Equipments Required :
A. Calibration Kit : VZ-35A
B. Multimeter
Procedure:
1.Install the sensor along with extension cable on the calibration kit by using M-10
connector
2. Check the -24 V DC input voltage at the proximeter terminal ( -24 V & COM)
3. Set the sensor on -10 V DC
4. Keep the kit is in Power OFF mode.
5. Set the screw gauge on the 0-0 position.
6. Now the display should read about 0 readings
7. Power on the kit (Before Power On check the power knob on 110VAC or 230VAC)
8. Rotate the knob to increase the speed of the calibration equipment used.
9. Rotate the screw gauge & check the AC mv rms signal on the multi meter. ( Refer the
table of mv RMS signal & the display readings)
10. Check the display readings as per the desired mv rms signal.
11. Check the current output from the monitor.
12. The sensor can be verified maximum upto 300 umpp(micron peak-peak) on the calibration
Kit.
For 0-800umpp
1. Note: This is only Example using through VZ35 we can verify our Sensor till 300 micron only.
2. Note: In case of VM-55/VM701 monitor verification connect the contact type sensor on the
Contact type calibration kit used then only the loop will get completed & you will get the
Readings
SITE VERIFICATION PROTOCOL
FM-SHINKAWA DATE
BRG / NO :- 1
BRG 1X - BRG1Y-
RACK NO / SLOT NO/ CHANEL NO :- R / S /CH RACK NO / SLOT NO/ CHANEL NO :- R / S /CH
MONITOR SERIAL NO :- 1 1Y:
MONITOR MODEL NO :- VM- 55/VM701
MONITOR RANGE :- 0 TO AS PER CUTOMER REQUIREMENT ( IN MICRON )
SENSOR MODEL NO :- VL – 202A – 08 -1012
SENSOR SERIAL NO :- 1X: 1Y:
SENSOR EXTENTION CABLE MODEL NO :- VW – 202AA– 3
SENSOR EXTENTION CABLE NO :- 1X: 1Y:
DRIVER MODEL NO :- VK- 202 –A1
DRIVER SERIAL NO :- 1X: 1Y:
DRIVER SET GAP VOLTAGE:- 1X: -10.5V ( DC ) 1Y:- -10.04 VDC
CALIBRATION KIT NO: VZ35-A SR NO: