Вы находитесь на странице: 1из 36

Uninterruptible UPS Systems

Power Supply Systems 10 kVA to 300 kVA


Catalog UPS (2400 kVA)
Series S
Supercedes:
Catalog USV (UPS) · 1999

1
MASTERGUARD protects 2

System overview of Series S 3–4

MASTERGUARD UPS units 4–7

UPS version 208 V, 60 Hz 8


Special versions of UPS 8
UPS system configurations 9
Technical data, UPS 400 V 10 – 14
Technical data, UPS 208 V 15 – 16
Configuration and installation 17 – 20
Selection and ordering data, UPS 400 V 21 – 22
Selection and ordering data, UPS 208 V 23

Accessories 24 – 29

Interfaces and additional accessories 24 – 26


External service bypass 27 – 29

MASTERGUARD frequency converter 30 – 31

Dimensions drawings 32 – 34

Conditions of sale and delivery 35

Year 2000 compatibility 35

Standards 36

Masterguard UPS · 2001


UPS Systems

MASTERGUARD protects

No matter how dirty your electrical power


system might be, MASTERGUARD

USV5005a
protects it. This Uninterruptible Power
Supply provides on-line double conver-
sion technology to ensure highest power Voltage fluctuations
security and reliability. So MASTER-
GUARD equalizes all irregularities in the
electrical power system. It makes brief
power disruptions harmless, and at the
same time has enough reserves to bridge
prolonged mains failures (Fig. 1).

USV5006a
Applications:
● DP equipment and systems Distorted voltage curve

● Computer centers
● Process control units
● Control rooms/Scada systems
● Communications equipment
USV5007a

● ISDN systems
● Drives in continuous production Frequency fluctuations
processes
● Production and automation systems
● Life-support systems in hospitals
● Air-traffic control systems
● Safety systems in power stations
USV5008a

● Broadcasting studios, SAT systems


Superimposed interference voltage
● Transport systems
2 ● Personal computers
● Workstations
● Servers and networks
● and many others
USV5009a

Short interruptions
USV5010a

Power failures

● Real
on-line UPS with the
double-conversion principle Fig. 1
Types of mains disturbances

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
System overview of Serie S

Fig. 2 Fig. 3
MASTERGUARD S52100 MASTERGUARD S52300

Introduction Special features ● Automatic bypass increases availability


of the electrical supply
A technically perfected system of UPS ● Real on-line principle of functioning, i.e.
units and batteries with outstanding ben- complete decoupling of the load from ● Compact design, low weight
efits for the customer is now available to all irregularities in the mains supply ● Low noise generation
ensure the uninterrupted supply of power ● Energy saving due to high level of effi- ● High degree of reliability
to electrical equipment with a single- ciency, even during partial-load operation
phase or three-phase mains connection ● IGBT power transistors
in the power range 10 to 2400 kVA.
● Electrical isolation for absolute protec- ● Highly integrated digital electronics
Individual units have an output of up to tion of the loads
● Specially suitable for non-linear
300 kVA 1) but several units can be con- ● Input filter reduces mains harmonic
nected in parallel to provide a total output distortion better than a 12-pulse
computer loads 3
of up to 2400 kVA 2) and/or to increase rectifier
Environmental protection
redundancy. ● The input power factor of the UPS is
approximately unity (cos ϕ ≈ 1) The latest regulations relating to environ-
The units provide the load with an electri-
mental protection are taken into consider-
cal power supply in accordance with the ● The UPS units can simply be connected ation during design, development and
real on-line principle. This is done with no in parallel; retrofitting is also possible production. The rules of Siemens AG for
interruptions of any kind and ensures a ● Rollers allow easy installation for units protection of the environment are also
constantly high-quality of supply. The use
up to and including 100 kVA applied.
of batteries with a back-up time of 60
minutes or more ensures a system which ● Connect, switch on and the UPS goes For example our material-saving design
safely bridges power failures. to work immediately contributes to the preservation of raw
● Parameterization with Windows PC materials and, with our battery manage-
System components ment system, a longer battery life is
● Internal barriers at the interfaces pro-
ensured. The materials are marked for
● UPS units, frequency converters vide complete protection for the user
better recycling.
● Parallel connecting kit ● Clear operating and indicating concept
– No operator needed during operation Power dissipation from the power section
● Battery systems – Clear indication of statuses, capacity is reduced to a minimum with the latest
utilization and battery quality by technological methods. This enables, for
● Battery measuring devices
means of simple LED display example, the selection of a significantly
● Profibus-DP interface – Fault indicator and audible signal smaller air-conditioning system, thus
reducing customers' operating costs.
● Computer interfaces ● Event memory for fault analysis
● Contact interfaces ● Battery conditioning for maintaining the Quality management
condition of the battery
● Air filters The quality management system for
● Detection of defective battery blocks development, manufacturing, sales
● EMC and mains filter
● Battery maintenance by an automatic and service is certified according to
● UPS management and service software battery management system with the DIN EN ISO 9001.
● Separate service switch, up to benefits of maximum battery life
3000 amps. ● Automatic battery circuit test
● Topcost-effectiveness
● Empty cubicles ● Temperature-dependent charging
● EMC limits are ensured in compliance because of
● Remote control boards
with European legal requirements and – high degree of efficiency,
● Telemonitoring via network / standards even with a partial load /
Internet (IP) ● Interfaces with software for all current non-linear partial load
● Connecting accessories computer operating systems
– consumption of reactive
1 2
power almost zero
) up to 60 kVA with 208 V ) up to 480 kVA with 208 V

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
UPS units

Fig. 4 Fig. 5
UPS unit MASTERGUARD S5220, 20 kVA with UPS unit MASTERGUARD S52300, 300 kVA. View of the inside
battery, 400 V type. View of the inside

Design Design features (10 to 100 kVA)


The UPS Series S units with an output of ● Low weight DIN VDE 0106 safety regulations) with
up to 100 kVA are ready-to-connect sys- a metalgrid
● Space-saving modular frame construc-
tems with a functional design (Fig. 2).
4 They contain the modular power section
tion with easily removable panels ● Built-in service bypass switch can be
used to disconnect the power electron-
with electronic components, measure- ● Control panel on front of unit
ics
ment and filter devices as well as the ter- ● Detachable front panel with safety lock
mination panel. ● The termination panel is completely
which can be locked at the top plus all-
sealed off to prevent touching of live
The units with up to 20 kVA are equipped round conductive contacts to bar inter-
components
with a battery compartment (see on the fering electromagnetic radiation
right side of Fig. 4). ● The control panel can be opened out-
● Enclosed floor panel with penetration
wards for servicing purposes
Due to the two types of battery compart- for connecting cables
ment, for low and for medium bridging ● Air inlet via ventilation holes at the
● Delivered on a special pallet with roller
times, there are two different housing front; air outlet at top of back panel (up
tracks which allow direct on-site
widths for the 10 to 20 kVA units. to 40 kVA) or on top of cubicle (60 kVA
removal from pallet
to 100 kVA)
The cubicle is HF-tight and fulfils the max- ● Height-adjustable feet ensure stable
imum EMC protection requirements. For ● Fans with low noise generation for
installation
larger batteries and in the case of outputs extracting heat
over 20 kVA, a battery cubicle is installed ● When the front panel is detached (see ● Air-filter pads can be fitted at the air
next to the UPS unit. Fig. 4), in the lower left part of the unit
inlet
the service bypass switch (SB) is
The UPS units above 125 kVA output are
accessible and the termination panel, ● All parts of the cubicle can be recycled
ready-to-connect systems in the system
which is covered (in compliance with
cubicle (Fig. 3). In the individual sections
of this cubicle, there are the modules of
the power section, including electronic Design features (125 to 300 kVA)
components and measurement and filter
devices. The cubicle is also HF-tight. ● Design features (125 to 300 kVA) Features differing from those for cubi-
cles of Series S, 10 to 100 kVA
● Cubicle system of Rittal make, in use
all over the world ● Single or double-wing doors at the
front
● Very easy accessibility of unit compo-
nents ● Delivered on pallet or pallets
● Stable housing frame ● Integrated service bypass switch
optional for types S 52125 and
● All panels are easy to mount or detach
S52150
● Cubicle suitable for false-floor installa- ● Air outlet on top of the cubicle
tion
● Cubicle frames with underclearance
● Extensive range of accessories
obtainable from Rittal, e.g. fastening
systems, etc.

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
UPS units

A UPS unit basically consists of several


power electronic components, filters,
measurement devices and wound com- Service bypass
ponents together with a termination Electronic
(up to 150 kVA unit) bypass
panel (Fig. 6).
Input
filter Converter
Power components
Loads
The power section consists of the follow- Mains
connection
ing components:
● Mains input filter Output SB
transformer
● Converter, consisting of rectifier, filter EMC and filter
filter Battery
and inverter manager
● Output transformer with filter for form-
ing three-phase sinusoidal output volt-

AUSV-5111c
age
Battery
● Electronic bypass
● Service bypass switch (SB) with which Fig. 6
the power electronics can be discon- Overview of components in UPS unit, 400 V
nected for servicing purposes (standard
feature up to 100 kVA; optional up to The output transformer and the filter
150 kVA) capacitor together form a filter circuit
which uses the pulse train to create a
● Battery manager sinusoidal output voltage with a low dis-
● Maintenance-free lead battery, inte- tortion factor. The load is well protected
grated in UPS units up to 20 kVA against the direct battery voltage by
means of electrical isolation.
● EMC filter
Electronic bypass

USV5013a
Input filter
A thyristor switch is the main component
The input filter reduces the phase effect of the electronic bypass.
of the input current by filtering the har-
monics. The bypass is completely independent of 5
other components and is therefore a
Converter redundant supply circuit. It provides the Fig. 7
load with an uninterruptible supply in the Principle of pulse-width modulation
The converter consists of the rectifier and following situations:
the inverter. The three-phase bridge of
the rectifier with series-connected line ● During manual switchover from inverter
reactor converts the mains voltage into to bypass operation
DC voltage. The IGBT inverter generates ● Overloading of the inverter or inverter ● Warning if battery temperature is too
an exactly symmetrical, three-phase volt- fault high
age system by means of high-frequency
pulse-width modulation (PWM) (Fig. 7). ● Short-circuit in the load ● Adapted reactions resulting from age-
Due to the high pulse frequency, the ing of the battery (self-learning effect)
closed-loop control system can intervene Battery manager
Options
very quickly. This produces a high-quality The battery manager provides a whole
output-voltage waveform, even in the With measuring modules (BMM) con-
package of functions with the following
case of non-sinusoidal current input (non- nected to the battery blocks, enhanced
basic features:
linear loads). The salient functional char- battery management is possible with the
– The reliability of the battery supply is
acteristics of the open-loop and closed- following functions:
assured
loop control systems of the inverter are – The battery's service life is increased ● Battery conditioning by means of
as follows: in comparison to other methods defined charging and discharging
● Digital, closed-loop voltage and fre- Features of the battery manager: ● Detection and recording of the current
quency control with a high dynamic battery quality
response, i.e. ● Active filtering of the superimposed AC
– Low distortion factor of the output current to << 1 %, thus reducing age- ● Detection and localization of defective
voltage, even in the case of non-linear ing of the battery battery blocks and their connectors
loads ● Charging only when required
– High peak currents
– Active influencing of the waveform ● Limitation of charging current reduces ● Battery
– Quartz-controlled natural frequency temperature increase of the battery maintenance by means
– Soft synchronization and parameteriz- ● Temperature-dependent charging pre-
of automatic battery manage-
able synchronization speed vents excessive or insufficient charging, ment with the benefit of
– Complete mains redundancy due to thus increasing battery availability
synchronization with mains voltage maximum battery service life
– Quick triggering of load fuses due to ● Discharge-time indicator
high short-circuit current ● Overdischarge protection prevents cell
reversal of weaker cells
● Regular, automatic battery circuit tests
detect faults in the battery circuit

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
UPS units

Battery the power section and electronics (safe ● Indication of current battery quality by
isolation in accordance with EN 60 950). the battery manager
The UPS units with outputs ranging from
10 kVA to 20 kVA are supplied with a Thanks to the use of digital signal proces- ● Servicing and monitoring software,
built-in battery as standard. This battery sors and ASICs, only a few components PowerProtect VIS, for Windows PCs
has a back-up time of 7 minutes in the are necessary, the result being a very (95/98/NT).
case of a 20 kVA unit and up to 20 min- high level of reliability.
The diagnostics system contains a non-
utes in the case of 10 kVA. In the ultima-
volatile memory which constantly col-
tive versions, these times are Control and indicator panel
lects information from the UPS. If
approximately 20 minutes and 50 min-
The clearly laid-out control and indicator required, this information can be read out
utes respectively. A built-in fuse discon-
panel provides the operator with informa- via the service interface.
nector provides electrical isolation
tion which is important for operating the
between battery and battery manager. The alarms and fault signals are shown as
unit. It is designed as a membrane-type
Separate battery cubicles are available for digital codes.
keyboard (see Fig. 8) and the indicators
larger outputs and longer back-up times.
provide an overview of the following: Typical alarms include
For details, see selection and ordering
– Power failure
data. ● Status of the mains supply (LED LINE)
– Residual battery time expired
● Status of the UPS unit and the battery – Inverter overheating
Options
– Service life of fan expired
● Back-up time of the battery in the event
● Parallel operation
of a power failure (LED strip) Typical fault signals include
Parallel operation of up to eight UPS
– Interrupted battery circuit
units of the same size is made possible ● UPS load (LED strip)
– Inverter fault
by means of a parallel operation kit ● Causes of faults when problems occur – Bypass defect.
(more than 8 on request). All Series S
units can be retrofitted with this kit. The digital display indicates the battery
back-up times and the fault codes for
In order to reduce harmonic effects and
diagnosis.
cope with more exacting EMC require-
ments, additional filters can be inserted Alarms (ALARM LED) and faults (FAULT
in the input circuit or input and output LED) are signalled by yellow or red LEDs
circuit. respectively. If there are several items of
information, they are shown in sequence.
● With an additional filter, the harmonic
effect of the input current to the 50 Hz A key-operated switch is used to switch
mains is reduced to less than 10 % between UPS operation (LINE LED) and
6 (recommended by the association of the bypass (BYPASS LED).
German power stations VDEW 1994).
An audible signal indicates any faults
The harmonic effect is therefore
which occur. It can be cancelled with the
smaller than in the case of a compara-
TEST/RESET key.
ble 12-pulse rectifier at the UPS input.
For servicing purposes, there is an RS232
An additional filter with the same bene-
interface on the control panel.
fits is available if a 60 Hz mains feeds.
The TEST/RESET key is for
● With further filters, the interference
emitted by UPS units with up to ● resetting the audible signal after fault
100 kVA output can be reduced even signals
further down to the limits of EN 55 022, ● outputting alarms from the fault mem-
Class B.
ory on the two-digit display
The termination panel in the bottom part ● testing the indicator lamps
of the unit can be provided with a sepa-
rate mains connection for the bypass.
Service funktions
The units can be supplied with degree of
The diagnostics and indicator system has
protection IP 31 and with filter pads for
the following special features to aid serv-
the air inlet.
icing:
Fig. 8
Electronics ● Real-time clock: events are stored in Control and indicator panel
real time. They can then be read out via
Like the power section, the electronics
the service interface on the control
have a modular design. The electronic
panel.
assemblies are assigned to the individual
power modules. The electronics of the ● Elapsed time counter: With recording
bypass are completely autonomous. The of the elapsed hours of UPS operation,
control panel and the unit’s interfaces an indication can be given of when
form a separate component. The unit’s maintenance is necessary.
interfaces are electrically isolated from

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
UPS units

Interfaces Using the interfaces Parallel operation


The UPS is equipped with various inter- A multi-transceiver is provided for the Up to eight units with the same output
faces (see table below). contact interface. The multi-transceiver is can be operated in parallel. The parallel
connected to the X4 contact interface in connecting kits needed for this (1 for
The connection for UPS Quick OFF is
the UPS. For further details, see section each UPS unit) include the necessary
available on terminals
“COT interface module” , page 24. connecting cables (length for 10 to
Terminal conditions for Quick OFF: 100 kVA unit: 5 m, 125 to 300 kVA: 15 m).
At interface X2, the MP21 multiplexer or
shielded cables with short-circuit-proof In this way, it is possible to increase the
the SNMP adapter, SC21, can be oper-
installation, maximum cable length of total output and provide redundancy, e.g.
ated. More details are provided in a sepa-
50 m, minimum conductor cross-section (n+1) operation. If a system made up of
rate document.
0.75 mm2. 400 Volt UPS units is expanded retro-
The X5 interface is used for shared moni- spectively, it must be ensured that only
A connection for the service interface is
toring on a PC in the case of multiblock Version "0" units are operated in parallel or
provided on the front of the control panel.
UPS systems. It is connected to the PC Version "1" units (this is indicated by the
There are several data interfaces (see by means of an additional RS 485/RS 232 8th character in the order number for the
table below) on the control panel. They converter and suitable cables. More unit). Each UPS has its own battery. The
can be accessed internally. details can be obtained on request. load outputs of the individual UPS units
must be led to a common load point via
separate isolating devices. The bridging
function of an integrated service bypass
can be used up to the rated current of the
UPS unit. In the case of larger currents,
an external service switch can take the
whole load. For more details, see the
section "External service bypass",
page 27.

Name Connectable system(s) Parameterizable for Remarks


Type/form
Identifiaction code

Combined interface PC with PowerProtect or service PC Contacts: 7


RS 232 und floating contacts 1) / Sub-D, 25-pole, (USS®) via RS 232 and/or monitoring Contact rating 24 V, 1A
female system Additional SELV power source
X2 Control system via floating contacts 12 V DC, 50 mA available 2)

Contact interface PC with PowerProtect NET, AS/400 Contact rating 24 V, 1 A


Floating contacts 1) / Sub-D, 9-pole, female PCs/workstations via multiplexer, Additional SELV power source
X4 Computer network with SNMP via 12 V DC, 50 mA available 2)
adapter, remote signalling panel FST-K

PC interface PC with PowerProtect VIS for UPS Cannot be used with service
RS 485 (serial) / Sub-D, 9-pole, female multiblock application interface
X5

Service interface Service PC (USS®) Cannot be used with PC


RS 232 (serial) / Sub-D, 9-pole, female interface
X3

1) Signals:
AC fail (power failure)
Bypass active (electronic bypass on)
Low battery
Summary alarm
2
) The 12 V DC, 50 mA power source from combined interface and contact interface may only be subjected to one load.

Additional interfaces Scope of supply


A separate assembly for integrating the UPS unit on a pallet, 1 accompanying set
UPS in Profibus-DP networks is available. of operating instructions, servicing/moni-
For more details, see the section "Acces- toring software (PowerProtect VIS) on
sories", page 26. CD-ROM and battery fuses.

Masterguard UPS · 2001


MASTERGUARD Series S
Additional basic versions of the unit
UPS units 208 V, 60 Hz, 10 kVA to 60 kVA

An additional basic version of the UPS An additional transformer lifts up the Options
unit for a 208 V three-phase system with input voltage to feed the standard recti- ● Emission of interference limited to val-
60 Hz can be supplied. fier. The 60 kVA, 208 V unit is shown in
ues in accordance with FCC Part 15,
Fig. 2 on page 3 (same housing as for
This type of unit has the same design as Class A
100 kVA unit, 400 V). A backfeed protec-
the Series S with 400 V, i.e. the cubicle
tion in accordance with UL 1778 can also ● Phase effect affecting the 60 Hz system
system, power components and inte-
be provided. < 10 % (better than 12-pulse rectifier)
grated battery belong to the same family
of devices but with other technical data. The mains voltage can be set to 220 V as ● Degree of protection IP 31 correspond-
an alternative. ing to NEMA2 and air filter
The technical data, the data for configura-
tion and installation as well as the order-
ing and selection data are located on their
own pages.

Special versions of the UPS unit

In addition to the basic versions ● Output voltage regulated by hand ● Special external paint finish
MASTERGUARD Series S units for 400 V in all levels ≤ 415 V ● Customized performance
or 208 V three-phase systems, numerous ● Protection against overvoltage caused
special versions of the unit can be built
from remote lightning or switching Note
according to a customer’s specific
operation
wishes. For example The S series of units can also be supplied
● Operation with a shared battery as frequency converters. For more
● Special frequency on the output side
details, see page 30.
≤ 100 Hz ● U-shaped sections instead of rollers on
feet (10 to 100 kVA). These shaped sec-
● Special voltage on the input or output
tions go from the front to the back.
side
● Halogen-free cables

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
UPS system configuration

Mains Mains

Battery

Battery Converter/ Bypass Converter/ Bypass


battery battery
manager manager
A USV-5116d

AUSV-5115c
SB SB

Load Load
Fig. 9 Fig. 10
UPS 10 to 20 kVA, with built-in battery, max. 50 or 20 min. back- UPS 10 to 100 kVA, separate battery in battery cubicles, 60 min. back-up time
up time, 1 mains connection and more, one mains connection

Mains 2 Mains 1

Battery Converter/ Bypass


battery
manager
A USV-5114c

SB

Load

Fig. 11
UPS 10 to 20 kVA, with built-in battery, two mains connections

Mains Mains

Battery Battery

Converter/ Bypass Converter/ Bypass


battery battery
manager manager

AUSV-5129a
SB SB

Loads

Fig. 12
Multiblock UPS system with one battery per UPS block, consisting of 2 to 8 identical UPS blocks, 10 to 150 kVA block size. Load capability of the integrated
service bypass up to the rated load of the UPS block.

Mains Mains Mains


UPSn UPS1 SB

Battery Battery

Converter/ Bypass Converter/ Bypass


battery battery
manager manager
A USV-5155

Load

Fig. 13
Multiblock UPS system with external service bypass (SB), consisting of 2 to 8 identical UPS blocks, 125 to 300 kVA block size

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 100 (800) kVA, 400 V
Technical data

UPS unit Type S5210 S5215 S5220 S5230 S5240 S5260 S5280 S52100
Rated power kVA 10 15 20 30 40 60 80 100

Input

Mains supply Standard For both rectifier and bypass


Option Separately for rectifier and bypass

Supply voltage 3 AC/N 380, 400 V ±15 %1), 415 V +10 %/–15 %

Supply frequency Hz 50 or 60 ±5 %

cos ϕ > 0.98

Apparent power without battery charging kVA 9 13 18 26 35 53 70 88


with battery charging kVA 10 14.5 20 28.5 38.5 58.5 77 97

Phase effect 6-pulse with input reactor ● ● ● ● ● ● ● ●

Current distortion factor with strengthened mains input filter < 8 % with harmonic-free 50 Hz mains resp. 60 Hz mains
(better than VDEW recommendation)2)

Mains configuration Symmetrical three-phase mains, e.g. TN-C, TN-S, TN-C-S, IT

Battery

Rated battery voltage V 552

Number of cells for lead-acid batteries 276

Minimum final discharge voltage V 455

Static voltage tolerance 1%

10 Input power at rated load kW 8.7 13 17 26 34 50 67 84


Inverter

Output

Rated voltage 3 AC/N 400 V, 380 V or 415 V parameterizable

Voltage tolerance static ±1 % at balanced load


±2 % at 50 % unbalanced load
±2 % at 100 % unbalanced load (single phase)
dynamic 4 % at 100 % load step

Recovery time ms < 10

Rated frequency Hz 50 or 60

Frequency tolerance self-clocked ±0.1 %


line-clocked ±1 % (adjustable to ±2 %, ±3 % or ±4 %)

Frequency change rate Hz/s 0.1 (adjustable to 1 or 2)

Phase displacement at balanced load °el ≤1


at 50 % unbalanced load °el ≤1
at 100 % unbalanced load °el ≤1

Voltage distortion factor with linear load <1%


with non-linear load <8%

Permissible non-linear load up to 100 %, acc. to EN 50 091-1

Permissible crest factor of load current max. 3

Overload capability up to 5 s 1.5 x IN


(three-phase) up to 30 s 1.35 x IN

Short-circuit current single-phase 3 x IN for 20 ms, clearing acc. to EN 50 091-1, -2 and -3


three-phase 2,1 x IN for 20 ms

Rated apparent power at cos ϕind = 0.8 kVA 10 15 20 30 40 60 80 100

Rated active power kW 8 12 16 24 32 48 64 80

Rated current at 400 V, cos ϕind = 0.8 A 14 22 29 44 58 87 116 145

1) Lower tolerance limit of 380 V not for continuous operation


2) VDEW: association of German power stations

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 100 (800) kVA, 400 V
Technical data

UPS unit Type S5210 S5215 S5220 S5230 S5240 S5260 S5280 S52100
Rated power kVA 10 15 20 30 40 60 80 100

Permissible ambient temp.1) during operation 0 °C to +40 °C, load reduction at higher temperatures
during storage –40 °C to +70 °C

Climatic category acc. to DIN IEC 721 Better than 3K2, however observe notes on installation site, page 17
Inspection acc. to DIN IEC 68-2

Cooling F (built-in fan)

Immunity to electrical interference IEC 801-2, -3, -4 and -6

Emitted interference (EMC) Standard EN 50 091-2 Tables 2 and 4


Option EN 55 022 Class B

Degree of protection basic version IP 20 (up to 40 kVA: IP 21)


acc. to EN 60 529
special versions IP 20 with air filter pads (up to 40 kVA: IP 21 with air filter pads)
IP 31 with air filter pads

Humidity in accordance with EN 60 068-2-56

Insulation group ΙΙΙa

Installation altitude Up to 1000 m above sea level


Above that, reduction of load (see page 17)

Cubicle color Ergo grey (similar to RAL 7044, silk grey)

Dimensions See chapter ”Dimension Drawings“

Efficiency2) at 100 % load % 91 92 92 92 92 92.5 93 93.5


at 75 % load % 90.5 91 92 91 92 92.5 92 93
at 50 % load % 89 88 91 89 91 91 90 92
at 25 % load % 83 84 86 85 87 88 86 89

Power loss Pv at rated load kW 0.8 1.1 1.4 2.1 2.8 3.9 4.8 5.6
at 75 % rated load kW 0.6 0.9 1.0 1.8 2.0 2.9 4.1 4.5 11
Conversion: at 50 % rated load kW 0.5 0.8 0.8 1.5 1.5 2.3 3.5 3.5
Power loss in BTU/h during idling kW 0.4 0.6 0.6 1.0 1.0 1.3 1.65 1.65
= Pv/[kW] x 3412

Air requirement m3/h 500 500 500 1000 1000 1500 1500 1500

Electronic bypass

Max. permissible overload current for 10 ms A 200 350 600 800 1100 2000 2500 3000
with external bypass fuse F1 selective

Noise level (acc. to DIN 45 635) dB (A) <54 <56 <56 <59 <59 <65 <66 <66

Weight without battery approx. kg 270 340 340 435 435 620 750 750
with battery type B, C, D approx. kg 450 560 560 – – – – –
(cubicle width 650 mm)
with battery type G, H, K, N approx. kg 700 770 770 – – – – –
(cubicle width 850 mm)

Built-in battery (cubicle 650 mm wide)

Back-up time 3 to 5 years service life min 10 o.20 11 7 – – – – –


at rated load 7 to 10 years service life min 16 10 6

Back-up time 3 to 5 years service life min 12 o.23 13 10 – – – – –


at 100 % non-linear load 7 to 10 years service life min 19 12 8
(e.g. computer)

Back-up time 3 to 5 years service life min 25 o.45 25 19 – – – – –


at 50 % non-linear load 7 to 10 years service life min 35 23 16

Air requirement acc. to DIN VDE 0510 for the battery section m3/h 0.3 o. 0.5 0.5 0.9 – – – – –

Further technical data for battery See technical data "Built-in batteries" (page 12)

Built-in battery (cubicle 850 mm wide) Back-up time (rated load): see page 21, more data on request

1
) Recommended temperatures for integrated batteries: + 20 °C to + 25 °C
Note: If ambient temperature above 25 °C for a long time, the service life of the battery is reduced by half with each 10 °C temperature increase
2
) The efficiency levels also apply with the optionally built-in filters

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 20 kVA
Technical data

Built-in batteries 10 kVA to 20 kVA

Rated voltage 552 V (2 volts per cell)

Number of cells per row 276

Charging time of a battery up to 90 % rated capacity Approx. 8 hours


with approx. 30 min
back-up time

Final discharge voltage 455 V (up to a minimum of 1.65 volts per cell)

Battery type Valve regulated recombination battery to DIN VDE 0510, Part 2

Housing material Flame-resistant plastic to EN 60 950, Class HB

Back-up time See selection and ordering data

Service life Approx. 3 to 5 years (general application)


(to EUROBAT) Approx. 7 to 10 years (high performance)

Recommended ambient temperature +20 °C to +25 °C

Maximum storage time without recharging Approx. 3 months when battery disconnector is open

12

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 125 kVA to 300 (2400) kVA, 400 V
Technical data

UPS unit Type S52125 S52150 S52200 S52300


Rated power kVA 125 150 200 300

Input

Mains supply Standard For both rectifier and bypass


Option Separately for rectifier and bypass

Supply voltage 3 AC/N 380, 400 V ± 15 %1), 415 V +10 %/–15 %

Supply frequency Hz 50 or 60 ± 5 %

cos ϕ 0.98

Apparent power without battery charging kVA 116 139 185 275
with battery charging kVA 127 150 198 295

Phase effect 6-pulse with input reactor ● ● ● ●

Current distortion factor with strengthened mains input filter < 8 % with harmonic-free 50 Hz mains resp. 60 Hz mains
(better than VDEW recommendation)2)

Mains configuration Symmetrical three-phase mains, e.g. TN-C, TN-S, TN-C-S, IT

Battery

Rated battery voltage V 552

Number of cells for lead-acid batteries 276

Minimum final discharge voltage V 455

Static voltage tolerance 1%

Input power at nominal load, cos ϕ = 0.8 kW 106 127 169 252 13
of inverter

Output

Rated voltage 3 AC/N 400 V, 380 V or 415 V parameterizable

Voltage tolerance statisch ±1 % at balanced load


±2 % at 50 % unbalanced load
±2 % at 100 % unbalanced load (single-phase)
dynamisch ±4 % at 100 % load step

Recovery time ms < 10

Rated frequency Hz 50 or 60

Frequency tolerance self-clocked ±0.1 %


line-clocked ±1 % (adjustable to ±2 %, ±3 % or ±4%)

Frequency change rate Hz/s 0.1 (adjustable to 1 or 2)

Phase displacement at balanced load °el ≤1


at 50 % unbalanced load °el ≤1
at 100 % unbalanced load °el ≤1

Voltage distortion factor with linear load <1%


with non-linear load <5%

Permissible non-linear load acc. to EN 50 091-1, max. 100 kVA

Permissible crest factor of load current max. 3

Overload capability up to 5 s 1.5 x IN


(three-phase) up to 30 s 1.35 x IN

Short-circuit current single-phase 3 x IN for 20 ms, clearing acc. to EN 50 091-1, -2 and -3


three-phase 2.1 x IN for 20 ms

Rated apparent power at cos ϕind = 0.8 kVA 125 150 200 300

Rated active power kW 100 120 160 240

Rated current at 400 V, cos ϕind = 0.8 A 181 217 289 432

1
) Lower tolerance limit of 380 V not for continuous operation.
2
) VDEW: association of German power stations

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 125 kVA to 300 (2400) kVA, 400 V
Technical data

UPS unit Type S52125 S52150 S52200 S52300


Rated power kVA 125 150 200 300

Permissible during operation 0 °C to +40 °C, load reduction at higher temperatures


ambient temp. during storage –40 °C to +70 °C

Climatic category acc. to DIN IEC 721 Better than 3K2, however observe notes on installation site, page 17
Inspection acc. to DIN IEC 68-2

Cooling F (built-in fan)

Immunity to electrical interference IEC 801-2, -3, -4 and -6

Emitted interference (EMC) EN 50 091-2, Tables 2 and 4

Degree of protection basic version IP 20


acc. to EN 60 529
special versions IP 20 with air filter pads
IP 31 with air filter pads

Insulation group ΙΙΙa

Installation altitude Up to 1000 m above sea level


Above that, reduction of load (see page 17)

Cubicle color RAL 7035 (light grey)

Dimensions See chapter ”Dimension Drawings“

Efficiency1) at 100 % load % 94 94 94.5 94.5


at 75 % load % 94 94 94.5 94
at 50 % load % 93.5 93.5 94 94
at 25 % load % 91 91.5 92 92

Power loss Pv at rated load kW 6.4 7.6 9.3 13.8


at 75 % rated load kW 4.8 5.5 6.6 11.2
Conversion: at 50 % rated load kW 3.5 3.9 4.7 7.2
Power loss in BTU/h during idling kW 2 2.3 3.3 4.6
14 = Pv/[kW] x 3412

Air requirement m3/h 3000 3000 4200 5000

Electronic bypass

Max. permissible overload current for 10 ms A 3000 3600 3900 6300

Noise level (acc. to DIN 45 635) dB (A) < 65 < 65 < 68 < 70
2)
Weight approx. kg 1000 1000 1310 18403)

1) The efficiency levels also apply with the optionally built-in filters.
2) Weight of UPS parts: left part: 1050 kg, right part: 260 kg
3) Weight of UPS parts: left part: 1410 kg, right part: 430 kg

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 60 (480) kVA, 208 V
Technical data

UPS unit Type S5210 S5215 S5220 S5230 S5240 S5260


Rated power kVA 10 15 20 30 40 60

Input

Mains supply Standard For both rectifier and bypass


Option Separately for rectifier and bypass

Supply voltage 3 AC/N 208 V, 220 V +10 % / –15 %

Supply frequency Hz 60 ±5 %

cos ϕ > 0.98

Apparent power without battery charging kVA 9 13 18 26 35 53


with battery charging kVA 10 14.5 20 28.5 38.5 58.5

Phase effect 6-pulse with input reactor ● ● ● ● ● ●

Current distortion factor with < 8 % with harmonic-free 60 Hz mains


strengthened mains input filter (better than VDEW recommendation)1)

Mains configuration Symmetrical three-phase mains, e.g. TN-C, TN-S, TN-C-S, IT

Battery

Rated battery voltage V 552

Number of cells for lead-acid batteries 276

Minimum final discharge voltage V 455

Static voltage tolerance 1%

Input power at nominal load kW 8.7 13 17 26 34 50 15


of inverter

Output

Rated voltage 3 AC/N 208 V, 220 V parameterizable

Voltage tolerance statisch ±1 % at balanced load


±2 % at 50 % unbalanced load
±2 % at 100 % unbalanced load (single-phase)
dynamisch 4 % at 100 % load step

Recovery time ms < 10

Rated frequency Hz 60

Frenquenztoleranzen self-clocked ±0.1 %


line-clocked ±1 % (adjustable to ±2 %, ±3 % or ±4 %)

Frequency change rate Hz/s 0.1 (adjustable to 1 or 2)

Phase displacement at balanced load °el ≤1


at 50 % unbalanced load °el ≤1
at 100 % unbalanced load °el ≤1

Voltage distortion factor with linear load <1%


with non-linear load <5%

Permissible non-linear load Up to 100 % of rated load acc. to EN 50 091-1

Permissible crest factor of load current max. 3

Overload capability up to 5 s 1.5 x IN


(three-phase) up to 30 s 1.35 x IN

Short-circuit current single-phase 3 x IN for 20 ms, clearing acc. to EN 50 091-1, -2 and -3


three-phase 2.1 x IN for 20 ms

Rated apparent power at cos ϕind = 0.8 kVA 10 15 20 30 40 60

Rated active power kW 8 12 16 24 32 48

Rated current at 400 V, cos ϕind = 0.8 A 28 42 56 83 112 167

1) VDEW: association of German power stations

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 60 kVA, 208 V
Technical data

UPS unit Type S5210 S5215 S5220 S5230 S5240 S5260


Rated power kVA 10 15 20 30 40 60

Permissible during operation 0 °C to +40 °C, load reduction at higher temperatures


ambient temp.1) during storage –40 °C to +70 °C

Climatic category acc. to DIN IEC 721 Better than 3K2, however observe notes on installation site, page 17
Inspection acc. to DIN IEC 68-2

Cooling F (built-in fan)

Immunity to electrical interference IEC 801-2, -3, -4 and -6

Emitted interference (EMC) Standard EN 50 091-2, Tables 2 and 4


Option FCC part 15, class A

Degree of protection basic version IP 20 (up to 40 kVA: IP 21), q NEMA Type 1


acc. to EN 60 529
special versions IP 20 with air filter pads (up to 40 kVA: IP 21 with air filter pads) q NEMA Type 2
IP 31 with air filter pads q NEMA Type 2

Humidity acc. to EN 60 068-2-56

Insulation group ΙΙΙa

Installation altitude Up to 1000 m above sea level


Above that, reduction of load (see page 17)

Cubicle color Ergo grey (similar to RAL 7044, silk grey)

Dimensions See chapter ”Dimension Drawings“

Efficiency2) at 100 % load % 90 90 90 91 91 91


at 75 % load % 89.5 89.5 90 90 91 90.5
at 50 % load % 87 86 87 88.5 90.5 90.5
at 25 % load % 82.5 82.5 83.5 84 86 86

Power loss Pv at rated load kW 0.9 1.3 1.8 2.4 3.1 4.7
16 at 75 % rated load kW 0.7 1.0 1.3 2.0 2.4 3.8
Conversion: at 50 % rated load kW 0.6 0.9 1.2 1.6 1.7 2.5
Power loss in BTU/h during idling kW 0.5 0.8 0.8 1.2 1.2 1.5
= Pv/[kW] x 3412

Air requirement m3/h 500 1000 1000 1000 1000 1500

Noise level (acc. to DIN 45 635) dB (A) <50 <57 <57 <57 <57 <65

Weight without battery approx. kg 340 400 400 550 550 1000
with battery type B, C, D approx. kg 560 620 620 – – –

Built-in battery

Back-up time 3 to 5 years service life min 10 od.20 11 7 – – –


at rated load 7 to 10 years service life min 16 10 6

Back-up time 3 to 5 years service life min 12 od.23 13 10 – – –


at 100 % non-linear load 7 to 10 years service life min 19 12 8
(e.g. computer)

Back-up time 3 to 5 years service life min 25 od.45 25 19 – – –


at 50 % non-linear load 7 to 10 years service life min 35 23 16

Air requirement acc. to DIN VDE 0510 for the battery section m3/h 0.3 od. 0.5 0.5 0.9 – – –

Further technical data for battery See technical data "Built-in batteries" (page 12)

1
) Recommended temperatures for integrated batteries: +20 °C to +25 °C.
Note: If ambient temperature above 25 °C for a long time, the service life of the battery is reduced by half with each 10 °C temperature increase.
2
) The efficiency levels also apply with the optionally built-in filters.

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 300 (2400) kVA
Configuration and installation

Installation site It is not necessary to reduce the load for Fig. 16 shows the connection to two
installation altitudes up to 2000 m above mains supplies. For this purpose, the
The following requirements must be
sea level as long as the ambient tempera- UPS unit must be equipped with a sec-
complied with when the installation site
ture does not exceed + 30 °C. ond mains feed (option). The bypass is
is selected:
supplied via U1, V1, W1 and N1 terminals.
● Ambient temperature between 0 °C 100 The rectifier is supplied via the U2, V2

AUSV5106a
and + 40 °C for UPS units without bat- and W2 terminals.
teries

Load in %
90 Connection of the N conductor (TN
● Ambient temperature for lead-acid bat- mains) is shown in all these figures. For
teries (in the UPS unit or in the battery 80
operation with an IT network, an N con-
cubicle) according to the recommenda- nection between mains, UPS and load is
tion of the battery manufacturer, not necessary.
between + 15 °C and + 25 °C. 70
When the conductor cross-sections are
● Avoid exposing the batteries and bat- being planned, it is necessary to take
tery cubicle to more than one hour of 1000 2000 3000 account of local conditions and regula-
direct sunlight per day. Installation altitude in m tions as well as the use-related voltage
drops due to the cable lengths. The val-
● Avoid harmful environmental influences Fig. 14 ues shown in the following tables are rec-
such as Permissible load in relation to installation altitude ommended values for copper conductors
– vibrations
with plastic insulation at ambient temper-
– dust Ambient temperature atures of up to + 40 °C and cable lengths
– corrosive atmosphere
The units without batteries can be oper- of up to 100 m. The listed current and
● Maintain clearance of at least 50 cm ated without restriction within the range connection values apply to a rated volt-
between top of cubicle and ceiling 0 °C to 40 °C. If they are operated contin- age of 400 V resp. 208 V, depending on
uously at higher temperatures, the load the type of unit, the rated load and the
● Because of cooling air outlet, do not
must be reduced: maximum battery charging current.
cover top of cubicle (60 to 300 kVA) and
Selective load fuses are determined
maintain 20 cm clearance from the wall
according to DIN 57 636, Part 21.
(up to 40 kVA). Side clearance not nec- Temperature up to 40 °C 45 °C 50 °C
essary. The neutral must be designed with the
Permissible 100 % 88 % 76 % same cross-section as a single phase.
● Take heat dissipation into consideration load
If the loads are non-linear (e.g. computer
● Ensure that floor can carry the load loads), the N conductor must be
Transport strengthened in accordance with the 17
● Units of 10 to 100 kVA can be supplied
table. The N1 and N3 terminals are each
with U-shaped sections instead of roll- Each UPS unit is delivered on a general- therefore double terminals.
ers on request. They are therefore ideal purpose pallet. The cubicle can be rolled
for false-floor installation. off at the place of installation by using the The power cables from the mains and to
tracks provided (only cubicles up to and the load must be connected as a clock-
Masterguard Series S UPS are as stand-
including 100 kVA). Units of 200 kVA and wise-rotating field.
ard suitable for bottom cable entry.
If the cables are fed from behind the upwards, are transported in two sections.
Connecting a battery
cubicle, there is a clearance below of The pallet dimensions are given in the
45 mm (10–100 kVA) resp. 100 mm section, "Dimension drawings". If an external battery is connected to an
(125–300 kVA). UPS unit, super-fast battery fuses in line
Connection with DIN 43 620 must be used in order to
Terminals resp. busbars for power cables
provide short-circuit protection for the
are located in the lower part of UPS units The UPS units, Series S, can be operated UPS batteries. A set of battery fuses is
front (see metalgrid in fig. 4 and 5, which in all symmetrical three-phase mains included in the scope of supply of every
covers the terminals). (TN, IT). Fig. 15, 17 or 19 shows the UPS UPS unit. For the types of fuses, see the
Signal, power and battery cables should power connections to the mains and following tables relating to configuration
be segregated from each other. loads and also to the battery cubicle (only and installation. Connect L+ with C2 or
in the case of an additional battery cubi- C3 and L– with D2 or D3.
With regard to battery cubicles, the spe- cle). The bypass and the rectifier are sup-
cial stipulations of DIN VDE 0510 Part 2 plied via the U1, V1, W1 and N1 terminals. Connecting a frequency converter
as well as the instructions for handling
the battery are to be observed. Example: phase L1 must be connected to The values on pages 18 and 19 apply in
U1, L2 to V1 and L3 to W1. the case of supply from one mains and
Installation altitude they also apply to load connection.
If units are installed at altitudes over
1000 m above sea level, the load must be
reduced as shown in Fig. 14 because of
the air's reduced cooling effect.

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 100 (800) kVA, 400 V
Configuration and installation

UPS units Type S5210 S5215 S5220 S5230 S5240 S5260 S5280 S52100
Rated power kVA 10 15 20 30 40 60 80 100

Supply from one mains (standard)1)


U1, V1, W1, N1 for rectifier and bypass

Minimum conductor cross-section 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 35 mm2/M10 50 mm2/M10 2 x 35 mm2/M10
Max. permissible conductor cross-section 6 mm2 6 mm2 6 mm2 35 mm2 35 mm2 2 x 50 mm2/M10 2 x 50 mm2/M10 2 x 50 mm2/M10
per terminal

Maximum current 14 A 22 A 29 A 44 A 58 A 87 A 116 A 145 A


Prescribed fuse type gL, to the mains (F1) 16 A 25 A 35 A 50 A 63 A 100 A 125 A 160 A

Supply from two mains (option)


U1, V1, W1, N1 for bypass: U2, V2, W2 (N) for rectifier

Mains 1 U1, V1, W1, N11)

Minimum conductor cross-section 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 35 mm2/M10 50 mm2/M10 2 x 35 mm2/M10
Max. permissible conductor cross-section 6 mm2 6 mm2 6 mm2 35 mm2 35 mm2 2 x 50 mm2/M10 2 x 50 mm2/M10 2 x 50 mm2/M10
per terminal

Maximum current 14 A 22 A 29 A 44 A 58 A 87 A 116 A 145 A


Prescribed fuse type gL, to the mains (F1) 16 A 25 A 35 A 50 A 63 A 100 A 125 A 160 A

Mains 2 U2, V2, W21)

Minimum conductor cross-section 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 35 mm2/M10 50 mm2/M10 2 x 35 mm2/M10
(N conductor not necessary although
spare terminal for N available)

Max. permissible conductor cross-section 6 mm2 6 mm2 6 mm2 35 mm2 35 mm2 2 x 50 mm2/M10 2 x 50 mm2/M10 2 x 50 mm2/M10

Maximum current 14 A 21 A 29 A 41 A 56 A 85 A 111 A 140 A


Prescribed fuse type gL, to the mains (F2) 16 A 25 A 35 A 50 A 63 A 100 A 125 A 160 A

Battery connection C2, D21)

Minimum conductor cross-section 6 mm2 10 mm2 10 mm2 16 mm2 25 mm2 35 mm2/M10 50 mm2/M 10 50 mm2/M 10
Max. permissible conductor cross-section 35 mm2 35 mm2 35 mm2 35 mm2 35 mm2 2 x 50 mm2/M10 2 x 50 mm2/M10 2 x 50 mm2/M10
18
Maximum current at final discharge 19 A 29 A 38 A 57 A 76 A 112 A 149 A 186 A

Fuse EFEN type 2 x 00G 2 x 00H 2 x 00A 2 x 00B 2 x 00C 4 x 00B 4 x 00C 4 x 00D

Load connection U3, V3, W3, N31)

Minimum conductor cross-section 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 35 mm2/M10 50 mm2/M10 2 x 35 mm2/M10
Max. permissible conductor cross-section 6 mm2 6 mm2 6 mm2 35 mm2 35 mm2 2 x 50 mm2/M10 2 x 50 mm2/M10 2 x 50 mm2/M10
per terminal

Maximum current 14 A 22 A 29 A 44 A 58 A 87 A 116 A 145 A


Permissible selective fuse to the load 10 A 16A 20 A 25 A 35 A 50 A 63 A 100A
if bypass ready
Neutral (N) to mains and load: when load is non 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
linear increase the cross-section by the factor of
1) In the case of rated outputs up to 40 kVA, with connector sleeves for finely stranded conductors in acc. with DIN 46 228. Above 40 kVA, with cable lugs in
acc. with DIN 46 235.
Mains Mains 2 Mains 1
L1 L1" L1'
L2 L2" L2'
L3 L3" L3'
N N N

F1 F2 F1

U1 V1 W1 N1 PE U2 V2 W2 PE U1 V1 W1 N1
Rectifier and Rectifier Bypass
bypass connection connection connection
D2 (_) _
D2 ( )
C2 (+) C2 (+)
AUSV-5165a

A USV-5166a

U3 V3 W3 N3 PE U3 V3 W3 N3 PE

Battery UPS unit Battery UPS unit


cubicle cubicle
Loads Loads

Fig. 15 Fig. 16
Connections in the case of one mains supply Connections in the case of two mains supplies
Battery connection only in the case of external battery cubicle Battery connection only in the case of external battery cubicle

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 125 kVA to 300 (2400) kVA, 400 V
Configuration and installation

UPS units Type S52125 S52150 S52200 S52300


Rated power kVA 125 150 200 300

Supply from one mains (standard)1)


U1, V1, W1, N1 for rectifier and bypass

Minimum conductor cross-section 2 x 50 mm2 2 x 70 mm2 2 x 95 mm2 2 x 185 mm2


Max. permissible conductor cross-section per terminal 2 x 95 mm2/M 10 2 x 95 mm2/M 10 2 x 185 mm2/M 12 2 x 185 mm2/M 12

Maximum current 220 A 250 A 351 A 526 A


Fuse type gL, to the mains (F1) 250 A 250 A 400 A 630 A

Mains supply from two mains (option)


U1, V1, W1, N1 for bypass: U2, V2, W2 (N) for rectifier

Mains 1 U1, V1, W1, N11)


Minimum conductor cross-section 95 mm2 2 x 50 mm2 185 mm2 2 x 150 mm2
Max. permissible conductor cross-section 2 x 95 mm2/M 10 2 x 95 mm2/M 10 2 x 185 mm2/M 12 2 x 185 mm2/M 12

Maximum current 181 A 217 A 289 A 432 A


Fuse type gL, to the mains (F1) 200 A 250 A 315 A 500 A

Mains 2 U2, V2, W21)


Minimum conductor cross-section 2 x 50 mm2/M10 2 x 70 mm2/M 10 2 x 95 mm2/M 12 2 x 185 mm2/M 12
(N conductor not necessary although
spare terminal for N available)

Max. permissible conductor cross-section 2 x 95 mm2/M 10 2 x 95 mm2/M 10 2 x 185 mm2/M 12 2 x 185 mm2/M 12

Maximum current 220 A 250 A 351 A 526 A


Fuse type gL, to the mains (F2) 250 A 250 A 400 A 630 A

Battery connection C3, D31)


Minimum conductor cross-section 2 x 50 mm2 2 x 50 mm2 2 x 95 mm2 2 x 150 mm2
Max. permissible conductor cross-section 2 x 95 mm2/M 10 2 x 95 mm2/M 10 2 x 185 mm2/M 12 2 x 185 mm2/M 12

Maximum current at final discharge 240 A 290 A 380 A 570 A

Fuse two in each case 3NE3227 (250 A) 3NE3230-0B (315 A) 3NE3232-0B (400 A) 3NE3335 (560 A) 19
Load connection U3, V3, W3, N31)
Minimum conductor cross-section 95 mm2 2 x 50 mm2 185 mm2 2 x 150 mm2
Max. permissible conductor cross-section per terminal 2 x 95 mm2/M 10 2 x 95 mm2/M 10 2 x 185 mm2/M 12 2 x 185 mm2/M 12

Maximum current 181 A 217 A 289 A 432 A


Permissible selective fuse to the load if bypass ready 63 A 80 A 100 A 160 A

Neutral (N) to mains and load: when load is non 1.5 1.4 1.3 1.2
linear increase the cross-section by the factor of
1)
With cable lug to DIN 46 235.

L1 Mains Mains 2 Mains 1


L1" L1'
L2 L2" L2'
L3 L3" L3'
N N N

F1 F2 F1

U1 V1 W1 N1 PE U2 V2 W2 PE U1 V1 W1 N1
Rectifier and Rectifier Bypass
bypass connection connection connection
D3 (_) D3 (_)
C3 (+) C3 (+)
AUSV-5112e

AUSV-5113d

U3 V3 W3 N3 PE U3 V3 W3 N3 PE

Battery UPS unit Battery UPS unit


cubicle cubicle
Loads Loads

Fig. 17 Fig. 18
Connections in the case of one mains supply Connections in the case of two mains supplies
Battery connection for an external battery cubicle Battery connection for an external battery cubicle

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 60 kVA, 208 V, 60 Hz
Configuration and installation Cross-section in AWG/and mm2

UPS units Type S5210 S5215 S5220 S5230 S5240 S5260


Rated power kVA 10 15 20 30 40 60

Supply from one mains (standard)


U1, V1, W1, N1 for rectifier and bypass

Minimum conductor cross-section AWG/mm2 8/6 8/10 6/16 4/25 2/35 2/0/2 x 25
Max. permissible conductor cross-section AWG/mm2 4/16 1/35 1/35 1/0/50 1/0/50 2 x 2/0/2 x 50
per terminal

Maximum current 28 A 42 A 56 A 83 A 111 A 167 A


Recommended fuse type gL, to the mains (F1) 35 A 50 A 63 A 100 A 125 A 200 A

Mains supply from two mains (option)


U1, V1, W1, N1 for bypass: U2, V2, W2 (N) for rectifier

Mains 1 U1, V1, W1, N1

Minimum conductor cross-section AWG/mm2 8/6 8/10 6/16 4/25 2/35 2/0/2 x 25
Max. permissible conductor cross-section AWG/mm2 4/16 1/35 1/35 1/0/50 1/0/50 2 x 2/0/2 x 50
per terminal

Maximum current 28 A 42 A 56 A 83 A 111 A 167 A


Recommended fuse type gL, to the mains (F1) 35 A 50 A 63 A 100 A 125 A 200 A

Mains 2 U2, V2, W2

Minimum conductor cross-section AWG/mm2 8/6 8/10 6/16 4/25 2/35 2/0/2 x 25
(N conductor not necessary although spare
terminal for N available)
Max. permissible conductor cross-section AWG/mm2 4/16 1/35 1/35 1/0/50 1/0/50 2 x 2/0/2 x 50

Maximum current 28 A 42 A 56 A 83 A 111 A 167 A


Recommended fuse type gL, to the mains (F2) 35 A 50 A 63 A 100 A 125 A 200 A

Battery connection C, D

Minimum conductor cross-section AWG/mm2 8/10 8/10 8/10 8/16 4/25 2 x 4/35
20 Max. permissible conductor cross-section AWG/mm2 4/25 4/25 4/25 2/35 2/35 2 x 0/70

Maximum current at final discharge 19 A 29 A 38 A 57 A 76 A 112 A

Fuse EFEN type 2 x 00G 2 x 00H 2 x 00A 2 x 00B 2 x 00C 4 x 00B

Load connection U3, V3, W3, N3

Minimum conductor cross-section AWG/mm2 8/6 8/10 6/16 4/25 2/35 2/0/2 x 25
Max. permissible conductor cross-section AWG/mm2 4/16 1/35 1/35 1/0/50 1/0/50 2 x 2/0/2 x 50
per terminal

Maximum current 28 A 42 A 56 A 83 A 111 A 157 A


Permissible selective fuse to the load if bypass ready 20 A 25 A 35 A 50 A 63 A 125 A

Mains L1 Mains 2 Mains 1 L1'


L1
L2 L2 L2'
L3 L3 L3'
N N N

F1 F2 F1

U1 V1 W1 N1 PE U2 V2 W2 PE U1 V1 W1 N1
Rectifier Rectifier Bypass
and bypass connection connection
D2 connection D2
C2 C2
A USV-5168a
AUSV-5167

U3 V3 W3 N3 PE
U3 V3 W3 N3 PE

Battery UPS unit Battery UPS unit


cubicle cubicle

Loads Loads

Fig. 19 Fig. 20
Connections in the case of one mains supply Connections in the case of two mains supplies
Battery connection only in the case of an external battery cubicle Battery connection only in the case of an external battery cubicle

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 100 kVA, 400 V
Selection and ordering data

Version Order No. Order No.


extension
6 S U 1 2 @@ - 1 @@@@ - @@A 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Basic version: Type: Power:

UPS, I/O: 3/3-ph., S5210 10 kVA ÓÒ


380/400/415 V,*) S5215 15 kVA ÓÃ
50/60 Hz*) S5220 20 kVA ÔÒ
Service Bypass (SB) S5230 30 kVA ÕÒ
4 data interfaces S5240 40 kVA ÖÒ
} @@
S5260 60 kVA ØÒ
S5280 80 kVA ÚÒ
S52100 100 kVA ÛÒ

Variations: Battery: Without integrated battery (10 to 100 kVA) Ü


– service life With integrated battery (10 to 20 kVA)
(s/l) 3 to 5 years (s/l): 10 min/10 kVA Á
– backup time 20 min/10 kVA; 11 min/15 kVA; 7 min/20 kVA Â
39 min/10 kVA; 23 min/15 kVA; 15 min/20 kVA â
62 min/10 kVA; 35 min/15 kVA; 23 min/20 kVA ã }@
7 to 10 years (s/l):
16 min/10 kVA; 10 min/15 kVA; 6 min/20 kVA ß
53 min/10 kVA; 30 min/15 kVA; 19 min/20 kVA æ
8 to 10 years (s/l):
90 min/10 kVA; 56 min/15 kVA; 35 min/20 kVA é

Parallel no (single block) Ü


operation yes (parallel block) Á }@

EMC, filters and Basic version in acc. with EN 50 091-2, Tab. 2 and 4 Ò
mains supply EMC acc. to EN 55 022, Class B Ö }@
One mains supply Ò
Two mains supply Ô
(1 x rectifier, 1 x bypass)
One mains supply and amplified filtering of the Ã
harmonics in input current 50 Hz
Two mains supplies and amplified filtering of the Ø }@ 21
harmonics in input current 50 Hz
One mains supply and amplified filtering of the Ù
harmonics in input current 60 Hz
Two mains supplies and amplified filtering of the Ú
harmonics in input current 60 Hz

Options: Degree IP 20 (up to 40 kVA: IP 21) Ò


of protection IP 20 (up to 40 kVA: IP 21) with air filter Ó }@
IP 31 with air filter Ã

Modules None Ü
Extended battery management with battery measur- Á
}@
ing modules (BMM) in the case of integrated battery
(10 to 20 kVA)

*) Defaults in bold letters, variations must be ordered. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16


||||| || ||||| ||||
6 S U 1 2 @@ - 1 @@@@ - @@A 0

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 125 kVA to 300 kVA, 400 V
Selection and ordering data

Version Order No. Order No.


extension
6 S U 1 2 @@ - 0 A @ 0 @ - @A A 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Basic version: Type: Power:

UPS, S52125 125 kVA ÛÓ


I/O: 3/3-ph., S52150 150 kVA ÛÔ
380/400/415 V,*) S52200 200 kVA ÛÕ } @@
50/60 Hz,*) S52300 300 kVA ÛÃ
EMC to
EN 50 091-2, Tab. 2 + 4,
4 data interfaces

Variations: Parallel Single-block operation, without SB à


operation/ Single-block operation, with SB (≤ 150 kVA) á }@
service bypass (SB) Parallel operation, without SB â

Mains supplies One mains supply Ò


and filters Two mains supply Ô
(1 x rectifier, 1 x bypass)
One mains supply and amplified filtering Ã
of the harmonics in input current 50 Hz
Two mains supplies and amplified filtering Ø }@
of the harmonics in input current 50 Hz
One mains supply and amplified filtering Ù
of the harmonics in input current 60 Hz
Two mains supplies and amplified filtering Ú
of the harmonics in input current 60 Hz

Options: Degree IP 20 Ò
of protection IP 20 with air filter Ó }@
IP 31 with air filter Ã

*) Defaults in bold letters, variations must be ordered. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16


||||| || ||||| ||||
6 S U 1 2 @@ - 0 A @ 0 @ - @A A 0
22

Special versions UPS Systems 10 kVA to 300 kVA

Add "–Z" and the order code to the Order No. and indicate the required setting values in plain text

Order code Setting Setting value Basic value

Y01 Setting

Mains
1 Rated voltage (380, 400, 415 V) ... V 400/230 V
2 Rated frequency (50, 60 Hz) ... Hz 50 Hz

Output
3 Increase of output voltage
(Rated voltage + 0...10 %) ... % 0%
4 Battery present (Yes/no) Yes

Y02 Battery parameters Further order codes


1 Manufacturer (make) Div. Y10: halogen-free cables
2 Type Div.
3 Battery temp. sensor present (Yes/no) Yes Y51: special paint finish of cubicle,
4 End-of-charge voltage (2,23...2,4 V/Z) ... V/Z 2,27 V/Z acc. to RAL
5 Recharging time (0...100 h) ... h Div.
6 Intervals between charging (10...504 h) ... h Div.
7 Charging voltage/temperature compensation
(0...-10 mV/K per cell) ... mV/K -3 mV/K
8 Rated capacity 20 h -value ... Ah Div.
9 Rated capacity 10 h -value ... Ah Div.
10 Rated capacity 1 h -value ... Ah Div.
11 Rated capacity 10 min-value ... Ah Div.
12 Internal resistance (per 12 V block) ... mΩ Div.
13 Maximum charging current ... A Div.

Masterguard UPS · 2001


MASTERGUARD Series S
UPS Systems 10 kVA to 60 kVA, 208 V
Selection and ordering data

Version Order No. Order No.


extension
6 S U 1 2 @@ - 6 @@@@ - @@A 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Basic version: Type: Power:

UPS, I/O: 3/3-ph., S5210 10 kVA ÓÒ


208/220 V, 60 Hz S5215 15 kVA ÓÃ
Service bypass (HU) S5220 20 kVA ÔÒ
4 data interfaces S5230 30 kVA ÕÒ } @@
S5240 40 kVA ÖÒ
S5260 60 kVA ØÒ

Variations: Battery Without integrated battery (10 to 60 kVA) Ü


With integrated battery (10 to 20 kVA)
3 to 5 years: 10 min/10 kVA Á
20 min/10 kVA; 11 min/15 kVA; 7 min/20 kVA Â
}@
7 to 10 years:
16 min/10 kVA; 10 min/15 kVA; 6 min/20 kVA ß

Parallel No (single-block) Ü
operation Yes (parallel-block) Á }@

EMC, filters and Basis version in acc. with EN 50 091-2, Tab. 2 and 4 Ò
mains supply FCC Part 15,Class A Ã }@
One mains supply Ò
Two mains supply Ô
(1 x rectifier, 1 x bypass)
One mains supply and amplified filtering Õ }@
of the harmonics in input current, 60 Hz
Two mains supplies and amplified filtering Ö
of the harmonics in input current, 60 Hz

Options: Degree IP 20 (up to 40 kVA: IP 21), NEMA 1 Ò


of protection IP 20 (up to 40 kVA: IP 21) with air filter, NEMA 2 Ó }@
IP 31 with air filter, NEMA 2 Ã
23
Modules None Ü
Extended battery management with battery measur- Á }@
ing modules (BMM) in the case of integrated battery
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
||||| || ||||| ||||
6 S U 1 2 @@ - 6 @@@@ - @@A 0

Special versions

Add "-Z" and the order code to the Order No. and indicate the required setting values in plain text

Order code Setting Setting value Basic value

Y01 UPS parameters


Mains
1 Mains voltage (380, 400, 415 V) ... V 208/120 V
Output
2 Increase of output
(Rated voltage + 0...10 %) ... % 0%
3 Battery present (Yes/no) Yes

Y02 Battery parameters


1 Manufacturer (make) Div.
2 Type Div.
3 Battery temp. sensor present (Yes/no) Yes
4 End-of-charge voltage (2,23...2,4 V/Z) ... V/Z 2,27 V/Z
5 Recharging time (0...100 h) ... h Div.
6 Intervals between charging (10...504 h) ... h Div.
7 Charging voltage/temperature compensation
(0...-10 mV/K per cell) ... mV/K -3 mV/K
8 Rated capacity 20 h -value ... Ah Div.
9 Rated capacity 10 h -value ... Ah Div.
10 Rated capacity 1 h -value ... Ah Div.
11 Rated capacity 10 min-value ... Ah Div.
12 Internal resistance (per 12 V-Block) ... mΩ Div.
13 Maximum charging current ... A Div.

Masterguard UPS · 2001


MASTERGUARD Series S
Accessories
Interfaces

COT module
A module can be supplied for multiplying
the contact interfaces of the UPS unit.
These interfaces can be multiplied by
arranging the modules side by side
(Fig. 21).
Each module provides a double contact
interface via 9-pole, Sub-D plug-in con-
nectors (low voltage 24 V, 1 A). Systems
can be connected according to the table
below.
The modules are secured to a mounted
rail and can be mounted outside a UPS in
a switchgear cubicle or cubicle for tele-
communications equipment. A separate
12 V DC power supply is needed for this.
In all Series S units, there is enough
space to fit a COT module and a suitable Fig. 21
power supply. The mounting location is COT interface module, 2 modules connected in parallel to a mounting rail.
on the termination panel at the bottom.
Modules have to be mounted on site. The signals are electrically isolated from
the power section of the UPS. This
ensures safe isolation in accordance with
EN 60 950.

Interface assignment of the COT

Type Connectable systems Signals Contact rating/


Form (max. 2 per module) Remarks
24 Identification

Status outputs

Floating contacts – Alarm system – AC fail Switching voltage acc. to


Sub-D 9-pole, female – Monitoring system – Bypass active DIN VDE 0110, insulation group A
X4 or X5 – Central control system – Low battery (residual battery 24 V, 1 A
time low)
– Summary alarm

Control-input signal

Type Connectable systems Signals Remarks


Form
Identification

Sub-D 9-pole, female A computer or control station with UPS OFF A 12 V DC SELV
X4/6 and 9 or authorization to switch off the UPS power source is also available:
X5/6 and 9 Load rating for current loops via cus-
tomer's computer: 12 V DC, 50 mA

Control system A floating contact (12 V rating) is


required for customer computer

Installation The signals between the COT module Each parallel module is connected to the
and the UPS are transmitted via shielded neighbouring module via a short ribbon
A number of interface modules can be
cables (X2 plugs). These are connected cable (see photo). Parallel connection of
mounted next to each other on a mount-
to the UPS at the contact interface (X4 up to 9 modules is possible. Power can
ing rail. A separate 12 V DC power supply
plug) on the rear of the control panel (see be supplied to up to 9 modules by parallel
is required. For information on a suitable
connection diagram included in scope of connection of the power units referred to
power supply when the same installation
supply). Both ends of the cable shield in the technical data.
method is used for a maximum of 3 COT
should be connected to ground (PE).
modules, see technical data. This power UPS OFF signal: If several computers are
supply must be provided from the Parallel operation of several modules: connected to the above modules, the
secured rail of the UPS (at the UPS out- UPS OFF signals can be sent simultane-
If several modules are to be mounted
put). There are two terminals (X1) on the ously. Only the UPS OFF signal from the
next to each other, the first module from
COT for connecting the 12 V DC power authorized computer, however, should be
the left (when seen from the component
supply. passed on to the COT module (X4 or X5
side, see Fig. 21) must be connected to
plug).
the power supply and to the contact
interface of the UPS unit.

Masterguard UPS · 2001


MASTERGUARD Series S
Accessories
Technical Data

Operating temperature 0 to 55 °C

Humidity during operation 20 to 80 %

Pollution severity 2, non-conductive pollution, no moisture condensation

Protection class To DIN VDE 0106, Part 1 (IEC 536)

Insulation To DIN EN 60 950/A2: 1994-09 and UL 508C: 1992-10 (draft)

Contact rating for alarms 24 V, 1 A

Rating of the two 12 V outputs Two times 50 mA


(SELV extra-low voltage)

Power supply of one module 12 V DC, 200 mA

Max. length of data cable Approx. 30 m

Dimensions See section "Dimension Drawings"

Note on a suitable power supply for 3 COT Safe electrical isolation between input and output voltage necessary.
modules Manufacturer's recommendation for product:
Power supply for installation of mounting rail: Order No.: CM 62-PS-230AC / 12DC / 1
Phoenix Contact GmbH & Co., Postfach 1341, D-32819 Blomberg, Tel. 05235/3-00
or a representative of Phoenix Contact GmbH in 45 countries

Ordering data

Designation Order No.

1 COT module 6SU5671-0AA00-0AA0

25
Scope of supply
The scope of supply for each module The scope of supply for a module does
includes not include
● One COT module with two contact ● Shielded data cable with 9-pole Sub-D
interfaces (each with Sub-D, 9-pole) plug (male) or socket (female). Pin
assignment 1:1 for connecting the sup-
● Cable adapter 2 x 5-pole tab connector
plied cable adapter to the UPS Series S
to 9-pole Sub-D plug (connection to
UPS) ● Mounting rail
● Connector for connecting a neighbour- ● Separate power supply
ing COT module (ribbon cable)
● Connection diagram

Additional accessories

Systems cubicles ● Cubicle complete with back and side For information on parallel operation, see
walls page 7.
Empty cubicles of various sizes can be
supplied for individually expanding or sup- ● Threaded rails inside Units delivered before 1.1.1997 can be ret-
plementing the UPS Series S units, 10 to rofitted for parallel operation by the serv-
● Cubicle mounted on pallet
100 kVA. They are uniformly constructed ice department after the unit version has
and match the design of the UPS units. been checked.
Parallel operation kit
The cubicles are suitable for installing
When parallel operation is used for
low-voltage switchgear, transformers, dis- With a parallel operation kit, UPS units
increasing the power output of UPS
tribution boards and electronic and con- of Series S which have already been sup-
installations with 400 V, it must be
ventional control equipment. plied can be retrofitted for parallel opera-
ensured that the units operated in parallel
tion. The kit comprises a paralleling
Design features are all Version 0 units or all Version 1
module and a signal cable and enables
units. This version number is shown at
● Space-saving modular rack design communication with parallel UPS units.
the 8th position in the order number.
One kit is required per UPS unit.
● Cubicles with 4 roller feet or, for a
width of 850 and 950 mm, 6 roller feet The signal cables are connected in a ring,
e.g. from UPS1 to UPS2, then to UPS3
● Air inlet through the doors
and finally back to UPS 1.
● Bottom plate with glands

Masterguard UPS · 2001


MASTERGUARD Series S
Accessories
Additional accessories

Profibus-DP connection ● Status of the units UPS at the X4 interface (see page 7). The
length of the connecting cable must not
By installing a Profibus-DP connection, ● Alarm information, information on
exceed 300 m. Ordering data see below.
the UPS Series S can be linked up to faults
higher-level automation systems. The ● Voltage levels at UPS output Software
Profibus-DP bus system enables very fast
cyclical data exchange between higher- ● Control information Solutions for communication with the
level systems such as Simatic S5, S7, UPS Series S units is available for all
Simadyn D, PC/PG and field units. Access Remote signalling panel FST-K known computer operating systems.
procedure: master/slave. Details can be found in the separate bro-
For displaying important, individual sig-
chure on MASTERGUARD software.
The following information is transmitted nals from the UPS, a remote signalling
Accessories and data cables for serial
by the MASTERGUARD Series S: panel can be used.
communication can be supplied on
A mimic-diagram panel is used to display request.
up to 4 UPS units. It is connected to the

Order data

Designation Order No. Dimensions (W x H x D) Weight


Packaging dimensions for
cables and sets

Cubicle, suitable for


S5210, S5215, S5220, S5230, S5240 6SU56 61-0AA00-0AA0 520 mm x 1325 mm x 850 mm 100 kg
6SU56 61-1AA00-0AA0 950 mm x 1325 mm x 850 mm 140 kg
S5260, S5280, S52100 6SU56 61-0BA00-0AA0 520 mm x 1725 mm x 850 mm 120 kg
6SU56 61-1BA00-0AA0 950 mm x 1725 mm x 850 mm 160 kg

Parallel operating set with signal cable, length 5 m 6SU56 72-0AA00-0AA0 200 mm x 390 mm x 260 mm 3 kg

Signal cable for parallel operating set, length 15 m 6SU56 72-0AK15-0AA0 Ø 400 mm x 100 mm 6 kg
26
Signal cable for parallel operating set, length 25 m 6SU56 72-0AK25-0AA0 Ø 400 mm x 100 mm 10 kg

Profibus-DP interface set for UPS Series S 6SU56 71-0CA00-0AA0 310 mm x 70 mm x 350 mm 0.8 kg

Remote signalling panel FST-K52 for one UPS block 6SU56 73-0AA00-0AA0 185 mm x 230 mm x 95 mm 0.9 kg
Series S

Remote signalling panel FST-K52 for a 2-block UPS 6SU56 73-0BA00-0AA0 380 mm x 320 mm x 140 mm 3.1 kg
system Series S

Remote signalling panel FST-K52 for a 3-block UPS 6SU56 73-0CA00-0AA0 380 mm x 320 mm x 140 mm 3.1 kg
system Series S

Remote signalling panel FST-K52 for a 4-block UPS 6SU56 73-0DA00-0AA0 380 mm x 320 mm x 140 mm 3.1 kg
system Series S

Masterguard UPS · 2001


MASTERGUARD Series S
Accessories
External service bypass HU 52 (HU = SB = service bypass)

Application Design features


For Masterguard single-block and multi- ● Cubicle with closed floor plate
block UPS systems from 125 kVA per
block upwards a HU52 service bypass
● Opening for connecting cables
switch (SB) is available, to transfer load ● After the covering panel at the bottom
from UPS to mains and vice versa with- has been removed, a fork-lift truck or
out interruption e.g. for servicing pur- hoisting car can be driven under the
poses. It is designed to match the UPS unit.
units (Fig. 22) and is integrated between
the UPS and the load (Fig. 23).
● The control element is accessible
when the door is opened
Fig. 23 shows a multiblock system with
an external service bypass (SB). A single-
● All live parts are covered (accident pre-
block system with an existing external SB vention regulations VGB 4)
can be expanded to create a multiblock ● Terminals and components are accessi-
system at any time by adding parallel ble from the front
blocks. When doing so, the rated current
of the SB should be borne in mind.
● Rittal cubicle system

Connection and use Fig. 22


External service bypass HU 52
The supply for the service bypass is con-
nected directly to the mains. The phase
angle and the phase sequence must
Mains Mains Mains
match the connected loads of the bypass
n 1 SB
feeder at the UPS unit. We recommend
to connect phase L1 to U2 phase L2 to
V2 and phase L3 to W2. The switch is Battery Battery
accessible when the front door is open. Converter/ Bypass Converter/ Bypass
The load can thus be switched from "UPS batterie- battery
manager manager
output" to "Mains operation" or vice versa

AUSV5156
without any interruption. When using the
switch, the Series S operating instruc-
Load
tions must be complied with.

Design
27
Fig. 23
The bypass type HU 630 A (Fig. 24) Overview of external SB with multiblock UPS system
basically consists of two fuse-switch
strips, fitted on the supply side with NH
630 A fuses (extra mains protection
therefore not necessary). The "UPS out-
put" is fitted with disconnecting links.
In the service-bypasses, types HU 1000, Q1 Q2
HU 1600 and HU 3000 (Fig. 25), there is a 2 4 2 4
load transfer switch with manual opera-
tion (3-step actuator). 1 1
N
AUSV-5157

All external SBs contain signalling con- PE


tacts for signalling the switch position.
U1 V1 W1 N PE U2 V2 W2 N PE U3 V3 W3 N PE

UPS output Mains supply Load

Fig. 24
Circuit diagram of the external SB, type HU 630 A

X1:
1
Q1 Q2 2

1 1+2 2 3
4
N
AUSV-5158

PE

U1 V1 W1 N PE U2 V2 W2 N PE U3 V3 W3 N PE

UPS output Mains supply Load

Fig. 25
Circuit diagram, types HU 1000 A / HU 1600 A / HU 3000 A

Masterguard UPS · 2001


MASTERGUARD Series S
External service bypass HU 52
Technical Data

Unit

Type HU 630 HU 1000 HU 1600 HU 3000

Rated current 630 A 1000 A 1600 A 3000 A

Operating voltage 3 AC/N 380 V/400 V/415 V

Operating frequency 50 Hz or 60 Hz

Types of mains systems IT, TN-S, TN-C

Permissible ambient temperature 0 °C to +40 °C

Degree of protection IP 31 to EN 60 529 (formerly DIN 40 050)

Humidity class F to DIN 40 040

Cubicle color Light grey to RAL 7035

Dimensions (W x D x H) mm 600 x 600 x 1900 600 x 600 x 1900 800 x 600 x 1900 800 x 800 x 2100

Weight approx. kg 200 240 320 470

Mains supply (U2, V2, W2)

Rated current A 630 1000 1600 3000

Rated output (at 400 V) kVA 436 962 1108 2077

Max. effective short-time current (1 s) kA 25 21 50 55

Possibilities of connection 2 x M 12 2 x M 12 4 x M 12 8 x M 12

UPS connection (U1, V1, W1)


28
Maximum current A 630 1000 1600 3000

Maximum output kVA 436 692 1108 2077


2)
Possibilities of connection 2 x M 12 (4 x 185 mm 2 x M 12 (4 x 240 mm2) 4 x M 12 (8 x 240 mm2) 8 x M 12 (16 x 240 mm2)

Output (U3, V3, W3)

Rated current A 630 1000 1600 3000

Possibilities of connection 2 x M 12 2 x M 12 4 x M 12 8 x M 12

Neutral connection (N/PE)

Neutral terminal size (N) 6 x M 12 6 x M 12 12 x M 12 24 x M 12

Earth terminal size (PE) 6 x M 12 6 x M 12 12 x M 12 24 x M 12

Masterguard UPS · 2001


MASTERGUARD Series S
External service bypass HU 52
Configuration overview

With symmetrical loading of the 3-phase MASTERGUARD UPS parallel installa-


power system and a rated voltage of 400 tions Series S in accordance with the fol-
V, a service bypass can be selected for lowing table.

Number of parallel External service bypass needed to create a single-block or multiblock system with a rated UPS-block output of
UPS blocks used

125 kVA 150 kVA 200 kVA 300 kVA

Total Redundant SB type Max. load SB type Max. load SB type Max. load SB type Max. load
ones output in output in output in output in
kVA kVA kVA kVA

1 -- Integrate d 125 Integrate d 150 HU 630 200 HU 630 300

2 1 HU 630 125 HU 630 150 HU 630 200 HU 630 300


0 HU 630 250 HU 630 300 HU 630 400 HU 1000 600

3 1 HU 630 250 HU 630 300 HU 630 400 HU 1000 600


0 HU 630 375 HU 1000 450 HU 1000 600 HU 1600 900

4 2 HU 630 250 HU 630 300 HU 630 400 HU 1000 600


1 HU 630 375 HU 1000 450 HU 1000 600 HU 1600 900
0 HU 1000 500 HU 1000 600 HU 1600 800 HU 3000 1200

5 2 HU 630 375 HU 1600 450 HU 1600 600 HU 1600 900


1 HU 1000 500 HU 1600 600 HU 1600 800 HU 3000 1200
0 HU 1000 625 HU 1600 750 HU 1600 1000 HU 3000 1500

6 2 HU 1000 500 HU 1600 600 HU 1600 800 HU 3000 1200


1 HU 1000 625 HU 1600 750 HU 1600 1000 HU 3000 1500
0 HU 1600 750 HU 1600 900 HU 3000 1200 HU 3000 1800

7 2 HU 1000 625 HU 1600 750 HU 1600 1000 HU 3000 1500


1 HU 1600 750 HU 1600 900 HU 3000 1200 HU 3000 1800
0 HU 1600 875 HU 1600 1050 HU 3000 1400 HU 3000 2077

8 3 HU 1000 625 HU 1600 750 HU 1600 1000 HU 3000 1500 29


2 HU 1600 750 HU 1600 900 HU 3000 1200 HU 3000 1800
1 HU 1600 875 HU 1600 1050 HU 3000 1400 HU 3000 2077
0 HU 1600 1000 HU 3000 1200 HU 3000 1600

Additional On request On request On request On request


combinations

Selection and ordering data

Servie bypass HU 52 in cubicle Number of UPS Order No.


Type connections

HU 630 4 6SU56 33-0FA00-0AF0


HU 1000 4 6SU56 33-0KA00-0AF0
HU 1600 8 6SU56 33-0PA00-0AF0
HU 3000 8 6SU56 33-0TA00-0AF0

Scope of supply
The external service bypass is supplied
as a complete unit, including door, roof, left
and right side walls, removable front base
strip, and connection diagram.
The cubicle is mounted on a pallet.

Masterguard UPS · 2001


MASTERGUARD Series S
Frequency converter 10 kVA to 300 (2400) kVA, 400 V
Frequency converter 10 kVA to 300 kVA

Another basic version is a MASTER- ● Output transformer with filter verters of the same version are operated
GUARDS Series S in the form of a fre- in parallel (see position 8 in the order
● EMC filter to EN 50 091-2
quency converter. The frequency can be number), i.e. for all units, there must be a
altered from 50 Hz to 60 Hz or vice versa Types of frequency converters: 4 or a 5 at this position.
from 60 Hz to 50 Hz between different 10 kVA, 20 kVA, 40 kVA, 60 kVA, 100 kVA,
The frequency converters can be discon-
400 V three-phase systems. 150 kVA, 200 kVA, 300 kVA
nected for servicing purposes only by
The units have the same design as the The following variants can be used: means of the upstream and downstream
400 V version of the UPS unit, i.e. the disconnecting devices due to the differ-
● Parallel operation of up to 8 identical
cubicle system and power components ent frequencies at the input and output.
units
are from the same family.
The accessories on pages 24 to 26 can
● Enhanced input filter, 50 Hz/60Hz
The following power components are be used.
contained in the frequency converter. ● Degree of protection IP20 (IP21) or
For configuration and installation, refer to
IP31, each with air filter
● Mains input filter the information given on pages 17 and 18
When an installation is being expanded, it or 19 specially the data for “supply from
● Converter
must be ensured that only frequency con- one mains”.

Technical Data

Frequency converter Type S5210 S5220 S5240 S5260 S52100 S52150 S52200 S52300
Rated power kVA 10 20 40 60 100 150 200 300

Input

Mains supply voltage 3 AC/N 380, 400 V ±15 %, 415 V +10 %/–15 %, 440 V +3,5 %/–15 %

Mains frequency Hz 50 or 60 ±5 %
30 cos ϕ > 0,98

Apparent power without battery charging kVA 9 18 35 53 88 139 185 275

Current distortion factor with amplified mains input filter < 8 % in the case of harmonics-free mains supply with 50 Hz
(≥ 150 kVA) (better than VDEW recommendation)1)

Mains configuration Symmetrical three-phase system, e.g. TN-C, TN-S, TN-C-S, IT

Output

Rated voltage 3 AC/N 400 V, 380 V, 415 V or 440 V parameterizable

Voltage tolerance static ±1 % at balanced load


±2 % at 50 % unbalanced load
±2 % at 100 % unbalanced load (single-phase)
dynamic 4 % at 100 % load step

Recovery time ms < 10

Rated frequency Hz 50 or 60

Frequency tolerances ±0.1 %

Phase displacement at balanced load °el ≤1


at 50 % unbalanced load °el ≤1
at 100 % unbalanced load °el ≤1

Voltage distortion factor at linear load / at non-linear load <1%/<8%

Permissible non-linear load acc. to EN 50 091-1, max. 100 kVA

Permissible crest factor of the load current max. 3

Overload capability up to 5 s 1,5 x IN / 1,35 x IN


(three-phase) up to 30 s

Short-circuit current single-phase 3 x IN for 20 ms, clearing acc. to EN 50 091-1, -2, -3


three-phase 2,1 x IN for 20 ms

Rated apparent power at cos ϕind = 0,8 kVA 10 20 40 60 100 150 200 300

Rated active power kW 8 16 32 48 80 120 160 240

Rated current at 400 V, cos ϕind = 0.8 A 14 29 58 87 145 217 289 432
1
) VDEW: association of German power stations.

Masterguard UPS · 2001


MASTERGUARD Series S
Frequency converter 10 kVA to 300 (2400) kVA, 400 V
Technical Data

Frequency converter Type S5210 S5220 S5240 S5260 S52100 S52150 S52200 S52300
Rated power kVA 10 20 40 60 100 150 200 300

Permissible during operation 0 °C to +40 °C, load reduction at higher temperatures


ambient temp. during storage –40 °C to +70 °C

Climatic category acc. to DIN IEC 721 Better than 3K2, however observe notes on installation site, page 17
Inspection acc. to DIN IEC 68-2

Cooling F (built-in fan)

Immunity to electrical interference IEC 801-2, -3, -4 and -6

Emitted interference EN 50 091-2 Tables 2 and 4

Degree of protection acc. to EN 60 529 IP 20 (up to 40 kVA: IP 21), IP 31 as option


Humidity in accordance with EN 60 068-2-56

Insulation group ΙΙΙa

Installation altitude Up to 1000 m above sea level


Above that, reduction of load (see page 17)

Cubicle color Ergo grey (similar to RAL 7044, silk grey) RAL 7035 (light grey)

Dimensions See chapter “Dimension Drawings”

Efficiency at 100 % load % 91 92 92 92.5 93.5 94 94.5 94.5


at 75 % load % 90.5 92 92 92.5 93 94 94.5 94
at 50 % load % 89 91 91 91 92 93.5 94 94
at 25 % load % 83 86 87 88 89 91.5 92 92

Power loss Pv at rated load kW 0.8 1.4 2.8 3.9 5.6 7.6 9.3 13.8
at 75 % rated load kW 0.6 1.0 2.0 2.9 4.5 5.5 6.6 11.2
Conversion: at 50 % rated load kW 0.5 0.8 1.5 2.3 3.5 3.9 4.7 7.2
Power loss in BTU/h during idling kW 0.4 0.6 1.0 1.3 1.65 2.3 3.3 4.6
= Pv/[kW] x 3412

Air requirement m3/h 500 500 1000 1500 1500 3600 4200 5000 31
Noise level (acc. to DIN 45 635) dB (A) <50 <50 <57 <65 <65 <65 <68 <70

Weight approx. kg 280 300 435 620 750 1000 1310 1840

Selection and ordering data

Version Order No. Order No.


extension
6 S U 1 2 @@ - @A @ 0 @ - @A A 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Basic version: Type: Power:

Frequency converter S5210 10 kVA ÓÒ


I/O: 3/3-ph., S5220 20 kVA ÔÒ
380/400/415 V, S5240 40 kVA ÖÒ } @@ Ã
50/60 or 60/50 Hz,1) S5260 60 kVA ØÒ
EMV to S52100 100 kVA ÛÒ
EN 50 091-2, Tables 2 S52150 150 kVA ÛÔ
and 4 S52200 200 kVA ÛÕ } @@ Ö
4 data interfaces S52300 300 kVA ÛÃ

Variations: Parallel no (single-block) 10-100 kVA Ü


operation yes (parallel-block) 10-100 kVA Á
no (single-block) ≥ 150 kVA à
}@
yes (parallel-block) ≥150 kVA â

Filter no etxra filter Ò


≥ 150 kVA / amplified filtering of the harmonics Ã
in the input current, 50 Hz }@
≥ 150 kVA / amplified filtering of the harmonics Ù
in the input current, 60 Hz

Options: Degree IP 20 (up to 40 kVA: IP 21) Ò


of protection IP 20 (up to 40 kVA: IP 21) with air filter Ó }@
IP 31 with air filter Ã
1
) I/O-frequency must be specified! 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
||||| || ||||| ||||
6 S U 1 2 @@ - @A @ 0 @ - @A A 0

Masterguard UPS · 2001


Dimension Drawings

MASTERGUARD Series S

S
s S
MASTERGUARD

MASTERGUARD
OVERLOAD

200 mm
200 mm
LOAD

BYPA SS

INVERTER

BATTE RY

LINE

ALARM

I I

USV-5121d
USV-5122c

55
1325

Æ 55

1325

850
850
100 100
450 320

40
40

70
70

57
57
USV-5126b

USV-5118b
70 70
650 650 520 520
UPS version 1 View of base Empty cubicle View of base

S S
MASTERGUARD

MASTERGUARD
200 mm 1) 0 mm1)
OVERLOAD

LOAD

BYPA SS

INVERTER

BATTE RY

LINE

ALARM

I I

USV-5128a
USV-5176

355 Æ 55
1325

Æ 55

1325

850
850

70
100 430 425

70
275 275

70
40
70

57

225
USV-5170

USV-5171

70 405

105
850 850 950 70 950
UPS version 2 View of base Empty cubicle View of base

Hood for IP 21
200

32 and IP 31 only
S
MASTERGUARD

S S
MASTERGUARD

MASTERGUARD

OVERLOAD

LOAD

BYPA SS

INVERTER

BATTE RY

LINE

ALARM

I I

200 mm
s
0 mm1)
1725
1725

1725
USV-5128a

USV-5121d

Æ 55 55
850

850
70

430 425 100


70

320
40
70
70

57
USV-5119b
USV-5127b

225

USV-5169

405 70
105

950 70 950 950 520 520


UPS version 3 View of base Empty cubicle Empty cubicle View of base
UPS version 3
and empty cubicle

UPS systems 10 to 100 kVA, 400 V: Pallet dimensions, on-site installation


Types (Order no. position 9, battery) UPS version
S5210, S5215, S5220 A, B, C, D 1 UPS version Pallet dimensions
S5210, S5215, S5220 G, H, K, N, X 2 (W x D x H) in
S5230, S5240 A 1 mm
S5260, S5280, S52100 A 3
1 800 x 1200 x 145
Frequency converter 10 to 100 kVA, 400 V: 2 1150 x 1200 x 145
Types (Order no. position 9, battery) UPS version 3 1150 x 1200 x 145

S5210, S5220, S5240 A 1


S5260, S52100 A 3
UPS systems 10 to 60 kVA, 208 V:
Types (Order no. position 9, battery) UPS version
S5210 A, B, C, D 1
S5215, S5220 A, B, C, D 2
S5230, S5240 A 2
S5260 A 3
1 ●
) Clearance = 0 mm in the case of cabling with a false floor. Otherwise clearance = largest bending Legend: : Feet of unit
radius. In the case of battery cubicles, keep air outlet free on the rear. : Cable gland

Masterguard UPS · 2001


Dimension Drawings

MASTERGUARD Series S

MASTERGUARD
s

OVERLOAD

LOAD

BYPAS S

INVERTE R

BATTERY

LINE

ALARM

I I

Cable gland Surface for mounting

52,5
1902 125
A USV-5160

101,5

110

500

602
550
801

71
USV-5159

102 1400

51
26
1604
Æ 11
Fastening
1604 holes

S52125 View of base


S52150

s
MASTERGUARD

OVERLOAD

LOAD

BYPAS S

INVERTE R

BATTERY

LINE

ALARM

I I

Cable gland Surface for mounting

52,5
1902

125
AUSV-5162

101,5
110

500

602
550
600 200 600
71

33
USV-5161

102 1400 600

51
26
1602
Æ 11 Fastening
2204
2204 holes

S52200 View of base

Hood for IP 31
200

only

s
MASTERGUARD

OVERLOAD

LOAD

BYPAS S

INVERTE R

BATTERY

LINE

ALARM

I I

Cable gland Surface for mounting


1902

52,5

125
AUSV-5164

101,5
110

500

602
550

600 200 600


AUSV-5163a

71

102 1400 899


51
26

1602
2504 Æ 11 Fastening
2504 holes

S52300 View of base

Transport with pallet Options:


IP31: add 200 mm in height (S5260 – S52300)

Pallet dimensions (D x W x H) in
mm

S52125, S52150 800 x 1720 x 140


S52200 800 x 1720 x 140 + 800 x 720 x 140
S52300 800 x 1720 x 140 + 800 x 1020 x 140

Height overall: add the height of UPS and pallet


Dimensions in mm

Masterguard UPS · 2001


Dimension Drawings

MASTERGUARD Series S Service bypass and accessories

s s
1900

1900
USV-5172

USV-5173

600 Depth 600 800 Depth 600

HU 630, HU 1000 HU 1600

s
2100

34
USV-5174

800 Depth 800


HU 3000

54
102
95
USV-5124b

Module width 45 mm
27
COT interface module
Side view

Dimensions in mm

Masterguard UPS · 2001


Conditions of Sale and Delivery

Outside Germany: ■
The technical data, dimensions and
Subject to the
General Conditions of Supply and Deli- weights are subject to change unless oth-
very erwise stated on the individual pages of
for Products and Services of the Electri- this catalog.
cal and Electronic Industry and to any The illustrations are for reference only.
other conditions agreed upon with the
recipients of Masterguard pricelists. We reserve the right to adjust the prices
and shall charge the prices applying on
the date of delivery.

Year-2000 compliance

The date change at the end of the millen- We are making detailed investigations These can be due to constellations result-
nium will affect not only DP systems but into the behavior of our products, applying ing from a specific combination of prod-
also products, systems and installations the internationally recognized test profiles ucts and systems or from individual
being used in the field of automation and of the British Standards Institution. The adaptation and/or expansion of the prod-
drive technology. results of these investigations can be ucts and systems.
found in our Year 2000 product database If you have any questions on this matter,
Apart from the hardware and software
components, the application programs under the following internet address: please contact your local Siemens office.
which process the date will especially be
affected by the changeover. http://www.ad.siemens.de/jahr2000

For our automation products and sys- Defects in the functioning of individual
tems, we at Masterguard have given top products, systems and whole plants may
priority to finding ways of smoothing the occur as a result of the changeover.
transition into the next millennium.

35

Masterguard UPS · 2001


Standards

Standards relating to uninterruptible power supply units and systems

DIN EN ISO 9001 Quality management system


DIN IEC 721 Climatic categories
DIN VDE 0100 Specifications for erecting heavy-current installations with rated voltages of up to 1000 V
DIN VDE 0106 Protection against electric shock, classification of electrical and electronic equipment
DIN VDE 0510 Accumulators and battery systems
DIN VDE 0532 Transformers and reactor coils
DIN VDE 0558 Semiconductor converters and their application, e.g. uninterruptible power supply systems (UPS)
DIN VDE 0843 (IEC 801) Electrical interference immunity
DIN 40 040 Utilization category and reliability data for components in telecommunications engineering and electronics
DIN 41 772 Converters, semiconductor rectifiers
DIN 45 635 Noise measurement on machines
DIN 54 840 Marking of plastic components
DIN 57 636, Part 21 Selectivity of fuses
EN 50 091 UPS product standard
EN 55 022 Radio interference of electrical equipment and installations
EN 60 529 IP degree of protection
EN 60 950 Safety
IEC 801/IEC 1000 Electrical interference immunity
SN 36 350-2 Requirements for the environment
VDI 2243 Design of technical products suitable for recycling

36

Issued by: Responsible for the contents:


MASTERRGUARD GmbH Jürgen Strathe
MASTERGUARD GmbH
P.O. Box 26 20
D-91014 Erlangen, Germany

Order No.: A19101-P861-xx-7600


Printed in Germany
Dispostelle 28000

Вам также может понравиться