Академический Документы
Профессиональный Документы
Культура Документы
net/publication/307938030
CITATIONS READS
2 225
2 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Patrícia Isabel Santos e Abreu on 22 September 2017.
Abstract— This paper evaluates the behavior of electricity distribution network with the least possible alterations in order
distribution networks protection systems, through a systematic to confine retrofit investments to acceptable and affordable
short-circuit analysis, as a means of characterizing the behaviour values.
of protective devices in distribution systems. A comparison is
made between two of the most common protection schemes, the The aims of this paper is to analyze the behaviour of the
first one using recloser and fuses and the second using electricity distribution network protection systems when a DG
overcurrent relays, with distributed power injections, in one of is placed on the network. The distribution network, at global
the IEEE publicly available radial test feeders. All simulations level, contains two protection schemes widely used: the
are performed using the Power Factory software package from overcurrent relays and recloser and fuse. Taking into account
DigSILENT. From the simulation results, conclusions are drawn these protection schemes, short-circuits were simulated on a
that provide insights into the behavior of protection systems, radial test network IEEE in order to analyze the impact of DG
highlighting the limitations of the original protections, and on the protections operation, considering two types of
devising strategies to meet quality assurance, coordination and injections, with different capacities. These simulations were
selectivity of proposed modified protection schemes. performed using the software package Power Factory of
DigSILENT.
Keywords— distributed generation, power system protection,
protection coordination, overcurrent protection. This paper is structured as follows: section 2 presents the
protection schemes coordination features and lists the main
I. INTRODUCTION problems pf lack of coordination of overcurrent relays and
recloser and fuses. Section 3 presents the network to analyze,
Traditional electrical distribution systems are based on a protection devices and distributed injections. Section 4 sets out
topology in which energy flows radially from the substation to the results obtained for each case study. The conclusions are
the loads. Presently, networks are progressively more complex reported in section 5.
to operate, since there are distributed power injections, leading
to bidirectional power flows.
II. PROTECTION DEVICES COORDINATION
With the increase in Distributed Generation (DG) units
protection systems are affected, forcing to reconsider the A. Recloser-fuse and fuse-fuse coordination
methods, assumptions and protection and control strategies. The fuses have two main characteristics of relevance in
The protections, as they are in conventional distribution coordination analysis: Minimum Melting (MM) and Total
networks, with their selectivity requirements, sensitivity, speed Clearing (TC). The MM feature corresponds to the time
and reliability, are not adapted to the existence of injections required to begin melting the fuse for a certain value of current
distributed in the network lacking, so the essential adjustments passing through it. The TC feature corresponds to the fuse total
to the implementation of smartgrids. melting time for a given amount of current flowing through it
Therefore, coordination, sensitivity and selectivity of the [1].
protection systems can no longer be taken for granted. It The recloser operates according to two curves: fast and
becomes essential to rethink the protection system in such a slow response. If a fault occurs the recloser must act before the
way that the possible multiple paths feeding a fault current do MM of the fuses in order to avoid fuse damage if the fault is
not jeopardize the system operation. Some typical network not a true fault. The recloser is usually located at the beginning
configuration schemes can be found in the literature, either of the feeder and fuses protect lateral feeders, showed in Fig. 1.
including combinations of recloser on the upstream feeder and
fuses on the laterals, or solely considering overcurrent relays. The coordination range of fuse and recloser for all fault
currents between Ifmin and Ifmax is illustrated in Fig. 2. Within
A coordinated strategy of protection and control needs to be this range the recloser operates before the fuse, which
carefully designed for the safe and reliable operation of the corresponds to the required coordination. The fast recloser
Recl oser
Main Feeder Fig. 3. Coordination of inverse time characteristic overcurrent relays [5].
Fus e1 Fus e2 The characteristics curves for each relay must have
Subs tation
different parameters (pickup current and time dial) to ensure
there is coordination and selectivity, as shown in Fig. 4.
Lateral Feeders
C. Protection Devices
In order to select the characteristics of the various
protection systems three-phase short circuits were simulated in
Fig. 5. IEEE 34-Node Test Feeder modified [15]. Power Factory, using the “complete method” which is based on
For the simulation of the test network some modifications the superposition theorem to determine the short-circuit
were made: three phase sections were kept as specified, single- currents.
The location of protective devices has been the main feeder C2. Reclosers
bus 800, and in the laterals, as shown in Fig. 6. The reclosers are usually designed with inverse time
848 overcurrent curves, as expressed in (2) [4].
846 Α
t ( Ι ) = TD × +Β (2)
844 p
Μ −1
P1
842
P5 where
802 806 808 812 814 850 816 824 P4 860 836 840
858 t : operation time of device (s)
P2 834 P3 P6
832
I : fault current seen by device (A)
800
XFM-1 888 890 862 TD : time dial setting (s)
M : ratio of I/Ipick-up (A)
852
A, B, р : constants for particular curve characteristics
Protective Device
828 830 854
For the recloser, placed in the main feeder, protection P1
Fig. 6. IEEE 34-Node Test Feeder with protection devices. (Fig. 6), a Cooper Power Systems, model Form 4C was chosen,
Two protection devices were located at the 832-890 lateral with instantaneous and delay trip sequences 103 and 134,
to ensure that the whole lateral was protected, both at 24.9kV respectively. Taking into account the short-circuit currents and
and at 4.16kV. the characteristics of the recloser, the operating range is
between 100 and 12000A, as referred in [19].
The main characteristics of the chosen protection devices
are explained below. They were defined to ensure coordination C3. Fuses
and selectivity without DG, in order to assess the response of a
standard protection system to an unplanned appearance of DG The fuses have two characteristics of primary importance in
on the network. the analysis of this problem: MM and TC. The characteristic
curves of the fuses are based on a log-log curve. The part of
interest on this curve approaches a straight line, given in (3)
C1. Overcurrent Relays
[13].
Protective relays present different characteristics according
to the inclination of their representative curves, defined by log(t) = a ⋅ log(I) + b (3)
various standards. In the present case standard IEC 60225 was
adopted, the most widely used in distribution networks. The where
inverse time characteristic was used, given by (1) [18]. t : fuse operation time (s)
I : fault current seen by fuse (A)
0.14 a, b : fuse constants from curve fitting
t = TD × 0.02 (1)
I The fuses selected to protect the lateral feeders were Gould-
−1
I Shawmut manufacturer models, adapted to each lateral
s characteristics.
where
t : relay operation time (s)
TD : time dial setting (s) IV. RESULTS
I : fault current seen by relay (A) Prior to the connection of any DG unit, the protection
IS : current pick-up (A) systems either using overcurrent relays or recloser and fuses,
The TD configuration of each relay is designed such that verified coordination and selectivity in all cases.
the upstream relay must provide a reserve function for the In general, the placement of 0.406MVA DG units did not
downstream relay. result in loss of protection coordination, for all simulated faults.
The choice of the reverse curve is related to the fact that In the case of recloser and fuses, the variation of the short-
this is widely used in many applications. It is softly tilted, circuit current was between 1 and 27%, computed according to
ensuring a quick response in a large interval of short-circuit equation (4):
currents.
I sDG − I cDG
The selected overcurrent relays were the General Electric ΔΙ(%) = (4)
I sDG
IAC51804A model, available in the software library. For each
case, taking account of short-circuit currents in a first phase it where
was necessary to choose the current transformers, followed by ∆I : current variation
the selection of the relays in each case. An overcurrent relay ISDG : short-circuit current without DG
was placed on top of the main feeder bus, numbered 800, as ICDG : short-circuit current with DG
illustrated in Fig. 6.
Three cases registered the largest variations, occurring on
buses 888 and 890, with short circuits simulated on each same
busbar, with a decrease in grid voltage (24.9kV to 4.16kV).
In the case of the 2.5MVA DG units, the results of the operate than in the situation without DG and P3 protection
simulations will be presented in two parts: Part 1 - simulations cleared faster.
with overcurrent relays and Part 2 - simulations with recloser
and fuses. Part 2 – Results with recloser and fuses
Simulations carried out with the 2.5MVA DG unit
Part 1 – Results with overcurrent relays correspond to larger short-circuit current values, also leading to
Without any DG units in place, the overcurrent relay loss of coordination of the protection scheme. A simulated fault
actuation times ranged between 124ms and 246ms. Table II at bus 842 lead to loss of selectivity at the P4 protection for a
shows some the operating times of P1 protection and the DG location at bus 850 and the other locations at buses
protections of the lateral feeders, for various short-circuit downstream the feeder. However, when locating DG at bus 832
simulations on multiple nodes. and downstream the feeder, and simulating short circuits on all
lateral feeders, loss of coordination was more severe, i.e., there
TABLE II. OPERATION TIMES VS FAULT NODES was a loss of selectivity of fuses P4, P5 and P6, except when
Fault node tP1 (ms) tP (ms) the DG was placed at the feeder where the short-circuit was
840 168 122
simulated.
862 168 122 Fig. 8 illustrates a case of lack of coordination between the
848 168 122 recloser and P4 protection when a fault occurs at bus 842 and
888 196 146 the DG unit is located at bus 834, at the starting point of the
890 246 146
lateral feeder where the fault occurs.
Fig. 8. Clearing time of recloser and fuse (P4) for a simulated fault at bus
842 with DG at bus 834.