Академический Документы
Профессиональный Документы
Культура Документы
SECTION 15622
PART 1 GENERAL
1.06 QUALIFICATIONS
1.09 WARRANTY
PART 2 PRODUCT
2.1 GENERAL
All there water chilling units shall have the capacities listed in the
section .Each unit shall be capable of producing the schedules leaving
chilled water temperature as design conditions.
2.2 COMPRESSOR
2.3 EVAPORATOR
B. Shell Material : Rolled carbon steel plate with fusion welded seams;
have carbon steel tube sheets ;drilled and reamed to accommodate the
tubes; with minimum 6.35mm corrosion allowance epoxy coated on
water side and intermediate tube supports spaced no more than four feet
apart.
E. Each tube will be roller expanded into tube sheets providing a leak
proof seal, and be individually replaceable.
G. Two Liquid level sight glasses will be located on the side of the shell
to aid in determining proper refrigerant charge.
H. The evaporator will have a refrigerant relief device sized to meet the
requirements of ASHRAE 15 safety code for Mechanical
Refrigeration.
1. Material: Copper
J.2 Clearance of not less than 150% of the hinged marine type water
box cover diameter shall be provide to allow free swing of the hinged
water box cover with no contact with adjacent piping or equipment or
the need to remove any piping appurtenances etc.
O. Waterside pressure drop shall not exceed 30 feet water gauge (13
PSI) for cooler and Manufacture shall indicate water pressure drop
through cooler.
2.4 CONDENSER
E. Water Boxes: Marine type, removable, carbon steel, with vent and
drain connections.
E.5 Condenser shall be designed for water velocity of at least 3 fps but
not greater than 9 fps.
2.5 INSULATION
H. Height: Eye level and readable and operable without the need
for ladder or stool.
1. Model number
5. Design voltage
6. Refrigerant type
7. Starter type
2. Data collected once per second up to once per hour for each
parameter
2.8.7.2.3 Start and stop the condenser water and chilled water
pumps.
2.8.7.3.1 Stop the chiller, if the minimum run time has been
exceeded.
2.8.7. 3.2 Stop the chilled water pump and close the chilled water
isolation valve.
2.8.7.4 The chiller system controller shall have a data port to enable
the exchange of data from the chiller unit controllers with the BMS.
2.9 Electrical
2.9.1 GENERAL
2.10 Motors
1. Output frequency
2. Output voltage
2.12 FINISHES
2.14 ACCESSORIES
2. Refrigerant compressor
4. Water-cooled condenser
8. Relief valves
1. Self-contained package
5. Pressure gauge
7. Relief valves
1. Self-contained package
5. Refrigerant compressor
7. Water-cooled condenser
2.13.4. Detector shall be provided with a failure relay out put that
energizes when the monitor detects a fault in its operation. Detector
shall be compatible with the Building Management system and shall
WATER COOLED CHILLING UNITS
AL SHUBAILY GRAND MALL, KHOBAR, KSA –REV.00
PROJECT STANDARD SPECIFICATIONS
2.14.2 The chiller factory test shall be carried out design ambient
temperature of 46 °C DB and 30°C WB, as well as 52°C DB with
reduced capacity without mechanical failure.
2.14.3 The chiller factory test shall be performed in the presence of the
client’s and engineer representative .The team will comprise maximum
2 representatives. All expenses to be borne on the Manufacture.
2.14.8 Test Report: A certified test report of all data shall be forwarded
to the Engineer for approval prior to project acceptance .Calibration
curves and information sheets for all instrumentation shall be provided.
PART 3: EXECUTION
3.01 INSTALLATION
a. Leak testing
3.05 CLEANING
3.06 DOCUMENTATION