Index of Revisions
Signature
Revised
Rev. Date Page Remarks Date Date
Items
Name of Reviser Name of Approver
R-02 20.05.2017
Copy
Quantity Quantity
Contractor Client
Set File Set File
1 1 3 1
Client: POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project: 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Title : Revision
WIND LOAD ON LONGITUDINAL FACE FOR 230kV TOWER MKD."T2"
R-02 Date :- 20.05.2017
Part Main Leg Length Bracing Length Secondary Length Horizontal Length Wind Ward
Bracing Member Face Area
m m m m (metres2)
A B C D E F G H I
Segment Height of Segment Top Wind Ward Wind Load Distribution Moment Load Load
No. from Segments Levels Face Area Fw = qref (H/10)2^α Cshp WA of Wind Load Force x Ht. Left Right
2
Top (metres) (metres) (metres ) (kg) (kg) (kg - metres) (kg) (kg)
H W A Fw
0.00 0.00
L1 1.2800 25.0000 0.33 821.92 410.96 10273.96 206.00 206.00
L1 1.2800 23.7200 0.33 781.66 801.79 19018.41 401.00 401.00
L1 1.2800 22.4400 0.34 768.76 775.21 17395.66 388.00 388.00
L1 1.2800 21.1600 0.35 757.63 763.19 16149.13 382.00 382.00
L1 1.2800 19.8800 0.44 881.69 819.66 16294.80 410.00 410.00
L2 1.2000 18.6000 0.52 984.01 932.85 17351.00 467.00 467.00
L2 1.1000 17.4000 0.48 843.35 913.68 15898.04 457.00 457.00
L2 1.1500 16.3000 0.50 825.11 834.23 13597.96 418.00 418.00
L2 1.1500 15.1500 0.51 777.31 801.21 12138.34 401.00 401.00
L2 1.1500 14.0000 0.51 728.06 752.68 10537.57 377.00 377.00
L3 1.2500 12.8500 0.68 877.72 802.89 10317.11 402.00 402.00
L3 1.3500 11.6000 0.72 847.40 862.56 10005.70 432.00 432.00
L3 1.4500 10.2500 0.77 798.11 822.76 8433.26 412.00 412.00
L3 1.5500 8.8000 0.85 760.01 779.06 6855.74 390.00 390.00
L4 1.6500 7.2500 1.04 760.05 760.03 5510.22 381.00 381.00
L4 1.7500 5.6000 1.10 620.69 690.37 3866.09 346.00 346.00
L4 1.8500 3.8500 1.16 450.09 535.39 2061.25 268.00 268.00
L4 2.0000 2.0000 1.24 251.04 350.57 701.13 176.00 176.00
Level 0 0.0000 0.0000 0.0000 0.00 125.52 0.00 63.00 63.00
Part Main Leg Length Bracing Length Secondary Length Horizontal Length Wind Ward
Bracing Member Face Area
m m m m (metres2)
Type of earth wire 7/4.0mm ACSR Grosbeak (AS PER ELE. INPUT DATA)
1) Length of wire on left side, L1 = 10% of span or Height 25.00 m
=
of Tower
2 ) Length of wire on right side, L2 = 100% of span = 66.00 m
3 ) Earthwire Span (L1 + 0.5 X L2) = 58.00 m
4 ) Diameter of Earth Wire = 12.000 mm
5 ) Weight of Earth Wire = 0.6900 Kg/m
6 ) Total Weight of Earth Wire per Tower = 40.020 Kg
7 ) Earth Wire Tension = 450 Kg
8 ) Wind ward face area (WA) = 0.70 sqm
9 ) Referance Wind Pressure (qref) = 1.210 KN/sqm = 123.34 Kg/sqm
10 ) Height of the Earth Wire from Ground (H) = 25.00 m
11 ) Power law index (α) = 0.095
12 ) Aerodynamic shap factor (Cshp) = 1.20
13 ) Wind Load Fw = qref (H/10)2^α Cshp W A = 274.12 Kgs
Wind Load on Conductor in Longitudinal Direction = 0.00 Kg
Wind Load on Conductor in Transverse Direction = 275.00 Kg
14 ) Angle of Deviation
o
In Plan = 0
o
In Elevation = 0
Vertical Long. Transverse
Load Due to Normal Tension Due to
0.00 450.00 0.00
Deviations in kg
Transverse Loads :-
Wind Load on Earth-Wire in Transverse Dirn. = 275 Kg
Load Due to Normal Tension Due to Deviation = 0 Kg
Say = 275 Kg
Longitudinal Loads :-
Wind Load on Earth-Wire in Longitudinal Dirn. = 0 Kg
Load Due to Normal Tension Due to Deviation = 450 Kg
Say = 450 Kg
Type of earth wire 7/4.0mm ACSR Grosbeak (AS PER ELE. INPUT DATA)
1) Length of wire on left side, L1 = 10% of span or Height 25.00 m
=
of Tower
2 ) Length of wire on right side, L2 = 100% of span = 66.00 m
3 ) Earthwire Span (L1 + 0.5 X L2) = 58.00 m
4 ) Diameter of Earth Wire = 12.000 mm
5 ) Weight of Earth Wire = 0.6900 Kg/m
6 ) Total Weight of Earth Wire per Tower = 40.020 Kg
7 ) Earth Wire Tension = 450 Kg
8 ) Wind ward face area (WA) = 0.70 sqm
9 ) Referance Wind Pressure (qref) = 1.210 KN/sqm = 123.34 Kg/sqm
Client : POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Title : Revision
LOADING FROM EARTH WIRE
R-02 Date :- 20.05.2017
Transverse Loads :-
Wind Load on Earth-Wire in Transverse Dirn. = 194 Kg
Load Due to Normal Tension Due to Deviation = 318 Kg
Say = 512 Kg
Longitudinal Loads :-
Wind Load on Earth-Wire in Longitudinal Dirn. = 194 Kg
Load Due to Normal Tension Due to Deviation = 318 Kg
Say = 512 Kg
Type of earth wire 7/4.0mm ACSR Grosbeak (AS PER ELE. INPUT DATA)
1) Length of wire on left side, L1 = 10% of span or Height 25.00 m
=
of Tower
2 ) Length of wire on right side, L2 = 100% of span = 66.00 m
3 ) Earthwire Span (L1 + 0.5 X L2) = 58.00 m
4 ) Diameter of Earth Wire = 12.000 mm
5 ) Weight of Earth Wire = 0.6900 Kg/m
6 ) Total Weight of Earth Wire per Tower = 40.020 Kg
7 ) Earth Wire Tension = 450 Kg
8 ) Wind ward face area (WA) = 0.70 sqm
9 ) Referance Wind Pressure (qref) = 1.210 KN/sqm = 123.34 Kg/sqm
10 ) Height of the Earth Wire from Ground (H) = 25.00 m
11 ) Power law index (α) = 0.095
12 ) Aerodynamic shap factor (Cshp) = 1.20
13 ) Wind Load Fw = qref (H/10)2^α Cshp W A = 274.12 Kgs
Wind Load on Conductor in Longitudinal Direction = 0.00 Kg
Wind Load on Conductor in Transverse Direction = 275.00 Kg
14 ) Angle of Deviation
o
In Plan = 0
o
In Elevation = 30
Vertical Long. Transverse
Load Due to Normal Tension Due to
-225.00 389.71 0.00
Deviations in kg
Client : POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Title : Revision
LOADING FROM EARTH WIRE
R-02 Date :- 20.05.2017
Transverse Loads :-
Wind Load on Earth-Wire in Transverse Dirn. = 275 Kg
Load Due to Normal Tension Due to Deviation = 0 Kg
Say = 275 Kg
Longitudinal Loads :-
Wind Load on Earth-Wire in Longitudinal Dirn. = 0 Kg
Load Due to Normal Tension Due to Deviation = 390 Kg
Say = 390 Kg
* EARTH WIRE LOADING (WITH 450 DAVIATION IN PLAN & 300 DAVIATION IN ELEVATION ) :-
Type of earth wire 7/4.0mm ACSR Grosbeak (AS PER ELE. INPUT DATA)
1) Length of wire on left side, L1 = 10% of span or Height 25.00 m
=
of Tower
2 ) Length of wire on right side, L2 = 100% of span = 66.00 m
3 ) Earthwire Span (L1 + 0.5 X L2) = 58.00 m
4 ) Diameter of Earth Wire = 12.000 mm
5 ) Weight of Earth Wire = 0.6900 Kg/m
6 ) Total Weight of Earth Wire per Tower = 40.020 Kg
7 ) Earth Wire Tension = 450 Kg
8 ) Wind ward face area (WA) = 0.70 sqm
9 ) Referance Wind Pressure (qref) = 1.210 KN/sqm = 123.34 Kg/sqm
10 ) Height of the Earth Wire from Ground (H) = 25.00 m
11 ) Power law index (α) = 0.095
12 ) Aerodynamic shap factor (Cshp) = 1.20
13 ) Wind Load Fw = qref (H/10)2^α Cshp W A = 274.12 Kgs
Wind Load on Conductor in Longitudinal Direction = 194.00 Kg
Wind Load on Conductor in Transverse Direction = 194.00 Kg
14 ) Angle of Deviation
o
In Plan = 45
o
In Elevation = 30
Vertical Long. Transverse
Load Due to Normal Tension Due to
-225.00 275.57 275.57
Deviations in kg
Transverse Loads :-
Wind Load on Earth-Wire in Transverse Dirn. = 194 Kg
Load Due to Normal Tension Due to Deviation = 276 Kg
Say = 470 Kg
Longitudinal Loads :-
Wind Load on Earth-Wire in Longitudinal Dirn. = 194 Kg
Load Due to Normal Tension Due to Deviation = 276 Kg
Say = 470 Kg
Client : POWER GRID COMPANY OF BANGLADESH LIMITED.
ETERN-HEI-FEPEC
Project
230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
:
Revision
EARTH QUAKE LOAD CALCULATION
0 Date :- 20.05.2017
W= 4925.208
40
UPPER BEAM LVL 450
18 0
18.00 4925.21
11184
8766
PLINTH LVL
Client : POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Revision
Title : LOADING DIAGRAM OF 230kV TOWER MKD. "T2"
R-02 Date :- 20.05.2017
40
UPPER BEAM LVL 450
18 1347
18.00 4925.21
11184
7419
PLINTH LVL
0
* LOADING DIAGRAMS (WITH 45 DEVIATION IN PLAN):-
* ALL LOADS IN KGS * ALL DIMENSIONS IN MTS.
40
UPPER BEAM LVL 318
18 6057
18.00 4925.21
6894
7404
(0)
PLINTH LVL
40
UPPER BEAM LVL 318
18 7404
18.00 4925.21
6894
6057
PLINTH LVL
Client : POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Revision
Title : LOADING DIAGRAM OF 230kV TOWER MKD. "T2"
R-02 Date :- 20.05.2017
-185
UPPER BEAM LVL 390
18 0
18.00 4925.21
11184
8766
(0)
PLINTH LVL
Client : POWER GRID COMPANY OF BANGLADESH LIMITED. ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION CONSORTIUM
Revision
Title : LOADING DIAGRAM OF 230kV TOWER MKD. "T2"
R-02 Date :- 20.05.2017
-185
UPPER BEAM LVL 390
18 1347
18.00 4925.21
11184
7419
PLINTH LVL
0 0
* LOADING DIAGRAMS (WITH 45 DAVIATION IN PLAN & 30 DEVIATION IN ELEVATION):-
* ALL LOADS IN KGS * ALL DIMENSIONS IN MTS.
-185
UPPER BEAM LVL 276
18 5247
18.00 4925.21
11184
6594
(0)
PLINTH LVL
-185
UPPER BEAM LVL 276
18 6594
18.00 4925.21
11184
5247
PLINTH LVL
Table for Member Designation and Force Details from STAAD Output
GANTRY TOWER MARKED T2
Maximum
Maximum compression
Sl Group Member No. In Tension for all for all LC
No. Designation STTAD Model Member Type LC (kg) ( kg)
1 L4 1 LEG 186280.56 0.00
2 L4 2 LEG 123748.00 130556.43
3 L4 3 LEG 0.00 193890.98
4 L4 4 LEG 122946.00 134297.17
5 L4 5 LEG 168167.42 0.00
6 L4 6 LEG 114856.92 112701.63
7 L4 7 LEG 0.00 175465.58
8 L4 8 LEG 105474.33 125062.97
9 L4 9 LEG 150752.81 0.00
10 L4 10 LEG 103411.02 96240.34
11 L4 11 LEG 0.00 157567.52
12 L4 12 LEG 89519.46 113112.41
13 L4 13 LEG 136359.53 0.00
14 L4 14 LEG 94256.16 81769.31
15 L4 15 LEG 0.00 142872.97
16 L4 16 LEG 75323.15 103676.19
17 L3 17 LEG 119588.39 0.00
18 L3 18 LEG 82886.92 68733.85
19 L3 19 LEG 0.00 125750.60
20 L3 20 LEG 62346.60 91937.14
21 L3 21 LEG 105752.40 0.00
22 L3 22 LEG 73725.11 57741.06
23 L3 23 LEG 0.00 111741.33
24 L3 24 LEG 51228.31 82619.16
25 L3 25 LEG 90028.89 0.00
26 L3 26 LEG 62822.40 47631.01
27 L3 27 LEG 0.00 95735.36
28 L3 28 LEG 41193.30 71418.34
29 L3 29 LEG 77133.32 0.00
30 L3 30 LEG 54027.39 39461.47
31 L3 31 LEG 0.00 82696.87
32 L3 32 LEG 32960.57 62494.88
33 L2 33 LEG 62752.78 0.00
34 L2 34 LEG 43875.70 31971.80
35 L2 35 LEG 0.00 68143.92
36 L2 36 LEG 25499.63 52157.17
37 L2 37 LEG 50528.32 0.00
38 L2 38 LEG 35322.15 26014.49
39 L2 39 LEG 0.00 55831.29
40 L2 40 LEG 19504.58 43528.66
41 L2 41 LEG 35870.81 0.00
42 L2 42 LEG 24822.88 19924.13
43 L2 43 LEG 0.00 40975.87
44 L2 44 LEG 13530.99 32818.50
45 L2 45 LEG 23033.27 1100.45
46 L2 46 LEG 15631.72 15363.22
47 L2 47 LEG 0.00 28282.85
Table for Member Designation and Force Details from STAAD Output
GANTRY TOWER MARKED T2
Maximum
Maximum compression
Sl Group Member No. In Tension for all for all LC
No. Designation STTAD Model Member Type LC (kg) ( kg)
48 L2 48 LEG 8976.13 23569.93
49 L2 49 LEG 11718.90 1200.00
50 L2 50 LEG 8358.50 9040.33
51 L2 51 LEG 0.00 14289.64
52 L2 52 LEG 5931.76 12140.71
53 L1 53 LEG 8089.86 0.00
54 L1 54 LEG 6449.40 5177.01
55 L1 55 LEG 0.00 8102.36
56 L1 56 LEG 5200.79 6461.55
57 L1 57 LEG 6772.39 0.00
58 L1 58 LEG 5190.44 3770.21
59 L1 59 LEG 0.00 6592.56
60 L1 60 LEG 4028.75 5010.53
61 L1 61 LEG 5251.50 0.00
62 L1 62 LEG 3796.71 2537.93
63 L1 63 LEG 0.00 5129.68
64 L1 64 LEG 2733.04 3675.07
65 L1 65 LEG 4050.01 0.00
66 L1 66 LEG 2787.15 1293.14
67 L1 67 LEG 0.00 3240.41
68 L1 68 LEG 1877.87 1977.27
69 L1 69 LEG 1313.99 0.00
70 L1 70 LEG 840.24 1293.14
71 L1 71 LEG 0.00 1088.24
72 L1 72 LEG 536.35 1293.14
73 DL18 101 LONG BRAC 8603.53 0.00
74 DL18 102 LONG BRAC 0.00 8479.75
75 DL18 103 LONG BRAC 8358.77 0.00
76 DL18 104 LONG BRAC 0.00 8724.52
77 DL17 105 LONG BRAC 8486.56 0.00
78 DL17 106 LONG BRAC 0.00 8911.38
79 DL17 107 LONG BRAC 8733.70 0.00
80 DL17 108 LONG BRAC 0.00 8664.24
81 DL16 109 LONG BRAC 8832.00 0.00
82 DL16 110 LONG BRAC 0.00 8846.13
83 DL16 111 LONG BRAC 8578.95 0.00
84 DL16 112 LONG BRAC 0.00 9099.19
85 DL15 113 LONG BRAC 8634.49 0.00
86 DL15 114 LONG BRAC 0.00 9195.12
87 DL15 115 LONG BRAC 8896.20 0.00
88 DL15 116 LONG BRAC 0.00 8933.41
89 DL14 117 LONG BRAC 8913.72 0.00
90 DL14 118 LONG BRAC 0.00 8963.24
91 DL14 119 LONG BRAC 8646.08 0.00
92 DL14 120 LONG BRAC 0.00 9230.88
93 DL13 121 LONG BRAC 8657.39 0.00
94 DL13 122 LONG BRAC 0.00 9237.90
95 DL13 123 LONG BRAC 8928.27 0.00
Table for Member Designation and Force Details from STAAD Output
GANTRY TOWER MARKED T2
Maximum
Maximum compression
Sl Group Member No. In Tension for all for all LC
No. Designation STTAD Model Member Type LC (kg) ( kg)
96 DL13 124 LONG BRAC 0.00 8967.02
97 DL12 125 LONG BRAC 8862.52 0.00
98 DL12 126 LONG BRAC 0.00 8936.61
99 DL12 127 LONG BRAC 8586.04 0.00
100 DL12 128 LONG BRAC 0.00 9213.09
101 DL11 129 LONG BRAC 8496.50 0.00
102 DL11 130 LONG BRAC 0.00 9119.68
103 DL11 131 LONG BRAC 8784.04 0.00
104 DL11 132 LONG BRAC 0.00 8832.14
105 DL10 133 LONG BRAC 8722.42 0.00
106 DL10 134 LONG BRAC 0.00 8720.17
107 DL10 135 LONG BRAC 8423.26 0.00
108 DL10 136 LONG BRAC 0.00 9019.33
109 DL9 137 LONG BRAC 8569.93 0.00
110 DL9 138 LONG BRAC 0.00 9182.92
111 DL9 139 LONG BRAC 8884.81 0.00
112 DL9 140 LONG BRAC 0.00 8868.04
113 DL8 141 LONG BRAC 9021.94 0.00
114 DL8 142 LONG BRAC 0.00 9045.21
115 DL8 143 LONG BRAC 8691.75 0.00
116 DL8 144 LONG BRAC 0.00 9375.40
117 DL7 145 LONG BRAC 8717.68 0.00
118 DL7 146 LONG BRAC 0.00 9396.41
119 DL7 147 LONG BRAC 9060.54 0.00
120 DL7 148 LONG BRAC 0.00 9053.56
121 DL6 149 LONG BRAC 5963.65 0.00
122 DL6 150 LONG BRAC 0.00 6029.35
123 DL6 151 LONG BRAC 5697.50 0.00
124 DL6 152 LONG BRAC 0.00 6295.51
125 DL5 153 LONG BRAC 820.13 0.00
126 DL5 154 LONG BRAC 0.00 1206.84
127 DL5 155 LONG BRAC 810.94 0.00
128 DL5 156 LONG BRAC 0.00 1216.10
129 DL4 157 LONG BRAC 622.71 0.00
130 DL4 158 LONG BRAC 0.00 1140.80
131 DL4 159 LONG BRAC 635.52 0.00
132 DL4 160 LONG BRAC 0.00 1128.09
133 DL3 161 LONG BRAC 671.00 0.00
134 DL3 162 LONG BRAC 0.00 977.41
135 DL3 163 LONG BRAC 651.12 0.00
136 DL3 164 LONG BRAC 0.00 997.44
137 DL2 165 LONG BRAC 288.87 0.00
138 DL2 166 LONG BRAC 0.00 1317.34
139 DL2 167 LONG BRAC 328.04 0.00
140 DL2 168 LONG BRAC 0.00 1278.48
141 DL1 169 LONG BRAC 831.65 0.00
142 DL1 170 LONG BRAC 0.00 985.52
143 DL1 171 LONG BRAC 700.37 0.00
Table for Member Designation and Force Details from STAAD Output
GANTRY TOWER MARKED T2
Maximum
Maximum compression
Sl Group Member No. In Tension for all for all LC
No. Designation STTAD Model Member Type LC (kg) ( kg)
144 DL1 172 LONG BRAC 0.00 1117.82
145 D18 201 TRANS BRAC 13160.86 0.00
146 D18 202 TRANS BRAC 853.22 12920.15
147 D18 203 TRANS BRAC 12725.25 2500.66
148 D18 204 TRANS BRAC 0.00 13355.76
149 D17 205 TRANS BRAC 11930.95 2382.29
150 D17 206 TRANS BRAC 0.00 12537.61
151 D17 207 TRANS BRAC 12345.93 0.00
152 D17 208 TRANS BRAC 867.32 12122.63
153 D16 209 TRANS BRAC 11575.68 0.00
154 D16 210 TRANS BRAC 784.98 11544.66
155 D16 211 TRANS BRAC 11174.09 2305.44
156 D16 212 TRANS BRAC 0.00 11946.26
157 D15 213 TRANS BRAC 10474.25 2230.41
158 D15 214 TRANS BRAC 0.00 11198.81
159 D15 215 TRANS BRAC 10862.78 0.00
160 D15 216 TRANS BRAC 810.51 10810.28
161 D14 217 TRANS BRAC 10092.37 0.00
162 D14 218 TRANS BRAC 734.20 10131.29
163 D14 219 TRANS BRAC 9716.55 2157.43
164 D14 220 TRANS BRAC 0.00 10507.11
165 D13 221 TRANS BRAC 9065.76 2086.68
166 D13 222 TRANS BRAC 0.00 9760.53
167 D13 223 TRANS BRAC 9429.25 0.00
168 D13 224 TRANS BRAC 757.21 9397.04
169 D12 225 TRANS BRAC 8692.60 0.00
170 D12 226 TRANS BRAC 685.84 8768.98
171 D12 227 TRANS BRAC 8341.00 2018.42
172 D12 228 TRANS BRAC 0.00 9120.58
173 D11 229 TRANS BRAC 7724.82 1952.89
174 D11 230 TRANS BRAC 0.00 8410.20
175 D11 231 TRANS BRAC 8065.00 0.00
176 D11 232 TRANS BRAC 708.24 8070.01
177 D10 233 TRANS BRAC 7456.86 0.00
178 D10 234 TRANS BRAC 641.90 7477.36
179 D10 235 TRANS BRAC 7127.56 1890.39
180 D10 236 TRANS BRAC 0.00 7806.66
181 D9 237 TRANS BRAC 6835.95 1890.39
182 D9 238 TRANS BRAC 0.00 7456.87
183 D9 239 TRANS BRAC 7165.25 0.00
184 D9 240 TRANS BRAC 685.35 7127.57
185 D8 241 TRANS BRAC 6774.63 0.00
186 D8 242 TRANS BRAC 641.90 6835.96
187 D8 243 TRANS BRAC 6445.33 1890.40
188 D8 244 TRANS BRAC 0.00 7165.26
189 D7 245 TRANS BRAC 6027.41 1860.38
190 D7 246 TRANS BRAC 0.00 6666.92
191 D7 247 TRANS BRAC 6351.48 0.00
Table for Member Designation and Force Details from STAAD Output
GANTRY TOWER MARKED T2
Maximum
Maximum compression
Sl Group Member No. In Tension for all for all LC
No. Designation STTAD Model Member Type LC (kg) ( kg)
192 D7 248 TRANS BRAC 674.34 6342.85
193 D6 249 TRANS BRAC 4198.92 0.00
194 D6 250 TRANS BRAC 517.81 4131.33
195 D6 251 TRANS BRAC 3904.23 1920.94
196 D6 252 TRANS BRAC 0.00 4426.01
197 D5 253 TRANS BRAC 820.23 1879.41
198 D5 254 TRANS BRAC 7.20 1879.41
199 D5 255 TRANS BRAC 809.88 1879.41
200 D5 256 TRANS BRAC 0.00 1158.87
201 D4 257 TRANS BRAC 621.60 1699.24
202 D4 258 TRANS BRAC 0.00 1140.94
203 D4 259 TRANS BRAC 635.92 1699.24
204 D4 260 TRANS BRAC 9.96 1699.24
205 D3 261 TRANS BRAC 671.22 0.00
206 D3 262 TRANS BRAC 17.26 1542.01
207 D3 263 TRANS BRAC 648.83 1542.01
208 D3 264 TRANS BRAC 0.00 998.05
209 D2 265 TRANS BRAC 285.47 1415.41
210 D2 266 TRANS BRAC 0.00 1317.78
211 D2 267 TRANS BRAC 329.24 0.00
212 D2 268 TRANS BRAC 27.88 1415.41
213 D1 269 TRANS BRAC 833.12 0.00
214 D1 270 TRANS BRAC 108.07 1328.23
215 D1 271 TRANS BRAC 685.23 1328.23
216 D1 272 TRANS BRAC 0.00 1121.89
217 HL3 301 LONG BELT 386.57 301.00
218 HL3 302 LONG BELT 0.00 423.75
219 HL2 303 LONG BELT 85.35 1027.89
220 HL2 304 LONG BELT 1176.82 304.00
221 HL1 305 LONG BELT 1.22 305.00
222 HL1 306 LONG BELT 31.97 306.00
223 H3 401 TRANS BELT 187.64 401.00
224 H3 402 TRANS BELT 75.82 402.00
225 H2 403 TRANS BELT 0.00 1177.22
226 H2 404 TRANS BELT 1331.49 0.00
227 H1 405 TRANS BELT 0.00 405.00
228 H1 406 TRANS BELT 36.36 406.00
MEMBER AND CONNCETION DESIGN FOR TOWER MARKED T2
DESIGN BASIS & REFERENCES :
3) FOR PROPERTIES OF EACH MEMBER, BS 4848 : Part 4 HAS BEEN REFERED SINCE SAME ARE USED.
4) FOR CALCULATING SLENDERNESS RATIO & PERM. STRESS OF BRACINGS, CL. 3.7 OF ASCE 10-97 IS REFERED
5) FOR LIMITING SLENDERNESS RATIO VALUES, CL. 4.7.3.2 OF BS 5950 : Part 1 : 2000 IS REFERED.
6) A) PERMISSIBLE TENSILE STRESS IS TAKEN AS MINIMUM GUARANTED YIELD STRESS FOR MILD STEEL Fy= 235 Mpa = 2395.5148 kg/sqcm
CONSIDERING PARTIAL MATERIAL FACTOR OF .85, DESIGN YELD STRENGTH OF MILD STEEL Fy= 0.85xFy= 199.75 Mpa = 2036.1876 kg/sqcm
B) PERMISSIBLE TENSILE STRESS IS TAKEN AS MINIMUM GUARANTED YIELD STRESS FOR HIGH TENSILE STEEL Fy= 345 Mpa = 3516.8196 kg/sqcm
CONSIDERING PARTIAL MATERIAL FACTOR OF .85, DESIGN YELD STRENGTH OF HT STEEL Fy= 0.85xFy= 293.25 Mpa = 2989.2966 kg/sqcm
7) NET AREA FOR MAIN LEG WORKOUT AS Ag-2*dh*t & BRACINGS IS WORKED OUT AS (A1 + A2.k), WHERE K=3A1/(3A1+A2)
REFER CLAUSE 4.6.3 of BS 5950 : Part 1 : 2000.
8) GRADE OF BOLTS USED FOR FASTENER = PROPERTY CLASS 8.8 AS PER ISO 898-1
9) MINIMUM YIELD STRENGTH OF THE FASTENER (Fy) = 640 N/mm2 640
10) MINIMUM ULTIMATE TENSILE STRENGTH OF THE FASTENER (Uf) = 800 N/mm2
11) SHEAR STRENGTH OF THE BOLT fsb = MIN ( 0.48xUf, 0.69xFy )x.85 = 326.40 Mpa = 3327.22 kg/sqcm
12) BEARING STRENGTH OF THE BOLT fbb = 0.64x( Uf + Fy )x.85 = 783.36 Mpa = 7985.32 kg/sqcm
13)TENSILE STRENGTH OF THE BOLT ftb = MIN ( 0.58xUf, 0.83xFy )x.85 = 394.40 Mpa = 4020.39 kg/sqcm
Basic Formulae
1) DIAMETER OF CONNECTION BOLT, db = 16 mm
2) DIAMETER OF HOLE FOR BOLT, dh = 17.5 mm
3) EFFECTIVE AREA OF MAIN LEG SECTION, Ae = Ag-2*dh*t
4) EFFECTIVE AREA OF BRACING SECTION, Ae = A1+A2.k ,WHERE k=3A1/(3A1+A2)
5) MODULUS OF ELASTICITY OF STEEL, E = 200100 N/sqmm = 2039755.352 kg/sqcm
6) VALUE, Cc for high tensile steel = π x SQRT(2 x E/Fy) = 116.06
7) (w/t)lim = 80 x 2.62/SQRT (Fy in Mpa) = 12.24
8) VALUE, Cc for mild steel = π x SQRT(2 x E/Fy) = 140.62
9) (w/t)lim = 80 x 2.62/SQRT (Fy in Mpa) = 14.83
10 ) STRESS REDUCTION FACTOR, ø FOR (w/t)act < (w/t)lim = 1
11 ) STRESS REDUCTION FACTOR, ø FOR (w/t)act >= (w/t)lim = 1.677-(0.677 x (w/t)act/(wt)lim)
12 ) PERM. STRESS IN COMPRESSION, fc FOR KL/r> Cc = [1-0.5 x ((KL/r)/Cc)^2]xøFy
13 ) PERM. STRESS IN COMPRESSION, fc FOR KL/r<=Cc = π^2 x E/(KL/r)^2
14 ) CAPACITY OF SECTION IN TENSION, Ft = At*ft
15 ) CAPACITY OF SECTION IN COMPRESSION, Fc = At*fc
16 ) CAPACITY OF BOLT IN BEARING, Fbb = fbb*t*db/10
17 ) NO. OF BOLT REQUIRED, Bn = Min of F in Tension or Compression/Min of bolt cap. in shear or bearing
18 ) CAPACITY OF BOLT IN SINGLE SHEAR, Fsb = 6689.77 kg
19 ) CAPACITY OF BOLT IN DOUBLE SHEAR, Fsb = 13379.53 kg
EFFECTIVE LENGTH COEFFICIENT K FOR KL/r VALUES
01 MAIN LEG OF TOWER FOR KL/rxx or ryy = 1.00
03 MAIN LEG OF TOWER FOR KL/rvv = 1.00
04 DIAGONAL BRACING OF TOWER FOR KL/rxx,ryy = 0.50
05 DIAGONAL BRACING OF TOWER FOR KL/rvv = 0.50
HORIZONTAL BELT OF TOWER KL/rxx OR ryy
06
OR rvv
= 1.00
101 DL+NC+WIND PERPENDICULAR TO BEAM(WOD) -374.67 -95819.86 -7376.87 0.00 0.00 0.00
102 DL+SC+NO WIND (WOD) -242.51 -59753.25 -4277.70 0.00 0.00 0.00
103 DL+NC+WIND PARALLEL TO BEAM (WOD) -4610.51 -118043.26 -4672.40 0.00 0.00 0.00
104 DL+NC+EQ LOAD IN LONGI DIR (WOD) -368.23 -35689.71 -2366.59 0.00 0.00 0.00
105 DL+NC+EQ LOAD IN TRANS DIR (WOD) -364.10 -14301.01 -796.69 0.00 0.00 0.00
201 DL+NC+WIND PERPENDICULAR TO BEAM (WD1) -2038.46 -142069.13 -8954.86 0.00 0.00 0.00
202 DL+SC+NO WIND (WD1) -3120.68 -133026.50 -6617.44 0.00 0.00 0.00
203 DL+NC+WIND PARALLEL TO BEAM (WD1) -5906.29 -146542.47 -5353.49 0.00 0.00 0.00
204 DL+NC+EQ LOAD IN LONGI DIR (WD1) -1943.24 -70193.92 -3211.50 0.00 0.00 0.00
205 DL+NC+EQ LOAD IN TRANS DIR (WD1) -1955.50 -52890.88 -1925.35 0.00 0.00 0.00
1
301 DL+NC+WIND PERPENDICULAR TO BEAM (WD2) -373.76 -95574.72 -7363.41 0.00 0.00 0.00
302 DL+SC+ NO WIND (WD2) -241.60 -59508.12 -4264.25 0.00 0.00 0.00
303 DL+NC+WIND PARALLEL TO BEAM (WD2) -4609.60 -117798.13 -4658.95 0.00 0.00 0.00
304 DL+NC+EQ LOAD IN LONGI DIR (WD2) -367.32 -35444.57 -2353.14 0.00 0.00 0.00
305 DL+NC+EQ LOAD IN TRANS DIR (WD2) -363.19 -14055.87 -783.24 0.00 0.00 0.00
401 DL+NC+WIND PERPENDICULAR TO BEAM (WD3) -1809.73 -132708.36 -8553.60 0.00 0.00 0.00
402 DL+SC+NO WIND (WD3) -2718.69 -118689.66 -6039.23 0.00 0.00 0.00
403 DL+NC+WIND PARALLEL TO BEAM (WD3) -5677.56 -137181.69 -4952.22 0.00 0.00 0.00
404 DL+NC+EQ LOAD IN LONGI DIR(WD3) -1714.52 -60833.15 -2810.23 0.00 0.00 0.00
405 DL+NC+EQ LOAD IN TRANS DIR(WD3) -1736.53 -45959.96 -1692.82 0.00 0.00 0.00
101 DL+NC+WIND PERPENDICULAR TO BEAM(WOD) 374.67 -95819.86 -7376.87 0.00 0.00 0.00
102 DL+SC+NO WIND (WOD) 242.51 -59753.25 -4277.70 0.00 0.00 0.00
103 DL+NC+WIND PARALLEL TO BEAM (WOD) -4409.99 68180.70 972.85 0.00 0.00 0.00
104 DL+NC+EQ LOAD IN LONGI DIR (WOD) -124.30 -23869.23 -2006.29 0.00 0.00 0.00
105 DL+NC+EQ LOAD IN TRANS DIR (WOD) -309.30 1860.60 -304.06 0.00 0.00 0.00
201 DL+NC+WIND PERPENDICULAR TO BEAM (WD1) -1246.16 -60847.98 -6482.78 0.00 0.00 0.00
202 DL+SC+NO WIND (WD1) -2607.18 5927.08 -2384.22 0.00 0.00 0.00
203 DL+NC+WIND PARALLEL TO BEAM (WD1) -5736.34 103719.32 2242.03 0.00 0.00 0.00
204 DL+NC+EQ LOAD IN LONGI DIR (WD1) -1736.90 19614.38 -476.29 0.00 0.00 0.00
205 DL+NC+EQ LOAD IN TRANS DIR (WD1) -1905.48 41257.58 942.16 0.00 0.00 0.00
20
301 DL+NC+WIND PERPENDICULAR TO BEAM (WD2) 373.76 -95574.72 -7363.41 0.00 0.00 0.00
302 DL+SC+ NO WIND (WD2) 241.60 -59508.12 -4264.25 0.00 0.00 0.00
303 DL+NC+WIND PARALLEL TO BEAM (WD2) -4410.90 68425.84 986.30 0.00 0.00 0.00
304 DL+NC+EQ LOAD IN LONGI DIR (WD2) -125.20 -23624.09 -1992.84 0.00 0.00 0.00
305 DL+NC+EQ LOAD IN TRANS DIR (WD2) -310.21 2105.74 -290.61 0.00 0.00 0.00
401 DL+NC+WIND PERPENDICULAR TO BEAM (WD3) -1048.57 -61917.88 -6399.15 0.00 0.00 0.00
402 DL+SC+NO WIND (WD3) -2243.09 1679.01 -2372.19 0.00 0.00 0.00
403 DL+NC+WIND PARALLEL TO BEAM (WD3) -5538.74 102649.42 2325.66 0.00 0.00 0.00
404 DL+NC+EQ LOAD IN LONGI DIR(WD3) -1539.30 18544.49 -392.66 0.00 0.00 0.00
405 DL+NC+EQ LOAD IN TRANS DIR(WD3) -1698.13 37757.83 857.05 0.00 0.00 0.00
Page 1 of 2
POWER GRID COMPANY OF BANGLADESH LIMITED. Document No.
Client : ETERN-HEI-FEPEC
Project : 230/132kV SHIKALBAHA GIS SUBSTATION SHI-T2-FDN-LOADS CONSORTIUM
Design By Revision
Title : SUPPORT REACTIONS FOR 230kV TOWER MKD."T2"
R-02 Date :- 20.05.2017
101 DL+NC+WIND PERPENDICULAR TO BEAM(WOD) -400.21 103874.40 -7612.90 0.00 0.00 0.00
102 DL+SC+NO WIND (WOD) -269.63 68287.80 -4526.54 0.00 0.00 0.00
103 DL+NC+WIND PARALLEL TO BEAM (WOD) -4640.65 126097.79 -4907.37 0.00 0.00 0.00
104 DL+NC+EQ LOAD IN LONGI DIR (WOD) -393.88 43744.24 -2601.60 0.00 0.00 0.00
105 DL+NC+EQ LOAD IN TRANS DIR (WOD) -389.76 22355.54 -1031.70 0.00 0.00 0.00
201 DL+NC+WIND PERPENDICULAR TO BEAM (WD1) -2057.46 147978.66 -9129.08 0.00 0.00 0.00
202 DL+SC+NO WIND (WD1) -3139.79 138936.02 -6790.64 0.00 0.00 0.00
203 DL+NC+WIND PARALLEL TO BEAM (WD1) -5929.89 152452.00 -5526.65 0.00 0.00 0.00
204 DL+NC+EQ LOAD IN LONGI DIR (WD1) -1962.36 76103.46 -3384.69 0.00 0.00 0.00
205 DL+NC+EQ LOAD IN TRANS DIR (WD1) -1974.62 58800.41 -2098.54 0.00 0.00 0.00
39
301 DL+NC+WIND PERPENDICULAR TO BEAM (WD2) -398.94 103516.74 -7596.21 0.00 0.00 0.00
302 DL+SC+ NO WIND (WD2) -268.36 67930.13 -4509.85 0.00 0.00 0.00
303 DL+NC+WIND PARALLEL TO BEAM (WD2) -4639.39 125740.13 -4890.68 0.00 0.00 0.00
304 DL+NC+EQ LOAD IN LONGI DIR (WD2) -392.61 43386.58 -2584.91 0.00 0.00 0.00
305 DL+NC+EQ LOAD IN TRANS DIR (WD2) -388.49 21997.88 -1015.01 0.00 0.00 0.00
401 DL+NC+WIND PERPENDICULAR TO BEAM (WD3) -1834.91 140650.38 -8786.39 0.00 0.00 0.00
402 DL+SC+NO WIND (WD3) -2745.46 127111.67 -6284.83 0.00 0.00 0.00
403 DL+NC+WIND PARALLEL TO BEAM (WD3) -5707.34 145123.71 -5183.96 0.00 0.00 0.00
404 DL+NC+EQ LOAD IN LONGI DIR(WD3) -1739.82 68775.16 -3042.00 0.00 0.00 0.00
405 DL+NC+EQ LOAD IN TRANS DIR(WD3) -1761.83 53901.97 -1924.59 0.00 0.00 0.00
101 DL+NC+WIND PERPENDICULAR TO BEAM(WOD) 400.21 103874.40 -7612.90 0.00 0.00 0.00
102 DL+SC+NO WIND (WOD) 269.63 68287.80 -4526.54 0.00 0.00 0.00
103 DL+NC+WIND PARALLEL TO BEAM (WOD) -4379.85 -60126.17 737.88 0.00 0.00 0.00
104 DL+NC+EQ LOAD IN LONGI DIR (WOD) -98.64 31923.77 -2241.29 0.00 0.00 0.00
105 DL+NC+EQ LOAD IN TRANS DIR (WOD) -283.64 6193.94 -539.07 0.00 0.00 0.00
201 DL+NC+WIND PERPENDICULAR TO BEAM (WD1) -1227.17 66757.51 -6657.00 0.00 0.00 0.00
202 DL+SC+NO WIND (WD1) -2588.07 -17.55 -2557.42 0.00 0.00 0.00
203 DL+NC+WIND PARALLEL TO BEAM (WD1) -5712.73 -97809.78 2068.87 0.00 0.00 0.00
204 DL+NC+EQ LOAD IN LONGI DIR (WD1) -1717.78 -13704.85 -649.48 0.00 0.00 0.00
205 DL+NC+EQ LOAD IN TRANS DIR (WD1) -1886.36 -35348.05 768.97 0.00 0.00 0.00
58
301 DL+NC+WIND PERPENDICULAR TO BEAM (WD2) 398.94 103516.74 -7596.21 0.00 0.00 0.00
302 DL+SC+ NO WIND (WD2) 268.36 67930.13 -4509.85 0.00 0.00 0.00
303 DL+NC+WIND PARALLEL TO BEAM (WD2) -4381.11 -60483.83 754.57 0.00 0.00 0.00
304 DL+NC+EQ LOAD IN LONGI DIR (WD2) -99.91 31566.11 -2224.60 0.00 0.00 0.00
305 DL+NC+EQ LOAD IN TRANS DIR (WD2) -284.91 5836.28 -522.38 0.00 0.00 0.00
401 DL+NC+WIND PERPENDICULAR TO BEAM (WD3) -1023.39 69859.88 -6631.94 0.00 0.00 0.00
402 DL+SC+NO WIND (WD3) -2216.33 6743.00 -2617.79 0.00 0.00 0.00
403 DL+NC+WIND PARALLEL TO BEAM (WD3) -5508.96 -94707.40 2093.92 0.00 0.00 0.00
404 DL+NC+EQ LOAD IN LONGI DIR(WD3) -1514.00 -10602.47 -624.43 0.00 0.00 0.00
405 DL+NC+EQ LOAD IN TRANS DIR(WD3) -1672.83 -29815.81 625.28 0.00 0.00 0.00
Page 2 of 2
DESIGN OF FOUNDATION BOLT FOR TOWER T2
Basic Data
8 M40 1720
410
X
205 205
34mm thk base plate
205
145
70
410
25 145
205 200x12
StiffnerPlate
40mm dia fdn bolts
200x200x20
60.00 60
X
88.10 145
56.90
25 70
12
200
A A
46.97 34
410
VIEW : X-X
Check for Bearing stress on concrete
Allowable bearing stress in concrete. = 12 Mpa
Area of Base plate, A (sqcm.). (((205+205)^2-(0.5x0^2))/100) = 1681 cm2
Bearing Stress, (MPa). (2018.998062x10)/1681 = 12.01 Mpa <
= 12.30 Mpa
OK
DESIGN OF BASE PLATE FOR TOWER T2
Check for bending Stress in Base Plate
Calculation of Moment due to tension in bolt/ bearing pressure in base plate
01 No of bolts resisted by critical section X-X. = 3
02 Tension /bolt. (1940.74/8) = 242.59 kN
03 Max. Lever arm. = 88.1 mm
04 Moment M1, due to tension in bolt. (242.59x2)x88.1/1000 = 64.12 kN-m
05 Maximum Bearing Pressure. = 12.0 Mpa
06 Distance from edge to the support point. = 142.1 mm
07 Moment M2, due to bearing pressure. (12.01x142.1)^2x410/2000000 = 49.72 kN-m
08 Design Moment. = 64.12 kN-m
By Date08-DEC-16 Chd
Y
X
Z Load 101
Whole Structure
Print Time/Date: 27/05/2017 21:50 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Saturday, May 27, 2017, 09:52 PM
PAGE NO. 1
****************************************************
* *
* STAAD.Pro V8i SELECTseries6 *
* Version 20.07.11.33 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= MAY 27, 2017 *
* Time= 21:29: 7 *
* *
* USER ID: Personal *
****************************************************
1. STAAD TRUSS
INPUT FILE: F:\Works\Shikalbaha_CCC\Design\Gantry\230kV Gantry_Rev 3\230kV Gantry Tower_Rev2\STAAD Ana.. .STD
2. START JOB INFORMATION
3. ENGINEER DATE 08-DEC-16
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KG
7. JOINT COORDINATES
8. 1 -0.75 0 -1.25; 2 -0.75 2 -1.1925; 3 -0.75 3.85 -1.1394; 4 -0.75 5.6 -1.0891
9. 5 -0.75 7.25 -1.0417; 6 -0.75 8.8 -0.9971; 7 -0.75 10.25 -0.9555
10. 8 -0.75 11.6 -0.9167; 9 -0.75 12.85 -0.8807; 10 -0.75 14 -0.8477
11. 11 -0.75 15.15 -0.8147; 12 -0.75 16.3 -0.7816; 13 -0.75 17.4 -0.75
12. 14 -0.75 18.6 -0.75; 15 -0.62 19.88 -0.62; 16 -0.49 21.16 -0.49
13. 17 -0.36 22.44 -0.36; 18 -0.23 23.72 -0.23; 19 -0.1 25 -0.1; 20 0.75 0 -1.25
14. 21 0.75 2 -1.1925; 22 0.75 3.85 -1.1394; 23 0.75 5.6 -1.0891
15. 24 0.75 7.25 -1.0417; 25 0.75 8.8 -0.9971; 26 0.75 10.25 -0.9555
16. 27 0.75 11.6 -0.9167; 28 0.75 12.85 -0.8807; 29 0.75 14 -0.8477
17. 30 0.75 15.15 -0.8147; 31 0.75 16.3 -0.7816; 32 0.75 17.4 -0.75
18. 33 0.75 18.6 -0.75; 34 0.62 19.88 -0.62; 35 0.49 21.16 -0.49
19. 36 0.36 22.44 -0.36; 37 0.23 23.72 -0.23; 38 0.1 25 -0.1; 39 0.75 0 1.25
20. 40 0.75 2 1.1925; 41 0.75 3.85 1.1394; 42 0.75 5.6 1.0891; 43 0.75 7.25 1.0417
21. 44 0.75 8.8 0.9971; 45 0.75 10.25 0.9555; 46 0.75 11.6 0.9167
22. 47 0.75 12.85 0.8807; 48 0.75 14 0.8477; 49 0.75 15.15 0.8147
23. 50 0.75 16.3 0.7816; 51 0.75 17.4 0.75; 52 0.75 18.6 0.75; 53 0.62 19.88 0.62
24. 54 0.49 21.16 0.49; 55 0.36 22.44 0.36; 56 0.23 23.72 0.23; 57 0.1 25 0.1
25. 58 -0.75 0 1.25; 59 -0.75 2 1.1925; 60 -0.75 3.85 1.1394; 61 -0.75 5.6 1.0891
26. 62 -0.75 7.25 1.0417; 63 -0.75 8.8 0.9971; 64 -0.75 10.25 0.9555
27. 65 -0.75 11.6 0.9167; 66 -0.75 12.85 0.8807; 67 -0.75 14 0.8477
28. 68 -0.75 15.15 0.8147; 69 -0.75 16.3 0.7816; 70 -0.75 17.4 0.75
29. 71 -0.75 18.6 0.75; 72 -0.62 19.88 0.62; 73 -0.49 21.16 0.49
30. 74 -0.36 22.44 0.36; 75 -0.23 23.72 0.23; 76 -0.1 25 0.1
31. MEMBER INCIDENCES
32. 1 1 2; 2 20 21; 3 39 40; 4 58 59; 5 2 3; 6 21 22; 7 40 41; 8 59 60; 9 3 4
33. 10 22 23; 11 41 42; 12 60 61; 13 4 5; 14 23 24; 15 42 43; 16 61 62; 17 5 6
34. 18 24 25; 19 43 44; 20 62 63; 21 6 7; 22 25 26; 23 44 45; 24 63 64; 25 7 8
35. 26 26 27; 27 45 46; 28 64 65; 29 8 9; 30 27 28; 31 46 47; 32 65 66; 33 9 10
36. 34 28 29; 35 47 48; 36 66 67; 37 10 11; 38 29 30; 39 48 49; 40 67 68; 41 11 12
37. 42 30 31; 43 49 50; 44 68 69; 45 12 13; 46 31 32; 47 50 51; 48 69 70; 49 13 14
38. 50 32 33; 51 51 52; 52 70 71; 53 14 15; 54 33 34; 55 52 53; 56 71 72; 57 15 16
151. 18 75 FX 401
152. 17 74 FX 388
153. 16 73 FX 382
154. 15 72 FX 410
155. 14 71 FX 467
156. 13 70 FX 457
157. 12 69 FX 418
158. 11 68 FX 401
159. 10 67 FX 377
160. 9 66 FX 402
161. 8 65 FX 432
162. 7 64 FX 412
163. 6 63 FX 390
164. 5 62 FX 381
165. 4 61 FX 346
166. 3 60 FX 268
167. 2 59 FX 176
168. 1 58 FX 63
169. LOAD 4 EARTH QUAKE PARALLEL TO BEAM
170. JOINT LOAD
171. 13 14 32 33 51 52 70 71 FX 123.13
172. LOAD 5 EARTH QUAKE PERPENDICULAR TO BEAM
173. JOINT LOAD
174. 13 14 32 33 51 52 70 71 FZ 123.13
175. LOAD 6 DL + NC + WIND PERPENDICULAR TO BEAM
176. JOINT LOAD
177. 19 38 57 76 FX 0
178. 19 38 57 76 FY -10.01
179. 19 38 57 76 FZ 112.5
180. 13 14 32 33 51 52 70 71 FX 0
181. 13 14 32 33 51 52 70 71 FY -1397.98
182. 13 14 32 33 51 52 70 71 FZ 2013.94
183. LOAD 7 DL + SC+ NO WIND
184. JOINT LOAD
185. 19 38 57 76 FX 0
186. 19 38 57 76 FY -10.01
187. 19 38 57 76 FZ 112.5
188. 13 14 32 33 51 52 70 71 FX 0
189. 13 14 32 33 51 52 70 71 FY -1517.98
190. 13 14 32 33 51 52 70 71 FZ 2144.81
191. LOAD 8 DL + NC + WIND PARALLEL TO BEAM
192. JOINT LOAD
193. 19 38 57 76 FX 68.75
194. 19 38 57 76 FY -10.01
195. 19 38 57 76 FZ 112.5
196. 13 14 32 33 51 52 70 71 FX 526.5
197. 13 14 32 33 51 52 70 71 FY -1397.98
198. 13 14 32 33 51 52 70 71 FZ 927.38
199. LOAD 9 DL + NC + EARTH QUAKE LOAD IN LONGITUDINAL DIRECTION
200. JOINT LOAD
201. 19 38 57 76 FX 0
202. 19 38 57 76 FY -10.01
203. 19 38 57 76 FZ 112.5
204. 13 14 32 33 51 52 70 71 FX 0
205. 13 14 32 33 51 52 70 71 FY -1397.98
206. 13 14 32 33 51 52 70 71 FZ 1095.72
P R O B L E M S T A T I S T I C S
-----------------------------------
378. UNIT CM KG
379. DEFINE ENVELOPE
380. 101 TO 105 201 TO 205 301 TO 305 401 TO 405 ENVELOPE 1 TYPE STRENGTH
381. END DEFINE ENVELOPE
382. LOAD LIST 101 TO 105 201 TO 205 301 TO 305 401 TO 405
383. PRINT MAXFORCE ENVELOPE
386. FINISH
************************************************************