Академический Документы
Профессиональный Документы
Культура Документы
Steel column
Lecture 10 - Page 1 of 6
The design of a base plate involves the following steps:
Pp
where Ωc = 2.50 ASD
Ωc
where: f’c = specified compressive strength of concrete, KSI
A1 = area of steel base plate concentrically loaded on conc, in2
= BN (where B and N use whole inches if possible)
B
bf See AISC p. 14-5
d 0.95d N
0.80bf
n n
N − 0.95d
m=
2
B − 0.80b f
n=
2
Lecture 10 - Page 2 of 6
tmin = minimum base plate thickness per AISC p. 14-6:
2 f pu 3.33 f pa
t min = L t min = L
0 .9 F y Fy
Pu Pa
where: f pu = where: f pa =
BN BN
m m
L = larger of L = larger of
n n
= LRFD ASD
Lecture 10 - Page 3 of 6
Example (LRFD)
GIVEN: A W14x82 A992 column has a factored axial load Pu = 700 KIPS. It
bears on a steel base plate using A36 steel. The footing has concrete f’c = 3000
PSI.
REQUIRED: Design the column base plate.
Pu
A1 =
0.6(0.85 f ' c )
700 KIPS
=
0.6(0.85(3KSI ))
A1 = 457.5 in2
0.95(14.3" ) − 0.8(10.1" )
=
2
= 2.75”
N≈ A1 + ∆
≈ 457.5in 2 + 2.75"
≈ 24.14”
TRY N = 24” and B = 20” (Area = 480 in2 > 457.5 in2)
Lecture 10 - Page 4 of 6
Step 3 – Determine “m” and “n”:
N − 0.95d
m=
2
24"−0.95(14.3" )
=
2
= 5.2”
B − 0.80b f
n=
2
20"−0.80(10.1" )
=
2
= 5.96”
2 f pu
t min = L
0 .9 F y
Pu
f pu =
BN
700 Kips
= = 1.46 KSI
(20" )(24" )
m = 5.2”
L = larger of
n = 5.96” use
2(1.46 KSI )
t min = 5.96"
0.9(36 KSI ) Base plate yield stress
Lecture 10 - Page 5 of 6
Step 5 – Draw “Summary Sketch”:
20”
W14x82 A992
col. centered 24”
on plate
7
1 " thick A36 steel base plate
8
Lecture 10 - Page 6 of 6
Lecture 12 – Bolted Connections
Below is a typical bolt and the terms given to the parts of a bolt:
Bolts used in structural steel fasteners fall within 2 categories – see AISC Table
2-5 p. 2-41:
1) Carbon steel bolts – These bolts achieve their total strength from shear
(or tension) strength across the diameter of the bolt. They are
relatively low-strength and are used primarily for low-load applications
such as for anchor rods. The typical carbon steel bolt used in
structural steel buildings is ASTM A307 and F1554 for use in anchor
rods.
Lecture 12 - Page 1 of 9
Possible Bolted Shear Failure Mechanisms:
There are 4 basic types of failure mechanisms for bolted connections under
shear:
1) Bolt Shear:
This is probably the most obvious failure mode. It occurs when the
applied load exceeds the shear capacity through the bolt. The
design shear strength is dictated in AISC Table J3.2 p. 16.1-104 and
AISC Table 7-1 p. 7-22. Possible remedies include using a larger
diameter bolt, higher grade of bolt or more bolts.
Result
Lecture 12 - Page 2 of 9
2) Edge Tear-Out:
This occurs when the bolt is located too close to the edge of the
plate in the direction of load. A minimum required edge distance, Le, is
dictated in AISC Table J3.4 p. 16.1-107. Possible remedies include
increasing the edge distance or reducing the bolt diameter.
Le
Lecture 12 - Page 3 of 9
3) Bearing Failure:
This type of failure occurs when one of the plates is too thin or not
strong enough for the applied loads. The design bearing strength at
bolt holes is dictated in AISC p. 16.1-111 and AISC Table 7-5 p. 7-28
and AISC Table 7-6 p. 7-30. Possible remedies increasing the plate
thickness, use a higher grade of steel or using larger diameter bolts.
Thin plate
Bearing failure
Lecture 12 - Page 4 of 9
4) Net Section Failure:
A net section failure occurs when there are too many bolt holes
perpendicular to the line of action – resulting in too little material to
carry the load. Think of Swiss cheese. The minimum spacing of
bolts is dictated in AISC J3.2 p. 16.1-106 as not less than 2⅔ times
the nominal bolt diameter, preferably 3 times the bolt diameter.
Usually 3” is used as the nominal bolt spacing for bolts < 1” in
diameter.
Lecture 12 - Page 5 of 9
Types of Bolted Connections
1) Bearing-Type Connections:
2) Slip-Critical Connections:
Lecture 12 - Page 6 of 9
Design Strength of Bearing-Type Fasteners
Rn
Allowable strength of bolt = ASD
Ω
where: Rn = FnAb
φ = 0.75 LRFD
Ω = 2.00 ASD
Shear Plane:
The shear plane is the plane in which the various connected parts
are in contact.
Single-shear Double-shear
Load Load
Lecture 12 - Page 7 of 9
Example 1 (LRFD)
GIVEN: A ¾” diameter ASTM A325-N bolt in single-shear is subjected to a
factored load of 14 KIPS.
REQUIRED: Determine the design shear strength of the bolt considering bolt
shear ONLY, and comment if the bolt is acceptable.
Pu = 14 KIPS
where: φ = 0.75
π
= (0.75" ) 2
4
= 0.44 in2
Lecture 12 - Page 8 of 9
Example 2 (LRFD)
GIVEN: Same as Example 1
REQUIRED: Determine bolt design shear using AISC Table 7-1 p. 7-22.
ASTM A325
Bolt Diameter, db = ¾”
Lecture 12 - Page 9 of 9
Lecture 13 – Bolted Connections (cont.)
K Beam
Cope
Lev
S
S
Girder
Connection angles
Lecture 13 - Page 1 of 5
Example (LRFD)
GIVEN: A W16x40 A992 steel beam “A” frames into a W18x55 A992 steel girder
“B”. The applied floor Service DL = 80 PSF and the applied floor Service LL =
100 PSF. Use ¾” diameter A325-X bolts with standard bolt holes and double-
angle A36 L3x3x¼ connection angles. The beam is coped at top flange only.
REQUIRED: Design the all-bolted beam-to-girder connection and provide a
summary sketch.
30’-0”
W18x55 Girder “B”
4 @ 6’-0” = 24’-0”
W16x40 Beam “A”
= 24 KIPS
Lecture 13 - Page 2 of 5
Step 2 – Use AISC Table 10-1 “All-Bolted Double-Angle Connections”, p. 10-22:
¾” Bolts
See Step 3
See Step 9
W16x40
Beam
See Step 5
See Step 7
See Step 5
See Step 8
Lecture 13 - Page 3 of 5
Step 3 – Check Bolt and Angle Design Strength:
ASTM A325
Bolt and angle design strength =
Thread Cond. = X 76.4 KIPS > 24 KIPS
Angle thickness = ¼”
5
W18x55 girder “Kdet” = 1 " from AISC p. 1-18
16
Use cope = 1½”
3
W16x40 beam “Kdet” = 1 " from AISC p. 1-20
16
Lecture 13 - Page 4 of 5
Step 8 – Check girder Support Design Strength:
W16x40 Beam
Cope = 1½”
Lev = 1¼”
S = 3”
S = 3”
W18x55 1¼”
Girder
Lecture 13 - Page 5 of 5
Lecture 15 – Welded Connections (cont.)
Example 1 (LRFD)
GIVEN: A W21x44 A992 girder with a factored end reaction = 87 KIPS has 2 –
L3x3x3/8 connection angles shop-welded to the girder web and field-welded to
the W12x58 A992 column flange as shown.
REQUIRED: Design the connection and provide a summary sketch.
W21x44 Girder
Minimum Web
L=? thickness
W12x58
Column
Weld A
3/16
2X weld
size L2x2x¼ erection
angle shop-welded to
col. flange
L=? 2 – L3x3x3/8
connection angles
Weld B
¼
Lecture 15 - Page 1 of 7
Step 1 – Refer to AISC Table 10-3 p. 10-48 for design info:
See Step 2
See Step 3
Lecture 15 - Page 2 of 7
Step 2 – Determine minimum length “L” by checking Weld B strength:
From Table above, using a ¼” weld, choose a length “L” such that
φRn > 87 KIPS
From Table above, using a 3/16” weld, choose a length “L” such
that φRn > 87 KIPS
From Table above, using a 3/16” weld, the required minimum web
thickness = 0.286” < 0.350” OK
Since the minimum length of Weld B = 12” which is greater than the
minimum length of Weld A → use 12” long angles.
Lecture 15 - Page 3 of 7
Step 7 – Draw summary sketch:
W21x44 Girder
1¼”
12”
W12x58
Column
Weld A
3/16
12” 2 – L3x3x3/8
connection angles
Weld B
¼
Lecture 15 - Page 4 of 7
Eccentric Loading on Weld:
Table 10-3 assumes that the loading is approximately concentric. In other words,
there is no moment acting on the weld.
Pu
Pu
Example 2 (LRFD)
GIVEN: A ½” plate is welded to the flange of a column as shown below. This
plate carries a cantilevered factored load of 25 KIPS.
REQUIRED: Determine if the weld is adequate to carry the eccentric loading.
Pu = 25 KIPS
16”
¼
¼
4”
Column L = 8”
flange
½” Plate
Lecture 15 - Page 5 of 7
Step 1 – Refer to AISC Table 8-5 p. 8-72:
See Step 3
See Step 2
See Step 4
See Step 3
Lecture 15 - Page 6 of 7
Step 2 – Determine coefficient “k”:
Since “L” = 8”
kL = 4”
k(8”) = 4”
k = 0.5
Since “L” = 8”
aL = 16”
k(8”) = 16”
a = 2.0
k = 0.5
Use “C” = 0.821
a = 2.0
Pu
Lmin = ERROR in AISC Manual!!!
φCC1 D
= (8”)(0.75)(0.821)(1.0)(4)
Lecture 15 - Page 7 of 7
Lecture 16 – AISC Code of Standard Practice
The Code also serves as a basis for technical project specifications, typically CSI
Specification Section 05100 – Structural Steel (see Lecture 17).
GLOSSARY
Lecture 16 - Page 1 of 13
Section 1 – GENERAL PROVISIONS
1.1 – Scope
The Code shall govern the fabrication and erection of structural steel
(unless otherwise noted in Contract Documents).
1.3 – Units
Either U.S. customary or metric units will be used. Each system shall
be independent of the other.
Lecture 16 - Page 2 of 13
1.7 – Existing Structures
Lecture 16 - Page 3 of 13
3.2 – Architectural, Electrical and Mechanical Design Drawings
3.3 – Discrepancies
Lecture 16 - Page 4 of 13
Section 4 – SHOP AND ERECTION DRAWINGS
4.4 – Approval
Lecture 16 - Page 5 of 13
Section 5 – MATERIALS
Lecture 16 - Page 6 of 13
6.4 – Fabrication Tolerances
Structural steel that does not require shop paint shall be cleaned of
oil, grease, dirt and any foreign material.
Section 7 – ERECTION
Lecture 16 - Page 7 of 13
7.2 – Job-Site Conditions
All leveling plates, nuts, washers and bearing plates that can be
handled without crane are set to line and grade by the Owner’s
Representative for Construction (otherwise set by Erector).
7.7 – Grouting
Lecture 16 - Page 8 of 13
7.8 – Field Connection Material
Unless otherwise noted, loose structural steel items that are not
connected to the steel frame by the Owner’s Representative for
Construction without assistance from Fabricator.
Safety protection for other trades that are not under the direct
employment of the Erector shall be the responsibility of the Owner’s
Representative for Construction.
Lecture 16 - Page 9 of 13
7.13 – Erection Tolerances
The Fabricator or the Erector may NOT cut, drill or otherwise alter
their work to accommodate other trades unless work is specified in
the Contract Documents.
Lecture 16 - Page 10 of 13
7.17 – Field Painting
8.1 – General
Certified mill test reports shall constitute sufficient evidence that the
mill product satisfies material order requirements.
Lecture 16 - Page 11 of 13
Section 9 – CONTRACTS
9.5 – Scheduling
The contract schedule shall state when the Design Drawings will be
released for construction so that erection can start at the
designated time and continue without interference or delay.
Lecture 16 - Page 12 of 13
Section 10 – ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
10.2 – Fabrication
• All welds exposed to view shall not project more than 1/16”
above the surface.
10.4 – Erection
Lecture 16 - Page 13 of 13
Lecture 17 – Structural Steel Specifications
• Design Drawings
• Specifications
The Design Drawings graphically present the specific design of the structure.
However, they do not indicate the specific requirements relating to:
• Materials
• Submittals
• Job conditions
• Testing & inspection
• Execution of work
Each division has been further refined into multiple sub-divisions (as
shown for Division 5 above). To obtain samples of specifications, go to
http://www.ogs.state.ny.us/dnc/generalInfo/masterspecdefault.htm
Lecture 17 - Page 1 of 8
Section 05100 – Structural Steel
PART 1 - GENERAL
Lecture 17 - Page 2 of 8
5. Exposed Structural Steel: All exposed structural steel is classified
as Architecturally Exposed Structural Steel (AESS) as defined by
AISC. Comply with AESS quality requirements for all exposed
structural steel.
1.4 SUBMITTALS
PART 2 - PRODUCTS
2.1 MATERIALS
2.2 FABRICATION
D. Provide holes for securing other work to structural steel framing. Cut,
drill or punch holes perpendicular to metal surfaces. Do not flame cut
holes or enlarge holes by burning. Drill holes in base and bearing
plates.
F. Anchor Rods: Furnish anchor rods, leveling plate and/or other devices
necessary for setting anchoring rods required for securing structural
steel to foundation, concrete or masonry.
A. Shop paint only structural steel work which will be exposed to view and
finish painted. Do not paint steel embedded in concrete or mortar or
receive a spray on fireproofing. Do not paint surfaces which are to be
Lecture 17 - Page 5 of 8
welded, including metal deck. Do not paint contact surfaces of high-
strength bolted connections or finished bearing surfaces such as
bearing plates and column base plates.
B. For steel to be shop primed and not exposed to view, remove loose rust
and mill scale by mechanical means in accordance with SSPC-SP3
"Power Tool Cleaning". For steel to be galvanized or primed and finish
painted, remove all dirt, grease, rust and loose mill scale in accordance
with SSPC-SP6 “Commercial Blast Cleaning”, unless recommended
otherwise by paint manufacturer.
2.4 CONNECTIONS
Lecture 17 - Page 6 of 8
G. Provide bearing bolt (X) fastener for all structural connections.
PART 3 - EXECUTION
3.1 INSPECTION
3.2 ERECTION
B. Clean bearing surfaces and other surfaces before assembly that will be
in permanent contact after assembly.
3.3 TOLERANCES
Lecture 17 - Page 7 of 8
3.4 TOUCH-UP PAINTING
A. After erection is complete, touch-up paint damaged shop priming coats
and welded areas. Remove weld slag before applying touch-up paint.
3.6 PROTECTION
A. Do not use members for storage or working platforms until permanently
secured.
END OF SECTION
Lecture 17 - Page 8 of 8
Lecture 18 – Open Web Steel Joists
Open web steel joists, or “Bar Joists” are very efficient structural members
commonly used to support roofs, and to a lesser degree, floors.
Steel joists are NOT considered structural steel. As such, they are manufactured
as proprietary structural members by various manufacturers. The Steel Joist
Institute, SJI, is an organization founded in 1928 that was established to set
standards for manufacture, design and construction of joists. It recognizes
manufacturers who comply with their standards. Some of the larger SJI
recognized manufacturers include Vulcraft, Canam Steel Corp. and SMI Joist
Company.
Lecture 18 - Page 1 of 10
K-Series Joists
The most commonly-used joist style is the so-called “K” series. It has a
depth ranging from 8” up to 30” and is used economically to span up to
60’-0”. A typical K series joist is as shown below:
Lecture 18 - Page 2 of 10
Steel joists are fastened to its supporting members usually by field-
welding as shown below:
Unlike structural steel beams, steel joists must use bridging placed
perpendicular to the span to obtain its stability. This bridging can be one
of 2 types:
• Horizontal Bridging
• Diagonal Bridging
Lecture 18 - Page 3 of 10
LH and DLH Series Joists
The LH series joists have depths ranging between 18” and 48” and are
suitable for spans up to 96’-0”. The DLH series joists have depths ranging
between 52” and 72” and are suitable for spans up to 144’-0”.
Lecture 18 - Page 4 of 10
Joist Girders
Joist girders are designed to carry the end reactions from equally-spaced
joists applied to the panel points. Typical depths of joist girders range
from 20” up to 96” with spans of 100’-0” or more.
Lecture 18 - Page 5 of 10
Example 1
GIVEN: A roof framing bay is as shown below. The service loads are as follows:
REQUIRED: Design the K series joists assuming the maximum joist spacing =
6’-0” (based on metal roof deck). Assume the joist + accessories weighs 10 PLF.
36’-0”
60’-0”
Lecture 18 - Page 6 of 10
Step 2 – Determine maximum uniformly distributed total service load:
1) D
2) D+L
3) D + L + (Lr or S or R)
4) D + (W or 0.7E) + L + (Lr or S or R)
5) 0.6D + W
6) 0.6D + 0.7E
S = Snow Load
= 6’(35 PSF)
= 210 PLF
W = Wind Load
= 6’(-12 PSF)
= -72 PLF
Check all 6 load combinations and select “worst” case total load:
1) D = 106 PLF
2) D + L = 106 PLF
3) D + L + (Lr or S or R) = 106 + 150 = 256 PLF
4) D + (W or 0.7E) + L + (Lr or S or R) = 106 + 210 = 316 PLF
5) 0.6D + W = 0.6(106) + (-72) = -8.4 PLF
6) 0.6D + 0.7E = 0.6(106) = 64 PLF
Use
Lecture 18 - Page 7 of 10
Step 3 – Select lightest joist from Vulcraft K series Load Table p. 12:
Span = 36’-0”
Possibilities:
For length = 36’, start at the top of the list and read down until Total
load > 316 PLF and Live load > 210 PLF
Lecture 18 - Page 8 of 10
Step 6 – Draw Summary Sketch of Roof Framing Plan:
28K6 @ 6’-0”
36’-0”
Lecture 18 - Page 9 of 10
Example 2
GIVEN: The roof framing bay from Example 1.
REQUIRED: Design the lightest weight 60’-0” span joist girder.
Joist Girder
28K6 @ 6’-0”
36’-0”
wL
Joist end reaction =
2
= 5688 LBS.
Lecture 18 - Page 10 of 10
Lecture 19 – Steel Deck
Steel deck, or sometimes called “metal deck” is used in steel framed construction
as an intermediate structural system to distribute floor and roof loads to
supporting beams. Decking is typically fastened to the steel supporting
members by either puddle welds or powder-actuated fasteners. Although made
of steel, it is NOT considered to be structural steel. Decking is corrugated having
a typical cross-section resembling:
Top flute
Deck height
Bottom flute
The Steel Deck Institute, SDI, was established in 1939 in an effort to regulate the
design, manufacture and installation of steel deck. Manufacturers complying with
SDI specifications include Vulcraft, Canam Steel Corp. and United Steel Deck,
Inc.
There are 3 general types of steel deck → roof deck, non-composite floor
deck and composite deck.
1. Roof Deck
Lecture 19 - Page 1 of 8
Built-up roof membrane
Rigid Insulation
Lecture 19 - Page 2 of 8
2. Non-Composite Floor Deck
Welded wire
mesh in
concrete slab
Lecture 19 - Page 3 of 8
3. Composite Floor Deck
Lecture 19 - Page 4 of 8
Roof Deck Example
GIVEN: A 1½” Type “F” (intermediate rib) roof deck is to be used in a 3-span
condition with a 7’-0” span. The SERVIVE roof loads are as follows:
REQUIRED: Design the lightest-weight 1½” Type “F” roof deck using the
Vulcraft catalog.
3 spans (min.)
1) D
2) D+L
3) D + L + (Lr or S or R)
4) D + (W or 0.7E) + L + (Lr or S or R)
5) 0.6D + W
6) 0.6D + 0.7E
S = Snow Load
= 40 PSF
W = Wind Load
= -8 PSF
Lecture 19 - Page 5 of 8
Check all 6 load combinations and select “worst” case total load:
1) D = 15 PSF
2) D + L = 15 PSF
3) D + L + (Lr or S or R) = 15 + 20 = 35 PSF
4) D + (W or 0.7E) + L + (Lr or S or R) = 15 + 40 = 55 PSF
5) 0.6D + W = 0.6(15) + (-8) = 1 PSF
6) 0.6D + 0.7E = 0.6(15) = 9 PSF
Use
Step 2 – Refer to the Vulcraft Catalog page 4 for 1½” Type F deck:
7’-0” span
3 span
From Table above, use Vulcraft 1½” Type F 19 Gage Roof Deck
→ Allow. Load = 59 PSF > 55 PSF
Lecture 19 - Page 6 of 8
Non-Composite Floor Deck Example
GIVEN: A floor framing plan for an office building is as shown below. The slab is
5” normal-weight concrete over “2.0 C Conform” non-composite 2” deck as
manufactured by Vulcraft. The superimposed SERVICE live load = 50 PSF and a
total superimposed SERVICE dead load (excluding slab weight) = 38 PSF.
REQUIRED: Design the lightest weight 2.0 C Conform non-composite deck
assuming 3-span condition.
4 @ 6’-0” = 24’-0”
1) D
2) D+L
3) D + L + (Lr or S or R)
4) D + (W or 0.7E) + L + (Lr or S or R)
5) 0.6D + W
6) 0.6D + 0.7E
No. of Spans = 3
Step 3 – Refer to “Reinf. Conc. Slab Allow. Loads” table Vulcraft p. 28:
5”
Lecture 19 - Page 8 of 8
Lecture 21 – Reinforced Concrete Properties
Reinforced concrete structures are typified by their strength, beauty, bulk and
longevity. It is the material of choice for many structures where these
characteristics are required. Concrete-framed structures have many desirable
advantages over other construction materials including:
• Very labor-intensive
• Quality control
• Formwork
• Longer construction schedule due to curing time
• Much larger, heavier member sizes (vs. steel-framed)
• Poor insulation values
Lecture 21 - Page 1 of 8
Concrete Materials:
Lecture 21 - Page 2 of 8
Reinforced Concrete Properties:
1) Compressive Strength
Lecture 21 - Page 3 of 8
2) Tensile Strength
Concrete is a brittle material and has very small tensile strength (about
10% of f’c). It is usually assumed that concrete has zero tensile
strength.
Example:
GIVEN: Concrete with f’c = 4000 PSI.
REQUIRED: Determine Econc
= 3,605,000 PSI
Lecture 21 - Page 4 of 8
4) Reinforcing Bars – Used to carry ALL of the tension in a concrete
member, as well as helping to carry shear and compression. The steel
uses for bars is typically new “billet” steel having the usual modulus of
elasticity “E” = 29,000 KSI. The size of a bar refers to its diameter in
1/8ths. For example a #5 bar is ⅝” in diameter (see table below). Rebar
should conform to ASTM A615 for deformed (ribbed) bars. Typical
grades include:
Lecture 21 - Page 5 of 8
Epoxy-coated reinforcing bars are regular bars with a shop-
applied coating of epoxy. These bars have exceptional resistance
to corrosion and are used in situations where there is high
water/salt exposure (such as road bridge decks, marine structures,
etc.). They are smooth to the touch and usually green in color.
Codes allow the placement of epoxy-coated bars to be closer to the
surface than regular bars because of the increased resistance to
corrosion. This usually results in a thinner, lighter concrete beam
or slab. Unfortunately, the epoxy coating is often scratched or
damaged during construction, leaving exposed bare steel. This
exposed bare steel is ripe for allowing moisture and salt deposits to
enter and actually INCREASING the propagation of corrosion.
For this reason, many state Departments of Transportation do not
allow epoxy-coated reinforcing bars for use in bridge decks.
Lecture 21 - Page 6 of 8
Reinforcing bars are placed a certain minimum distance away from
the edge of the member to ensure that it will not be susceptible to
water/salt infusion. This is referred to as cover distance. The
cover distance requirements shown below are obtained from ACI
318-02 “Building Code Requirements for Structural Concrete.”
Required minimum
cover distance Concrete member
Reinforcing bars
Required minimum
cover distance
Lecture 21 - Page 7 of 8
5) Slump – Fresh concrete uses a slump test to determine the workability
of the concrete as per ASTM C 143. It is, however, not a very useful
measure of the concrete’s strength. It is possible to get very workable
concrete with high slump (i.e., very fluid) with the use of
superplasticizers.
Lecture 21 - Page 8 of 8
Lecture 22 – Introduction to ACI 318-02
The American Concrete Institute (ACI) is the governing agency for all concrete
construction in the U.S. It was established in 1904 to serve and represent user
interests in the field of concrete. The ACI publishes many different standards,
but the most commonly referenced standard used by architects and engineers is
the ACI 318 “Building Code Requirements for Structural Concrete.” It is updated
every 7 years and the latest version is ACI 318-02 updated in 2002.
Almost all Building Codes, including the IBC, refer to ACI 318 as the basis for
structural design of concrete members.
Contents:
PART 1—GENERAL
Lecture 22 - Page 1 of 8
PART 3—CONSTRUCTION REQUIREMENTS
COMMENTARY REFERENCES......................................................318-353
APPENDIXES
Lecture 22 - Page 2 of 8
Analysis and Design – General Considerations
Design Basis:
Load Factors:
1) 1.4(D + F)
2) 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)
3) 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W)
4) 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R)
5) 1.2D + 1.0E + 1.0L + 0.2S
6) 0.9D + 1.6W + 1.6H
7) 0.9D + 1.0E + 1.6H
Lecture 22 - Page 3 of 8
Example 1
GIVEN: The interior column of a 2-story concrete-framed building has the
following applied service loads to the 1200 ft2 tributary area as shown:
REQUIRED: Determine the maximum factored load, Pu, at the bottom of the 20”
x 20” square column.
Lecture 22 - Page 4 of 8
Step 1 – Determine the total service loads on the roof:
Step 3 – Determine the total service dead load of the concrete column:
⎛ 20" ⎞⎛ 20" ⎞
Column dead load, Dcolumn = ⎜ ⎟⎜ (
⎟(28 ft ) 150lb / ft
3
)
⎝ 12 ⎠⎝ 12 ⎠
= 11,667 lbs.
= 11.7 KIPS
Lecture 22 - Page 5 of 8
Step 4 – Sum all service dead loads together:
1) 1.4(D + F)
1.4(351.3) = 491.8 KIPS
Lecture 22 - Page 6 of 8
Example 2
GIVEN: The cantilevered floor balcony beam/slab as shown below. The service
superimposed dead load (not including concrete) = 14 PSF and the
superimposed service live load = 75 PSF.
REQUIRED: Determine the maximum factored moment, Mu on the cantilevered
beam.
14’-0”
18”
5” slab
10” Beam
16’-0”
wu
14’-0”
Lecture 22 - Page 7 of 8
Step 1 – Determine service dead load, D acting on beam:
5” slab
18”
10”
8’-0” 18” – 5” slab
16’-0”
wu L2
For a cantilevered beam, Mmax = Mu =
2
Mu = 186.2 KIP-FT
Lecture 22 - Page 8 of 8
Lecture 23 – Flexural Members
Flexural members are those that experience primarily bending stresses, such as
beams. A typical reinforced concrete beam is shown below:
Width “b”
Hanger bars
Depth to steel “d”
(#4 or #5 bars)
Height “h”
Lecture 23 - Page 1 of 9
Sometimes, 2 (or more) rows of main tension bars are necessary. It is
important to provide minimum adequate cover around all reinforcing bars
so that these bars can properly bond with the concrete. ACI 318 dictates
that the minimum spacing between bars is 1.5 times the maximum
concrete aggregate size. Typical concrete batches use a maximum
aggregate size of ¾” diameter, so then the minimum bar spacing = 1.5(¾”)
= 1⅛”.
Height “h”
Min. bar
spacing
Lecture 23 - Page 2 of 9
As = Total cross-sectional area of all tension bars, in2
Lecture 23 - Page 3 of 9
Example 1
GIVEN: A rectangular concrete beam is similar to the one shown above.
Use the following:
• Height h = 20”
• Width b = 12”
• Concrete f’c = 4000 PSI
• Concrete cover = ¾”
• All bars are A615 – Grade 60 (fy = 60 KSI)
• Stirrup bar = #3
• 4 - #7 Tension bars
REQUIRED:
1) Determine total area of tension bars, As.
2) Determine depth to center of tension bars, d.
A 200
3) Determine ρactual = s where ρmin = and state if it is acceptable.
bd fy
As = 2.40 in2
= 20” – ¾” – ⅜” – ½(⅞”)
d = 18.44”
As 200
ρactual = ρmin =
bd fy
2.40in 2 200
= =
(12" )(18.44" ) 60000 PSI
Lecture 23 - Page 4 of 9
A basic understanding of beam mechanics is necessary to study concrete beam
behavior. Consider a simply-supported homogeneous rectangular beam loaded
by a uniformly-distributed load as shown below:
Applied loads
Span L
Taking a section through the beam at any place along the length reveals the
following stress distribution about the cross-section of the beam:
Compression
Neutral
Axis The stress distribution
varies linearly from zero
stresses at the neutral
axis, to a maximum tensile
or compressive stress at
the extreme edges.
Homogeneous Beam
Tension
Lecture 23 - Page 5 of 9
In a reinforced concrete beam, the stress distribution is different. Above the
neutral axis, the concrete carries all the compression, similar to the
homogeneous beam. Below the neutral axis however, the concrete is incapable
of resisting tension and must rely on the reinforcing bars to carry all the tension
loads.
Compression
Neutral
Axis The actual stress distribution
in the compression side
varies non-linearly from zero
stresses at the neutral axis,
to a maximum compressive
stress at the extreme edge.
Looking at a side view of the stress distribution of the reinforced concrete beam:
0.85f’cb
“Whitney” stress block
½ (a)
a = β 1C
Neutral d
Axis Moment arm = Z
T = Asfy T = Asfy
Lecture 23 - Page 6 of 9
Assuming an idealized beam, tension equals compression:
Tension = Compression
Asfy = Area of Whitney stress block
Asfy = 0.85f’cab
Solve for a:
As f y
a= = β 1C
0.85 f ' c b
⎡ ⎛ ρ act f y ⎞⎤
Mu = 0.9Asfyd(1 - ⎢0.59⎜⎜ ⎟⎟⎥ )
⎢⎣ ⎝ f 'c ⎠⎥⎦
ρmax = maximum allowable ratio of tension steel reinforcement per ACI 318
= 0.75ρbal
Lecture 23 - Page 7 of 9
Example 2
GIVEN: The concrete beam from Example 1 is used to support the loading as
shown below.
REQUIRED:
1. Determine the maximum factored applied moment, Mmax.
2. Determine the usable moment capacity of the beam, Mu, and determine if
it is acceptable based on Mmax.
3. Determine if the beam is acceptable based on ρmax.
20’-0”
wu L2
Mmax =
8
(3KLF )(20'−0" ) 2
=
8
⎡ ⎛ (0.0108)(60 KSI ) ⎞⎤
= 0.9(2.40 in2)(60 KSI)(18.44”)(1 - ⎢0.59⎜ ⎟⎥ )
⎣ ⎝ 4 KSI ⎠⎦
= 2161.4 KIP-IN
Mu = 180.1 KIP-FT
Lecture 23 - Page 8 of 9
Step 3 – Determine if the beam is acceptable based on ρmax:
ρmax = maximum allowable ratio of tension steel reinforcement per ACI 318
= 0.75ρbal
= 0.0285
ρmax = 0.75(0.0285)
Lecture 23 - Page 9 of 9
Lecture 24 – Flexural Members (cont.)
⎡ ⎛ ρ act f y ⎞⎤
Mu = 0.9Asfyd(1 - ⎢0.59⎜⎜ ⎟⎟⎥ )
⎢⎣ ⎝ f 'c ⎠⎥⎦
Designing a beam using the equation above is much more difficult. Assuming the
material properties and dimensions are known, the equation above still has 2
unknown variables – As and ρact. Therefore, design of steel reinforcement for a given
beam is largely one of trial-and-error.
Beam Design
Design of concrete beam members is often one of trial-and-error. It’s difficult
to directly solve for all the variables in a reinforced concrete beam. Usually,
material properties are known as well as maximum applied factored moment,
Mmax.
Beams are usually rectangular having the width typically narrower than the
height. The diagram below shows typical beam aspect ratios:
h ≈ 1.5b → 2.5b
Lecture 24 - Page 1 of 9
Beam Design Aid
It is still difficult to directly design a reinforced concrete beam even if
dimensions and material properties are known. The use of design aids are
commonly used to streamline the design process instead of laboriously using
a trial-and-error approach.
Mu
The design aid shown below is used for design or analysis. Values of
φbd 2
are in units of PSI. It can be used to directly solve for ρact knowing factored
actual moment Mu, f’c, fy, b and d.
Lecture 24 - Page 2 of 9
Table 2 – Concrete f’c = 4000 PSI, Grade 60 Bars
Lecture 24 - Page 3 of 9
Example 1
GIVEN: A rectangular concrete beam with dimensions is shown below (stirrup bars
not shown). Use concrete f’c = 4000 PSI and grade 60 bars.
REQUIRED:
1) Determine the usable moment capacity Mu of the beam using formula.
2) Determine the usable moment capacity Mu of the beam using Table 2.
b =12”
d = 18”
3 - # 7 bars
As
ρact =
bd
ρact = 0.0083
⎡ ⎛ ρ act f y ⎞⎤
Mu = 0.9Asfyd(1 - ⎢0.59⎜⎜ ⎟⎟⎥ )
⎢⎣ ⎝ f 'c ⎠⎥⎦
⎡ ⎛ (0.0083)(60 KSI ) ⎞⎤
= 0.9(1.80 in2)(60 KSI)(18”)(1 - ⎢0.59⎜ ⎟⎥ )
⎣ ⎝ 4 KSI ⎠⎦
= 1621 KIP-IN
Mu = 135 KIP-FT
Lecture 24 - Page 4 of 9
Step 2 - Determine the usable moment capacity Mu of the beam using Table 2:
From Table 2:
Mu
At ρ = 0.0083 → = 461.4 PSI
φbd 2
Mu = 461.4 PSI(φbd2)
= 461.4 PSI[(0.9)(12”)(18”)2]
= 1,614,531 LB-IN
= 1615 KIP-IN
Mu = 134.6 KIP-FT
Lecture 24 - Page 5 of 9
Example 2
GIVEN: The concrete beam below. Use the following:
REQUIRED: Design the rectangular beam such that h ≈1.5b and ρact ≈ ½ (ρmax).
wu = 2 KLF
28’-0”
wu L2
Mmax =
8
(2 KLF )(28'−0" ) 2
=
8
= 2352 KIP-IN
= 2,352,000 LB-IN
Lecture 24 - Page 6 of 9
Step 2 – Select values from Table 2:
= ½(0.0214)
Mu
b) At ρ = 0.0107 → = 581.2 PSI
φbd 2
Step 3 – Solve for “b” and “d” by substituting Mmax for Mu in above equation:
Mu
= 581.2 PSI
φbd 2
φ = 0.9
d = 1.5b
2352000
= 581.2 PSI
(0.9)(b)(1.5b) 2
2352000
= 581.2 PSI
(0.9)(2.25b 3 )
2352000
b=3
(0.9)(2.25)(581.2)
d = 1.5b
= 1.5(12”)
d ≈ 18”
Lecture 24 - Page 7 of 9
Step 4 – Select beam dimensions:
As
From above, ρact = 0.0107 =
bd
As = 0.0107(b)(d)
= 0.0107(12”)(18.375”)
As = 2.36 in2
As
No. of bars =
Area _ of _ one _ bar
2.36in 2
=
0.79in 2 _ per _#8 _ bar
Lecture 24 - Page 8 of 9
Step 7 – Check beam height with “Minimum Thickness of Beams” Table:
From Table:
L
h≈
16
(28'−0" )(12" / ft )
≈
16
Step 8 – Draw “Summary Sketch” labeling all information necessary to build it:
12”
2 - #4 hanger
bars
#3 stirrup bars
20”
@ 9” o.c.
Notes:
1) Concrete f’c = 4000 PSI normal-weight
2) All bars ASTM A615 Grade 60
Lecture 24 - Page 9 of 9
Lecture 25 – T- Beams
Concrete beams are often poured integrally with the slab, forming a much stronger
“T” – shaped beam. These beams are very efficient because the slab portion
carries the compressive loads and the reinforcing bars placed at the bottom of the
stem carry the tension. A T-beam typically has a narrower stem than an ordinary
rectangular beam. These stems are typically spaced from 4’-0” apart to more than
12’-0”. The slab portion above the stem is designed as a one-way slab spanning
between stems (see Lecture 26).
Slab
Overhang
width d
bw Clear distance bw
NOTE: Stirrups in T-beam
are required (not shown in
this sketch)
Lecture 25 - Page 1 of 9
Assuming T-beams are symmetrical, the following design dimensions are used:
8hf
½(Clear distance)
¼(Beam span)
b = smaller or
(2 x overhang width) + bw
T-Beam Analysis
T-beams are analyzed similarly to rectangular beams, except the
compression area is a narrow “strip” usually located in the slab.
a = Effective conc.
compressive b = Effective flange width
thickness
hf
a
Z = (d - ) d
2
Ac = Shaded area
= Effective concrete
compression area As = Total area of
= (a)(b) bw
main tension bars
Lecture 25 - Page 2 of 9
Mu = Usable moment capacity of T-beam
= φTZ
where: φ = 0.9
a
=d-
2
Lecture 25 - Page 3 of 9
Example 1
GIVEN: A commercial building has T-beams spaced 6’-6” (center-to-center) with a 4”
concrete slab as shown in the framing plan and cross-section views below. Use the
following information:
• Superimposed service floor dead load (NOT including conc. wt.) = 40 PSF
• Superimposed service floor live load = 100 PSF
• Concrete f’c = 3000 PSI
• ASTM A615 Grade 60 bars
REQUIRED:
1) Determine the maximum factored moment, Mmax, on the T-beam.
2) Determine the usable moment capacity, Mu, for the T-beam.
T-beam
6’-6”
Perimeter girder Column
Typ.
Framing Plan
Lecture 25 - Page 4 of 9
6’-6”
4”
16”
2 - #9 bars
8”
wu L2
Det. Maximum factored moment, Mmax =
8
Mmax = 95 KIP-FT
Lecture 25 - Page 5 of 9
Step 2 – Determine effective concrete slab width “b”:
b = smaller or
T
=
0.85 f ' c
120 KIPS
=
0.85(3KSI )
= 47.1 in2
Lecture 25 - Page 6 of 9
Step 4 – Determine usable moment capacity, Mu for the T-beam:
47.1in 2
=
60"
a = 0.79”
a
=d-
2
0.79"
= 16” -
2
Z = 15.6”
Mu = φTZ
= 0.9(120 KIPS)(15.6”)
= 1685 KIP-IN
Mu = 140.4 KIP-FT
Lecture 25 - Page 7 of 9
Heavily-Reinforced T-Beams
T-beams with a lot of tension reinforcement may have a portion of the effective
concrete area located within the stem as shown below:
hf
d
Z
Ac = Shaded area
= Effective concrete
compression area
bw
As
Similar to ordinary rectangular reinforced concrete beams, the ACI 318 limits
the amount of tension steel in T-beams so that the steel will yield prior to
concrete compression failure. The maximum area of steel, As is shown in the
table below.
Lecture 25 - Page 8 of 9
Example 2
GIVEN: The T-beam from Example 1.
REQUIRED: Determine the maximum area of tension steel permitted, As max:
From Example 1:
Lecture 25 - Page 9 of 9
Lecture 27 – Two-Way Slabs
Two-way slabs have tension reinforcing spanning in BOTH directions, and may take
the general form of one of the following:
Lecture 27 - Page 1 of 13
The following Table may be used to determine minimum thickness of various two-
way slabs based on deflection:
Flat Plates
Flat plates are the most common type of two-way slab system. It is commonly
used in multi-story construction such as hotels, hospitals, offices and
apartment buildings. It has several advantages:
• Easy formwork
• Simple bar placement
• Low floor-to-floor heights
Lecture 27 - Page 2 of 13
The ACI 318 code allows a direct design method that can be used in most
typical situations. However, the following limitations apply:
Design Strips
a) L1 > L2:
L2 L2
Column
(typ.)
Exterior Column Strip
Interior Column Strip
Interior Column Strip
Middle Strip
Middle Strip
L1
Lecture 27 - Page 3 of 13
b) L2 > L1:
L2 L2
Middle Strip
Middle Strip
L1
1 2 3 4 5
2
wu L2 Ln
Mo = where Ln = clear span (face-to-face of cols.)in the direction of analysis
8
Lecture 27 - Page 4 of 13
Bar Placement per ACI 318-02
Lecture 27 - Page 5 of 13
Example 1
GIVEN: A two-way flat plate for an office building is shown below. Use the following:
REQUIRED: Use the “Direct Design Method” to design the two-way slab for the
design strip in the direction shown.
20’-0”
Ln 20’-0”
20’-0”
L2/4 L2/4
½ Middle strip
= ½(16’ – Col. strip) ½ Middle strip
Col. strip = ½(16’ – Col. strip)
Design Strip = 16’
Lecture 27 - Page 6 of 13
Step 1 – Determine slab thickness h:
Ln
Since it is a flat plate, from Table above, use h =
30
= 220” = 18.33’
220"
h=
30
= 7.333”
= 278.4 PSF
= 0.28 KSF
3) Successive span lengths in each direction must not differ by more than
1/3 of the longer span. YES
4) Columns must not be offset by more than 10% of the span (in direction
of offset) from either axis between centerlines of successive columns.
YES
5) Loads must be uniformly distributed, with the unfactored live load not
more than 2 times the unfactored dead load (L/D < 2.0). YES
Lecture 27 - Page 7 of 13
Step 4 – Determine total factored moment per span, Mo:
2
wu L2 Ln
Mo =
8
Mo = 188 KIP-FT
Step 5 – Determine distribution of total factored moment into col. & middle strips:
Step 6 – Determine tension steel bars for col. & middle strips:
b = 96”
8”
d
Lecture 27 - Page 8 of 13
Mu 586,800 LB − IN
=
φbd 2
(0.9)(96" )(7" ) 2
= 138.6 PSI
As
ρ=
bd
As = ρbd
= (0.0033)(96”)(7”)
= 2.22 in2
As
Number of bars required =
As _ per _ bar
2.22in 2
=
0.20in 2 _ per _#4 _ bar
Lecture 27 - Page 9 of 13
b) Column strip for region 2 :
b = 96”
8” d
Mu 699,600 LB − IN
=
φbd 2
(0.9)(96" )(7" ) 2
= 165.2 PSI
Use ρ = 0.0033
Lecture 27 - Page 10 of 13
c) Middle strip for region 2 :
b = 96”
8” d
Mu 474,000 LB − IN
=
φbd 2
(0.9)(96" )(7" ) 2
= 112.0 PSI
Use ρ = 0.0033
Lecture 27 - Page 11 of 13
Step 7 – Draw “Summary Sketch” plan view of bars:
20’-0”
4’-0” 4’-0”
16’ – 0”
Lecture 27 - Page 12 of 13
Example 2
GIVEN: The two-way slab system from Example 1.
REQUIRED: Design the steel tension bars for design strip shown (perpendicular to
those in Example 1).
20’-0”
½ Middle strip = 6’-0”
20’-0”
Lecture 27 - Page 13 of 13
Lecture 28 – Shear in Beams
Heavy loads on concrete beams produce diagonal shear cracks as shown below:
Column
Shear cracks in areas (typ.)
of high shear
Cracking in beams is normal and indicates the tension bars are actually working.
Excessive cracking needs to be controlled by additional bars called stirrups
placed perpendicular to the cracks as shown below:
Lecture 28 - Page 1 of 9
Stirrups may take the shape of the following typical configurations:
Vertical shear is carried by the concrete shear capacity and the shear
capacity provided by the stirrups. In other words:
φ = 0.75
= 2 f ' c bw d
Vu − φVc
=
φ
Lecture 28 - Page 2 of 9
If Vs < 4 f ' c bw d d
2
then Max. stirrup spacing smax = smaller of
or
24”
If 4 f ' c bw d < Vs < 8 f ' c bw d
d
then Max. stirrup spacing smax = smaller of 4
or
Av f y d
s= < Smax
Vs
Lecture 28 - Page 3 of 9
Example
GIVEN: A simply-supported concrete beam having the following: (Assume the
beam is adequate based on flexure)
wu = 5.6 KLF
(includes beam wt.)
Conc.
column
20’-0”
12”
Beam Cross-Section
Lecture 28 - Page 4 of 9
Step 1 – Determine maximum factored shear Vu at “d” away from face of support:
wu L
Simply-supported beam end reaction =
2
wu = 5.6 KLF
Vu = 47.6 KIPS
56 KIPS
0 Shear
0
Diagram
d = 1.5’
Lecture 28 - Page 5 of 9
Step 3 – Determine range where stirrups are required:
wu = 5.6 KLF
Vu = 47.6 KIPS
56 KIPS
½(φVc) = 10.25 KIPS
0 0
-47.6 KIPS
-10.25 KIPS
d = 1.5’ Stirrups Stirrups d = 1.5’
required Stirrups not required required
Vu − φVc
=
φ
Vs = 36.1 KIPS
Lecture 28 - Page 6 of 9
Step 5 – Determine stirrup spacing, s:
Then: d 18"
= = 9”
2 2
Max. stirrup spacing smax = smaller of
or
24”
2 - #3 bars
spanning crack
Av = 2(0.11 in2 per #3 bar)
= 0.22 in2
6” < 9”
Lecture 28 - Page 7 of 9
Step 6 – Determine number of stirrups – assuming only ONE spacing:
wu = 5.6 KLF
Vu = 47.6 KIPS
56 KIPS
½(φVc) = 10.25 KIPS
0 0
-47.6 KIPS
-10.25 KIPS
d = 1.5’ Stirrups Stirrups d = 1.5’
required Stirrups not required required
Lecture 28 - Page 8 of 9
Step 7 – Draw “Summary Sketch”:
20’-0”
15 - #3 U-shaped stirrups
at ea. end of beam
12”
15 - #3 Grade 60 U-
shaped stirrup bars @
6” o.c. at each end of 20”
beam
Beam Cross-Section
Lecture 28 - Page 9 of 9
Lecture 29 – Shear in Beams (cont.)
Example
GIVEN: The 20” x 34” concrete girder as shown below. Use the following:
REQUIRED: Determine the stirrup bar requirements. Assume only one spacing
for the beam.
wu = 1.2 KLF
Conc.
column
40’-0”
20”
#3 U-shaped d = 32”
h = 34”
stirrup bars
Beam Cross-Section
Lecture 29 - Page 1 of 6
Step 1 – Draw shear diagram:
wu = 1.2 KLF
Conc.
column
40’-0”
74 64.4
39.4 29.8
4.8
NOTE: All -4.8
loads are in
Kips -29.8 -29.8
-39.4 -74
32"
Vu = 74 KIPS - (1.2 KLF )
12" / ft
= 70.8 KIPS
Lecture 29 - Page 2 of 6
Step 4 – Determine range where stirrups are required:
wu = 1.2 KLF
Vu = 70.8
74 64.4
½(φVc) = 30.4
39.4
29.8
4.8
-4.8
Shear Diagram
-39.4 -74
Stirrups reqd.
= 7.5 feet
= 90”
Lecture 29 - Page 3 of 6
Step 5 – Determine shear strength provided by stirrups, Vs:
Vu − φVc
=
φ
Vs = 13.5 KIPS
Then: d 32"
= = 16”
2 2
Max. stirrup spacing smax = smaller of
or
24”
Use
Lecture 29 - Page 4 of 6
b) Check spacing requirement:
Assumed shear
crack
Av f y d
s= < Smax #3 U-shaped
Vs
stirrup bars
2 - #3 bars
spanning crack
Av = 2(0.11 in2 per #3 bar)
= 0.22 in2
See shear
diagram
⎛ (96"−32" ) + 90" ⎞
=⎜ ⎟ +1
⎝ 16" o.c. ⎠
Lecture 29 - Page 5 of 6
Step 8 – Draw “Summary Sketch”:
40’-0”
11 - #3 U-shaped stirrups
at ea. end of beam
20”
11 - #3 Grade 60 U-
shaped stirrup bars @
16” o.c. at each end of 34”
beam
Beam Cross-Section
Lecture 29 - Page 6 of 6
Lecture 30 – Development of Reinforcement, Splices, Hooks
Concrete
Rebar
T = Asfy
Ld
The development length is based upon the BOND between the rebar and the
concrete. Factors affecting this bond include the following:
Lecture 30 - Page 1 of 9
Determining Ld for Tension Bars:
d b f y αβλ
Ld =
25 f ' c
d b f y αβλ
Ld =
20 f ' c
where:
db = diameter of bar
α = alpha
= Bar location factor
= 1.3 for top reinforcement
= 1.0 for all other locations
β = beta
= Coating factor
= 1.5 for epoxy coated bars
= 1.0 for uncoated bars
λ = lambda
= Lightweight aggregate factor
= 1.3 for lightweight aggregate
= 1.0 for normal weight aggregate
Lecture 30 - Page 2 of 9
Example 1
GIVEN: A #6 rebar under tension force. Assume the following conditions:
d b f y αβλ
Ld =
25 f ' c
⎛6⎞
⎜ ⎟(60,000 PSI )(1.0)(1.0)(1.0)
Ld = ⎝ ⎠
8
25 4000 PSI
Ld = 28.5”
Concrete
#6 Rebar
Ld = 28.5”
Lecture 30 - Page 3 of 9
Assuming “normal” conditions, the following table may be used to determine
development lengths of bars in tension:
Example 2
GIVEN: The same information as Example 1.
REQUIRED: Using the table above, determine the Ld for a #6 bar.
Lecture 30 - Page 4 of 9
Determining Ld for Compression Bars:
= larger of or
Ldc = 0.0003dbfy
Example 3
GIVEN: A #6 bar in compression. Use f’c = 4000 PSI and Grade 60 bars.
REQUIRED: Determine the Ldc for the bar.
6
db f y (60,000 PSI )
Ldc = 0.02 = 0.02 8 = 14.2” ← Use
f 'c 4000 PSI
= larger of or
Ldc = 14.2”
Lecture 30 - Page 5 of 9
Lap Splices of Bars
Bars are generally fabricated to lengths of about 60’-0”, but transportation,
workability and other concerns often require bars to be less than about
40’-0” long. For long walls, beams, slabs and other situations requiring
long lengths of bars, lap splicing is commonly used. It is good practice to
place laps at regions of small tension, i.e., low moment.
Concrete
Ls
Lecture 30 - Page 6 of 9
Hooked and Bent Bars
Hooks are used in concrete members where there is not sufficient straight
length to achieve the full development length Ld.
Ldh = Lhbλ
Lecture 30 - Page 7 of 9
Where: Lhb = Basic development length of hook in tension
db
= 1200
f 'c
λ = 1.0 unless otherwise specified below:
fy
= if using other than Grade 60 bars
60,000
Re quired _ As
=
Pr ovided _ As
Example 4
GIVEN: A #5 Grade 40 bar is in tension as shown below. Use LIGHTWEIGHT
concrete with f’c = 4000 PSI.
REQUIRED: Determine the min. required hook dimensions “X”, “Y” and “Z”.
Z = Ldh
Side cover = 1½”
Y
End cover = 1½” Critical section
X = 12db
= 12(5/8”)
X = 7½”
Lecture 30 - Page 8 of 9
Step 2 – Determine dimension “Y”:
= 4(5/8”)
Y = 2½”
db
Lhb = 1200
f 'c
5
= 1200 8"
4000 PSI
= 11.9”
Ldh = Lhbλ
fy 40000 PSI
= = = 0.67
60000 PSI 60000 PSI
Ldh = Lhbλ
= 11.9”(1.0)(1.3)(0.67)
Ldh = 10.4”
Lecture 30 - Page 9 of 9
Lecture 31 – Serviceability
• Beam deflection
• Lateral drift
• Vibration
We will be focusing our discussion on beam deflection. The ACI 318-02 Code
dictates that the deflections be checked on the basis of effective moment of
inertia, Ie, under service loads. Before we can determine the value of the
effective moment of inertia, we must first have an understanding of the gross
moment of inertia, Ig, and the cracked moment of inertia, Icr.
bh 3
=
12
Lecture 31 - Page 1 of 7
Cracked Moment of Inertia Icr:
N.A. d
nAs
by 3
Icr = + nAs (d − y ) 2
3
⎡ bd ⎤
nAs ⎢ 1 + 2 − 1⎥
⎣ nAs ⎦
y=
b
Lecture 31 - Page 2 of 7
Effective Moment of Inertia, Ie:
⎧⎪⎛ M ⎞
3
⎡ ⎛M ⎞
3
⎤ ⎫⎪
Ie = ⎨⎜⎜ cr ⎟⎟ I g + ⎢1 − ⎜⎜ cr ⎟⎟ ⎥ I cr ⎬ ≤ I g
⎪⎩⎝ M a ⎠ ⎢⎣ ⎝ M a ⎠ ⎥⎦ ⎪⎭
h
=
2
Lecture 31 - Page 3 of 7
Example 1
GIVEN: A simply-supported rectangular beam is shown below. The loads
indicated are SERVICE loads. Use concrete f’c = 4000 PSI and grade 60 bars.
REQUIRED:
1) Determine the gross moment of inertia Ig of the beam.
2) Determine the cracked moment of inertia Icr of the beam.
3) Determine the maximum allowable mid-span deflection of the beam
assuming ∆allow = L/360.
4) Determine the actual mid-span deflection of the beam using Ie.
25’-0”
12”
2 - #4 hanger
bars
#3 stirrup bars
20”
@ 9” o.c.
Lecture 31 - Page 4 of 7
Step 1 – Determine gross moment of inertia Ig:
bh 3
Ig =
12
(12" )(20) 3
=
12
Ig =8000 in4
by 3
Icr = + nAs (d − y ) 2
3
= 8.04
⎡ bd ⎤
nAs ⎢ 1 + 2 − 1⎥
⎣ nAs ⎦
y=
b
⎡ (12" )(18.375" ) ⎤
(8.04)(2.37in 2 ) ⎢ 1 + 2 2
− 1⎥
= ⎣ (8.04)(2.37in ) ⎦
12"
= 6.2”
Lecture 31 - Page 5 of 7
by 3
Icr = + nAs (d − y ) 2
3
(12" )(6.2" ) 3
= + 8.04(2.37in 2 )(18.375"−6.2" ) 2
3
L
∆allow =
360
(25'−0" )12" / ft
=
360
∆allow = 0.83”
= 379,473 Lb-In
= 379.4 KIP-In
= 31.6 KIP-FT
Lecture 31 - Page 6 of 7
Ma = maximum unfactored moment at specific
location along the moment diagram
wL2
=
8
(1.5KLF )(25'−0" ) 2
=
8
Ma = 117.2 KIP-FT
⎧⎪⎛ M ⎞
3
⎡ ⎛M ⎞
3
⎤ ⎫⎪
Ie = ⎨⎜⎜ cr ⎟⎟ I g + ⎢1 − ⎜⎜ cr ⎟⎟ ⎥ I cr ⎬
⎪⎩⎝ M a ⎠ ⎢⎣ ⎝ M a ⎠ ⎥⎦ ⎪⎭
Ie = 3004 in4
5wL4
∆act =
384 E conc I e
⎛ 1500 PLF ⎞
5⎜ ⎟(25'−0" x12" / ft )
4
= ⎝ ⎠
12
384(57000 4000 PSI )(3004in 4 )
∆act = 1.22”
Lecture 31 - Page 7 of 7