All devices equipment and enclosure shall be UL listed or equivalent.
6. The CCTV system shall utilize PoE (Power-over-Ethernet) technology
based IEEE 802.3af standard Relay Servers (Integrated Security
Switch) which shall serve as power supply for IP-based cameras.
7. Each Camera and each Relay Server shall have an IP address on a
Network (i.e. LAN, W AN, VPN).
8. All control commands shall be transmitted over the network using TCP/IP
protocol.
108
108
108
2.1 CCTV Camera
A. Video cameras shall comply with the following minimum requirement:
1. The IP-cameras utilizing CCD or CMOS shall be of fixed, pan/tilt/zoom
type as indicated in the Drawings.
2. The Contractor shall propose the suitable lenses appropriate to the
viewing areas and the sensor elements. Automatic aperture control shall
be provided. Where zoom lenses are specified, these shall be motorized
and shall also have an auto-iris and spot filter. The zoom lens shall be
rated at 10:1.
3. The IP-cameras shall have RJ-45 port for integrated signal and power
over Ethernet, optional 24 VAC socket, mounting holes; with built-in
local memory storage (micro or mini-SD) for alarm capturing.
4. Cameras shall be supplied from the manufacturer with a case to house
the electronics and shall be UL listed. Cameras supplied as printed
circuit board (PCB) assemblies without a case shall not be acceptable.
5. Where the lens is inbuilt into the camera (i.e. not interchangeable) a
number of different focal length lens shall be available.
6. Video cameras shall comply with the following technical data:
109
109
109
11. The camera housing shall be proprietary and shall suit the needs of the
application. Cameras that will be used outdoor shall have a
weatherproof type enclosure. In some areas, where aesthetics are a
concern or camera concealment is necessary, a decorative enclosure
shall be provided. The camera and lens package shall be suitably
installed in the housing. The Contractor shall include full details of camera
housings with the bid.
2.2 Monitor
A. Monitors shall comply with the following requirements:
2. The monitor wall shall be installed within the visual angle view of the
operators. The space below the monitors shall be built as 19” frame racks
for installation for the video alarm units.
2.3 NVR
Network Video Recorders (NVR) shall comply with the following features and requirements:
1. Remote Image through Network (i.e. LAN, W AN, VPN). with password
protection for viewing.
2. High compression ratio supporting Mpeg4, H.264, and Motion Jpeg.
3. Watermarks video protection to avoid video tampering.
4. Scheduled recording: once daily, weekly, monthly.
5. Integrated video capture, Video and Audio Recording over TCP/IP
Networks.
6. Image enhancement, zoom & scaling up to any size on screen.
110
110
110
7. Easy-to-use user friendly icon-based interface.
8. On-line context-sensitive help.
9. Video monitoring and recording on both server site and client site.
10. Instant retrieval of the specified video segment according to time and date.
11. Worldwide video standard: NTSC, PAL 12. Supports up to 16, 32, or 64
Devices
13. Video and Audio Recording over TCP/IP Networks.
14. Multitasking simultaneously record, playback, search, transmission,
schedules, alarm trigger etc.
15. Can support minimum Terabyte (TB) capacity
16. Duplex Operation: Simultaneous Recording and Playback
17. Continuous and Alarm-Based Recording
18. Full-Featured Search Capabilities: Search Based on Camera, Time, or
Date
19. Video recording
Period – 90 days of motion detect
Recording at 25 to 30 frames per second (fps).
20. Playback control, speed playback, frame by frame, fast forward, reverse
etc.
21. Video output – VGA or composite.
1.1 HP
1.2 Cisco
3. Ports:
3.1 Auto-sensing 10/100 ports (IEEE 802.3 Type 10Base-T, IEEE 802.3u
Type 100Base-TX); Media Type; Auto-MDIX; Duplex, half or full
only.
111
111
111
IEEE 802.3u Type 100Base-TX, IEEE 802.3ab Type 1000Base);
Duplex: 10Base-T/100Base-TX: half or full; 1000Base-T: full
only.Open mini-GBIC (SFP) slots.
3.4 Processor: 300 MHz, 16MB flash, 128MB SDRAM; packet buffer size:
1 MB.
3.5 Performance: Up to 13.0 million pps throughput, 17.6 Gbps
routing/switching capacity, table size for 8000 entries.
3.6 Mounting: Standard 19-inch (483-mm) rack.
V. References:
The following are the references considered in the development of this guide.
1. RA 6541 – Building Codes of the Philippines Chapter Section 2.02 Standard for Fire
protection
2. RA 6514 – Fire Code of the Philippines Section 10.2.6.4 Fire Detection, Alarm and
Communication System.
3. National Fire Protection Association – NPFA 72 – National Fire Code 2007 Edition
4. Product Brochures ( Simplex, Notifier-Honey well, Edwards, GST)
5. Websites
5.1 http://www.edwards-signals.com/
5.2 http://www.notifier.com/
5.3 http://www.simplex-grinnell.com/
112
112
112
5.4 http://www.nfpa.org/
ANNEX “A”
Sample Contract
Contract
1. This contract has a validity of one (1) year effective upon receipt of confirmation.
2. This contract is renewable upon expiration of contract effectively.
Supplier Responsibilities
Customer Responsibilities
1. Maintenance materials like oil, filters and coolant additives will be charged to
customer. Only the specified oil, filters and coolant additives will be used.
2. Daily check-up of the unit conditions to include levels; recording and updating the
maintenance log sheet to include load conditions, gauge reading and reporting
immediately to the supplier unusual sound or performance deviation.
3. Immediately feedback regarding unit operational problem/s must be relayed to the
supplier thru established communication system.
Terms
113
113
113
Communication Systems
1. Persons to Contact
a. Mr. X – Service Manager
b. Mr. Y – Sales Engineer
2. Contact Numbers
a. Service Department – Telephone Numbers
b. Sales Department – Telephone Numbers
Scope of Work
114
114
114