Вы находитесь на странице: 1из 8

Contactors and Contactor Assemblies

Contactors for Switching Motors SIRIUS


3RT10 contactors, 3-pole
Contac tors and Contactor Assemblies

Selection and ordering data


AC/DC operation (40 Hz ... 60 Hz, DC)
Withdrawable coils
Integrated coil circuit (varistor)
Auxiliary and control conductors: screw connections
Main conductor: bar connections, for 3RT10 54 (55 kW) box terminals 1)
Size Ratings Auxiliary Rated control DT Order No. Weight
AC-2 and AC-3 utilization categories AC-1 contacts, supply approx.
Tu: up to 60 °C Tu: 40 °C lateral voltage Us
Operat. Ratings of three-phase Operat.
current Ie motors at 50 Hz and current
Ie
up to 230 V 400 V 500 V 690 V
500 V
A kW kW kW kW A NO NC AC/DC V PG 101 1 unit kg
3RT10 54 Conventional operating mechanism
S6 115 37 55 75 110 160 2 2 110 ... 127 } 3RT10 54-1AF36 3.5
220 ... 240 } 3RT10 54-1AP36
150 45 75 90 132 185 2 2 110 ... 127 } 3RT10 55-6AF36 3.1
220 ... 240 } 3RT10 55-6AP36
185 55 90 110 160 215 2 2 110 ... 127 } 3RT10 56-6AF36
220 ... 240 } 3RT10 56-6AP36
NSB0621g

S10 225 55 110 160 200 275 2 2 110 ... 127 } 3RT10 64-6AF36 5.7
220 ... 240 } 3RT10 64-6AP36
265 75 132 160 250 330 2 2 110 ... 127 } 3RT10 65-6AF36
220 ... 240 } 3RT10 65-6AP36
3RT10 7 .
300 90 160 200 250 330 2 2 110 ... 127 } 3RT10 66-6AF36
220 ... 240 } 3RT10 66-6AP36
S12 400 132 200 250 400 430 2 2 110 ... 127 } 3RT10 75-6AF36 9.1
220 ... 240 } 3RT10 75-6AP36
500 160 250 355 400 610 2 2 110 ... 127 } 3RT10 76-6AF36
NSB0605g

220 ... 240 } 3RT10 76-6AP36

3RT10 54 Solid-state operating mechanism · for DC 24 V PLC output


S6 115 37 55 75 110 160 2 2 96 ... 127 } 3RT10 54-1NF36 3.5
200 ... 277 } 3RT10 54-1NP36
150 45 75 90 132 185 2 2 96 ... 127 } 3RT10 55-6NF36 3.1
200 ... 277 } 3RT10 55-6NP36
185 55 90 110 160 215 2 2 96 ... 127 } 3RT10 56-6NF36
200 ... 277 } 3RT10 56-6NP36
NSB0645g

S10 225 55 110 160 200 275 2 2 96 ... 127 } 3RT10 64-6NF36 5.7
200 ... 277 } 3RT10 64-6NP36
265 75 132 160 250 330 2 2 96 ... 127 } 3RT10 65-6NF36
200 ... 277 } 3RT10 65-6NP36
300 90 160 200 250 330 2 2 96 ... 127 } 3RT10 66-6NF36
200 ... 277 } 3RT10 66-6NP36
S12 400 132 200 250 400 430 2 2 96 ... 127 } 3RT10 75-6NF36 9.1
200 ... 277 } 3RT10 75-6NP36
500 160 250 355 400 610 2 2 96 ... 127 } 3RT10 76-6NF36
200 ... 277 } 3RT10 76-6NP36

For further voltages, see page 3/37. 1) As an option, the 3RT10 54-1 contactor (55 kW)
For accessories, see page 3/42. can also be supplied with bar connections
For spare parts, see page 3/64. instead of box terminals. No additional charge
is made. At the 8th digit of the Order No.,
For technical data, see page 3/104, 3/120. replace the "1" with "6", e.g. 3RT10 54-6. ..
For int. circuit diagrams, see page 3/148.
For dimension drawings, see page 3/220.

3/24 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Switching Motors
3RT10 contactors, 3-pole

Selection and ordering data


AC/DC operation (40 Hz ... 60 Hz, DC)
Withdrawable coils
Integrated coil circuit (varistor)
Auxiliary and control conductors: screw connections
Main conductor: bar connections, for 3RT10 54 (55 kW) box terminals 1)
Size Ratings Auxiliary Rated control DT Order No. Price Weight
AC-2 and AC-3 utilization categories AC-1 contacts, supply approx.
Tu: up to 60 °C Tu: 40 °C lateral voltage Us
Operat. Ratings of three-phase Operat.
current Ie motors at 50 Hz and current
Ie
up to 230 V 400 V 500 V 690 V
500 V
A kW kW kW kW A NO NC AC/DC V PG 101 1 unit kg
3RT10 56
Solid-state operating mechanism · for DC 24 V PLC output/PLC relay output,
with remaining lifetime indication
S6 115 37 55 75 110 160 1 1 96 ... 127 } 3RT10 54-1PF35 3.5
200 ... 277 } 3RT10 54-1PP35
150 45 75 90 132 185 1 1 96 ... 127 } 3RT10 55-6PF35 3.1
200 ... 277 } 3RT10 55-6PP35
185 55 90 110 160 215 1 1 96 ... 127 } 3RT10 56-6PF35
200 ... 277 } 3RT10 56-6PP35
S10 225 55 110 160 200 275 1 1 96 ... 127 } 3RT10 64-6PF35 5.7
200 ... 277 } 3RT10 64-6PP35
NSB0612g 265 75 132 160 250 330 1 1 96 ... 127 } 3RT10 65-6PF35
200 ... 277 } 3RT10 65-6PP35
300 90 160 200 250 330 1 1 96 ... 127 } 3RT10 66-6PF35
200 ... 277 } 3RT10 66-6PP35

S12 400 132 200 250 400 430 1 1 96 ... 127 } 3RT10 75-6PF35 9.1
200 ... 277 } 3RT10 75-6PP35
500 160 250 355 400 610 1 1 96 ... 127 } 3RT10 76-6PF35
200 ... 277 } 3RT10 76-6PP35
3RT10 56
Solid-state operating mechanism · with AS-Interface
and remaining lifetime indication
S6 115 37 55 75 110 160 1 1 96 ... 127 } 3RT10 54-1QF35 3.5
200 ... 277 } 3RT10 54-1QP35
150 45 75 90 132 185 1 1 96 ... 127 } 3RT10 55-6QF35 3.1
200 ... 277 } 3RT10 55-6QP35
185 55 90 110 160 215 1 1 96 ... 127 } 3RT10 56-6QF35
200 ... 277 } 3RT10 56-6QP35
S10 225 55 110 160 200 275 1 1 96 ... 127 } 3RT10 64-6QF35 5.7
200 ... 277 } 3RT10 64-6QP35

NSB0611g 265 75 132 160 250 330 1 1 96 ... 127 } 3RT10 65-6QF35
200 ... 277 } 3RT10 65-6QP35
300 90 160 200 250 330 1 1 96 ... 127 } 3RT10 66-6QF35
200 ... 277 } 3RT10 66-6QP35

S12 400 132 200 250 400 430 1 1 96 ... 127 } 3RT10 75-6QF35 9.1
200 ... 277 } 3RT10 75-6QP35
500 160 250 355 400 610 1 1 96 ... 127 } 3RT10 76-6QF35
200 ... 277 } 3RT10 76-6QP35

For further voltages, see page 3/37. 1) As an option, the 3RT10 54-1 contactor (55 kW)
For accessories, see page 3/42. can also be supplied with bar connections
For spare parts, see page 3/64. instead of box terminals. No additional charge
is made. At the 8th digit of the Order No.,
For technical data, see page 3/104, 3/120. replace the "1" with "6", e.g. 3RT10 54-6. ..
For int. circuit diagrams, see page 3/148.
For dimension drawings, see page 3/220.

Siemens NS K · 2002 3/25


Contactors and Contactor Assemblies
Contactors for Switching Motors SIRIUS
3RT12 vacuum contactors, 3-pole

Selection and ordering data


AC/DC operation (40 Hz ... 60 Hz, DC)
Withdrawable coils
Integrated coil circuit (varistor)
Auxiliary and control conductors: screw connections
Main conductor: bar connections
Size Ratings Auxiliary Rated control DT Order No. Price Weight
AC-2 and AC-3 utilization categories AC-1 contacts, supply approx.
Tu: up to 60 °C Tu: 40 °C lateral voltage Us
Operat. Ratings of three-phase Operat.
current Ie motors at 50 Hz and current
Ie
up to 230 V 400 V 500 V 690 V
1000 V
A kW kW kW kW A NO NC AC/DC V PG 101 1 unit kg
Conventional operating mechanism
3RT12 6 . S10 225 55 110 160 200 330 2 2 110 ... 127 } 3RT12 64-6AF36 6.4
220 ... 240 } 3RT12 64-6AP36
265 75 132 160 250 330 2 2 110 ... 127 } 3RT12 65-6AF36
220 ... 240 } 3RT12 65-6AP36
300 90 160 200 250 330 2 2 110 ... 127 } 3RT12 66-6AF36
220 ... 240 } 3RT12 66-6AP36
S12 400 132 200 250 400 610 2 2 110 ... 127 } 3RT12 75-6AF36 9.6
220 ... 240 } 3RT12 75-6AP36
500 160 250 355 500 610 2 2 110 ... 127 } 3RT12 76-6AF36
220 ... 240 } 3RT12 76-6AP36

NSB0607g Solid-state operating mechanism · for DC 24 V PLC output


3RT12 7 . S10 225 55 110 160 200 330 2 2 96 ... 127 } 3RT12 64-6NF36 6.4
200 ... 277 } 3RT12 64-6NP36
265 75 132 160 250 330 2 2 96 ... 127 } 3RT12 65-6NF36
200 ... 277 } 3RT12 65-6NP36
300 90 160 200 250 330 2 2 96 ... 127 } 3RT12 66-6NF36
200 ... 277 } 3RT12 66-6NP36
S12 400 132 200 250 400 610 2 2 96 ... 127 } 3RT12 75-6NF36 9.6
200 ... 277 } 3RT12 75-6NP36
500 160 250 355 500 610 2 2 96 ... 127 } 3RT12 76-6NF36
200 ... 277 } 3RT12 76-6NP36

NSB0606g Solid-state operating mechanism · for DC 24 V PLC output/PLC relay output,


with remaining lifetime indication
S10 225 55 110 160 200 330 1 1 200 ... 277 } 3RT12 64-6PP35 6.4
(availa-
265 75 132 160 250 330 1 1 200 ... 277 } 3RT12 65-6PP35
ble from
March 300 90 160 200 250 330 1 1 200 ... 277 } 3RT12 66-6PP35
2002)
S12 400 132 200 250 400 610 1 1 200 ... 277 } 3RT12 75-6PP35 9.6
(availa-
500 160 250 355 500 610 1 1 200 ... 277 } 3RT12 76-6PP35
ble from
March
2002)
Solid-state operating mechanism · with AS-Interface
and remaining lifetime indication
S10 225 55 110 160 200 330 1 1 200 ... 277 } 3RT12 64-6QP35 6.4
(availa- 265 75 132 160 250 330 1 1 200 ... 277 } 3RT12 65-6QP35
ble from
March 300 90 160 200 250 330 1 1 200 ... 277 } 3RT12 66-6QP35
2002)
S12 400 132 200 250 400 610 1 1 200 ... 277 } 3RT12 75-6QP35 9.6
(availa- 500 160 250 355 500 610 1 1 200 ... 277 } 3RT12 76-6QP35
ble from
March
2002)
.

For further voltages, see page 3/37.


For further vacuum contactors, 335 kW and
450 kW (3TF68/69), see page 3/165.
For accessories, see page 3/43.
For spare parts, see page 3/64.
For technical data, see page 3/113, 3/121.
For int. circuit diagrams, see page 3/148.
For dimension drawings, see page 3/222.

3/26 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Special Applications
3RT14, 3-pole
for switching resistive loads (AC-1)

Application
AC and DC operation The contactors are suitable for (AC-1) or as contactors, for The accessories for the SIRIUS
(size S3) use in any climate. They are example in variable-speed 3RT10 contactors can also be
UC operation (AC/DC) safe from touch to DIN VDE drives which normally only have used here.
(sizes S6 to S12) 0106 Part 100. to carry the current.
IEC 60 947, EN 60 947 3RT14 contactors are used for
(VDE 0660) switching resistive loads

Selection and ordering data

Ratings Rated control DT Order No. Price Weight


AC-1 utilization category, supply voltage approx.
Tu: 40 °C Us
3RT14 46-1A . .0 Operational Ratings of three-phase loads
current Ie (p. f. = 0.95) at
up to 690 V 230 V 400 V 500 V 690 V
A kW kW kW kW PG 101 1 unit kg
With screw connections · for screwing and snapping onto
35 mm and 75 mm standard mounting rails
Size S3 · (without auxiliary contacts)
AC operation
140 53 92 115 159 24 V, 50 Hz B 3RT14 46-1AB00 1.8
110 V, 50 Hz B 3RT14 46-1AF00
nsb0061g

230 V, 50 Hz } 3RT14 46-1AP00


DC operation · DC solenoid system
140 53 92 115 159 DC 24 V } 3RT14 46-1BB40 2.7
DC 220 V B 3RT14 46-1BM40

AC/DC operation (40 Hz ... 60 Hz, DC)


Withdrawable coils
Integrated coil circuit (varistor)
Auxiliary and control conductors: screw connections
Main conductor: bar connections
Size Ratings Auxiliary Rated control DT Order No. Price Weight
AC-1 utilization category, contacts, supply voltage approx.
Tu: 40 °C lateral Us
3RT14 6 . Operat. Ratings of three-phase loads
current Ie (p. f. = 0.95) at
up to 230 V 400 V 500 V 690 V
690 V
A kW kW kW kW NO NC AC/DC V PG 101 1 unit kg
Conventional operating mechanism
S6 275 105 180 225 310 2 2 110 ... 127 } 3RT14 56-6AF36 3.1
220 ... 240 } 3RT14 56-6AP36
S10 400 151 263 329 454 2 2 110 ... 127 } 3RT14 66-6AF36 5.7
220 ... 240 } 3RT14 66-6AP36
S12 690 261 454 568 783 2 2 110 ... 127 } 3RT14 76-6AF36 9.1
220 ... 240 } 3RT14 76-6AP36
NSB0608g Solid-state operating mechanism · for DC 24 V PLC output
3RT14 7 . S6 275 105 180 225 310 2 2 96 ... 127 } 3RT14 56-6NF36 3.1
200 ... 277 } 3RT14 56-6NP36
S10 400 151 263 329 454 2 2 96 ... 127 } 3RT14 66-6NF36 5.7
200 ... 277 } 3RT14 66-6NP36
S12 690 261 454 568 783 2 2 96 ... 127 } 3RT14 76-6NF36 9.1
200 ... 277 } 3RT14 76-6NP36
Solid-state operating mechanism · for DC 24 V PLC output/PLC relay output,
with remaining lifetime indication
S6 275 105 180 225 310 1 1 96 ... 127 } 3RT14 56-6PF35 3.1
200 ... 277 } 3RT14 56-6PP35
S10 400 151 263 329 454 1 1 200 ... 277 } 3RT14 66-6PP35 5.7
S12 690 261 454 568 783 1 1 200 ... 277 } 3RT14 76-6PP35 9.1
NSB0605g Solid-state operating mechanism · with AS-Interface
and remaining lifetime indication
S6 275 105 180 225 310 1 1 96 ... 127 } 3RT14 56-6QF35 3.1
200 ... 277 } 3RT14 56-6QP35
S10 400 151 263 329 454 1 1 200 ... 277 } 3RT14 66-6QP35 5.7
S12 690 261 454 568 783 1 1 200 ... 277 } 3RT14 76-6QP35 9.1

For further voltages, see page 3/37. For spare parts, see page 3/63. For int. circuit diagrams, see page 3/148.
For accessories, see page 3/42. For technical data, see page 3/122. For dimension drawings, see page 3/218.

Siemens NS K · 2002 3/27


Contactors and Contactor Assemblies
Contactors for Special Applications SIRIUS
3RT13 contactors, 4-pole (4 NO contacts)
for switching resistive loads (AC-1)
Sizes S2 and S3 Size S0
AC and DC operation Application
Up to 4 auxiliary contacts In order to make 4-pole contac-
IEC 60 947-4-1/EN 60 947-4-1 (either laterally mounted or tor assemblies using two 3RT13 Switching resistive loads
(VDE 0660, Part 102) snapped onto the top) 2. contactors, the fourth pole of Isolating systems with
the left-hand contactor must unearthed or poorly earthed
Contactor assemblies with always be moved to the left- neutral conductors
Design mechanical interlock hand side. The contactor
The contactors are suitable for System transfers when alterna-
assembly can then be made
use in any climate. They are The 4-pole 3RT13 contactors tive AC power supplies are
easily with the aid of the
safe from touch to DIN VDE with 4 NO contacts as the main used
3RA19 24-1A mechanical inter-
0106, Part 100. contacts are suitable for mak- lock fitted onto the front and the As contactors, e.g. for vari-
The accessories for the 3-pole ing contactor assemblies with a 3RA19 22-2C mechanical con- able-speed drives which only
SIRIUS contactors can also be mechanical interlock, e.g. for nectors. The laterally mountable have to carry current and not
used for the 4-pole designs. system transfers. 3RA19 24-2B mechanical inter- switch
lock can be used if the contactor
Mountable auxiliary contacts Size S00 assembly is mounted on a base-
Contactor assemblies can be plate.
Size S00
made using two 3RT13 1.
4 auxiliary contacts
(to EN 50 005) contactors in conjunction with Sizes S2 and S3
the mechanical interlock and Contactor assemblies can be
Size S0 two connecting clips (Order made using two 3RT13 3 or
Up to 2 auxiliary contacts No.: 3RA19 12-2H, pack com- 3RT13 4. contactors in conjunc-
(either laterally mounted or prising 10 interlocking elements tion with the laterally mountable
snapped onto the top) and 20 clips for 10 contactor 3RA19 24-2B mechanical inter-
assemblies, see accessories lock and the 3RA19 . 2-2G
It is not permissible to use 2-
pole auxiliary switch blocks with on page 3/75). mechanical connectors. The
cable entry from one side mechanical interlock for fitting
(3RH19 21-1LA.. and onto the front cannot be used for
3RH19 21-1MA..) nor to use the size S2 and S3 contactors.
solid-state compatible auxiliary
switch block (3RH19 21-.FE22).

Selection and ordering data


AC operation
4 NO contacts

Ratings Rated control Screw connection Cage Clamp connection Weight


Utilization category supply voltage approx.
AC-1 Us DT Order No. Price DT Order No. Price
Tu: 40/60 °C
Operational Ratings of three-
current Ie phase loads
(p.f. = 0.95) at
50 Hz and
400 V
A kW PG 101 1 unit PG 101 1 unit kg
For screwing and snapping onto 35 mm standard mounting rail
3RT13 1.-1A . 00 Size S00 1)
18/16 12/11 24 V, 50/60 Hz } 3RT13 16-1AB00 } 3RT13 16-2AB00 0.19
110 V, 50/60 Hz } 3RT13 16-1AF00 } 3RT13 16-2AF00
230 V, 50/60 Hz } 3RT13 16-1AP00 } 3RT13 16-2AP00
22/20 14.5/13 24 V, 50/60 Hz } 3RT13 17-1AB00 } 3RT13 17-2AB00 0.19
nsb0065

110 V, 50/60 Hz } 3RT13 17-1AF00 } 3RT13 17-2AF00


230 V, 50/60 Hz } 3RT13 17-1AP00 } 3RT13 17-2AP00
Size S0
35/30 2) 22/20 24 V, 50 Hz } 3RT13 25-1AB00 – 0.36
3RT13 2.-1A . 00 110 V, 50 Hz } 3RT13 25-1AF00 –
230 V, 50 Hz } 3RT13 25-1AP00 –
40/35 2) 26/23 24 V, 50 Hz } 3RT13 26-1AB00 – 0.36
110 V, 50 Hz } 3RT13 26-1AF00 –
230 V, 50 Hz } 3RT13 26-1AP00 –

Size S00: Auxiliary switch blocks can be snapped on according to EN 50 005. .


Sizes S0 ... S3: Auxiliary switch blocks can be snapped on according to EN 50 012 and EN 50 005.
(for S0 no more than 2 auxiliary contacts, refer also to page 3/28 ).

For further voltages, see page 3/37. For description, see page 3/28. 1) Size S00:
For accessories, see page 3/41. For int. circuit diagrams, see page 3/148. Coil voltage tolerance
For spare parts, see page 3/62. For dimension drawings, see page 3/223. at 50 Hz: 0.8 ... 1.1 x Us
at 60 Hz: 0.85 ... 1.1 x Us
For technical data, see page 3/130.
2) Required conductor cross-section 10 mm2.

3/28 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Special Applications
3RT13 contactors, 4-pole (4 NO contacts)
for switching resistive loads (AC-1)

Selection and ordering data


AC and DC operation
4 NO contacts

Ratings Rated control Screw connection Cage Clamp connection Weight


Utilization category supply voltage approx.
AC-1 Us DT Order No. Price DT Order No. Price
Tu: 40/60 °C
Operational Ratings of three-
current Ie phase loads
(p.f. = 0.95) at
50 Hz and
400 V
A kW PG 101 1 unit PG 101 1 unit kg
For screwing and snapping onto 35 mm standard mounting rail
AC operation
3RT13 36-1A . 00 Size S2
60/55 39/36 24 V, 50 Hz } 3RT13 36-1AB00 – 0.93
110 V, 50 Hz } 3RT13 36-1AF00 –
230 V, 50 Hz } 3RT13 36-1AP00 –
Size S3
110/100 72/66 24 V, 50 Hz B 3RT13 44-1AB00 – 2.0
110 V, 50 Hz B 3RT13 44-1AF00 –
230 V, 50 Hz } 3RT13 44-1AP00 –
140/120 92/79 24 V, 50 Hz B 3RT13 46-1AB00 – 2.11
nsb0066

110 V, 50 Hz B 3RT13 46-1AF00 –


230 V, 50 Hz } 3RT13 46-1AP00 –
DC operation · DC solenoid system
3RT13 4.-1A . 00 Size S00
18/16 12/11 DC 24 V } 3RT13 16-1BB40 } 3RT13 16-2BB40 0.25
DC 220 V } 3RT13 16-1BM40 } 3RT13 16-2BM40
22/20 14.5/13 DC 24 V } 3RT13 17-1BB40 } 3RT13 17-2BB40 0.25
DC 220 V } 3RT13 17-1BM40 } 3RT13 17-2BM40
Size S0
35/30 1) 22/20 DC 24 V } 3RT13 25-1BB40 – 0.59
DC 220 V B 3RT13 25-1BM40 –
nsb0712g

40/35 1) 26/23 DC 24 V } 3RT13 26-1BB40 – 0.59


DC 220 V B 3RT13 26-1BM40 –
Size S2

3RT13 1.-2B . .0 60/55 39/36 DC 24 V } 3RT13 36-1BB40 – 1.56


DC 220 V B 3RT13 36-1BM40 –
Size S3
110/100 72/66 DC 24 V } 3RT13 44-1BB40 – 3.1
DC 220 V B 3RT13 44-1BM40 –
140/120 92/79 DC 24 V } 3RT13 46-1BB40 – 3.1
nsb0069

DC 220 V B 3RT13 46-1BM40 –

Size S00: Auxiliary switch blocks can be snapped on according to EN 50 005.


Sizes S0 ... S3: Auxiliary switch blocks can be snapped on according to EN 50 012 and EN 50 005.
(for S0 no more than 2 auxiliary contacts, refer also to page 3/28).

For further voltages, see page 3/37. 1) Required conductor cross-section 10 mm2.
For accessories, see page 3/41.
For spare parts, see page 3/62.
For technical data, see page 3/130.
For description, see page 3/28.
For int. circuit diagrams, see page 3/148.
For dimension drawings, see page 3/223.

Siemens NS K · 2002 3/29


Contactors and Contactor Assemblies
Contactors for Special Applications SIRIUS
3RT15 contactors, 4-pole (2 NO + 2 NC contacts)
for switching motors

AC and DC operation Design Application


IEC 60 947-4-1/EN 60 947-4-1 The contactors are suitable for It is not permissible to use 2- Changing the polarity of hoist-
(VDE 0660, Part 102) use in any climate. They are pole auxiliary switch blocks ing gear motors
safe from touch to DIN VDE with cable entry from one side Switching two separate loads
0106, Part 100. (3RH19 21-1LA.. and
The accessories for the 3-pole 3RH19 21-1MA..) nor to use Note:
SIRIUS contactors can also be the solid-state compatible 3RT15 contactors are not suit-
used for the 4-pole designs. auxiliary switch block able for switching a load
(3RH19 21-1FE22). between two current sources.
Mountable auxiliary contacts Size S2
Size S00 Up to 4 auxiliary contacts
4 auxiliary contacts (either laterally mounted or
(auxiliary switch blocks snapped onto the top; auxiliary
to EN 50 005) switch blocks to EN 50 012
and EN 50 005)
Size S0
Up to 2 auxiliary contacts
(either laterally mounted or
snapped onto the top; auxiliary
switch blocks to EN 50 012
and EN 50 005).

Selection and ordering data


2 NO contacts + 2 NC contacts 1)

Ratings Rated control Screw connection Cage Clamp connection Weight


Utilization category supply voltage approx.
Us
AC-2 and AC-3 AC-1 DT Order No. Price DT Order No. Price
Tu: up to 60 °C Tu: 40/60 °C
Operatio- Rating of Operational
nal cur- three-phase current Ie
rent Ie motors at
50 Hz and
at 400 V 400 V
A kW A PG 101 1 unit PG 101 1 unit kg
For screwing and snapping onto 35 mm standard mounting rail
AC operation
Size S00 2)
3RT15 1.-1 . . . .
9 4 18/16 24 V, 50/60 Hz } 3RT15 16-1AB00 } 3RT15 16-2AB00 0.19
110 V, 50/60 Hz } 3RT15 16-1AF00 } 3RT15 16-2AF00
230 V, 50/60 Hz } 3RT15 16-1AP00 } 3RT15 16-2AP00
12 5.5 22/20 24 V, 50/60 Hz } 3RT15 17-1AB00 } 3RT15 17-2AB00 0.19
110 V, 50/60 Hz } 3RT15 17-1AF00 } 3RT15 17-2AF00
230 V, 50/60 Hz } 3RT15 17-1AP00 } 3RT15 17-2AP00
nsb0065

Size S0
25 11 40/35 3) 24 V, 50 Hz C 3RT15 26-1AB00 – 0.36
110 V, 50 Hz } 3RT15 26-1AF00 –
3RT15 1.-2 . . . .
230 V, 50 Hz } 3RT15 26-1AP00 –
Size S2
40 18.5 55/50 24 V, 50 Hz B 3RT15 35-1AB00 – 0.93
110 V, 50 Hz B 3RT15 35-1AF00 –
230 V, 50 Hz } 3RT15 35-1AP00 –
DC operation · DC solenoid system
nsb0069

Size S00
9 4 18/16 DC 24 V } 3RT15 16-1BB40 } 3RT15 16-2BB40 0.25
3RT15 26-1 . . . . DC 220 V } 3RT15 16-1BM40 } 3RT15 16-2BM40
12 5.5 22/20 DC 24 V } 3RT15 17-1BB40 } 3RT15 17-2BB40 0.25
DC 220 V } 3RT15 17-1BM40 } 3RT15 17-2BM40
Size S0
20 11 40/35 3) DC 24 V } 3RT15 26-1BB40 – 0.59
DC 220 V B 3RT15 26-1BM40 –
nsb0068

Size S2
40 18.5 55/50 DC 24 V } 3RT15 35-1BB40 – 1.56
DC 220 V C 3RT15 35-1BM40 –

For further voltages, see page 3/37. 1) For changing polarity; 3) Required conductor cross-section 10 mm2.
For accessories, see page 3/41. not suitable for reversing.
For spare parts, see page 3/62. 2) Size S00:
For technical data, see page 3/132. Coil voltage tolerance
For int. circuit diagrams, see page 3/148. at 50 Hz: 0.8 ... 1.1 x Us
at 60 Hz: 0.85 ... 1.1 x Us
For dimension drawings, see page 3/223.

3/30 Siemens NS K · 2002


Contactors and Contactor Assemblies
SIRIUS Contactors for Special Applications
3RT16 capacitor contactors
This prevents disturbances in The capacitor contactors of The capacitor contactors of
AC operation
the power system and welding size S00 comprise an NO con- size S3 can be fitted addition-
IEC 60 947, EN 60 947 of the contactors. tact and another unassigned ally with a 2-pole auxiliary
(VDE 0660) NC contact in the auxiliary switch block (2 NO, 2 NC or
Only discharged capacitors are
switch block fitted to the basic 1 NO + 1 NC), type 3RH19 21-
The contactors are suitable for permitted to be switched on
unit. 1EA.. for lateral mounting.
use in any climate. They are with capacitor contactors.
safe from touch to DIN VDE Recommendation: use dis- The auxiliary switch block For the capacitor making and
0106 Part 100. charge chokes for parallel con- which is snapped onto the ca- breaking capacity of the basic
nection with the capacitors, pacitor contactor of sizes S0 3RT10 contactor variant, see
The 3RT16 capacitor contactors Order No.: 4EJ99 00-0EG, see and S3 contains the three lead- the technical data.
are special variants of the size Catalog SR 10.6. ing NO contacts and one stan-
S00 to S3 SIRIUS contactors. dard NO contact, which is
The capacitors are precharged unassigned. Size S00 also con-
by means of the mounted lea- tains another unassigned NO
ding NO contacts and resistors; contact in the basic unit.
only then do the main contacts
close.

Selection and ordering data


AC operation

AC-6b utilization category Auxiliary Rated control Screw connection Weight


For switching three-phase capacitors at an contacts, supply voltage approx.
ambient temperature of 60 °C 2) unassigned Us1)
Capacitor rating at operational voltage DT Order No. Price
50/60 Hz
230 V 400 V 500 V 690 V
kvar kvar kvar kvar AC PG 101 1 unit kg
For screwing and snapping onto 35 mm standard mounting rail
3RT16 27-1A . 01 Size S00
4 - 7.5 7 - 12.5 9 - 15 12 - 21 2 NO 24 V, 50 Hz B 3RT16 17-1AB03 0.24
110 V, 50 Hz B 3RT16 17-1AF03
230 V, 50 Hz } 3RT16 17-1AP03

Size S0
0

8 - 15 14 - 25 18 - 30 24 - 42 1 NO 24 V, 50 Hz C 3RT16 27-1AB01 0.38


07

110 V, 50 Hz C 3RT16 27-1AF01


b0

}
ns

230 V, 50 Hz 3RT16 27-1AP01

3RT16 47-1A . 01

Size S3
16 - 30 28 - 50 36 - 60 48 - 84 1 NO 24 V, 50 Hz B 3RT16 47-1AB01 1.93
110 V, 50 Hz B 3RT16 47-1AF01
230 V, 50 Hz } 3RT16 47-1AP01

nsb0071

For further voltages, see page 3/37. 1) Coil voltage tolerance: 0.85 ... 1.1 x Us.
For accessories, see page 3/43. 2) For size S3: 55 °C.
For technical data, see page 3/134.
For wiring diagram, see page 3/152.
For dimension drawings, see page 3/224.

Siemens NS K · 2002 3/31