Вы находитесь на странице: 1из 15

MATERIAL SCHEDULE

JOINT GULF BUSINESS COMPANY


P.O. Box 13200, Salwa Road, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

MATERIAL SCHEDULE
INERTIA BASES FROM VIMCO – USA:

Qty
S. No. Ref. No. Model / Details
(Nos.)
BIB-785412-8
3
Size: 78” x 54”x 12”
1 CHILLED WATER PUMP
24
OSM-1B-158
(3 x 8)
BIB-603606-4
3
HEATING PRIMARY Size: 60” x 36”x 06”
2
PUMP 12
OSM-1A-127
(3 x 4)
BIB-422406-4
4
HEATING SECONDARY Size: 42” x 24”x 06”
3
PUMP-01-02 16
OSM-1A-125
(4 x 4)
BIB-543006-4
2
HEATING SECONDARY Size: 54” x 30”x 06”
4
PUMP-03 8
OSM-1A-127
(2 x 4)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
PRODUCT CATALOGUE /TECHNICAL
DATA SHEET
JOINT GULF BUSINESS COMPANY
P.O. Box 13200, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

CALCULATION DETAILS OF INERTIA BASE


FOR CHILLED WATER PUMP

I. GUIDELINES:
• Weight of the Inertia Base should be more than the weight of Pump + Motor.
• Depth of the Inertia Base should not be less than 1/10 of the length of Inertia Base.

II. CALCULATION:

1. Dimensions = 78” x 54" x 12"

2. Density of concrete = 0.083 lbs/Inch3

3. Weight of Concrete = 78" x 54" x 12" x 0.083 = 4195.15 lbs

4. Base Weight = 90 lbs

5. Weight of Inertia Base = 4285.15 lbs

6. Weight of Pump set = 2695.00 lbs

2695.00 x 1.20 = 3234.00 lbs


7. Weight of Pump set (considered) =
(20% safety of water weight & piping)

8. Total weight (Base + Equipment) = 4285.15+ 3234.00 = 7519.15 lbs

9. No. of isolators = 8 Nos.

10. Unit Weight for Isolators = 7519.15 ÷ 8 = 939.90 lbs

11. Spring Isolator model selected = OSM-1B-158 (1" Deflection)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS ROAD , HOUSTON , TEXAS 77041 , U.S.A INTERNET ADDRESS: www.vimco.biz

78"

67.50"

INERTIA BASE MODEL: BIB 785412-08


EQUIPMENT MFR.:
EQUIP. MODEL:
54" FRAME MODEL:
KW / HP:
RPM:
EQUIP. WEIGHT:
PIPING WEIGHT:
BASE WEIGHT:
TOTAL WEIGHT:
LOC. LOAD ISOLATOR DEFL.
1,2 939.90 lbs OSM-1B-158 1"
N.T.S 3,4 939.90 lbs OSM-1B-158 1"
5,6 939.90 lbs OSM-1B-158 1"

7,8 939.90 lbs OSM-1B-158 1"


1/2 " REBAR ON 8 " CENTERS
SHIP BASES: ASSEMBLED KNOCKDOWN
12" 13"
FEATURES
4.19"
* Modular construction: available in 6" interval lengths,
widths and all standard thicknesses (4", 6", 8", 10")
* Red oxide coated formed steel components
* Welded adjustable height saving isolator brackets
N.T.S

Notes / Remarks : Project : Title : BIB Drawing no.


Client : Bolted Inertia BaseTM S-3000.07
Consultant : (8 Support points)
Representative : Rev. 0
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS
3532-A ROAD
EAST TC , HOUSTON
JESTER , TEXAS BUSINESS
, BROOKWOOD 77041 , U.S.A
PARK , HOUSTON , TEXAS 77018 , U.S.A INTERNET ADDRESS: www.vimco.biz

ISOLATOR RATED SOLID


MODEL LOAD LOAD
(lbs) (lbs)
OSM-1B-150 83 125
OSM-1B-151 150 225
OSM-1B-152 216 325
OSM-1B-153 300 450
OSM-1B-154 400 600
OSM-1B-155 500 750
OSM-1B-156 600 900
OSM-1B-157 733 1100
OSM-1B-158 1200 1800
OSM-1B-159 1666 2500
OSM-1B-150-161 481 722
OSM-1B-151-161 532 799
OSM-1B-152-161 597 896
OSM-1B-153-161 666 1000
OSM-1B-154-161 750 1125
OSM-1B-155-161 871 1307
OSM-1B-156-161 1016 1525
N.T.S. OSM-1B-157-161 1108 1663
OSM-1B-158-161 1616 2425
OSM-1B-159-161 2083 3125

NOTES FEATURES
1. Isolators have a min. operating Kx/Ky ratio of 1.0 * Large diameter laterally stable springs
2. Springs have 50% additional travel to solid beyond rated load. * Welded construction
3. Isolators should be selected in the range of -30% to +25% of rated load. * Anti-skid elastomeric acoustical pad
4. Consult spring chart for isolator performance data. * Built-in leveling device
* Mounting holes furnished as standard
* Galvanized finish
* Spring elements color-coded for easy field verification

Notes / Remarks : Project : Title : OSM-1B Drawing no.


Client : Free-standing Spring Mount S-2055.02
Consultant : Welded Construction
Representative : (1" deflection) Rev. 1
JOINT GULF BUSINESS COMPANY
P.O. Box 13200, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

CALCULATION DETAILS OF INERTIA BASE


FOR HEATING PRIMARY PUMP

I. GUIDELINES:
• Weight of the Inertia Base should be more than the weight of Pump + Motor.
• Depth of the Inertia Base should not be less than 1/10 of the length of Inertia Base.

II. CALCULATION:

1. Dimensions = 60” x 36" x 06"

2. Density of concrete = 0.083 lbs/Inch3

3. Weight of Concrete = 60" x 36" x 06" x 0.083 = 1075.68 lbs

4. Base Weight = 70 lbs

5. Weight of Inertia Base = 1145.68 lbs

6. Weight of Pump set = 710.60.00 lbs

710.60 x 1.20 = 852.72 lbs


7. Weight of Pump set (considered) =
(20% safety of water weight & piping)

8. Total weight (Base + Equipment) = 1145.68+ 852.72 = 1998.40 lbs

9. No. of isolators = 4 Nos.

10. Unit Weight for Isolators = 1998.40 ÷ 4 = 499.60 lbs

11. Spring Isolator model selected = OSM-1A-127 (1" Deflection)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS ROAD , HOUSTON , TEXAS 77041 , U.S.A INTERNET ADDRESS: www.vimco.biz

78"

67.50"

INERTIA BASE MODEL: BIB 785412-08


EQUIPMENT MFR.:
EQUIP. MODEL:
FRAME MODEL:
54" KW / HP:
RPM:
EQUIP. WEIGHT:
PIPING WEIGHT:
BASE WEIGHT:
TOTAL WEIGHT:
LOC. LOAD ISOLATOR DEFL.
1 939.90 lbs OSM-1B-158 1"
N.T.S 2 939.90 lbs OSM-1B-158 1"
3 939.90 lbs OSM-1B-158 1"
4 939.90 lbs OSM-1B-158 1"
1/2 " REBAR ON 8 " CENTERS
SHIP BASES: ASSEMBLED KNOCKDOWN
12" 13"
FEATURES
4.19"
* Modular construction: available in 6" interval lengths,
widths and all standard thicknesses (4", 6", 8", 10")
* Red oxide coated formed steel components
* Welded adjustable height saving isolator brackets
N.T.S

Notes / Remarks : Project : Title : BIB Drawing no.


Client : Bolted Inertia BaseTM S-3000.06
Consultant : (4 Support points)
Representative : Rev. 0
JOINT GULF BUSINESS COMPANY
P.O. Box 13200, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

CALCULATION DETAILS OF INERTIA BASE


FOR HEATING SECONDARY PUMP-01

I. GUIDELINES:
• Weight of the Inertia Base should be more than the weight of Pump + Motor.
• Depth of the Inertia Base should not be less than 1/10 of the length of Inertia Base.

II. CALCULATION:

1. Dimensions = 42” x 24" x 06"

2. Density of concrete = 0.083 lbs/Inch3

3. Weight of Concrete = 42" x 24" x 06" x 0.083 = 501.98 lbs

4. Base Weight = 30 lbs

5. Weight of Inertia Base = 531.98 lbs

6. Weight of Pump set = 325.60 lbs

325.60 x 1.20 = 390.72 lbs


7. Weight of Pump set (considered) =
(20% safety of water weight & piping)

8. Total weight (Base + Equipment) = 531.98+ 390.72= 922.70 lbs

9. No. of isolators = 4 Nos.

10. Unit Weight for Isolators = 922.70 ÷ 4 = 230.68 lbs

11. Spring Isolator model selected = OSM-1A-125 (1" Deflection)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS ROAD , HOUSTON , TEXAS 77041 , U.S.A INTERNET ADDRESS: www.vimco.biz

78"

67.50"

INERTIA BASE MODEL: BIB 785412-08


EQUIPMENT MFR.:
EQUIP. MODEL:
FRAME MODEL:
54" KW / HP:
RPM:
EQUIP. WEIGHT:
PIPING WEIGHT:
BASE WEIGHT:
TOTAL WEIGHT:
LOC. LOAD ISOLATOR DEFL.
1 939.90 lbs OSM-1B-158 1"
N.T.S 2 939.90 lbs OSM-1B-158 1"
3 939.90 lbs OSM-1B-158 1"
4 939.90 lbs OSM-1B-158 1"
1/2 " REBAR ON 8 " CENTERS
SHIP BASES: ASSEMBLED KNOCKDOWN
12" 13"
FEATURES
4.19"
* Modular construction: available in 6" interval lengths,
widths and all standard thicknesses (4", 6", 8", 10")
* Red oxide coated formed steel components
* Welded adjustable height saving isolator brackets
N.T.S

Notes / Remarks : Project : Title : BIB Drawing no.


Client : Bolted Inertia BaseTM S-3000.06
Consultant : (4 Support points)
Representative : Rev. 0
JOINT GULF BUSINESS COMPANY
P.O. Box 13200, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

CALCULATION DETAILS OF INERTIA BASE


FOR HEATING SECONDARY PUMP-02

I. GUIDELINES:
• Weight of the Inertia Base should be more than the weight of Pump + Motor.
• Depth of the Inertia Base should not be less than 1/10 of the length of Inertia Base.

II. CALCULATION:

1. Dimensions = 42” x 24" x 06"

2. Density of concrete = 0.083 lbs/Inch3

3. Weight of Concrete = 42" x 24" x 06" x 0.083 = 501.98 lbs

4. Base Weight = 30 lbs

5. Weight of Inertia Base = 531.98 lbs

6. Weight of Pump set = 279.40 lbs

279.40 x 1.20 = 335.28 lbs


7. Weight of Pump set (considered) =
(20% safety of water weight & piping)

8. Total weight (Base + Equipment) = 531.98+ 335.28= 867.26 lbs

9. No. of isolators = 4 Nos.

10. Unit Weight for Isolators = 867.26÷ 4 = 216.82 lbs

11. Spring Isolator model selected = OSM-1A-125 (1" Deflection)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS ROAD , HOUSTON , TEXAS 77041 , U.S.A INTERNET ADDRESS: www.vimco.biz

78"

67.50"

INERTIA BASE MODEL: BIB 785412-08


EQUIPMENT MFR.:
EQUIP. MODEL:
FRAME MODEL:
54" KW / HP:
RPM:
EQUIP. WEIGHT:
PIPING WEIGHT:
BASE WEIGHT:
TOTAL WEIGHT:
LOC. LOAD ISOLATOR DEFL.
1 939.90 lbs OSM-1B-158 1"
N.T.S 2 939.90 lbs OSM-1B-158 1"
3 939.90 lbs OSM-1B-158 1"
4 939.90 lbs OSM-1B-158 1"
1/2 " REBAR ON 8 " CENTERS
SHIP BASES: ASSEMBLED KNOCKDOWN
12" 13"
FEATURES
4.19"
* Modular construction: available in 6" interval lengths,
widths and all standard thicknesses (4", 6", 8", 10")
* Red oxide coated formed steel components
* Welded adjustable height saving isolator brackets
N.T.S

Notes / Remarks : Project : Title : BIB Drawing no.


Client : Bolted Inertia BaseTM S-3000.06
Consultant : (4 Support points)
Representative : Rev. 0
JOINT GULF BUSINESS COMPANY
P.O. Box 13200, Doha, Qatar TEL: +974 4275 193, FAX: +974 4275 195
Email: info@jgbqatar.com Web: www.jgbqatar.com

CALCULATION DETAILS OF INERTIA BASE


FOR HEATING SECONDARY PUMP-03

I. GUIDELINES:
• Weight of the Inertia Base should be more than the weight of Pump + Motor.
• Depth of the Inertia Base should not be less than 1/10 of the length of Inertia Base.

II. CALCULATION:

1. Dimensions = 54” x 30" x 06"

2. Density of concrete = 0.083 lbs/Inch3

3. Weight of Concrete = 54" x 30" x 06" x 0.083 = 806.76 lbs

4. Base Weight = 40 lbs

5. Weight of Inertia Base = 846.76 lbs

6. Weight of Pump set = 523.60 lbs

523.60 x 1.20 = 628.32 lbs


7. Weight of Pump set (considered) =
(20% safety of water weight & piping)

8. Total weight (Base + Equipment) = 846.76 + 628.32 = 1475.08 lbs

9. No. of isolators = 4 Nos.

10. Unit Weight for Isolators = 1475.08 ÷ 4 = 368.77 lbs

11. Spring Isolator model selected = OSM-1A-127 (1" Deflection)

HVAC EQUIPMENTS & ACCESSORIES, INDUSTRIAL INSULATIONS & ACCESSORIES, INDUSTRIAL VALVES,
GASPHASE MEDIA & ODOR CONTROL SYSTEM, WATER FILTRATION PRODUCTS.
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS ROAD , HOUSTON , TEXAS 77041 , U.S.A INTERNET ADDRESS: www.vimco.biz

78"

67.50"

INERTIA BASE MODEL: BIB 785412-08


EQUIPMENT MFR.:
EQUIP. MODEL:
FRAME MODEL:
54" KW / HP:
RPM:
EQUIP. WEIGHT:
PIPING WEIGHT:
BASE WEIGHT:
TOTAL WEIGHT:
LOC. LOAD ISOLATOR DEFL.
1 939.90 lbs OSM-1B-158 1"
N.T.S 2 939.90 lbs OSM-1B-158 1"
3 939.90 lbs OSM-1B-158 1"
4 939.90 lbs OSM-1B-158 1"
1/2 " REBAR ON 8 " CENTERS
SHIP BASES: ASSEMBLED KNOCKDOWN
12" 13"
FEATURES
4.19"
* Modular construction: available in 6" interval lengths,
widths and all standard thicknesses (4", 6", 8", 10")
* Red oxide coated formed steel components
* Welded adjustable height saving isolator brackets
N.T.S

Notes / Remarks : Project : Title : BIB Drawing no.


Client : Bolted Inertia BaseTM S-3000.06
Consultant : (4 Support points)
Representative : Rev. 0
VIBRATION MANAGEMENT CORPORATION
5930 THOMAS
3532-A ROAD
EAST TC , HOUSTON
JESTER , TEXAS BUSINESS
, BROOKWOOD 77041 , U.S.A
PARK , HOUSTON , TEXAS 77018 , U.S.A INTERNET ADDRESS: www.vimco.biz

ISOLATOR RATED SOLID


MODEL LOAD LOAD
(lbs) (lbs)
OSM-1A-121 40 60
OSM-1A-122 66 100
OSM-1A-123 110 165
OSM-1A-124 173 260
OSM-1A-125 246 370
OSM-1A-126 300 450
OSM-1A-127 560 840

FEATURES
* Large diameter laterally stable springs
* Welded construction
* Anti-skid elastomeric acoustical pad
* Built-in leveling device
* Mounting holes furnished as standard
* Galvanized finish
* Spring elements color-coded for easy field verification

N.T.S.

NOTES
1. Isolators have a min. operating Kx/Ky ratio of 1.0
2. Springs have 50% additional travel to solid beyond rated load.
3. Isolators should be selected in the range of -30% to +25% of rated load.
4. Consult spring chart for isolator performance data.

Notes / Remarks : Project : Title : OSM-1A Drawing no.