Rev. No.: 08
Dated: Aug/2017 EQUIPMENT / PIPING THICKNESS MEASUREMENT SHEET
SMP / WI No.: SMP-INSP-051
INSPECTION DEPARTMENT
Page: 1 of 1
Drowing/Sketch Thickness Thickness Reading
Insulation - No Measurement
Orig.
(mm)
Remark(s)

N Scaffolding- 1 Location *
Thk.
(mm) 0 90 180 270 N E S W
(TMLs)
1-1ӯ 4.5
2-1ӯ 4.5
3 3-1ӯ 4.5
4-1ӯ 4.5
5-1ӯ 4.5

25-AU-8232138-RE31O

1 Thickness Gauge S.R. No. : GE DM5E (S/N: 1309726)


Calibration date : 23-DEC-2018
LINE # 25-AU-8232152-RE31O
Probe # and Frequency : DK-537 - 5 MHz (S/N: 1835/58)
North East of TV-8202 Applicable Procedure : PK SHEM 7.05 & SMP-INSP-051
Criteria for passing Inspection : API 570
Eqpt. / Piping Material : A 106 GR.B / A 53 GR.B
Corrosion Allowance (mm) : 1.2 mm
Corrosion Rate (mm / Year) : -
Remaining Life (Year) : -
Surface Temperature (ºC) : AMBIENT
Condition of Piping : Satisfactory X Unsatisfactory
:
Recommendation (if any)
Classification: Internal Use
Plant : VCM – UNIT 82 Description : NORTH OF TV-8202 Inspector(s) : ADAM Date : 05/06/2019
Eqpt / Line No. : 25-AU-8232152-RE31O Service : UTILITY AIR JP