TECHNICAL SPECIFICATIONS OF MODULAR OPERATION THEATERS

EPOXY FLOORING & WALL FOR OPERATION THEATERS SELF LEVELING


FLOOR COATING
SELF-LEVELING – 3 MM. CERAMIC ENHANCED EPOXY FLOORING:

SK 601 (SL) HCRMS SELF LEVELING FLOOR COATING IS EPOXY CERAMIC AGGREGATE MIXED
ABRASION RESISTANT FLOOR COATING SYSTEM HAVING EXCELLENT BACTERICIDAL PROPERTIES. IT
IS EASILY CLEANABLE AND IDEAL SYSTEM FOR CLEAN ROOM AREAS OF PHARMACEUTICAL
FORMULATION PLANTS AND OPERATION THEATRE OF HOSPITALS WHERE PRIMARY CONCERN IS
CLEANLINESS AND ANTI BACTERIAL PROPERTIES.

SINCE THE SYSTEM IS CERAMIC ENHANCED THE ABRASION RESISTANCE, SCRATCH RESISTANCE,
COMPRESSIVE STRENGTH, FLEXURAL STRENGTH AND OTHER PHYSICAL PROPERTIES ARE FAR MORE
SUPERIOR TO THE COMMON EPOXY SELF LEVELING SYSTEM. CHEMICAL RESISTANT PROPERTIES ARE
ALSO SUPERIOR IN NATURE.

SCOPE OF WORK:

1) APPLICATION OF SK 115 CONCRETE PRIMER OVER THE PREPARED SURFACE.


2) APPLICATION OF 1.5 MM THICK SK 601 (SL) HCRMS SELF LEVELING FLOOR COATING BASE
COAT .
3) APPLICATION OF EPOXY FINAL COAT WITH PIGMENTS, ANTIBACTERIAL ANTIFUNGAL
CHEMICALS.
WALL COATING & CEILING
1) EPOXY TRETMENT ON WALL CONTROL RH FACTOR
WITH ANTIBACTERIA &ANTIFUNGAL PROPERTIES & WASHEBLE WITH
WATER MAKES WALL SMOOTH, JOINTLESS & DOES NOT PERMIT ANY
FUNGAS OR BACTERIA GROW.
SCOPE OF WORK:

1) APPLICATION OF ONE COAT OF SK119 WALL PRIMER.


2) LEVELING OF PLASTERED WALL BY USING SPECIAL BIRLA ACRYLIC
PLASTER PUTTY.
3) AGAIN APPLICATION OF ONE COAT OF EPOXY WALL PRIMER.
4) APPLICATION OF TWO COATS OF EPOXY PAINT WITH ANTIBACTERIA &
ANTIFUNGAL CHEMICALS

COVINGS
.WE USE SOLVENT FREE EPOXY FOR MAKING COVINGS.
WALL TO FLOOR COVINGS – 75 MM X 75 MM RADIAL.

SCOPE OF WORK:
1) APPLICATION OF POLYESTER PUTTY ON WALL TO MAKE SURFACE PLANE &
SMOOTH.

2) APPLICATION OF EPOXY PRIMER WITH HARDENER.

3) EPOXY PAINT WITH ANTIBACTERIAL Z& ANTIFUNGAL ADDITIVES.

2.CLADDING WITH PPGI-SS ,PPGI-PPGI 60 MM PUFF PANNEL

THIS GIVE OPERATION THEATER JOINTLESS LOOK, VERY STURDY, WALKEBLE


PANNEL .
LED LIGHTS CAN BE GIVEN IN CLADDING OG PUFF PANNEL.

3. SURGEON’S CONTROL PANEL:


THE SURGEON CONTROL PANEL SHALL MEET HTM 2022 : 1997 FOR MEDICAL GAS
PIPE LINE SYSTEM DESIGN, HTM 2020/2021 FOR ELECTRICAL SAFETY CODES FOR
HIGH AND LOW VOLTAGE SYSTEM, WIRED TO THE CURRENT IEE REGULATIONS
AND BS 7971 AND EC – CONFORMITY DECLARATION CE.
THE THEATRE SURGEON’S CONTROL PANEL HAS BEEN DESIGNED TO COPE WITH
CHANGING TECHNOLOGY AND EQUIPMENT IN OPERATING ENVIRONMENTS.
CONTROL PANEL SHOULD BE USER FRIENDLY AND EASE OF OPERATING AND
MAINTAINING PURPOSE.
THE PANEL SHALL BE “TILED MEMBRANE” TYPE, CAN BE CONFIGURED TO
INCORPORATE ALL THE SERVICES THAT OPERATION THEATRE STAFF REQUIRED.
THE FASCIA SHALL BE MADE WITH SUPERIOR QUALITY UV RESISTANCE
MEMBRANE WITH STERILISABLE FEATURE. THE MEMBRANE BACKING IS MADE OF
2.5 MM THICK ALUMINIUM THAT IS RUST RESISTANCE. THE CONNECTION
BETWEEN THE SURGEON CONTROL PANEL AND THE DISTRIBUTION BOARD SHALL
BE BY A MULTIPLEXED SYSTEM, PROVIDING A PWM SIGNAL ON A TWO-CORE
CABLE.
THE PANEL SHALL CONTAIN 6 SERVICES TILES FOR

(A) TIME DAY CLOCK.

(B) TIME ELAPSE CLOCK.

(C) CONTROLLER FOR TEMPERATURE AND HUMIDITY WITH INDICATOR.

(D) GENERAL LIGHTING SYSTEM.

(E) MEDICAL GAS ALARM PANEL.

(F) HEPA FILTER WORKING & STATUS.

(G) PRESSURE IN OPERATION THEATRE.

(H) OUTSIDE O.T. AIR PRESSURE.

(I) AIR VELOCITY OF LAF.


TIME DAY CLOCK SHALL BE DIGITAL TYPE AND CLOCKS HAVE HIGH BRIGHTNESS
CHARACTERS, NOT LESS THAN 30 MM IN HEIGHT.
TIME ELAPSED DAY CLOCK SHALL BE DIGITAL TYPE AND CLOCK HAS HIGH
BRIGHTNESS CHARACTERS, NOT LESS THAN 30 MM IN HEIGHT.
CONTROLLER FOR TEMPERATURE AND HUMIDITY TO BE PROVIDED

CONTROLLER FOR TEMPERATURE AND HUMIDITY TO BE PROVIDED IN PANEL TO


CONTROL FROM OT. TEMPERATURE INDICATOR SHALL INDICATE THE THEATRE
TEMPERATURE WILL BE CONNECTED TO THE LOCAL PRESSURE SWITCHES OF
AIR-CONDITIONING SYSTEM. INDICATOR SHALL BE DIGITAL TYPE HAVE HIGH
BRIGHTNESS CHARACTERS, NOT LESS THAN 30 MM IN HEIGHT.
GENERAL LIGHTING SYSTEM INCORPORATES ALL THE NECESSARY CONTROLS OF
THE LIGHTING SYSTEM INSIDE THE THEATRE.
THE MEDICAL GAS ALARM SHALL INDICATE LOW GAS PRESSURE FOR EACH GAS
SERVICE PRESENT IN THE OPERATING THEATRE AND SHALL HAVE AN AUDIBLE
DUZZER WITH MUTE FACILITY. THE MEDICAL GAS ALARMS SHALL BE CONNECTED
TO LOCAL PRESSURE SWITCHES LOCATED DOWNSTREAM OF THE LAST
ISOLATION VALVES.
A HAND FREE SET ADDRESHING SYSTEM INCORPORATED IN THE PANEL FROM
WHICH YOU CAN CALL ANY O.T. ATTENDENT FOR GETTING ANY REQIUREMENT
INSIDE O.T..
THE CONTROL PANEL SHALL BE DESIGNED FOR FRONT – ACCESS ONLY
ALL HIGH VOLTAGE EQUIPMENT IS INSTALLED IN A SEPARATE ENCLOSURE.
THE REMOTE CABINET WILL HOUSE THE OPERATING LAMP TRANSFORMERS, MAIN
FAILURE RELAYS, ELECTRICAL DISTRIBUTION EQUIPMENT AND CIRCUIT
PROTECTION EQUIPMENT FOR ALL CIRCUITS WITHIN THE OPERATING THEATRE.
ALL INTERNAL WIRING SHALL TERMINATE IN CONNECTORS WITH SCREW AND
CLAMP SPRING CONNECTIONS, THE CLIP-ON TYPE MOUNTED, ON A DIN RAIL AND
LABELED WITH INDELIBLE PROPRIETARY LABELS.
INDIVIDUAL FUSES OR MINIATURE CIRCUIT BREAKERS SHALL PROTECT ALL
INTERNAL CIRCUITS.
ALL INTERNAL WIRES SHALL BE MARKED WITH PLASTIC FERRULE TYPE CABLE
MARKERS, FOR EASE IDENTIFICATION.
4. LED X-RAY VIEWING SCREEN:
THE SYSTEM SHALL MEET HTM 2020/2021 FOR ELECTRICAL SAFETY CODES FOR
HIGH AND LOW VOLTAGE SYSTEM, HTM 2007 FOR ELECTRICAL SUPPLY AND
SERVICES DISTRIBUTION AND WIRED THE CURRENT IE REGULATIONS & BS 7971.
THE THEATRE IS EQUIPPED WITH A 2 PLATE X-RAY VIEWING SCREEN. IT DESIGNED
TO PROVIDE FLICKS FREE LUMINANCE FOR THE FILM VIEWING PURPOSE. IT IS
INSTALLED FLUSHED WITH THE THEATRE WALL FOR HYGIENIC AND EASE OF
CLEANING PURPOSE. THE X-RAY VIEWING SCREEN IS DESIGNED FOR THE
PURPOSE OF FRONT ACCESS.
THE X-RAY VIEWING SCREEN IS ILLUMINATED BY 4 PIECES OF HIGH FREQUENCY
FLUORESCENT LAMPS AND THE DIMMING IS CONTROLLED BY THE USAGE OF
DIMMING BALLAST WITH PCB THAT IS MOUNTED INSIDE THE BOX.
THE DIFFUSER IS ABLE TO DIFFUSE THE LIGHT EVENLY AND TO PROVIDE ENOUGH
LUMINANCE FOR FILM VIEWING. IT IS MADE OF HIGH QUALITY OPAQUE ACRYLIC
SHEET. THE FILM IS HELD FIRMLY BY USING SPRING-LOADED CLIPS FOR EASE OF
MOUNTING AND DEMOUNTING. THE BODY IS BUILT BY USING ELECTROLYSED
STEEL WITH POWDER COATED TO IS STANDARDS.
THE DIMMING CONTROL IS USING VARIABLE RESISTANCE CONTROL THAT IS ABLE
TO TURN ON THE LIGHT WHILE STEP UP THE BRIGHTNESS TILL THE FULL
BRIGHTNESS STATUS. IT COULD BE DONE BY EITHER USING ROTARY CONTROL
SYSTEM OR PCB BUTTON CONTROL SYSTEM.

5. PRESSURE RELIEF DAMPER:


PRESSURE RELIEF DAMPERS (CASCADE PRESSURE STABILISER) IS PROVIDED IN
EACH THEATRE TO PREVENT CROSS CONTAMINATION OF AIR FROM CLEAN AND
DIRTY AREAS. THE MAIN PURPOSE OD PRESSURE DAMPER TO GIVE FRESH AIR
INSIDE O.T. & MAINTAIN POSITIVE PRESSURE INSIDE O.T.
SUITABLY SIZED AIR PRESSURE RELIEF DAMPER IS STRATEGICALLY PLACED,
ENABLE DIFFERENTIAL ROOM PRESSURE TO BE MAINTAINED AND ENSURE THAT
WHEN DOORS ARE OPENED BETWEEN CLEAN AND DIRTY AREA. COUNTER-
WEIGHT BALANCING SYSTEM IS PROVIDED IN THE PRD TO MAINTAIN POSITIVE
PRESSURE INSIDE THE OPERATION THEATRE. AIR PRESSURE STABILIZERS SHALL
HAVE UNIQUE CAPABILITY OF CONTROLLING DIFFERENTIAL PRESSURE TO CLOSE
TOLERANCE. THE PRD SHALL REMAIN CLOSED AT PRESSURE BELOW THE SET
PRESSURE AND SHALL OPEN FULLY AT PRESSURE ONLY FRACTIONALLY ABOVE
THE THRESHOLD PRESSURE.
THE PRESSURE RELIEF DAMPERS ARE ACCURATE TO A RANGE OF 1 PASCAL
OVER THEIR WORKING RANGE OF 5 – 35 PA.
THE BODY IS EPOXY POWDER COATED AS PER STANDARD BS COLOURS. MEETS
INTERNATIONAL QUALITY AND SAFETY REQUIREMENTS
FIRST CLASS ELECTROLYZED STEEL PLATE IS USED FOR BODY AND WITH HIGH
GRADE SS 304 STAINLESS STEEL FOR BLADES.
THE PRD DESIGN IS AS PER HTM 2025:1994 FOR VENTILATION IN HEALTHCARE
PREMISES.

6. DOORS AND FRAMES (HERMETICALLY SEALED TYPE)


2100 MM HEIGHT & 1500 MM:
TO MAINTAIN STERILITY AND THE CORRECT AIR PRESSURE IN THE DEPARTMENT, ALL
DOORS INTO AND OUT OF THE OPERATING THEATRE AND ANCILLARY ROOMS SHOULD BE
OF THE SLIDING, HERMETICALLY SEALING TYPE.
THE DOORS SHOULD BE CONSTRUCTED WITH HIGH-DENSITY PARTICLEBOARD CORES,
AND HIGH-PRESSURE LAMINATE FACED ON BOTH SIDES.
THE CORES SHOULD BE SET FIRMLY IN AN ALUMINIUM FRAME, SUITABLY SEALED WITH A
NONPOROUS NON-SHEDDING GASKET.
THE ALUMINIUM FRAMES SHOULD CONTAIN THE DOOR SEAL.
THE DOOR SHOULD SEAL ON ALL FOUR EDGES IN THE CLOSED POSITION.
THE DOOR TRACK SHOULD BE CONSTRUCTED FROM AN ALUMINIUM EXTRUSION, FIXED
FIRMLY TO THE WALLS.
THE DOOR SHOULD RUN ON NYLON WHEELS WITHIN THE TRACK.
THE TRACK AND WHEEL DESIGN SHOULD BE SUCH THAT DURING THE LAST 50MM AT
TRAVEL ON THE CLOSING CYCLE, THE DOOR MOVES IN 3 DIRECTIONS TO FORM A SEAL
AGAINST THE FLOOR, AT THE BOTTOM AND AGAINST THE FRAME ON BOTH SIDES AND AT
THE TOP.
NYLON RUNNER GUIDES SHOULD BE FIXED TO THE FLOOR IN SUCH A WAY THAT THEY DO
NOT OBSTRUCT TROLLEY MOVEMENT THROUGH THE DOOR.
THEY SHOULD PROVIDE STABILITY DURING THE OPENING AND CLOSING CYCLES AND
ASSIST IN CREATING THE NECESSARY PRESSURE AT THE BOTTOM OF THE DOOR TO
MAINTAIN THE SEAL.
FLOOR GUIDES ACROSS THE DOOR OPENING, OR DOORS WITH NO FLOOR GUIDANCE
SHOULD NOT BE CONSIDERED.
TO ENSURE EFFICIENT SEALING OF THE DOORS, THE DOOR MANUFACTURER SHOULD
PROVIDE THE DOORFRAMES.
THEY SHOULD CONSIST OF REINFORCED PLASTERBOARD PANELS FACED WITH THE SAME
LAMINATE AS THE DOORS.
THE DOORFRAMES SHOULD BE EDGED WITH AN ALUMINIUM EXTRUSION AND WITH
CONCEALED FIXINGS THAT ARE ADJUSTABLE DURING INSTALLATION TO ENSURE A 100%
HERMETIC SEAL IS ACHIEVED.
VISION PANELS SHOULD BE FITTED TO ALL DOORS.

7 DOORS AUTOMATION UNIT:


THE DOOR WITH ITS AUTOMATION UNIT CONFORMS TO MACHINE DIRECTIVE 93/87/EC, LOW
VOLTAGE DIRECTIVE 73/23/EEC AND 93/68/EEC AND EMC DIRECTIVE 89/336/EEC AND
92/31/EEC AND 93/97/EEC.
THE SLIDING DOORS SHOULD BE ELECTRICALLY OPERATED.
AUTOMATION UNITS SHOULD BE OF THE SINGLE-PHASE ELECTRONIC TYPE MOUNTED
DIRECTLY TO THE
DOOR TRACK.
THE UNITS SHOULD CONSIST OF A COMPUTERISED ELECTRONIC CONTROLLER AND
MOTOR. THE DRIVE MECHANISM SHOULD BE BY HEAVY-DUTY STEEL REINFORCED
TOOTHED FABRIC BELT.
THE CONTROLLER SHOULD HAVE THE FACILITY TO INDIVIDUALLY SET OPENING SPEEDS,
PARTIAL OPENING, CLOSING SPEEDS, TIME DELAYS AND A VARIETY OF LOCKING AND
INTERLOCKING OPTIONS, WITHIN FACTORY PRE-SET LIMITS.
THE DOOR CONTROLLER SHOULD ALSO HAVE THE ABILITY TO SENSE ADDITIONAL LOADS
ON THE DOOR CAUSED BY ANY OBSTRUCTION IN ITS PATH AND TO AUTOMATICALLY STOP
OR REVERSE THE DIRECTION OF TRAVEL.
THE CONTROLLER SHOULD BE CAPABLE OF EITHER BEING OPERATED BY ELBOW
SWITCHES/FOOT SWITCHES, KEY SWITCHES.
ALL DOORS SHOULD BE ABLE TO BE OPERATED EASILY MANUALLY IN THE EVENT OF
FAILURE OF THE POWER SUPPLY
OR THE AUTOMATION UNITS.

8.STORAGE UNIT
THE STORAGE UNIT SHOULD BE MADE WITH 1.50 MM THICK E.G.P 120GSM ZINC
COATED STEEL PANELS. THE STORAGE UNIT SHOULD BE DIVIDED 2 EQUAL PARTS
AND EACH PART SHOULD HAVE INDIVIDUAL GLASS DOORS WITH LOCKING
SYSTEM.
EACH PART SHOULD BE PROVIDED WITH GLASS RACKS TO KEEP SURGICAL
MEDICINES ETC. STORAGE UNIT IS PROVIDED IN OPERATING THEATRE.
IT IS FLUSH MOUNTED INTO THE THEATRE WALL WITH A STERILE JOINTING
SYSTEM.
ALL WALL-MOUNTED EQUIPMENT SHOULD BE FLUSH MOUNTED AND SEALED INTO
THEATRE WALL BY MEANS OF A STERILE JOINTING SYSTEM.

9. LIST / WRITING BOARD:


A LIST/WRITING BOARD SHOULD BE PROVIDED IN OPERATING THEATRE.
IT SHOULD COMPRISE A FLUSH MOUNTED, 1.50MM THICK, WHITE LAMINATE BOARD,
BONDED TO A 2MM STEEL SHEET POWDER COATED FOR ADDITIONAL RIGIDITY.
IT SHOULD BE MOUNTED FLUSH INTO THE THEATRE WALL WITH A STERILE JOINTING
SYSTEM.
ALL WALL-MOUNTED EQUIPMENT SHOULD BE FLUSH MOUNTED AND SEALED INTO
THEATRE WALL BY MEANS OF A STERILE JOINTING SYSTEM.

10. RECESS MOUNTED IP54 PROTOCOL, NON-HYGROSCOPIC PERIPHERAL LIGHTS


HAVING COMPACT FLUORESCENT LAMP AND DIGITAL BALLAST

11. ELECTRICAL: ELECTRICAL WIRING, CONDUITING AND CABLING INSIDE THE OT


AREA UP TO
OT ELECTRICAL DB FOR ELV.

12. TWO BAY SURGICAL SCRUB SINK


COMPACT SURGICAL SCRUB SINK SHOULD BE DESIGNED FOR USE IN OPERATION
THEATRE COMPLEX PROVIDED WITH A CONVENIENT SINK FOR PRE-OP SCRUB UP.
EACH FIXTURE SHOULD BE FABRICATED FROM HEAVY GAUGE TYPE 304
STAINLESS STEEL & SHOULD BE SEAMLESS WELDED CONSTRUCTION
POLISHED TO A SATIN FINISH.
THE SCRUB SINK SHOULD BE PROVIDED WITH A FRONT ACCESS PANEL, WHICH
SHOULD BE EASILY REMOVED FOR ACCESS TO THE WATER CONTROL VALVE,
WASTE CONNECTIONS, STOPPERS & STRAINERS.
HANDS FREE OPERATION INCLUDES INFRARED SENSOR WITH BUILT-IN RANGE OF
ADJUSTMENT.
THERMOSTATIC MIXING VALVE CONTROL SHOULD BE LOCATED BEHIND THE
ACCESS PANEL & MAINTAIN CONSTANT WATER TEMPERATURE.
USER DEFINED SETTINGS OF 1, 3, 5 & 10 MIN. SHOULD BE AVAILABLE. THIS TIMING
CAN BE CHANGED TO MEET INDIVIDUAL APPLICATION REQUIREMENT.
SHOULD BE PROVIDED WITH ELBOW ACTION TAPS, INFRARED SENSOR
THERMOSTATIC CONTROL WITH FAIL-SAFE TEMPERATURE CONTROLS.
ALL UNITS SHOULD HAVE RADIUSED ANTI SPLASH FRONTS.
KNEE OPERATED SWITCH TO BE OFFERED AS AN OPTION.

13. DIRTY HATCH BOX SIZE 600 X 600 X 450 MM


A HATCH SS 304 1MM THICK SHOULD BE PROVIDED IN EACH OPERATION THEATRE
TO
REMOVE WASTE MATERIALS FROM THE OPERATION THEATRE TO DIRTY AREA
JUST
ADJACENT TO OPERATION THEATRE.
EACH HATCH SHOULD BE EQUIPPED WITH TWO DOORS AND THE DOOR SHOULD
BE OPERATED
ELECTRONICALLY. THE HATCH SHOULD BE DESIGNED IN SUCH A WAY THAT ONLY
ONE DOOR
SHOULD BE OPENED ONE TIME.

14. PASS BOX SIZE 600 X 600 X 450 MM


PASS BOX SS 304 1MM THICK SHOULD BE PROVIDED IN EACH OPERATION
THEATRE TO
EXCHANGE MATERIALS FROM THE OPERATION THEATRE TO STERILE STORE AREA
JUST
ADJACENT TO OPERATION THEATRE.
EACH SHOULD BE EQUIPPED WITH TWO DOORS AND THE DOOR SHOULD BE
OPERATED
ELECTRONICALLY HAVING UV LIGHT. THE PASS BOX SHOULD BE DESIGNED IN
SUCH A WAY
THAT ONLY ONE DOOR SHOULD BE OPENED ONE TIME.

15. SUPPLY OF SINGLE ARM PENDANT


- HAVING HORIZONTAL MOVEMENTS ONLY, COMPRISING OF - 1 X ARM 1000 MM
HAVING A CARRYING CAPACITY OF MAXIMUM LOAD OF 80 KG
-ROTATION OF 330 DEG.
- 1 X BASIC CONSOLE - 800 MM
- 1 X FIXED SHELF
- 1 X DRAWER
- 8 X MAINS SOCKET (5/15AMP)
- 8 X MEDICAL GAS TERMINAL & HOSE ASSEMBLY (2XO2, 2XVAC, 1XAIR(4BAR),
1XAIR (7 BAR), 1XN2O, AGSS – 01NO.)
- MEDICAL RAIL - ONE SET

16. SUPPLY OF DOUBLE ARM PENDANT


- 2 X ARM 800 MM & 600MM HAVING A CARRYING CAPACITY OF MAXIMUM LOAD
OF 80 KG -ROTATION OF 330 DEG.
- 1 X BASIC CONSOLE - 600 MM
- 1 X FIXED SHELF
- 1 X DRAWER
- 8 X MAINS SOCKET (5/15AMP)
- 5 X MEDICAL GAS TERMINAL & HOSE ASSEMBLY (1XO2, 2XVAC, 1XAIR (4BAR),
1XAIR (7 BAR),)
- MEDICAL RAIL - ONE SET

17 . OT LIGHT TYPE: TWIN DOME OPERATING LED LIGHT FOR EACH OT


IT SHOULD BE POWER LED WHICH SHOULD PROVIDE DIRECT, REFLECTION FREE
ILLUMINATION WHICH ALLOWS TO HAVE DOUBLE THE EFFICIENCY COMPARES TO
CONVENTIONAL LIGHT SOURCE. IT SHOULD HAVE LFL LENS COMBINATION AND
HAVE THE PRIMARY OPTICS WHICH GUIDES THE LIGHT IN A PARALLEL, WHILE
SECONDARY OPTICS ENSURES BEAMS OF COHERENT LIGHT. THE RESULTS
SHOULD BE AN EXCELLENT ILLUMINATION IN THE OT FIELD IN TERMS OF AREA
AND DEPTH. IT SHOULD BE COLD INFRARED –FREE LIGHT. IT SHOULD BE FLAT,
SEALED LIGHT BODY SPECIALLY DESIGNED FOR LAMINAR FLOW CEILINGS. IT
SHOULD HAVE FLOW OPTIMIZES LIGHT HEAD AND REDUCED SURFACE
TEMPERATURE MINIMIZE TURBULENCES IN LAMINAR AIR FLOW. IT SHOULD HAVE
IR-FREE ILLUMINATION AVOIDS TISSUE DESICCATION AND SWEAT ON THE
SURGEON’S FOREHEAD. IT SHOULD HAVE OPTIMIZED RATIO LIGHT HEAD/LIGHT
FIELD DIAMETER. THE SIZE OF THE LIGHT BODY SHOULD NOT BE MORE THEN
800MMX 720MM. THE HIGH ILLUMINATION INTENSITY SHOULD BE 140000-
160000LUX AT 1M DISTANCE. IT SHOULD HAVE DEEP FIELD ILLUMINATION
L1+L2=800-1100 MM. IT SHOULD HAVE ADJUSTABLE LIGHT FIELD FROM 180MM TO
300MM WHICH PROVIDED FLEXIBILITY OF SURGERY. IT SHOULD HAVE TWIN
IDENTICAL LIGHT HEAD OF 160000LUX EACH. IT SHOULD HAVE COLOR
TEMPERATURE MORE THEN 4500K. IT SHOULD HAVE COLOR RENDERING INDEX
RA>94. IT SHOULD HAVE DIAMETER OF LIGHT FIELD FROM 180-290MM. THE DEPTH
OF LIGHT FIELD SHOULD BE NOT LESS THEN 800MM. TEMPERATURE AT SURGEON
HEAD SHOULD BE <1 C AND TEMPERATURE ON SURFACE LIGHT HEAD <37C. IT
SHOULD HAVE LIGHT HEAD DIMMABLE .IT SHOULD BE SUPPLIED WITH FOUR NON
STERILE POSITIONING HANDLES AND ONE STERILE SUSPENSION HANDLES. IT
SHOULD BE SUPPLIED WITH DUAL CONTROL PANEL REMOTE OR WALL. IT SHOULD
HAVE INTERFACE FOR OR INTEGRATION. IT SHOULD HAVE UPGRADE GUARANTEE
FOR ALL LED OR LIGHTS GIVING THE USER AN OPTION TO UPGRADE THE
LIGHTING TECHNOLOGY BY CHANGING THE LED PADS, NOT THE MECHANICAL
SYSTEM.

18.LAMINAR AIR FLOW SYSTEM


THE LAMINAR AIR FLOW IS DESIGNED TO PROVIDE A VERY HIGH DEGREE
OF PROTECTION FOR OPERATION THEATERS AND CREATES AN
ENVIRONMENT FREE FROM BIOLOGICAL AND PARTICULATE
CONTAMINATION. OPERATION THEATERS REQUIRES CONTROL OF AIR
BORNE CONTAMINATION TO PREVENT DAMAGE TO PARTS OR A HAZARD TO
HEALTH. AMBIENT AIR IS DRAWN THROUGH A PRE-FILTER WHICH IS
INTRODUCED IN THE WORK AREA THROUGH THE HEPA FILTER. THE
AVERAGE VELOCITY IN THE WORK AREA IS MAINTAINED BETWEEN 0.5&
0.5 M/SEC. AIR CLEANLINESS IN THE WORK AREA IS BETTER THAN CLASS
3.5 ( 100) IN ACCORDANCE WITH US. FED STANDARDS 209 E.
LAMINAR AIR FLOW SYSTEM

THE LAMINAR AIR FLOW WE DESIGNED DUCTLESS TO PROVIDE A VERY


HIGH DEGREE OF PROTECTION FOR OPERATION THEATERS AND CREATES AN
ENVIRONMENT FREE FROM BIOLOGICAL AND PARTICULATE CONTAMINATION
AS DUCT ARE BREEDING GROUND FOR FUNGUS & BACTERIA. OPERATION
THEATERS REQUIRES CONTROL OF AIR BORNE CONTAMINATION TO PREVENT
DAMAGE TO PARTS OR A HAZARD TO HEALTH. AMBIENT AIR IS DRAWN
THROUGH A PRE-FILTER WHICH IS INTRODUCED IN THE WORK AREA
THROUGH THE HEPA FILTER. THE AVERAGE VELOCITY IN THE WORK AREA IS
MAINTAINED BETWEEN 0.5& 0.5 M/SEC. AIR CLEANLINESS IN THE WORK
AREA IS BETTER THAN CLASS 3.5 ( 100) IN ACCORDANCE WITH US. FED
STANDARDS 209 E.
FEATURES :

1) SIZE: 72 INCH X 32 INCH X 18 INCH ,2 NUMBERS.


2) MOTOR – 1 HP. WITH SEALED DOUBLE BEARING, 2 NUMBERS.
3) BLOWER – 2 NOS. RIGHT & LEFT 7 INCH X 4 ½ INCH, 4 NUMBERS.
4) U.V. LIGHTS – 256 NM. AND 36 INCH SIZE GERMICIDAL TYPE.
2 NUMBERS.

5) PRE FILTER – PROLONGED WASHABLE PRE-FILTER ARRESTING 90% OF


5 MICRON PARTICLES. 2 NUMBERS.
 LAMINAR AIR FLOW SYSTEM IS CAPABLE OF DELIVERY 1200 CFM.
OF AIR FILTER PRESSURE, AIR PRESSURE DROP FROM 0.25 MM.
0.90” WG.
 LAF SYSTEM SOUND LEVEL DOES NOT EXCEED 65 DBA
 LAF SYSTEM AVERAGE AIR FLOW VELOCITY IS 100 ( + 10) FPM 6”
BELOW THE FILTER.
 LAF SYSTEM IS INDEPENDENT OF AIR COOLING SYSTEM
WHICH PREVENTS MOISTURE DEPOSITED ON THE HEPA
FILTER. & OUR LAF FILTER NEEDNOT TO CHANGE FOR 2-3
YEARS .
 LAF HAVE EPOXY COATED GI BODY & NO DUCT AT ALL PRE
FILTER CLEANING ARE VERY EASY SO MAINTENANCE FREE
SYSTEM.

POSITIVE PRESSURE SYSTEM

FEATURES :

1. MOTOR – 1 HP. WITH SEALED DOUBLE BEARING.

2. BLOWER – 2 NOS. RIGHT & LEFT 7 INCH X 4 ½ INCH

3. U.V. LIGHTS – 256 NM. AND 36 INCH SIZE GERMICIDAL TYPE.

4. PRE FILTER – PROLONGED WASHABLE PRE-FILTER ARRESTING 90%


OF 5 MICRON PARTICLES.
5. PRESSURE DAMPER GIVES 16% FRESH AIR FROM OUTSIDE

O.T.& REMAINING 84% AIR IS AGAIN RECYCLE FROM O.T.

6. AIR CONDITIONER CONDENSING COIL GIVEN IN PPS SYSTEM

GIVES 21 DEGREE +_3 DEGREE SUPPLY.

7. CARBON FILTER REMOVES ALL VOC(VOLATAIL ORGANIC

CHEMICAL) IE SMELL.

8. HEPA FILTER GIVEN IN PPS FILTER ALL O.T. AIR 0.3 MICRON

FILTER WHICH ARREST ALL BACTERIA & FUNGUS.

9. POSITIVE PRESSURE SYSTEM GIVES 30 AIR CYCLE IN

OPERATION THEATER & GIVES COOL AC AIR COMES THRUGH

HEPA GIVES BEST SOLUTION FOR CENTRAL AIR

CONDITIONER NORM OF NABH.

10. OUR PPS REQUIRE VERY LESS AC TONAGE AS COMPAIRE TO

AHU & FURTHER NO NEED TO KEEP IT ON ROUND THE CLOCK

AS PER NORMS OF NABH FOR AHU TO KEEP IT ON ROUND THE

CLOCK THUS GIVE LOT OF SAVING IN ELECTRICITY.

PPS MAINTENANCE FROM INSIDE OT JUST TO CLEAN

/CHANGE PREFILTER FROM FRONT PANNEL OF PPS SO AC

INCORPORETED IN PPS ARE MAINTENANCE FREE.