D R A COMPANY Doc. No. JGC Doc. No. Prev. Rev. This Rev.
IN P - 2
04-SEBUILT
0 15
B-D-B00-1380-008 D-B00-1380-008 2 50
AS 1
1 2 3 4 5 6 7 8
A A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
B B
GROUNDING WORK
B-D-B00-1380-004 TYPICAL INSTALLATION DETAILS - SUBSTATION WORK
REFERENCE DRAWINGS
REVISIONS
PROJECT TITLE:
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
A
SHEET A
DESCRIPTION REMARKS
NO.
1 COVER SHEET
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
2 INDEX
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
5 TYPICAL INSTALLATION DETAILS GROUNDING WORK - ELECTRICAL SUBSTATION
10 TYPICAL INSTALLATION DETAILS GROUNDING WORK - L/V MOTOR (HORIZONTAL) FOR PAVED AND UNPAVED
17 TYPICAL INSTALLATION DETAILS GROUNDING WORK - A.F.C. CONTROL STATIONS (GROUND LEVEL)
21 TYPICAL INSTALLATION DETAILS GROUNDING WORK - WIRE FIXING ON PERFORATED CABLE TRAY
26 TYPICAL INSTALLATION DETAILS GROUNDING WORK - LADDER AND STAIRWAY 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
30 TYPICAL INSTALLATION DETAILS GROUNDING WORK - GROUNDING BAR RasGas Company Limited
E E
32 TYPICAL INSTALLATION DETAILS GROUNDING WORK - BRANCH WIRE CONNECTION ("C" TYPE CONNECTOR) CONTRACTOR:
33 TYPICAL INSTALLATION DETAILS GROUNDING WORK - BRANCH WIRE CONNECTION (THERMIT WELD TYPE)
34 TYPICAL INSTALLATION DETAILS GROUNDING WORK - PIPE SUPPORT FOR GROUNDING WIRE
TITLE:
35 TYPICAL INSTALLATION DETAILS GROUNDING WORK - STUB-UP PIPE TYPICAL INSTALLATION DETAILS
36 TYPICAL INSTALLATION DETAILS GROUNDING WORK - INSTRUMENT GROUNDING FOR BSIH BUILDING GROUNDING WORK
37 TYPICAL INSTALLATION DETAILS GROUNDING WORK - INSTRUMENT GROUNDING BAR FOR BSIH INDEX (2/39)
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
NOTE:
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
2 2
UP TO 35mm 25mm
2
50 UP TO 70mm 35mm 2 L.V. SWGR 95mm 2
2 2
95mm & OVER & M/V MOTOR 70mm
W/SPACE HEATER 70mm 2 BUSDUCT 95mm 2
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
LOCAL CONTROL 2
16mm M.V. MCC 70mm 2
STATION
2
LOCAL PANEL 35mm L.V. MCC 70mm 2
B B
2
PACKAGE UNIT 35mm L.V. D/P 35mm 2
2
WELDING OUTLET 35mm TERMINAL BOARD 16mm 2
2 2
PUMP SKID 35mm NEUTRAL 95mm
TANK 70mm 2
OUTGOING 70mm 2
TANK MISCELLANEOUS
70mm 2
35mm 2
(FOR LIGHTNING) PANEL
RECTIFIER FOR 2
35mm LADDER AND STAIRS 35mm 2
CATHODIC PROT.
2
GROUNDING REEL 35mm TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
LEGEND:
- GROUNDING ELECTRODE
WITH INSPECTION PIT.
A - GROUNDING COPPER BAR A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
- GROUNDING CABLE RISER
2
- GROUNDING WIRE 95mm
2
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
- GROUNDING WIRE 70mm
2
- GROUNDING WIRE 35mm
NOTES:
B B
TRANSFORMER YARD
1. FOR SIZE OF GROUNDING WIRE, REFER
SHEET NO. 3.
ELECTRICAL
2. PIPE SUPPORT COLUMNS IN PROCESS AREA
SUBSTATION
SHALL BE GROUNDED DIRECTLY AT INTERVALS
REFER TO SHEET NO.5
NOT EXCEEDING 23 M (75 FT.)
D D
STACK
BARZAN ONSHORE PROJECT
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO.
LEGEND:
1 GROUNDING COPPER BAR, COPPER WITH TIN COATED SUB-CON
- GROUNDING ELECTRODE
MAIN GROUNDING LOOP, PVC INSULATED COPPER WIRE, WITH INSPECTION PIT.
2 2 SUB-CON
95 mm
A - GROUNDING ELECTRODE FOR A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 FLEXIBLE BRAID BONDS BUILDING - GROUNDING COPPER BAR
- GROUNDING WIRE CONNECTION
GROUNDING ROD, 254 SMO (6% MO), STAINLESS STEEL
5 SUB-CON - THERMIT WELD FOR UNDERGROUND
LENGTH: 3600mm
- C. TYPE CONNECTOR FOR ABOVEGROUND
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
NOTES:
B B
C
4. FOR GROUNDING COPPER BAR, REFER TO C
SHEET NO. 29.
NOTE2 1
D D
GROUNDING BAR SWITCHGEAR ROOM GROUNDING BAR
DN
DN
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
CONTRACTOR:
TO MAIN PLANT
2
GROUNDING TITLE:
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO.
NOTES:
GROUNDING ROD, 254 SMO (6% MO), STAINLESS STEEL
1 SUB-CON
LENGTH: 3600mm
1. NON-ELECTRICAL EQUIPMENT THAT ARE
2 RIGID PVC CONDUIT SUB-CON DIRECTLY BOLTED TO A GROUNDED
A A
METALLIC STRUCTURE DO NOT REQUIRE
3 SUB-CON ADDITIONAL GROUNDING.
THERMIT CONNECTOR, PVC TAPED
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
SUB-CON 2. EQUIPMENT LOCATED REMOTELY FROM
4 GROUNDING WIRE, PVC INSULATED COPPER WIRE
THE MAIN GROUNDING LOOP MAY BE
MAIN GROUNDING LOOP, PVC INSULATED COPPER WIRE, GROUNDED BY MEANS OF INDIVIDUAL
5 2 SUB-CON
70 mm CONDUCTOR AND GROUNDING ELECTRODE.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 STEEL ANGLE (L-50x50x5t), HOT DIP GALVANIZED SUB-CON
3. FOR SIZE OF GROUNDING WIRE, REFER TO
SHEET NO. 3.
7 PERFORATED CABLE TRAY W/ COVER, HOT DIP GALVANIZED SUB-CON
HIGHEST TOWER IN
PROCESS AREA
C C
HEAT EXCHANGER
(SEE NOTE 1)
VESSEL ON
STRUCTURE
(SEE NOTE 1)
D D
VESSEL OR TOWER HEAT EXCHANGER
M
2
2 2 (SEE NOTE 4)
8 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
2 DATE DRN DSGND CHKD APVD APVD
PROJECT TITLE:
EL
MIN.
450
(SEE NOTE 2)
4 4 6 OR 7
4
RasGas Company Limited
E (SEE NOTE 3) (SEE NOTE 3) E
1 1 CONTRACTOR:
5 3
2
MAIN GROUNDING LOOP (70 mm )
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
610 NO. NOTES:
INSPECTION PIT
"A" 400 "A"
1 750MM LENGTH OF 300MM DIAMETER PVC PIPE SUB-CON
1. THE RESISTANCE TO GROUND OF THE TOTAL
300 SCHEDULE 40.
CONCRETE SYSTEM LOOP WITH ALL GROUNDING RODS
A
WELD ENCASEMENT GROUNDING ROD, 254 SMO (6% MO), STAINLESS STEEL CONNECTED AND EQUIPMENT GROUNDING A
2 SUB-CON
5 SIZE: 20MM DIA x 3600MM LONG DISCONNECTED SHALL BE LESS THAN 1 (ONE)
GROUNDING CLAMP, SINGLE CONDUCTOR TYPE, OHM.
FINISHED 3 SUB-CON
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
30
COPPER
GRADE
GROUNDING CLAMP, THREE CONDUCTOR TYPE,
70
HANDLE 4 SUB-CON
COPPER
300
APPROX.
STOPPER
INSPECTION PIT COVER (STEEL PLATE 6t)
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
5 WITH STOPPER (L-50x50x5x50L), SUB-CON
HOT DIP GALVANIZED AND HANDLE
750
5
STOPPER
DETAIL "A"
REQUIRED
B B
PVC PIPE
PIT IDENTIFICATION
SAND SHALL BE PAINTED
BY STENCIL
AS
1
CONCRETE PIT1
ENCASEMENT
HANDLE
1
C C
2
GROUNDING WIRE
300
400 400
300
610
D
WELD D
5
SECTION "A" - "A"
FINISHED GRADE
SOLDERING
HANDLE (IF REQUIRED)
2 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
STOPPER
DATE DRN DSGND CHKD APVD APVD
4 PROJECT TITLE:
750
2
DETAIL "A" RasGas Company Limited
REQUIRED
E PVC PIPE E
GROUNDING WIRE
2
SAND GROUNDING WIRE
CONTRACTOR:
2
AS
3
1 2
TITLE:
SOLDERING TYPICAL INSTALLATION DETAILS
(IF REQUIRED)
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 SUB-CON 4. FOR SIZE OF GROUNDING WIRE, REFER TO
WITH 1-SPRING, 2-FLAT WASHER, SIZE = M10 x 35L
SHEET NO. 3.
TRANSFORMER
B B
SECONDARY
TERMINATION BOX
C 3 C
NEUTRAL GROUND
PRIMARY TERMINATION BOX
TERMINATION BOX
OUTDOOR INDOOR
1 2
D
5 D
3
AUX. TERMINATION BOX
300
4 4 (NOTE 1) 3 6
PROJECT TITLE:
CONTRACTOR:
SECONDARY CABLE
PRIMARY CABLE
CONTROL CABLE NEUTRAL GROUNDING WIRE (NOTE 4)
TITLE:
(NOTE 4)
CONNECT TO ELECTRODE TYPICAL INSTALLATION DETAILS
GROUNDING WORK
TRANSFORMER (8/39)
GROUNDING WIRE
F GROUNDING WIRE SCALE : NONE CONTRACTOR JOB NO. : 0-5858-2 DOC. CLASS : 2 F
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON 3. FOR POWER WORK DETAILS, REFER TO
DWG. NO. B-D-B00-1380-005.
2
5 BONDING WIRE, 95 mm GROUNDING WIRE SUB-CON
4. FOR SIZE OF GROUNDING WIRE, REFER TO
GROUNDING COPPER BAR, 500x50x6t SHEET NO. 3.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 SUB-CON
COPPER WITH TIN COATED
BOLT AND NUT, WITH 1-SPRING, 2-FLAT WASHERS 5. BUS DUCT SUPPORT SHALL BE CONNECTED TO
7 SUB-CON PLANT GROUND GRID EITHER DIRECTELY OR
SIZE:M10x35L, HOT DIP GALVANIZED
BONDED THROUGH BUS DUCT AS PER
B SPECIFICATION. B
OUTDOOR INDOOR
SUBSTATION
BUS DUCT
SECONDARY
BUS DUCT BOX 2 3
C C
PRIMARY
TERMINAL BOX (NOTE 5)
5
ELEVATED FLOOR
NEUTRAL
D
GROUND D
TERMINAL BOX
1 2
AUX.
TERMINAL 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
(NOTE 1) 6
2 3 RasGas Company Limited
E 2 3 E
COVER
SAND
TITLE:
TYPICAL INSTALLATION DETAILS
DR01A
PROJECT COMPANY DRAWING NO. REVISION
TRENCH CONTROL (SEE CABLE SCHEDULE)
IN CABLE B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
CONTROL STATION
1 CRIMP TYPE TERMINAL LUG FOR MOTOR SUB-CON
1. FOR INSTALLATION DETAILS OF STUB-UP
PIPE AND BRANCH CONNECTOR, REFER TO
2 BOLT WITH 1-SPRING, 1-FLAT WASHER BY VENDOR
A SHEET NOS. 33 35. A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS
4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED
3. GRID CONDUCTORS & GROUNDING ELECTRODE
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON CONDUCTORS SHALL BE INSTALLED DIRECTLY
IN THE EARTH WITHOUT BREAKS AT A MIN.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON DEPTH OF 450MM BELOW GRADE WHEN
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
POWER CABLE PROTECTIVE COVERING, SUCH AS CONCRETE
3 4
B
SLAB, IS PROVIDED. B
1 2
FINISHED GRADE 4. FOR SIZE OF GROUNDING WIRE, REFER TO
2 SHEET NO. 3.
16 mm
5
5
MAIN GROUNDING LOOP
(NOTE 4) 3 4
1 2
(NOTE 1)
C C
5
(NOTE 3)
CONTROL STATION 5
MAIN GROUNDING
(NOTE 4) LOOP
(NOTE 4)
D 6 D
SIDE VIEW (UNPAVED AREA) (NOTE 1)
PROJECT TITLE:
5 (NOTE 1)
CONTRACTOR:
CABLE D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
(NOTE 1) B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
1 CRIMP TYPE TERMINAL LUG FOR MOTOR SUB-CON
1. FOR INSTALLATION DETAILS OF STUB-UP
PIPE AND BRANCH CONNECTOR, REFER TO
2 BOLT WITH 1-SPRING, 1-FLAT WASHER BY VENDOR
A
SHEET NOS. 33 35. A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED 3. GRID CONDUCTORS & GROUNDING ELECTRODE
CONDUCTORS SHALL BE INSTALLED DIRECTLY
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON
IN THE EARTH WITHOUT BREAKS AT A MIN.
DEPTH OF 450MM BELOW GRADE WHEN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
H/V MOTOR
C CONTROL STATION CONTROL STATION C
CONTROL CABLE
POWER CABLE
3 4
D D
3 4 (NOTE 1)
1 2 1 2
PROJECT TITLE:
5 5
5 5 BARZAN ONSHORE PROJECT
GROUNDING WIRE
(NOTE 3) (NOTE 3)
(NOTE 4) (NOTE 4)
CONTRACTOR:
6 (NOTE 1)
6 (NOTE 1)
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS
4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED
3. GRID CONDUCTORS & GROUNDING ELECTRODE
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON CONDUCTORS SHALL BE INSTALLED DIRECTLY
IN THE EARTH WITHOUT BREAKS AT A MIN.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON DEPTH OF 450MM BELOW GRADE WHEN
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
MOTOR MOTOR
CONTROL
C C
STATION
1 2 CONTROL STATION
POWER CABLE
2
16 mm
1 2
CONTROL CABLE
D D
3 4
PROJECT TITLE:
FINISHED
GRADE FINISHED GRADE
BARZAN ONSHORE PROJECT
5
5
TITLE:
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS
4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED 3. FOR GROUNDING OF CABLE TRAY, REFER TO
SHEET NOS. 20 & 21.
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON
4. FOR GROUNDING OF LADDER, REFER TO
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON SHEET NO. 26.
C C
1 2 PERFORATED TRAY
W/ COVER
(NOTE 3)
(NOTE 4)
POWER CABLE
CONTROL STATION
D TANK D
2
16 mm
PROJECT TITLE:
3 4
BARZAN ONSHORE PROJECT
3 4 (NOTE 1)
RasGas Company Limited
E E
FINISHED
CONTRACTOR:
GRADE
(NOTE 5)
5
TITLE:
5 5 TYPICAL INSTALLATION DETAILS
(NOTE 6) MAIN GROUNDING WIRE
GROUNDING WORK
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY NOTES:
NO.
1 CRIMP TYPE TERMINAL LUG FOR MOTOR SUB-CON 1. FOR INSTALLATION DETAILS OF STUB-UP PIPE,
REFER TO SHEET NO. 33 35.
2 BOLT WITH 1-SPRING, 1-FLAT WASHER BY VENDOR
A 2. FOR POWER WORK DETAILS, REFER TO A
1 2 CRIMP TYPE TERMINAL LUG FOR CONTROL STATION,
3 2 SUB-CON DWG. NO. B-D-B00-1380-005.
16 mm
BOLT AND NUT WITH 1-SPRING,2-FLAT WASHERS FOR 3. GRID CONDUCTORS & GROUNDING ELECTRODE
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 SUB-CON
POWER CABLE CONTROL STATION, SIZE:M8x35L, HOT DIP GALVANIZED CONDUCTORS SHALL BE INSTALLED DIRECTLY
IN THE EARTH WITHOUT BREAKS AT A MIN.
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON
DEPTH OF 450MM BELOW GRADE WHEN
UNPROTECTED. THE MIN. BURIAL DEPTH
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
UNISTRUT CHANNEL ( -40x40x10x2.5t),
7 SUB-CON SLAB, IS PROVIDED.
HOT DIP GALVANIZED
5 8
8 UNISTRUT CLAMP, HOT DIP GALVANIZED SUB-CON 4. FOR SIZE OF GROUNDING WIRE, REFER TO
B B
SHEET NO. 3.
(NOTE 1)
9 MASONRY ANCHOR WITHOUT STUD (M6), ZINC PLATED SUB-CON
3 4
BOLT WITH 1-SPRING, 1-FLAT WASHER FOR MASONRY
10 SUB-CON
7 ANCHOR, SIZE : M6 x 20L, HOT DIP GALVANIZED
9 10
(NOTE 3)
5
C C
(NOTE 3)
(NOTE 1)
D 1 2 D
CONTROL STATION
2
16 mm
RasGas Company Limited
E E
CONTRACTOR:
3 4
FINISHED GRADE
TITLE:
TYPICAL INSTALLATION DETAILS
5
GROUNDING WORK
5 (NOTE 3)
PIT PUMP MOTOR (14/39)
GROUNDING
F SCALE : NONE CONTRACTOR JOB NO. : 0-5858-2 DOC. CLASS : 2 F
WIRE
PCWBS CONTRACTOR DRAWING NO. SIZE
(NOTE 4) D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
6 (NOTE 1) 6
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
1 CRIMP TYPE TERMINAL LUG FOR MOTOR SUB-CON 1. FOR INSTALLATION DETAILS OF BRANCH
CONTROL STATION CONNECTOR, REFER TO SHEET NO. 32.
(IF REQUIRED) 2 BOLT WITH 1-SPRING, 1-FLAT WASHER VENDOR
2
A 16 mm 2. FOR POWER WORK DETAILS, REFER TO A
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 3. FOR GROUNDING OF CABLE TRAY, REFER TO
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
MOV 4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED SHEET NOS. 20 & 21.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
3 4
B B
1 2
PLATFORM WALKWAY
POWER CABLE
5
VALVE &
PIPELINE
CONTROL STATION
D CONTROL CABLE D
PROJECT TITLE:
1 2
BARZAN ONSHORE PROJECT
(NOTE 4) 3 4
CONTRACTOR:
PLATFORM WALKWAY
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
PIPELINE (NOTE 3)
PCWBS CONTRACTOR DRAWING NO. SIZE
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
1 CRIMP TYPE TERMINAL LUG FOR MOTOR SUB-CON 1. FOR INSTALLATION DETAILS OF BRANCH
CONNECTOR, REFER TO SHEET NO. 32.
2 BOLT WITH 1-SPRING, 1-FLAT WASHER VENDOR
A 2. FOR POWER WORK DETAILS, REFER TO A
2
3 CRIMP TYPE TERMINAL LUG FOR CONTROL STATION,16 mm SUB-CON DWG. NO. B-D-B00-1380-005.
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 3. FOR BONDING WIRE OF CABLE TRAY,
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 SUB-CON
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED REFER TO SHEET NO.20 & 21.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
B B
CONTROL STATION
C C
POWER CABLE
A.F.C MOTOR
CONTROL CABLE
1 2
D D
PLATFORM
PROJECT TITLE:
3 4
BARZAN ONSHORE PROJECT
PERFORATED
5 (NOTE 4) CONTRACTOR:
TRAY WITH COVER
(NOTE 1)
DETAIL "A"
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 1. FOR INSTALLATION DETAILS OF STUB-UP
2 SUB-CON PIPE & BRANCH CONNECTOR, REFER TO
FOR CONTROL STATION, SIZE : M8x35L, HOT DIP GALVANIZED
A A
SHEET NOS. 33 35.
3 BRANCH CONNECTOR, THERMIT WELD SUB-CON
2. FOR POWER WORK DETAILS, REFER TO
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
DWG. NO. B-D-B00-1380-005.
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON 3. FOR SIZE OF GROUNDING WIRE, REFER TO
SHEET NO. 3.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
NAME PLATE
B B
400
STEEL CHANNEL
SUPPORT (L-100x50x5t)
C C
JUNCTION BOX
ARMORED CABLE
1200
1 2 (NOTE 1)
MORTAR (BY ELECT) "a" "a"
MIN.
50
5
GL.
D D
MIN.
300
UNISTRUT CLAMP
AND CHANNEL
2
4 mm 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
GROUNDING MAIN GRID
DATE DRN DSGND CHKD APVD APVD
JUNCTION BOX
1 2 CONTRACTOR:
BY CIVIL
UNISTRUT CLAMP AND CHANNEL
MIN.
CABLE TRENCH
50
TITLE:
GL. TYPICAL INSTALLATION DETAILS
GROUNDING WORK
GROUNDING CABLE
(NOTE 2) AFC CONTROL STATIONS (GROUND LEVEL)(17/39)
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
3 RIGID PVC CONDUIT, 1-1/4 " SUB-CON 2. FOR POWER WORK DETAILS, REFER TO
DWG. NO. B-D-B00-1380-005.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 BRANCH CONNECTOR, THERMIT WELD SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 CABLE GLAND FOR GROUNDING WIRE, M20S JGC
B B
C C
POWER OUTLET
D D
5
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
JUNCTION BOX
CONTRACTOR:
FINISHED GRADE
3 3 TITLE:
TYPICAL INSTALLATION DETAILS
(NOTE 1) (NOTE 1)
GROUNDING WORK
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
2
4 GROUNDING WIRE FOR CABLE TRAY, 4 mm SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
B B
TERMINAL BLOCKS
2
1
GROUNDING LUG CABLE ARMOR
FUSE
R
STREET
CLAMP JUBILEE
5 LTG POLE
OR HOSE CLAMP BY VENDOR OUTLINE
4 LIGHTING CABLES
R S T N G
D
3 5 D
GROUT
TO LTG POLE
FINISHED GROUNDING LUG
GRADE FOUNDATION
BY CIVIL
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 MAIN GROUNDING LOOP WIRE, 70 mm SUB-CON
CABLE TRAY 2
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 BRANCH CONNECTOR, "C" TYPE CONNECTOR SUB-CON
DETAIL "A"
C TO MAIN C
GROUNDING GRID
CABLE TRAY
W/ COVER
2 3
GROUNDING WIRE
5
1
D D
SEE DETAIL "B"
CABLE TRAY
BARZAN ONSHORE PROJECT
1 W/ COVER 5
CONTRACTOR:
4 TO MAIN 6
GROUNDING GRID
(NOTE 1)
7
TITLE:
TYPICAL INSTALLATION DETAILS
TRAY RUNG
GROUNDING WORKS
D-B00-1380-008 A3
DETAIL "B"
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY NOTES:
NO.
1 CABLE FIXING TIE, NYLON, UV RESISTANT, COLOR BLACK SUB-CON 1. WIRES SHALL BE SECURELY FIXED TO THE
PERFORATED TRAY THE INTERVALS SHALL NOT
2 BRANCH CONNECTOR, "C’ TYPE CONNECTOR SUB-CON EXCEED 1-TRAY LENGTH ON HORIZONTAL RUNS
A A
AND 1 METER ON VERTICAL RUNS.
2
3 BONDING WIRE, 4 mm SUB-CON
2. FOR POWER WORK DETAILS, REFER TO
ROUND HEAD BOLT AND NUT WITH 1-SPRING, 2-FLAT
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
DWG. NO. B-D-B00-1380-005.
4 SUB-CON
WASHERS, SIZE : M8x25L, HOT DIP GALVANIZED
3. FOR CABLE TRAY GROUNDING DETAILS, REFER
TO GROUNDING PHILOSOPHY DIAGRAM;
B-D-B00-1384-001.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
4. FOR INSTALLATION DETAILS OF BRANCH
CONNECTOR, REFER TO SHEET NO. 32.
B B
C C
4
D D
1 2 (NOTE 4) CONTRACTOR:
PERFORATED TRAY W/COVER (IF REQUIRED)
4
GROUNDING
WIRE 3 TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY NOTES:
NO.
GROUNDING PIECE, HOT DIP GALVANIZED STEEL,
1 VENDOR 1. FOR INSTALLATION DETAILS OF GROUNDING
(120x38x12t)
LUG, STUB-UP PIPE AND BRANCH CONNECTOR,
2
2 CRIMP TYPE TERMINAL LUG, 35 mm SUB-CON REFER TO SHEET NOS. 31, 33 AND 35.
A A
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 2. FOR SIZE OF GROUNDING WIRE, REFER TO
3 SUB-CON
FOR GROUNDING LUG, SIZE:M10x35L, HOT DIP GALVANIZED SHEET 3.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON
3. GRID CONDUCTORS & GROUNDING ELECTRODE
CONDUCTORS SHALL BE INSTALLED DIRECTLY
5 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON IN THE EARTH WITHOUT BREAKS AT A MIN.
DEPTH OF 450MM BELOW GRADE WHEN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
C C
HEAT EXCHANGER
SEAL WELD
(BY VENDOR)
1 (NOTE 1)
D D
2 3
CONTRACTOR:
GROUNDING WORK
5 (NOTE 1)
HEAT EXCHANGER (22/39)
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
GROUNDING PIECE, HOT DIP GALVANIZED STEEL,
1 VENDOR 1. FOR INSTALLATION DETAILS OF GROUNDING
(120x38x12t)
LUG, STUB-UP PIPE AND BRANCH CONNECTOR,
2
2 CRIMP TYPE TERMINAL LUG, 35 mm SUB-CON REFER TO SHEET NOS. 31, 33 AND 35.
A A
SEAL WELD
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 2. FOR SIZE OF GROUNDING WIRE, REFER TO
(BY VENDOR) 3 SUB-CON
FOR GROUNDING LUG, SIZE:M10x35L, HOT DIP GALVANIZED SHEET 3.
1
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON
3. GRID CONDUCTORS & GROUNDING ELECTRODE
CONDUCTORS SHALL BE INSTALLED DIRECTLY
5 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON
2 3 IN THE EARTH WITHOUT BREAKS AT A MIN.
DEPTH OF 450MM BELOW GRADE WHEN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
C
DETAIL "A" C
HORIZONTAL DRUM
VERTICAL DRUM
D (NOTE 1) D
PROJECT TITLE:
PLATFORM
SEE DETAIL "A" BARZAN ONSHORE PROJECT
(NOTE 1)
CONTRACTOR:
GROUNDING WORK
D-B00-1380-008 A3
(NOTE 1) 5 5
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
GROUNDING PIECE, HOT DIP GALVANIZED STEEL,
1 VENDOR 1. FOR INSTALLATION DETAILS OF GROUNDING
(120x38x12t)
LUG, STUB-UP PIPE AND BRANCH CONNECTOR,
2
2 CRIMP TYPE TERMINAL LUG, 70 mm SUB-CON REFER TO SHEET NOS. 31, 33 AND 35.
A A
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS 2. FOR SIZE OF GROUNDING WIRE, REFER TO
3 SUB-CON
FOR GROUNDING LUG, SIZE:M10x35L, HOT DIP GALVANIZED SHEET 3.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON 3. GRID CONDUCTORS & GROUNDING ELECTRODE
CONDUCTORS SHALL BE INSTALLED DIRECTLY
TOWER
5 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON IN THE EARTH WITHOUT BREAKS AT A MIN.
DEPTH OF 450MM BELOW GRADE WHEN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
C C
FINISHED
GRADE
GROUNDING WIRE
(NOTE 3)
(NOTE 2) (NOTE 2)
D D
(NOTE 1) 5
2 3
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
4
GROUNDING WORK
TOWER (24/39)
D-B00-1380-008 A3
DETAIL "A"
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO.
NOTES:
1 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON
1. IF TANK DIAMETER IS LESS THAN 30,000
MAIN GROUNDING LOOP
mm, STATIC GROUNDING TERMINATION
A A
SHALL BE TWO POINTS, ( 0 AND 180 ).
6 (NOTE 4) 3 CRIMP TYPE TERMINAL LUG SUB-CON
2. FOR SIZE OF GROUNDING CABLE FOR
BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 SUB-CON ELECTRICAL EQUIPMENT, REFER TO
SIZE : M10x35L, HOT DIP GALVANIZED
SHEET NO.3.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
0,0 ) 6 BRANCH GROUNDING WIRE SUB-CON
3 1 SHEET NOS. 32 & 35.
. OTE
0 A N 180
DI E 4. FOR SIZE OF GROUNDING WIRE, REFER TO
E
(S SHEET 3.
B B
C C
TANK
(NOTE 3)
GL
MIN. DEPTH
6 (NOTE 4)
(NOTE 5)
TANK 6 TANK
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
5
BARZAN ONSHORE PROJECT
4 (NOTE 3)
MIN.
E E
300
CONTRACTOR:
6
GROUNDING PIECE
(SEE SHEET NO. 31) 3 (NOTE 4)
TITLE:
TO MAIN GROUNDING
TYPICAL INSTALLATION DETAILS
(NOTE 3) 1 LOOP
6 GROUNDING WORK
DETAIL "B" DETAIL "A" TANKAGE (25/39)
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
LADDER NO. NOTES:
GROUNDING PIECE, HOT DIP GALVANIZED STEEL,
1 SUB-CON
(120x38x12t) 1. FOR INSTALLATION DETAILS OF GROUNDING
2
LUG, STUB-UP PIPE AND BRANCH CONNECTOR,
2 CRIMP TYPE TERMINAL LUG, 35 mm SUB-CON REFER TO SHEET NOS. 31, 33 AND 35.
A A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON
3. GRID CONDUCTORS & GROUNDING ELECTRODE
5 BRANCH CONNECTOR, THERMIT WELD TYPE SUB-CON CONDUCTORS SHALL BE INSTALLED DIRECTLY
IN THE EARTH WITHOUT BREAKS AT A MIN.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
DEPTH OF 450MM BELOW GRADE WHEN
UNPROTECTED. THE MIN. BURIAL DEPTH
MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
SEAL
WELD
1 (NOTE 1)
2 3
C FINISHED GRADE C
(NOTE 1) 5 4 (NOTE 1)
GROUNDING WIRE (NOTE 3)
(NOTE 2)
D STAIRWAY D
PROJECT TITLE:
CONTRACTOR:
2 3
TITLE:
TYPICAL INSTALLATION DETAILS
FINISHED GRADE
GROUNDING WORK
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NO. NOTES:
GROUNDING PIECE, NON FIRE PROOFING,
1 SUB-CON 1. FOR INSTALLATION DETAILS OF GROUNDING
HOT DIP GALVANIZED STEEL, (70 x 38 x 12t)
LUG, STUB-UP PIPE AND BRANCH CONNECTOR,
GROUNDING PIECE, FOR FIRE PROOFING,
2 SUB-CON REFER TO SHEET NOS. 31, 33 AND 35.
A HOT DIP GALVANIZED STEEL, (120 x 38 x 12t) A
2
SUB-CON 2. FOR SIZE OF GROUNDING WIRE, REFER TO
3 CRIMP TYPE TERMINAL LUG, 35 mm
STEEL SEAL SHEET 3.
COLUMN 1 (NOTE 1) BOLT AND NUT WITH 1-SPRING, 2-FLAT WASHERS
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
WELD
4 SUB-CON
FOR GROUNDING LUG, SIZE:M10x35L, HOT DIP GALVANIZED 3. GRID CONDUCTORS & GROUNDING ELECTRODE
CONDUCTORS SHALL BE INSTALLED DIRECTLY
5 RIGID PVC CONDUIT, 1-1/4" SUB-CON IN THE EARTH WITHOUT BREAKS AT A MIN.
DEPTH OF 450MM BELOW GRADE WHEN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
3 4 6 SUB-CON
BRANCH CONNECTOR, THERMIT WELD TYPE UNPROTECTED. THE MIN. BURIAL DEPTH
150 MAYBE REDUCED TO 300MM. WHEN A
PROTECTIVE COVERING, SUCH AS CONCRETE
SLAB, IS PROVIDED.
B B
5 (NOTE 1)
FINISHED GRADE
(NOTE 3)
GROUNDING WIRE
C (NOTE 2) C
FIRE PROOFING
D
STEEL D
COLUMN SEAL
2 (NOTE 1)
WELD
PROJECT TITLE:
150
CONTRACTOR:
FINISHED GRADE
TITLE:
TYPICAL INSTALLATION DETAILS
(NOTE 3)
GROUNDING WIRE GROUNDING WORK
(NOTE 2) STEEL COLUMN (27/39)
D-B00-1380-008 A3
6
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
BOLT AND NUT WITH 1-SPRING,2-FLAT WASHERS 2. FOR SIZE OF GROUNDING WIRE, REFER TO
3 SUB-CON
FOR GROUNDING LUG,SIZE:M10x35L,HOT DIP GALVANIZED SHEET 3.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 RIGID PVC CONDUIT, 1-1/4" SUB-CON
2
5 FLEXIBLE COPPER BRAID, 35 mm 350L JGC
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 STEEL ANGLE(L-50x50x5t),HOT DIP GALVANIZED SUB-CON
2
B 8 GROUND BONDING WIRE, 35 mm SUB-CON B
GATE
GATE POST
SEAL
7
WELD
C C
5 6
7
SEAL
(NOTE 1) 1 WELD POST
D D
2 3
(NOTE 1) 4 FENCE
FENCE
SEAL
WELD
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
1 2 3 1 2 3 (NOTE 1)
BARZAN ONSHORE PROJECT
8
GROUNDING WIRE FINISHED GRADE RasGas Company Limited
E E
(NOTE 2)
CONTRACTOR:
GROUNDING WIRE
4
(NOTE 2)
GATE
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
FENCE
FENCE AND GATE (28/39)
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. DESCRIPTION AND SPECIFICATION SUPPLY BY NOTES:
NO.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 CRIMP TYPE TERMINAL LUG SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 GROUNDING WIRE SUB-CON
9 2
B 8 RIGID PVC CONDUIT, 1-1/4 " SUB-CON B
1
BOLT WITH 1-SPRING,1- FLAT WASHER FOR MASONRY
9 SUB-CON
ANCHOR, HOT DIP GALVANIZED SIZE: M8 X 20L
3
UNISTRUT CHANNEL, ( -40X40X10X2.5t),
10 SUB-CON
HOT DIP GALVANIZED
5
11 UNISTRUT CLAMP, HOT DIP GALVANIZED SUB-CON
APP.450
STRUCTURE 7 SEAL WELD
1
8
(SEE NOTE 2)
3
5
GL
STRUCTURE
10 11 12 13
D 3 D
4 6
INDIVIDUAL GROUNDING OF
ELECTRIC EQUIPMENT OR
STATIC GROUNDING
FOUNDATION
~ 6
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
APP.450
DATE DRN DSGND CHKD APVD APVD
7
PROJECT TITLE:
CONTRACTOR:
10 11 12 13
INDIVIDUAL GROUNDING OF
500
ELECTRIC EQUIPMENT OR TITLE:
GROUNDING WORK
50
DR01A
PROJECT COMPANY DRAWING NO. REVISION
(SEE NOTE 1)
FOR STEEL STRUCTURE
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
5 STEEL CHANNEL, 100x50x5t, HOT DIP GALVANIZED SUB-CON
STEEL STRUCTURE
1
(NOTE 1) (NOTE 1)
6 MASONRY ANCHOR, M8, ZINC PLATED SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
BOLT WITH 1-FLAT & 1-SPRING WASHER FOR MASONRY ANCHOR,
7 SUB-CON
HOT DIP GALVANIZED, M8 x 20L
SEAL WELD 4
B B
1
2
SECTION VIEW WITHOUT INSULATOR
STEEL STRUCTURE
CONCRETE STRUCTURE 6 7
(NOTE 1) (NOTE 1)
(NOTE 1)
SEAL WELD 4
C C
2 1
1 SECTION VIEW WITHOUT INSULATOR
D
(ONLY FOR IE AND ISE EARTHING) D
CONCRETE STRUCTURE 2 6
MOUNTING PLATE
(NOTE 1)
4
2
2
SECTION VIEW WITH INSULATOR CONTRACTOR:
1
(ONLY FOR IE AND ISE EARTHING)
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
300
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
NOTES:
A A
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
INSULATION OR FIRE
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
70 PROOF THICKNESS
B B
30
C
9 C
19
38
D D
11 HOLE
PROJECT TITLE:
CONTRACTOR:
GROUNDING PIECE
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
B MIN. MIN. B
2
25 25
MIN.
25
1
C C
SEE DETAIL
GROUNDING WIRE
D D
1
24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
CONTRACTOR:
DETAIL OF CONNECTOR
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
BRANCH WIRE CONNECTION
("C" TYPE CONNECTOR) (32/39)
SCALE : NONE CONTRACTOR JOB NO. : 0-5858-2 DOC. CLASS : 2
F ABOVE GROUND F
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
1 THERMIT WELD TYPE CONNECTOR SUB-CON 1. THERMO WELDING TOOL AND MATERIALS
SHALL BE SUITABLE FOR CONDUCTOR SIZES
2 PVC INSULATION TAPE (GREEN COLOR) SUB-CON AND TYPE OF JOINT.
A A
MIN. MIN.
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
25 2 25
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
B MAIN GROUNDING WIRE B
1
MIN.
25
GROUNDING WIRE
C C
1
BARED CONDUCTOR
PVC SHEATH
D D
PROJECT TITLE:
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
BRANCH WIRE CONNECTION
(THERMIT WELD TYPE) (33/39)
UNDERGROUND
F SCALE : NONE CONTRACTOR JOB NO. : 0-5858-2 DOC. CLASS : 2 F
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 UNISTRUT CLAMP, HOT DIP GALVANIZED SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
1 PROTECTION PIPE
B B
3 UNISTRUT CLAMP
30
C C
SECTION "A"-"A"
40
20
10
UNISTRUT CHANNEL
D D
CONCRETE FOUNDATION
OR FIRE PROOF COLUMN STEEL STRUCTURE STEEL STRUCTURE
CONTRACTOR:
3 TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
SEAL WELD SEAL WELD PIPE SUPPORT FOR GROUNDING WIRE (34/39)
F
3 SCALE : NONE CONTRACTOR JOB NO. : 0-5858-2 DOC. CLASS : 2 F
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
MATERIAL
NO. NO. DESCRIPTION AND SPECIFICATION SUPPLY BY
NOTES:
1 RIGID PVC CONDUIT, 1-1/4" SUB-CON
1. SHALL WHERE REQUIRED, STUB-UP PIPE
2 MASONRY ANCHOR WITHOUT STUD, M6, ZINC PLATED SUB-CON SHALL SUIT THE CONTOUR OF COLUMNS,
A
TYPE "A" FOUNDATION FOOTING, PLINTHS, ETC. FOR A
BOLT WITH 1-SPRING, 1-FLAT WASHER FOR MASONRY SUB-CON NEAT INSTALLATION.
3
ANCHOR,SIZE:M6x20L, HOT DIP GALVANIZED
UNISTRUT CHANNEL ( -40x40x10x2.5t),
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 SUB-CON
HOT DIP GALVANIZED
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 NON-HARDENING SEALING COMPOUND SUB-CON
4 5
B B
FOUNDATION
MIN.150
GROUNDING WIRE
2 3
6
FINISHED GRADE
CLEAN SAND
MIN.200
C
1 C
GROUNDING WIRE
DETAIL "A"
PROJECT TITLE:
CONCRETE 4 5
BARZAN ONSHORE PROJECT
ENCASEMENT
MIN.150
50 50
FINISHED GRADE
SITE
CONTRACTOR:
MIN.350
AT
FINISHED GRADE
TITLE:
TYPICAL INSTALLATION DETAILS
MIN.200
1
50
GROUNDING WORK
1 D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
2 OF GROUNDING BARS.
B3 25 mm PVC-BLUE I.S. EARTH
I/A SYSTEM GROUNDING (Y/G3)
3. FOR GROUNDING BAR:
YELLOW/GREEN - DETAIL DESIGN BY INSTRUMENT
2
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
PLANT GROUNDING WIRE (Y/G3) (25mm ) - MATERIAL SUPPLY BY ELECTRICAL
INSTRUMENT GROUNDING WIRE (G3)
2 (REFER TO SHEET 37)
YELLOW/GREEN GREEN (25mm )
2 - INSTALLATION BY ELECTRICAL
(25mm )
SYSTEM GROUNDING WIRE (Y3)
PLANT GROUNDING WIRE (Y/G3) 4. FOR GROUNDING WIRE:
B B
INST. SYS. PLANT PLANT INST. PLANT. PLANT. 6. INSTRUMENT EARTH BUSBAR:
INTRINSIC SAFE (I.S.) I.S. GROUNDING GROUNDING GROUNDING GROUNDING GROUNDING GROUNDING GROUNDING
GROUNDING WIRE (B3) BUS BAR 1 BUS BAR 1 BUS BAR 1 BUS BAR 1 BUS BAR 2 BUS BAR 2 BUS BAR 3 BUS BAR 4 I.S.E.: INTRINSIC SAFE EARTH
BLUE
(WITH (WITH (WITH (WITHOUT (WITHOUT (WITH (WITHOUT (WITHOUT (WITH INSULATOR & SPECIAL ROD)
2
(25mm ) INSULATOR) INSULATOR) INSULATOR) INSULATOR) INSULATOR) INSULATOR) INSULATOR) INSULATOR)
C I.E. : INSTRUMENT EARTH C
2 2 2
70mm (Y/G4) 70mm (Y/G4) 70mm (Y/G4)
(NOTE 4) (NOTE 4) (NOTE 4)
2
70mm (Y/G4) (NOTE 4) ELECTRICAL
2
YELLOW TAPE 70mm (Y/G4) (NOTE 4) 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
2
70mm
BLUE TAPE
INSIDE OF CONTROL ROOM BARZAN ONSHORE PROJECT
(BY ELECTRICAL)
TITLE:
TYPICAL INSTALLATION DETAILS
LESS THAN 1 LESS THAN 1
GROUNDING WORK
TYPICAL INSTRUMENT GROUNDING ARRANGEMENT FOR PROCESS TRAIN SIH BUILDING D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
4 STEEL ANGLE, 50x50x5tx50L, HOT DIP GALAVANIZED SUB-CON
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
6 MASONRY ANCHOR, M8, ZINC PLATED SUB-CON
B 500 B
25 40 35 30 30 30 30 30 30 30 30 30 30 35 7
15
15
25
25
50
20
20
50
25
15
15
C C
1 50 30 30 30 30 30 30 30 30 30 50 40 25
5
D D
CONTRACTOR:
1 5
3
TITLE:
30
1
UNDER FREE ACCESS FLOOR (ONLY FOR IE AND ISE EARTHING) D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
2
B3 25 mm PVC-BLUE I.S. EARTH ACCOMODATE THE REQUIRED NUMBER
I/A SYSTEM EARTH (Y/G3) OF GROUNDING BARS.
YELLOW/GREEN
3. FOR MORE DETAILS, REFER TO
(BY VENDOR)
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
PLANT EARTH WIRE (Y/G3) BF-D-B00-1370-009
INSTRUMENT EARTH WIRE (G3)
2
YELLOW/GREEN GREEN (25mm )
(BY VENDOR) 4. FOR DETAIL OF EARTHING WITHIN VENDOR
SYSTEM EARTH WIRE (Y3)
SCOPE, REFER TO VENDOR DOCUMENT.
PLANT EARTH WIRE (Y/G3)
B B
2
C 70mm (Y/G4) 70mm
2
C
(Y/G4)
2
70mm
(Y/G4)
I.S. EARTH
GROUNDING BAR (WITH INSULATOR)
(BY VENDOR)
2 2 2
70mm (Y/G4) 70mm (Y/G4) 70mm (Y/G4)
(BY VENDOR) (BY VENDOR) (BY VENDOR)
INSIDE OF ANALYZER HOUSE
2
70mm (Y/G4)
D D
OUTSIDE OF ANALYZER HOUSE
2
YELLOW TAPE 70mm (Y/G4)
(BY ELECTRICAL)
CONTRACTOR:
TITLE:
TYPICAL INSTALLATION DETAILS
GROUNDING WORK
TYPICAL INSTRUMENT GROUNDING ARRANGEMENT FOR PROCESS TRAIN SIH ANALYZER HOUSE INSTRUMENT GROUNDING FOR ANALYZER HOUSE (38/39)
D-B00-1380-008 A3
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B
1 2 3 4 5 6 7 8
ALL RIGHTS RESERVED. THIS DOCUMENT IS THE PROPERTY OF RASGAS COMPANY LIMITED AND CONTAINS INFORMATION WHICH IS PROPRIETARY. THIS INFORMATION TO BE HELD IN
ACCORDING TO SITE CONDITION.
NOTE 1 4 1-SERRATED WASHER SUB-CON
FOR GROUNDING LUG (SIZE=M6 AND HOT DIP GALVANIZED) 2.INTERMEDIATE GROUNDING POINTS SHALL BE
INTRODUCED AT EACH 100 METERS.
CONFIDENCE. NO DISCLOSURE OR OTHER USE OF THIS DOCUMENT IS TO BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF RASGAS COMPANY LIMITED.
SEE DETAIL"A" HAVE AN END EARTHING CONNECTION. B
VALVE
4.CONNECTION OF EARTHING WIRE TO THE PIPE
SUPPORT SHALL USE BOLT/NUT OR TAPPING
SCREW AS PER CIVIL STANDARD.
B
PIPE SUPPORT
2
3
D D
M6 SERRATED WASHER
INSULATION INSULATION
2 3 2 3
PIPE PIPE 24.APR.12 N.FELIX Y.OKA T.KOJIMA K.OGAWA -
PROJECT TITLE:
DETAIL "C"
BARZAN ONSHORE PROJECT
CONTRACTOR:
4
PIPE SUPPORT SEE DETAIL "D" 1
OR STEEL STRUCTURE
3 4
TITLE:
TYPICAL INSTALLATION DETAILS
DETAIL "A" DETAIL "B"
GROUNDING WORK
DR01A
PROJECT COMPANY DRAWING NO. REVISION
IN
B B-D-B00-1380-008 50
5
P-2
04-SE UILT 1 2 3 6 7 8
AS B