CURRENT TRANSFORMER INSTALLATION QUIZ

©Stephen Brooks BEng CEng MIET


Identify these three types of current transformers

__________ __________ __________

Used in Indoor Used in Outdoor


Used in Distribution
Distribution & Distribution &
systems up to 11kV
Transmission systems Transmission systems
Which direction does the secondary current flow for the primary current
direction shown?

P1
S1

OR

S2
P2
Label the cores and P1/P2 and S1/S2 labels for the CT shown

Core ? Core ? Core ? Core ?


For the following protection CT what is its nominal accuracy and at what
current does it stop being accurate?

600A
P1 S1

10P20
P2 S2
Provide the missing connections from the CT’s to the terminal block

To
secondary
P1 S1 P1 S1 P1 S1 circuits
P2 S2 P2 S2 P2 S2

R Y B
ANSWER

BAR TYPE RING TYPE POST TYPE

Used in Indoor Used in Outdoor


Used in Distribution
Distribution & Distribution &
systems up to 11kV
Transmission systems Transmission systems
ANSWER

P1
S1

S2
P2
ANSWER

Core 1 Core 2 Core 3 Core 4


1S1 1S2 2S1 2S2 3S1 3S2 4S1 4S2

P1 P2
ANSWER

It’s a 10P20 CT so therefore its nominal accuracy =


600A 10%
P1 S1 For a 10P20 CT its accuracy range is up to 20 times
10P20 the primary rated current..
P2 S2 Therefore..

Accuracy range = 20 * 600A = 12,000A

So during a fault condition, as long as the current


does not exceed 12,000A the secondary current will
be an accurate representation of the primary current
ANSWER

To
secondary
P1 S1 P1 S1 P1 S1 circuits
P2 S2 P2 S2 P2 S2

R Y B
THANK YOU!!