Вы находитесь на странице: 1из 6

PLS-CADD Version 14.

20x64 10:44:35 01 October 2015


Custom Engineering Solutions - Panama Training
Project Name: 'D:\space\PLS CAAD PROFILE\66kv\66.DON'

Criteria Report

Weather Cases

WC Description Air Wind Wind Wire Wire Wire


Wire Ambient Weather NESC Wire Wind Wire
# Density Vel. Pres. Ice Ice Ice
Temp Temp Load Constant Height Gust
Factor Thick Density Load
Factor Adjust Response
(Pa/(m/s)^2)(m/s) (Pa) (cm) (N/m^3) (N/m)
(deg C) (deg C) (N/m) Model Factor
-----------------------------------------------------------------------------------
----------------------------------------------------------
1 MinTemp-NoWind 0.613 0 0.0 0.00 0.000 0.00
15 0 1.00 0.00 None 1
2 MinTemp-2/3Wind 0.613 26 430.0 0.00 0.000 0.00
15 0 1.00 0.00 None 1
3 EverydayTemp-NoWind 0.613 0 0.0 0.00 0.000 0.00
30 0 1.00 0.00 None 1
4 EverydayTemp-FullWind 0.613 46 1300.0 0.00 0.000 0.00
30 0 1.00 0.00 None 1
5 MaxTemp-NoWind 0.613 0 0.0 0.00 0.000 0.00
80 0 1.00 0.00 None 1
6 MinTemp-OP-NoWind 0.613 0 0.0 0.00 0.000 0.00
15 0 1.00 0.00 None 1
7 MinTemp-OP-2/3Wind 0.613 26 430.0 0.00 0.000 0.00
15 0 1.00 0.00 None 1
8 EverydayTemp-OP-NoWind 0.613 0 0.0 0.00 0.000 0.00
30 0 1.00 0.00 None 1
9 EverydayTemp-OP-FullWind 0.613 46 1300.0 0.00 0.000 0.00
30 0 1.00 0.00 None 1
10 MaxTemp-OP-NoWind 0.613 0 0.0 0.00 0.000 0.00
53 0 1.00 0.00 None 1

Cable Tension Criteria

LC WC Description Cable Allowable Maximum Maximum


Applicable
# # Condition %Ultimate Tension Catenary
Cable
(N) (m)

-----------------------------------------------------------------------------------
----
1 3 EverydayTemp-NoWind Creep RS 17.000 0.000 0.000
aaac
2 2 MinTemp-2/3Wind Creep RS 30.000 0.000 0.000
aaac
3 4 EverydayTemp-FullWind Creep RS 50.000 0.000 0.000
aaac
4 8 EverydayTemp-OP-NoWind Creep RS 15.000 0.000 0.000
opgw
5 7 MinTemp-OP-2/3Wind Creep RS 25.000 0.000 0.000
opgw
6 9 EverydayTemp-OP-FullWind Creep RS 40.000 0.000 0.000
opgw

Automatic Sagging Criteria

LC WC Description Cable Allowable Maximum Maximum


Applicable
# # Condition %Ultimate Tension Catenary
Cable
(N) (m)

-----------------------------------------------------------------------------------
----
1 3 EverydayTemp-NoWind Creep RS 17.000 0.000 0.000
aaac
2 2 MinTemp-2/3Wind Creep RS 30.000 0.000 0.000
aaac
3 4 EverydayTemp-FullWind Creep RS 50.000 0.000 0.000
aaac
4 8 EverydayTemp-OP-NoWind Creep RS 15.000 0.000 0.000
opgw
5 7 MinTemp-OP-2/3Wind Creep RS 25.000 0.000 0.000
opgw
6 9 EverydayTemp-OP-FullWind Creep RS 40.000 0.000 0.000
opgw

Weight Span Criteria (Method 1)

Condition WC Weather Case Cable


# Description Condition
-------------------------------------------------------------
Condition 1 (usually Wind) 0 Initial RS
Condition 2 (usually Cold) 0 Initial RS
Condition 3 (usually Ice) 0 Initial RS

Interaction Diagram Criteria

LC WC Weather Case Cable


# # Description Condition
-----------------------------------

Structure Groups Criteria

Group Group
Rule for
Load Cases Structures
Name Description
Group Membership
In Group In Group
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
-------------------------------------------
All Built in group that all structures belong to
Automatic: all structures
0 2
Has DE At least one dead end set on structure
Automatic: has a DE between sets 1 and 60
0 2
No DE No dead end sets on structure
Automatic: has no DE between sets 1 and 60
0 0
All sets DE All sets on structure are dead end
Automatic: has only DE between sets 1 and 60
0 2
Not all sets DE At least one set on structure is not dead end
Automatic: has non DE between sets 1 and 60
0 0
Angle Structure near nonzero line angle
Automatic: line angle outside 0.00 to 0.00 (deg) within 0.10 (m) of structure
0 0
PLS-POLE PLS-POLE created structure
Automatic: PLS-POLE created
0 0
PLS-POLE has DE PLS-POLE created structure with at least one dead end
set Automatic: PLS-POLE created and has a DE between sets 1 and 60
0 0
PLS-POLE no DE PLS-POLE created structure without any dead end sets
Automatic: PLS-POLE created and has no DE between sets 1 and 60
0 0
PLS-POLE angle PLS-POLE created structure near nonzero line angle
Automatic: PLS-POLE created and line angle outside 0.00 to 0.00 (deg) within 0.10
(m) of structure 0 0
TOWER TOWER created structure
Automatic: TOWER created
0 0
TOWER has DE TOWER created structure with at least one dead end set
Automatic: TOWER created and has a DE between sets 1 and 60
0 0
TOWER no DE TOWER created structure without any dead end sets
Automatic: TOWER created and has no DE between sets 1 and 60
0 0
TOWER angle TOWER created structure near nonzero line angle
Automatic: TOWER created and line angle outside 0.00 to 0.00 (deg) within 0.10 (m)
of structure 0 0

Structure Loads Criteria

LC WC Load Case Cable Wind Bisect Wire Wire + Wire Struct


Struct Struct. Struct. Struct. Pole Pole
# # Description Condition Dir. Wind Vert. Struct. Tension Weight
Wind Wind Ice Ice Tip Tip
Angle Load Wind Load Load
Area Load Thick Density Deflection Deflect
Factor Load Factor Factor
Factor Model Check Limit
Factor
(cm) (N/m^3) % or (m)
-----------------------------------------------------------------------------------
----------------------------------------------------------------
Strength Factors for each Load Case

LC WC Load Case Strength Strength Strength Strength Strength Strength


Strength Strength Strength Strength
# # Description Factor Factor Factor Factor Factor Factor
Factor Factor Factor Factor
Steel Poles Wood Concrete Concrete Concrete Guys
Non- Braces Insul- Found-
Tubular Arms Poles Poles Poles Poles
Tubular ators ation
Towers Ultimate First Zero
Arms
Crack Tension

-----------------------------------------------------------------------------------
-------------------------------

Survey Point Clearance Criteria

LC WC Weather Case Cable


# # Description Condition
-----------------------------------

Danger Tree Locator Criteria

LC WC Weather Case Cable


# # Description Condition
-----------------------------------

Survey Point Clearance and Danger Tree Locator functions are considering a
Continuous Range
of wind values from left blowout to right blowout.

Survey Point Clearance functions are treating points with insufficient vertical
clearance but
adequate horizontal clearance as questionable violations and flagging them with
blue markers
in graphics views and a blue "??" in reports.

Phase Clearance Criteria

LC WC Weather Case Cable


# # Description Condition
-----------------------------------
1 0 Initial RS
2 0 Initial RS

Insulator Swing Criteria

Condition WC Weather Case Cable


# Description Condition
--------------------------------------------
Condition 1 0 Initial RS
Condition 2 0 Initial RS
Condition 3 0 Initial RS
Condition 4 0 Initial RS

Blowout and Departure Angle Report Criteria

LC WC Weather Case Cable


# # Description Condition
-----------------------------------

Galloping Criteria
Weather case for swing angle: 0 Creep RS
Weather case for sag: : 0 Creep RS
Galloping amplitude safety factor (multiplies major axis for all methods): 1.00
Required separation between ellipses: 0.00 (m)
Checking single loop (Davison)
Checking double loop (Toye)

Note that any given galloping ellipse is only checked against other ellipses that
share the same start and stop structures (those that do not will be marked as
N/A below).

Weight spans calculated by exact method using catenary in blown out plane

Wind & Weight Span Report

LC WC Weather Case Cable


# # Description Condition
-----------------------------------

Weather case for final after creep 'EverydayTemp-NoWind'


Weather case for final after load EverydayTemp-FullWind

Clearance line voltage (kV) 0, clearance line vertical buffer (m) 0


Display of centerline and side profile clearance lines turned ON.
Display of spikes for points requiring additional clearance turned ON.
Spikes are drawn for all feature codes (no codes have been exlcuded)

Maximum tensions calculated using actual section geometry

Terrain:
Ground profile width (m) 3.048
Display width (m) 15.24

Bimetallic conductor settings:


Default settings from CRI file (used for wires that do not have conductor
specific settings):
Outer strands do not take compression at high temperature.
Cable file 'd:\space\pls caad profile\66kv\aaac' (using conductor specific
settings:
Outer strands do not take compression at high temperature.
Cable file 'd:\space\pls caad profile\66kv\opgw' (using conductor specific
settings:
Outer strands do not take compression at high temperature.

SAPS Finite Element Sag-Tension:


SAPS Analysis Level 2
Option to include chained insulators in L2 and L3 models (always included in L4)
is turned ON
Default attachment stiffnesses (for level 2 analysis provided, may be overridden
with attachment point specific value in Section/Modify)
Dead Ends: 0 (N/m) Transverse, 0 (N/m)
Longitudinal
Non dead end with post insulator: 0 (N/m) Transverse, 0 (N/m)
Longitudinal
Non dead end with non post insulator: 0 (N/m) Transverse, 0 (N/m)
Longitudinal

Вам также может понравиться