IEEE TRANSACTIONS ON SUSTAINABLE ENERGY 1

Combined Central and Local Active and Reactive


Power Control of PV Inverters
Sam Weckx, Student Member, IEEE, Carlos Gonzalez, and Johan Driesen, Senior Member, IEEE

Abstract—The increasing amount of photovoltaic (PV) generation insufficient voltage support when local parameters are not tuned
results in a reverse power flow and a violation of the overvoltage limits to the structure of the grid. Most of these local controllers are
in distribution networks. PV inverters can curtail active power or characterized by only one parameter, making it impossible to be
consume reactive power to avoid these excessive high voltages. Local
controllers of active and reactive power that are based on measure- optimal for different states of the system. Besides that, local
ments of the produced PV power have a fast response to the changing controllers cannot avoid transformer overloading.
production levels of the PV installation. The performance of these local The installation of a communication infrastructure for smart
controllers depends on the tuning of the control parameters, which are metering offers new possibilities for voltage control. Intelligence
grid and time dependent. In this paper, local control functions are can be added to a substation or another local agent responsible for
defined as piecewise linear functions. The parameters of all the local
control functions are regularly reoptimized. This results in an optimal network control. An optimization of reactive power consumption
use of reactive power and a minimum amount of curtailed active results in the most efficient reactive power support to avoid
power, while respecting network limitations. The optimization of these overvoltage or to remain in a specified voltage band. This
parameters is formulated as a convex optimization problem, which optimization can be performed at a central unit [8]–[10] or by
can be solved sufficiently fast. The performance of the control is an iterative communication procedure between intelligent neigh-
evaluated on an existing three-phase four-wire distribution grid and
is compared with different local control methods. boring PV inverters [1], [11], [12]. However, system conditions
in a grid with a high penetration of PV generation can rapidly
Index Terms—Central control, convex optimization, local
change due to the movement of clouds. It is, therefore, important
control, photovoltaic (PV) generation, power curtailment,
reactive power control, voltage control. that the reactive control can adapt to changing system conditions
[13]. Reactive power support as planned by an optimization unit
can, therefore, become insufficient or excessive when no real-
I. INTRODUCTION time optimization is performed. Computational and communi-
cational burdens might hinder this real-time implementation.
HE increasing penetration of photovoltaic (PV) panels
T challenges the future grid operation. During periods of
low demand, the high active power injection by the PV inverters
Local controllers are not vulnerable to these changing conditions.
The amount of reactive power that can be supplied is limited.
At time steps of high active power production, the part of
can result in transformer overloading or a rise of the grid voltage to
the inverter capacity remaining for reactive power might not be
critical levels. Voltage rise is normally the main limiting factor to
sufficient to keep the voltage at acceptable levels. Moreover, due
prevent the increase in PV generation in low-voltage (LV) net-
to the high values in LV networks, the effect of reactive
works [1]. PV inverters provide their nominal or maximum power
power is limited. Active power curtailment is then required to
during just a small fraction of the time so that the remaining power
avoid a violation of the upper voltage limit. Local active power
capacity available in the inverter can be used for voltage control.
curtailment methods are proposed in [1], [14], and [15]. This
Voltage control by reactive power control and active power cur-
curtailment is a direct cost to the owner of the PV panels due to
tailment is shown to be an economically interesting solution [2].
the reduction of generated energy. It is, therefore, recommended
Different local reactive power control methods are proposed.
to make optimal use of the available reactive power to minimize
These include methods based on local voltage measurements [1],
the amount of active power curtailment.
[3]–[5], local power production measurements [1], [3], [4], [6], or
In this paper, a centralized optimization algorithm optimizes
a combination of both [3], [4]. In [7], local measurements are
the parameters of the local controllers every 15 min. The local
used to define the voltage reference for a reactive voltage
controllers are optimized to obtain near-optimal performance,
controller. These local control methods can result in a significant
even when the PV production changes due to cloud movement in
amount of unnecessary reactive power consumption or
this 15-min time period.
Manuscript received September 10, 2013; revised December 05, 2013; In [16], a centralized optimization algorithm tunes one pa-
accepted January 09, 2014. The Flemish Institute for Technological Research rameter of each local reactive power controller reacting on local
VITO and Research group ELECTA are members of the Energyville Research measurements of the voltage. In this paper, both curtailed active
Institute.
S. Weckx is with Research group ELECTA, KU Leuven, 3001 Leuven, and reactive power are controlled based on a local measurement
Belgium, and also with the Flemish Institute for Technological Research VITO, of the produced PV power. The local control methods are defined
Boerentang 200 Mol, Belgium (e-mail: sam.weckx@esat.kuleuven.be). by multiple parameters, resulting in a more optimal behavior.
C. Gonzalez and J. Driesen are with Research group ELECTA, KU Leuven,
3001 Leuven, Belgium. The corresponding optimization problem is a convex optimiza-
Digital Object Identifier 10.1109/TSTE.2014.2300934 tion problem, which can be solved efficiently.

1949-3029 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY

This paper is structured as follows. In Section II, the effec-


tiveness of reactive voltage control in three-phase four-wire
unbalanced radial distribution networks is studied. In Section III,
the convex optimization problem that results in the tuning of
the local control parameters is presented. The test system is
described in Section IV. Finally, Section V discusses the obtained
results and compares them with different local control methods.

II. EFFECTIVENESS OF REACTIVE POWER IN THREE-PHASE


FOUR-WIRE LV NETWORKS
Distribution networks are characterized by low values. It Fig. 1. Neutral-point shifting due to the absorption of reactive power in phase :
is well described in literature that for a single-phase line with (a) PV inverter connected to phase and (b) phase voltages before and after
absorption of reactive power in phase .
mainly resistive line impedance, reactive power has a limited
effect on the voltage [3], [17]. European LV distribution net-
works are, however, often of the three-phase four-wire type. The measurement of the produced PV power. The first two local
connection of single-phase loads and PV units to three-phase control methods only use reactive power. Reactive voltage
four-wire LV networks will not only alter the voltage profile in control alone can sometimes be insufficient and active power
the connected phase, but also the two other phase voltages due to also needs to be curtailed to avoid excessively high voltages. The
a neutral-point shift [18]. The neutral-point shift origins from the third local control method combines reactive voltage support
return current through the neutral conductor. Consider a three- with active power curtailment. Active power curtailment starts
phase four-wire cable with with a PV unit connected at from a voltage of 1.09 p.u. with a total reduction of the produced
one side and a delta-grounded wye (Dyn) transformer with a power at 1.11 p.u. The reactive power contribution from the
perfectly balanced network at the other side. Fig. 1 presents the inverters that are nearest to the transformer will be negligible
phase voltages before and after reactive power absorption of a PV since the measured voltage levels at these inverters will be lower,
unit connected to phase . The phase voltages are considered to and therefore, can result in a weaker voltage support [4]. If the
be balanced before reactive power absorption by the PV panel. reactive power capabilities of inverters close to the transformer
The full line is the phase voltage before the absorption of reactive want to be exploited, the droop parameters have to be made
power, and the dashed line is the phase voltage after the location-dependent [14].
absorption. Inverters equipped with the fourth local control method react
Reactive power absorption in phase significantly increases to a local measurement of the produced PV power. Inverters
the phase voltage of phase and decreases the phase voltage of close to the transformer will participate in voltage control, but
phase . Therefore, in grids with low values, decreasing have no feedback about the actual voltage. Time periods with a
the voltage in one phase can be done with less reactive power large amount of PV generation often do not coincide with the
injection in another phase than by absorbing reactive power in moments of peak power demand. This results in a rise of the grid
the specific phase itself. This effect is important for reactive voltage. A controller based on a local measurement of the
power control in grids where PV panels are not equally spread produced power can help to avoid voltage limit violations by
across the three phases. When the voltage rises to critical levels in absorbing reactive power during peak production. This fourth
the phase with the highest PV production, local reactive con- local control method requires the inverter to have a higher rating
trollers of PV panels connected to the other phases could respond than the maximal produced PV power. It is assumed that each
as well. These panels can make their reactive power support inverter can still inject or absorb reactive power to obtain a
dependent on their PV production, as a high PV production can of 0.95 at maximal PV production.
be a good indication of overvoltage in the phase with the highest The local control methods in Fig. 2 will not result in a
PV production. A central optimization of all the local control minimum use of reactive power while avoiding voltage pro-
parameters which is regularly repeated can take this into account. blems. In this work, local control parameters are centrally
Neutral-point shifting also occurs with active power injection. optimized to guarantee these conditions. The optimized local
As shown in [18], active power injection in one phase increases controllers react to their PV output power, like local control
the voltage of that phase, but decreases the voltage in the other method 4. The control functions are first-order splines. A first-
two phases. Therefore, grids where the PV installations are order spline is a piecewise linear function. The place where the
unequally distributed across the three phases are significantly piecewise functions of the spline connect are called knots. For a
more vulnerable to overvoltage [19]. PV generation in a distri- given time step, the control function is divided into a fixed
bution grid is rarely spread equally across the three phases, amount, i.e., 10, of piecewise functions for the range of possible
resulting in phases that can be more vulnerable to severe voltage PV output power levels. For a PV output power level that is
rises than others. constrained in the interval between two knots, the output value of
Four different local voltage control methods are presented in the controller is defined through linear interpolation. The output
Fig. 2 [3], [4]. The first three controllers react to the local voltage value of the local controller at each knot is optimized. Therefore,
measurement, whereas the fourth controller reacts on a local the more knots that are used, the better the performance of the
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

WECKX et al.: COMBINED CENTRAL AND LOCAL ACTIVE AND REACTIVE POWER CONTROL OF PV INVERTERS 3

Fig. 2. Four different local control methods: (a) local control method 1 ;
(b) local control method 2 ; (c) local control method 3 , ; and
(d) local control method 4 .
Fig. 3. Example of two optimized local control functions defined by a piecewise
linear function with 10 knots: (a) local control function for a PV unit connected to
controller, but the higher the computational complexity. In this the phase with the highest PV production and (b) local control function for a PV
work, the amount of knots is limited to 10. This leads to good unit connected to a phase with less PV production.
results, as shown in Section V, and has a limited computational
complexity. between two optimization steps at night, justifying a constant
Fig. 3 shows two local control functions, each consisting of 10 reactive power control.
piecewise functions. Both curtailed active and reactive power are
controlled. The first local control function is a typical control
III. OPTIMIZATION PROBLEM
function of the phase with the highest PV production. Starting
from a certain level of power output, reactive power is absorbed The centralized control system should determine setpoints of
to reduce the voltage. For higher power output levels, active the reactive power and curtailed power of PVs based on the
power also needs to be curtailed. The second local control expected PV output power during the next time period. In
function is a typical control function of a phase with less PV practice, however, the PV output power in the next time period
production. As was shown in Fig. 1, when voltage problems can vary significantly due to the movement of clouds and is
occur, i.e., in phase due to a higher amount of rated PV power uncertain. To cope with this uncertainty, the local controllers are
connected to this phase, reactive power injection in phase can tuned by the central optimization for different possible PV
decrease the phase voltage in phase . Therefore, starting from a production levels. These different levels are discretized,
certain power output, the controller injects reactive power to e.g., 10 points, which form the knots of a first-order spline.
decrease the voltage in the other phase. From a certain amount of Constraints are then defined for each possible knot of the spline.
produced power, the voltage will increase in its own phase and Two examples of optimized local control functions defined by
the reactive power injection has to be limited. For high amounts splines were already presented in Fig. 3.
of produced power, the inverter rating will limit the reactive The PV inverter complex output power is limited by the
power injection. Active power needs only be curtailed at very nominal inverter apparent power rating
high production levels. The knots of the splines are marked by
dots in Fig. 3. By regularly retuning the knots of the splines, i.e.,
every 15 min, the local controller that reacts on the produced
power can adapt to increasing and decreasing loads, i.e., during where is the produced PV power by the inverter connected
lunchtime. to node , for knot (kW); is the curtailed PV power by the
At night, when the produced PV power is zero, the proposed inverter connected to node , for knot (kW); and is the
method reduces to a standard central reactive voltage control reactive power by the inverter connected to node , for knot
method, where the reactive power injected or absorbed by the PV (kvar).
inverters remains constant until the next central optimization of If a spline of 10 knots is applied, each inverter has 10 complex
reactive power takes place. There is a lower correlation between output power constraints (1) as for each possible PV output
load profiles, resulting in smaller voltage fluctuations in the time power level the inverter rating should be respected. The inverter
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY

cannot curtail more than the produced PV power, which requires The voltage estimation is done based on information of the
constraint previous time step. It is considered that households are equipped
with smart meters. This way, the voltage at node , caused by the
load of the households , can be calculated by performing a
load flow with the load of the households. An alternative way to
A constraint on the power factor can be set by a linear obtain is to use a measurement of the voltage in node and
constraint subtract the influence of the PV units on this voltage during the
previous time step by making use of the sensitivity factors.
All the possible voltages should be limited between a mini-
mum and maximum voltage
where is a constant defining the allowable ratio between
reactive and active power.
The first-order splines formed by the knots and
define the functions and . All where and are the minimum and maximum allowed
the points of these functions will satisfy constraints (1), (2), and voltages. As previously stated, the voltages in the beginning of
(3). The convexity of these constraints implies that any point on a the feeder should not be considered to reduce the amount of
straight line between two points in the convex set is part of the set constraints. Small violations of constraint (5) can exist due to
and, therefore, satisfies the inverter limits. This justifies the limited variations of the base load and linearization errors by the
discretization in a limited amount of points. linear models. This can be avoided by introducing a small extra
For all different PV output levels, the voltage should remain conservative margin in the limits of (5). The voltage is limited to
within limits. The influence of PVs on the voltage magnitude can of the nominal voltage, but to include a conservative
be approximated with a linearized model [9], [20]–[22], resulting margin, and are chosen to be of the nominal
in an affine constraint. The voltage at node , for a set of possible voltage. All possible voltages should comply with the voltage
output powers can be defined as limits. Due to the convexity of constraints (4) and (5), every
voltage caused by a linear interpolation obtained by the splines
will comply with these limits when the relative output power of
each PV inverter is equal.
The objective of the controllers is to curtail as little active
where is the voltage at node due to the load of the power as possible. A small penalty term for reactive power is
households during the previous time step (V); is the voltage added to the objective function to avoid the use of reactive power
at node with the local controllers activated (V); is the when no critical voltage conditions can be reached. The unnec-
sensitivity of the voltage magnitude in node by active power essary use of reactive power could lead to increased losses. The
injected at node (V/kW); and is the sensitivity of the total amount of reactive power is automatically constrained by
voltage magnitude in node by reactive power injected at node the limits of the inverters. A small weighting factor equal to
(V/kvar). 0.01 is introduced to ensure that the reduction of curtailment
For each set of possible output powers , a voltage dominates the penalty term for reactive power. Smaller positive
exists. Due to the small geographical area, the produced PV weighting factors can be applied. The final optimization problem
output power relative to the nominal power production is defined as
could be considered as equal. Having a spline of 10 knots
for each PV inverter will then result in 10 possible voltages at
each node .
In practice, the irradiation between different PV panels can
slightly differ due to cloud movement. When using splines with
10 knots, the amount of possible combinations, and therefore,
also possible voltages to include, equals , although a lot of The solution of this convex optimization problem defines all
combinations are very unlikely and all combinations with only the knots of the piecewise linear local control functions. The
low PV production levels will not cause any problems. Some active and reactive power are defined in kW and kvar.
relevant combinations of different irradiation levels could also be Different extra constraints can be added to optimization
included by sampling some scenarios. These scenarios represent problem (6). Fair active power curtailment can be imposed by
a realistic cloud pattern with lower irradiation in a certain area of the next constraint
the distribution grid. This will increase the number of constraints.
Simulation results, though, show that defining the splines based
on the assumption of equal relative PV output power level gives
good results, even when the relative output power is not equal.
Typically, the voltages of a limited amount of control points at This constraint results in an equal percentage of curtailed
the end of the feeders have to be considered, as these are subject power when PV panels produce the same percentage of the
to the largest voltage deviations. This can again significantly nominal power. Another possibility is to allow only active
reduce the number of constraints. power curtailment, as in [14]. This can be achieved by adding a
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

WECKX et al.: COMBINED CENTRAL AND LOCAL ACTIVE AND REACTIVE POWER CONTROL OF PV INVERTERS 5

constraint that makes equal to zero. If transformer over-


loading can take place, a constraint on the maximal apparent
power can be introduced. Again this constraint has to hold for all
possible PV output power levels

where and form the load of the household connected to


node and is the maximal apparent power going through the
transformer. The sum of the (estimated) active and reactive
household loads can be replaced with an estimate of the total
active and reactive load.
Fig. 4. Measured PV profile and 15 min ahead PV prediction for both
In this paper, the adaptive central controller is compared to the a sunny and cloudy day (top) and the prediction error for both days (bottom).
local control methods in Fig. 2 and compared to a static central
controller. In a static central optimization, the setpoints for the
reactive power and curtailed active power are defined and do not arrangement in Belgium. The network consists of 62 customers
depend on local measurements of the produced power. To define and is depicted in Fig. 5. This network is a semi-urban reference
these setpoints, it is assumed that the PV power is constant during network in the LINEAR project [25]. It has been used to
the next time period and equals its expected value. For time scales investigate the impact of an increasing amount of PV [19],
shorter than 1 h, forecasts based on a persistence model tend to [20] in public LV distribution networks. It was shown that it
outperform satellite-based forecasting methods [23], [24]. Fig. 4 can cope with PV units installed at the rooftop of 50% of all the
shows the 15-min ahead prediction by a persistence model for a houses. Overloading of the transformer did not occur.
sunny and cloudy day. It is clear that forecast errors increase in All main feeder cables are of type EAXVB 1 kV
the presence of clouds and, therefore, the performance of a static except for the cable between nodes 2 and 4, which is of type
central controller will decrease. The smaller the time period EAXVB 1 kV . Cable properties are defined in
between consecutive optimizations, the faster the central con- Table I. The impedance values are calculated according to design
troller can correct for prediction errors due to clouds. The static specifications in the Belgian standard for underground distribu-
calculation of both reactive and curtailed active power becomes tion cables NBN C33-322 [26] with an assumed operating
temperature of 45 . All households have a single-phase
connection with a nominal line-to-neutral voltage of 230 V and
are equally spread across the three phases. The voltage at the
secondary side of the transformer is considered to be 235 V
during no load, which can be considered as a typical LV
transformer tap to avoid low voltages at the end of the feeder.
Statistically representative residential load profiles are available
to perform load flow simulations. A constant power load model
was assumed. Generation of these load profiles is described in
[27]. No data of reactive power consumption by loads was
available and reactive power by loads is, therefore, neglected
in the simulation.
The PV profile was measured at a fixed rooftop PV installation
where is the expected power production of the PV unit at KU Leuven with a time step of 1 min. All PV panels are
connected to node during the next time step as predicted by the assumed to have equal orientation. The PV generation units have
persistence model. The obtained setpoints and can be a nominal capacity of 5 kVA and are unequally spread across the
locally overruled when inverter constraints are not met because phases. All households connected to phase have a PV unit,
of forecast errors. That is, when the PV production suddenly whereas only 50% of the other households have a PV unit. The
unexpectedly drops, the curtailed active power remains limited to voltage is limited to of the nominal voltage. The time step
this level. used in the simulation is 1 min.

IV. SIMULATED NETWORK V. RESULTS


The network used in the simulations is an existing three- In this section, the four local controllers in Fig. 2 are compared
phase four-wire radial distribution system with a TT earthing both with the adaptive central control method, which tunes the
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY

Fig. 5. The network used in the simulations. All lengths are drawn to scale.

TABLE I
PROPERTIES SIMULATED NETWORK
OF THE

local control functions by solving (6), and with the static central
optimization (9) of the PV inverters.
One week in summer is simulated on a 1-min basis. To take
into account cloud movement, the PV profiles of all households
with an index higher than 40 were delayed by 1 min to obtain
more realistic PV profiles [28]. The local control functions
though are tuned under the assumption that the PV profiles of
all households are equal. Even with this assumption, perfor-
mance of the adaptive controller is superior as will be shown in
Fig. 6. Empirical cdf of the maximum grid voltage for different control methods.
this section. All voltages are obtained by applying the backward–
forward sweep power flow method [29]. Convergence problems
due to the nondifferentiable points of the voltage-dependent local
controllers [3] are mitigated by applying a diminishing step size unable to adapt to quickly changing conditions, i.e., to a sudden
in the backward–forward sweep power flow method. The adap- increase of irradiation in the area. The combined central and local
tive central controller updates the local control parameters every control approach is better at adapting to these changing condi-
15 min, whereas the static central controller updates the setpoints tions and significantly reduces excessive voltages. To avoid
of the reactive power and curtailed active power every 15 min. excessive high voltages, the third local control method and the
No constraint to impose fair active power curtailment (7) is added proposed combined central and local control approach should be
in the first simulation. preferred.
In Fig. 6, an empirical cumulative distribution function (cdf) An advantage of centrally coordinated controllers is that they
plots the maximum voltage occurring in the grid. Voltages above can ask to inject/absorb reactive power in one phase to avoid
1.1 p.u. need to be avoided. The first local control method shown excessive voltages in another phase. Therefore, reactive voltage
in Fig. 2 reduces the maximum voltage, but fails to avoid voltages support is more equally spread across the three phases, resulting
above 1.1 p.u. With this local control method, all PV panels will in decreased losses. The individual reactive power support by
absorb high amounts of reactive power. However, due to the each household is presented in Fig. 7. In this figure, a modified
neutral-point shifting effect discussed in Section II, reactive box plot [20] is applied to display the reactive power support. An
power absorption in one phase can increase the voltage in another additional box, spanning the 5th–95th percentiles, is added to the
phase. In unbalanced three-phase four-wire grids, this will result standard box plot. Phase has a higher loading due to the higher
in higher voltages of the phase with the highest installed PV penetration level of PV generation. High voltages mainly occur
generation. The fourth local control method also absorbs high in this phase. The first local control method results in excessive
amounts of reactive power in all phases at the same time, and reactive power support by each household. With the second and
therefore, reduces the voltage insufficiently. The second local third local control method, only nodes with high voltages will
controller only absorbs reactive power in phases with high absorb reactive power to reduce the voltage. The last local control
voltages, which clearly improves the voltage reduction. To method results in equal reactive power absorption of all nodes,
further reduce high voltages, active power curtailment can be including the nodes of low loaded phases, which is less efficient.
added to the second local control method, which is done in the The adaptive central method results in both reactive power
third local control method. This further improves the perfor- injection and absorption of all nodes. Depending on the phase
mance of the voltage control. The static central controller is of the connection, PV units absorb or inject reactive power. This
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

WECKX et al.: COMBINED CENTRAL AND LOCAL ACTIVE AND REACTIVE POWER CONTROL OF PV INVERTERS 7

TABLE II
AVERAGE DAILY SYSTEM LOSSES AND THE AVERAGE TOTAL AMOUNT OF CURTAILED
ACTIVE POWER IN THE GRID FOR DIFFERENT CONTROL METHODS

Fig. 7. Reactive power support of each household for different control methods.
A modified box plot is used, where the whiskers extend to the minimum and
maximum values.

is because excessive voltages occur mainly in phase due to the


higher PV penetration. Injecting reactive power in phase
Fig. 8. Total produced power for fair and unfair active power curtailment with
reduces the voltage in phase due to the neutral-point shifting. and without reactive voltage control: (a) with reactive power control and
The application of the first local control method results in (b) without reactive power control.
excessive use of reactive power and, therefore, an unnecessary
extra loading of grid components. The application of the second
and third local control method results in increased loading of the daily produced energy in the grid during this week in summer
highest loaded phase , whereas applying the last local control equals 810 kWh, so the amount of curtailed energy is almost
method results in an equal increased loading of each phase. negligible. Local control method 3, which had a similar perfor-
Avoiding the extra power through the highest loaded phase is mance in avoiding voltage limit violations as the proposed
beneficial for the system losses. combined central and local control approach, has increased
A comparison between the losses and the amount of curtailed losses and curtails more energy. In case of a failure in the
energy is provided in Table II. A traditional voltage control is communication system, local control method 3 could be applied
added, where a PV installation will disconnect for 10 min in case as a less optimal backup for the proposed method.
of any voltage limit violation and reconnect when the voltage is In the previous simulation, active power curtailment was
within limits again. This type of control results in a high amount unfair: customers connected to phase curtailed more power.
of curtailed energy. Due to the disconnection of many units, the By adding constraint (7) to the optimization formulation of
peak load seriously drops, which results in a significant decrease the local control functions, all PV panels will curtail an equal
of the average amount of losses. Without any type of voltage percentage of the generated power. This will result in an
control the losses are lower than with reactive voltage control. No increased total amount of curtailed energy, because PV panels
reactive power is absorbed or injected. The assumed constant to nonproblematic phases will also curtail produced energy. The
power model of both the loads and the PV-units will then result in total active power produced for both fair and unfair curtailment is
smaller currents in case of higher voltages. The central methods plotted in Fig. 8(a). In case of fair curtailment, the extra reduction
have smaller losses than the local methods due to the more of produced power is limited due to the intelligent application of
optimal use of reactive power. If necessary a limited amount of reactive power. There is a limited amount of increased curtailed
active power is curtailed by the central methods. The average energy during peak production only.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON SUSTAINABLE ENERGY

VI. FURTHER RESEARCH


In this paper, local control parameters are tuned repeatedly to
control reactive power and the curtailed active power in unbal-
anced distribution grids. It can be investigated how often the
local control parameters have to be adapted. That is, local control
parameters can be tuned for a whole week to avoid overvoltage.
The amount of communication is decreased, at the expense of
reduced performance.
In this paper, the local controllers react to changes of the
produced PV power. Another interesting extension would be to
make the local controller react to local voltage measurements as
well. The optimization of the control parameters then becomes a
non-convex problem, requiring global optimization methods or
algorithms that can generate acceptable solutions in a limited
computation time.

VII. CONCLUSION
This papers describes a combination of a central and local
control method for voltage control by PV inverters in unbalanced
distribution grids. It was shown that in unbalanced three-phase
four-wire grids the neutral-point shifting effect requires special
care for active and reactive power control. The reactive and
curtailed active power controlled by the PV inverters are a
function of the produced PV power and are defined by a first-
order spline. The parameters of all the splines are regularly
retuned by a central convex optimization program, i.e., every
15 min. This way, the local controllers can respond quickly to
changing weather conditions, while a central optimization of the
local parameters guarantees a near-optimal use of the reactive
power and a minimum amount of curtailed active power.
Simulations show that the proposed control ensures that the
voltage complies with the limits, while it results in fewer losses
Fig. 9. Individual average daily curtailed active power of each household for than the local control methods. It curtails less active power than
fair and unfair active power curtailment with and without reactive voltage
control. local control methods that curtail active power and is able to
curtail active power in a fair way.

Fig. 8(b) plots the total produced power for both fair and unfair
curtailment when reactive power injection or absorption by the REFERENCES
PV generation is not permitted. Without reactive power control, [1] G. Mokhtari, A. Ghosh, G. Nourbakhsh, and G. Ledwich, “Smart robust
the active power curtailment has to be increased to comply with resources control in LV network to deal with voltage rise issue,” IEEE
the voltage limits. Fair active power curtailment will then result Trans. Sustain. Energy, vol. 4, no. 4, pp. 1043–1050, Oct. 2013.
[2] T. Stetz, F. Marten, and M. Braun, “Improved low voltage grid-integration
in a significant reduction of the produced power. This empha- of photovoltaic systems in Germany,” IEEE Trans. Sustain. Energy, vol. 4,
sizes the need for reactive power support by PV panels when the no. 2, pp. 534–542, Apr. 2013.
goal is to produce a maximum amount of renewable energy [3] K. Turitsyn, P. Sulc, S. Backhaus, and M. Chertkov, “Options for control of
reactive power by distributed photovoltaic generators,” Proc. IEEE, vol. 99,
without violating voltage limitations. The individual average no. 6, pp. 1063–1073, Jun. 2011.
daily active power curtailment for each PV unit is shown in [4] E. Demirok, P. Casado Gonzalez, K. H. Frederiksen, D. Sera, P. Rodriguez,
Fig. 9. In case of unfair curtailment, only a handful of customers and R. Teodorescu, “Local reactive power control methods for overvoltage
prevention of distributed solar inverters in low-voltage grids,” IEEE
is curtailing power. Especially, the customers connected at the J. Photovolt., vol. 1, no. 2, pp. 174–182, Oct. 2011.
end of the feeder to phase will have the disadvantage of [5] P. Vovos, A. Kiprakis, A. Wallace, and G. Harrison, “Centralized and
increased curtailment. The extra cost of fair curtailment will be distributed voltage control: Impact on distributed generation penetration,”
IEEE Trans. Power Syst., vol. 22, no. 1, pp. 476–483, Feb. 2007.
significantly higher without reactive power control. This cost [6] M. Braun, T. Stetz, R. Bründlinger, C. Mayr, K. Ogimoto, H. Hatta,
depends on the compensation the distribution system operator H. Kobayashi, B. Kroposki, B. Mather, M. Coddington, K. Lynn,
(DSO) will pay to the owners of the PV panels due to the G. Graditi, A. Woyte, and I. MacGill, “Is the distribution grid ready to
accept large-scale photovoltaic deployment? State of the art, progress,
reduction of generated energy and the cost of grid losses. An and future prospects,” Prog. Photovolt. Res. Appl., vol. 20, no. 6,
economic analysis is outside the scope of this text. pp. 681–697, 2012.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

WECKX et al.: COMBINED CENTRAL AND LOCAL ACTIVE AND REACTIVE POWER CONTROL OF PV INVERTERS 9

[7] K. Tanaka, M. Oshiro, S. Toma, A. Yona, T. Senjyu, T. Funabashi, and [25] E. Peeters, C. Develder, J. Das, J. Driesen, and R. Belmans, “Linear:
C. Kim, “Decentralised control of voltage in distribution systems by Towards a breakthrough of smart grids in Flanders,” in Proc. 2nd Int.
distributed generators,” IET Gener. Transm. Distrib., vol. 4, no. 11, Conf. Innov. Sustain. Prod., vol. 3, Bruges, Belgium, Apr. 18–21, 2010,
pp. 1251–1260, 2010. pp. 3–6.
[8] G. Valverde and T. Van Cutsem, “Model predictive control of voltages in [26] Kabels Voor Ondergrondse Aanleg, met Synthetische Isolatie en Versterkte
active distribution networks,” IEEE Trans. Smart Grid, vol. 4, no. 4, Mantel (Type 1 kV), NBN Standard C 33-322, 1975.
pp. 2152–2161, Dec. 2013. [27] W. Labeeuw and G. Deconinck, “Residential electrical load model based on
[9] Y. He, M. Petit, and P. Dessante, “Optimization of the steady voltage profile mixture model clustering and Markov models,” IEEE Trans. Ind. Informat.,
in distribution systems by coordinating the controls of distributed genera- vol. 9, no. 3, pp. 1561–1569, Aug. 2013.
tions,” in Proc. 3rd IEEE PES Innov. Smart Grid Technol. Conf., Berlin, [28] M. Schmidt, A. Panosyan, E. Barthlein, K. O’Brien, and O. Mayer, “Method
Germany, 2012, pp. 1–7. of generating sets of PV plant power time series for grid simulation
[10] A. Gabash and P. Li, “Active-reactive optimal power flow for low-voltage purposes,” in Proc. 3rd IEEE PES Innov. Smart Grid Technol. Conf.,
networks with photovoltaic distributed generation,” in Proc. IEEE Int. Berlin, Germany, 2012, pp. 1–7.
Energy Conf. Exhibition, Florence, Italy, IEEE, 2012, pp. 381–386. [29] C. Cheng and D. Shirmohammadi, “A three-phase power flow method for
[11] S. Bolognani and S. Zampieri, “A distributed control strategy for reactive real-time distribution system analysis,” IEEE Trans. Power Syst., vol. 10,
power compensation in smart microgrids,” IEEE Trans. Autom. Control, no. 2, pp. 671–679, May 1995.
vol. 58, no. 11, pp. 2818–2833, Nov. 2013.
[12] P. Sulc, S. Backhaus, and M. Chertkov, “Optimal distributed control of
reactive power via the alternating direction method of multipliers,” Comput.
Res. Repository (CoRR), vol. abs/1310.5748, Oct. 2013. Sam Weckx (S’11) received the M.Sc. degree in
[13] A. Cagnano, F. Torelli, F. Alfonzetti, and E. D. Tuglie, “Can PV plants electrical engineering in 2009 and mechanical engi-
provide a reactive power ancillary service? A treat offered by an on-line neering in 2010 from the Katholieke Universiteit
controller,” Renew. Energy, vol. 36, no. 3, pp. 1047–1052, 2011. Leuven (KU Leuven), Leuven, Belgium, where he is
[14] R. Tonkoski, L. A. Lopes, and T. H. El-Fouly, “Coordinated active power currently working toward the Ph.D. degree. He has a
curtailment of grid connected PV inverters for overvoltage prevention,” Ph.D. fellowship with the Research Foundation Flan-
IEEE Trans. Sustain. Energy, vol. 2, no. 2, pp. 139–147, Apr. 2011. ders (FWO-VITO).
[15] E. Demirok, D. Sera, R. Teodorescu, P. Rodriguez, and U. Borup, “Evalua- He is a Research Assistant with the Department of
tion of the voltage support strategies for the low voltage grid connected PV Electrical Engineering ESAT-ELECTA, Katholieke
generators,” in Proc. IEEE Energy Convers. Congress Expo. (ECCE), Universiteit Leuven. His research interests include the
Atlanta, GA, IEEE, 2010, pp. 710–717. application of distributed optimization in smart grids
[16] Y. Chistyakov, E. Kholodova, K. Netreba, A. Szabo, and M. Metzger, and voltage control in distribution networks.
“Combined central and local control of reactive power in electrical grids
with distributed generation,” in Proc. IEEE Int. Energy Conf. Exhibition,
Florence, Italy, IEEE, 2012, pp. 325–330.
[17] K. De Brabandere, B. Bolsens, J. Van den Keybus, A. Woyte, J. Driesen,
and R. Belmans, “A voltage and frequency droop control method for parallel Carlos Gonzalez received the M.Sc degree in elec-
inverters,” IEEE Trans. Power Electron., vol. 22, no. 4, pp. 1107–1115, trotechnics from Polytechnic University of Catalonia
Jul. 2007. (UPC, Barcelona Tech), Barcelona, Spain, in 2009.
[18] L. Degroote, B. Renders, B. Meersman, and L. Vandevelde, “Neutral-point He is working toward the Ph.D. degree at Katholieke
shifting and voltage unbalance due to single-phase dg units in low voltage Universiteit Leuven (KU Leuven), Leuven, Belgium.
distribution networks,” in Proc. IEEE Bucharest PowerTech., Bucharest, From 2006 to 2010, he was a Researcher with
Romania, IEEE, 2009, pp. 1–8. Citcea—UPC and Catalonia Institute for Energy Re-
[19] C. Gonzalez, J. Geuns, S. Weckx, T. Wijnhoven, P. Vingerhoets, T. De Rybel search IREC, Barcelona, Spain. Since 2010, he has
et al., “LV distribution network feeders in Belgium and power quality been a Research Assistant with ESAT-ELECTA in the
issues due to increasing PV penetration levels,” in Proc. 3rd IEEE PES Katholieke Universiteit Leuven (KU Leuven). His
Innovative Smart Grid Technol. Conf., Berlin, Germany, Oct. 14–17, 2012. research interests include power quality in smart grids
[20] J. Tant, F. Geth, D. Six, P. Tant, and J. Driesen, “Multiobjective battery and fault detection.
storage to improve PV integration in residential distribution grids,” IEEE
Trans. Sustain. Energy, vol. 4, no. 1, pp. 182–191, Jan. 2013.
[21] P. Richardson, D. Flynn, and A. Keane, “Optimal charging of electric
vehicles in low-voltage distribution systems,” IEEE Trans. Power Syst.,
vol. 27, no. 1, pp. 268–279, Feb. 2012. Johan Driesen (S’93–M’97–SM’12) received the
[22] P. Richardson, D. Flynn, and A. Keane, “Local versus centralized charging M.Sc. and Ph.D. degrees in electrical engineering
strategies for electric vehicles in low voltage distribution systems,” IEEE from the Katholieke Universiteit Leuven (KU Leuven),
Trans. Smart Grid, vol. 3, no. 2, pp. 1020–1028, Jun. 2012. Leuven, Belgium, in 1996 and 2000, respectively.
[23] R. Perez, S. Kivalov, J. Schlemmer, K. Hemker, D. Renné, and T. Hoff, Currently, he is a Professor with KU Leuven and
“Validation of short and medium term operational solar radiation forecasts teaches power electronics and electric drives. In 2000,
in the US,” Solar Energy, vol. 84, no. 12, pp. 2161–2172, 2010. he was with the Imperial College of Science, Technol-
[24] V. Lonij, V. Jayadevan, A. Brooks, J. Rodriguez, K. Koch, M. Leuthold ogy and Medicine, London, U.K. In 2002, he was with
et al., “Forecasts of PV power output using power measurements of 80 the University of California, Berkeley, CA, USA.
residential PV installs,” in Proc. 38th IEEE Photovolt. Specialists Conf., Currently, he conducts research on distributed genera-
Austin, TX, IEEE, 2012, pp. 003 300–003 305. tion, power electronics, and its applications.

Вам также может понравиться