Академический Документы
Профессиональный Документы
Культура Документы
V65D (VF)
INSTRUCTION MANUAL
D rive R eady
R un
R un Forw ard
D IGITAL DC M O TO R P
C O N TRO LLER V65D
R un R everse
S
A la rm
D I G IT A L D C M O T O R D R IV E
1 Specifications --------------------------------------------- 2
3 Installation --------------------------------------------- 4
5 Wiring --------------------------------------------- 7
13 Communication --------------------------------------------- 42
Item Specifications
V65D-DCD4-VF
Type
0035 0070 0110 0150 0180 0270 0380 0500 0720
Motor (HP)
Main Circuit
Input Power 3∮ 200 ~ 440 VAC ±10%, 50/60Hz
(※1)
(VAC)
Control Loop 1∮ 200/220 VAC ±10%, 50/60Hz
Ambient
Operated Temperature 0 - + 45°C 0 - + 35°C
Environment (※2)
Humidity Relative humidity below 85℃ (non-condensing)
Altitude (※3) Below Altitude 500M (sea level)
Cooling Self-cooling Cooling Fan
16bit microprocessor
System Loop:Control loop, I/O ports, Terminal control including Soft-Start
loop, Speed Comparison loop, Current Comparison loop….etc.
System
Construction Programming: By Human Machine Interface(HMI) or Serial Link
Speed Setting: By adjustable resistor or Serial link
Soft-Start Setting: 0 ~ 600 seconds
Main Structure
Current Limit: Bi-direction, which can be controllerd simultaneously or
individually
3∮Bridge Rectification Wiring (SCR× 6)….. 2Q series
Main Circuit 3∮Bridge Rectification Wiring (SCR × 12)…. 4Q series
1φ Full-Wave Hybrid Bridge Rectifier, power supplied by external RF, TF
Output is a multiple(x 0.9)of power supply = field voltage, the maximum
Field Circuit output is 20A Max.
Field can be selected as voltage control, current control
Control Board Self-diagnosis
Instantaneous Over-current: 200%, 10 sec
Output Current
Overload: 150%, 30 sec
Field Loss of
Magnetic Field Loss Interlocking Protection
Motor
SPEC. 3∮
TYPE V65D-DCD4-0035-VF
AUX. SUPPLY 50/60HZ 200/200V
SERIAL NO.
www.euntay.tw
2. 2 Notices:
(1) When the drive connects to the power, the user can not do the wire or remove any
connector of the drive.
(2) A ground terminal “E” of the drive must be grounded (EARTH).
(3) Do not make the high voltage test to the components of drive.
3. Installation
The installing environment of the drive will directly influence its performance and lifetime.
Therefore, it must be considered when installing V65D DC Drive.
Ambient Temperature: 0 ~ +45°C (35A and 70A), 0 ~ +35°C (rated > 70A)
Avoid rainwater, moisture or direct sunlight exposure.
Avoid locations with vibration or electromagnetic interference.
In order to ensure heat dissipation, the space of devices must be considered when
installing.
(1) Cooling air should be allowed to vertically flow drive’s control board, power board and
heat sink.
(2) Clearance over 150mm at the top and bottom side of the drive should be kept for
airflow at least.
(3) When there are devices installed at the upper and lower side of the drive, clearance
over 175mm should be kept at least.
If several drives are installed in the same box, please install a fan to cool down the ambient
temperature.
S h ie ld
Sleeve
Isolated Layer
(4) Grounding Cable:
a. A grounding terminal GND is connected by the third method (Grounding resistance
is below 100Ω.).
b. A grounding wire of drive should not be mutually grounded together with an electric
welding machine and large power motor, which must be separately grounded.
c. The diameter of grounding wire is as short as possible according to the technical
standard of electric equipment.
d. Please refer to the following diagram when mutually grounded with several drives.
Pluggable Terminal
EXTERNAL
AC FIELD
DC TACHO
220V~440VAC
SPEED METER
5.3 Electric Connection Diagram:
- 13 -
SETPOINT
RAMP INPUT CURRENT METER
ENABLE
DRIVE READY
SRART/RUN
ZERO SPEED
JOG/ENABLE
FAST STOP
V65D 5.0 O5
Press the S key after the Press the P key to the next If it is in Parameter Setting
parameter is changed, and parameter if no parameter is Mode (no flash), the
then go to the next parameter. changed. display will automatically
return to the normal mode
in 15 seconds.
0 - MAX
The Maximum Brake Current of Drive.
BRAKE MAX According to CURRENT
According to drive’s specifications, the
16 drive’s
maximum value is set as 1.25 multiply of
LIMIT specifications CAPACITY OF
motor rated current.
V65D
0 - MAX The small amount brake current of drive.
According to
BRAKE BAND CURRENT The value of parameter is for brake in the
17 drive’s
LIMIT CAPACITY OF setting value of parameter “BRAKE BAND
specifications
V65D (SLP)”.
According to
The small amount brake range of drive.
BRAKE BAND the tolerance
18 0 – 100% The tolerance amount of over-speed (SPEED
(SLP) amount of
SLP) is as the small amount brake range.
over-speed
0~MAX
According to
MOTOR CURRENT Overload current of motor, An overload trip’s
19 motor’s
OVERLOAD CAPACITY execution is according to this parameter.
specifications
OF V65D
SPEED ACC
SELECT ACC SPEED DEC Open Collector output terminal “ACC”,
49 SPEED ACC
TB function selection of terminal
DRIVE
RUNNING
SPEED ACC
RUNNING
Parameter Lock and the internal parameter
calibration
0000: Program Unlock
PASSWORD 1234: Reset Program
& 0000 / 1234 / 0001~9999: Program Lock
51 0000
YUNNTAY 0001 ~ 9999 Note:
MODE#2 a. The parameter returns to default setting
when power is turned off and restarts.
b. Setting password to enter function of
calibration parameter group.
10.2.3 ACTG:
AC tacho-generator feedback (The only one of 20VAC/1000rpm generator), the voltage
is set from FBK MAX VOL ACTG at the highest speed of motor. (the maximum speed of
the motor for SPEED IN=10Vdc).
Example: If the AC TG specification is 20VAC/1000RPM, the required speed of a motor
is 1800rpm, the voltage calculation for this parameter is: 20VAC÷1000rpm × (required
speed 1800rpm) = 36 VAC. when this speed reaches to the maximum, the armature
voltage will be limited by the maximum voltage listed in Table 10.1. This parameter can
be set as 52VAC. That is, 2600rpm. If the higher speed is required, please refer to 9.24.
10.2.4 FBK DCTG:
DC Tacho-Generator specification is selected by FBK DCTG SELECT.
(1) DCTG 1000rpm / 30VDC
(2) DCTG 1000rpm / 60VDC
(3) DCTG 1000rpm / 100VDC
10.2.5 DC TG Voltage Setting:
The voltage of DC TG is set by the parameter of “FBK MAX VOL DCTG” in the
maximum speed of motor (the max speed of this motor for SPEED IN = 10Vdc).
Message
Description Error Cause Troubleshooting
Display
z Phase loss z Check 3-phase voltage.
z Check fuse.
z Phase loss z Fuse burnout z Check if current limit is larger
RST PHASE than rated current.
ALARM z Power voltage
below 180VAC Check the wiring is well and
Poor 3-phase wiring
screws are tightened.
Power board error Replace power board.
z Check if the setting of
Armature voltage is armature voltage is correct.
OVER SPEED higher than parameter: z No speed feedback.
Overspeed alarm
ALARM Maximum armature z Generator disconnection.
voltage z Wrong feedback device
selection.
z Check if parameter setting is
z Wrong load current
correct.
MOTOR setting
Motor overload z Check motor bearing coupler
OVERLOAD z Motor shaft locked
and connection to load.
z Wrong field current
z Check the field current.
z Check cooling fan.
z Drive’s fan error z Check fan socket.
z The plug isn’t put in z Check the position of cooling
the Fan socket fan and drive.
z Poor ventilation in a z Measure the temperature in
SCR TEMP SCR temperature the control panel. A cooling
control panel
ALARM alarm fan or air-conditioner must
z High ambient
be installed if the
temperature
temperature exceeds the
z Wrong controller specification.
setting
z Check the setting of
armature current.
z Check the power.
z No power for R220V z Check internal fuse (The
z No power for and TOV internal fuse is located on
power board z Internal fuse (3A) the top of control power
No Display z Incorrect power for blew input. If replaced, please
partial power boad z Incorrect power board disconnect the power and
z Correct power remove the board.).
z Incorrect control
board z Replace power board.
z Replace control board.
FAST STOP The status of “FAST z FAST STOP terminal z Close terminals and press
OPEN STOP” is actived is opened the “P” key.
After troubles are solved, DRIVE will be set as ENABLE and reset by pressing the P key or
external RESET terminal.
3
5
A
N
D
7
0
A
M
P
D
ri
v
e
R
e
a
d
y
P
R
u
n
DIGITAL DC MOTOR
R
u
n
F
o
r
w
a
r
d
CONTROLLER V65D
S
R
u
n
R
e
v
e
rs
e
A
l
a
r
m
1
1
0
A
M
P
D
ri
v
e
R
e
a
d
y
P
R
u
n
DIGITAL DC MOTOR
R
u
n
F
o
r
w
a
r
d
CONTROLLER V65D
S
R
u
n
R
e
v
e
rs
e
A
l
a
r
m
P
R
u
n
DIGITAL DC MOTOR
R
u
n
F
o
r
w
a
r
d
CONTROLLER V65D
S
R
u
n
R
e
v
e
rs
e
A
l
a
r
m
3
8
0
A
N
D
5
0
0
A
M
P
R
5
5
.9
R
5
2
.
4
3
2
5
.
7
D
ri
v
e
R
e
a
d
y
6 0 P
R
u
n
6 0 DIGITAL DC MOTOR
R
u
n
F
o
r
w
a
rd
06
CONTROLLER V65D
S
R
u
n
R
e
v
e
rs
e
0
A
l
a
r
m
5
7
.
0
9
1
?
1
0
?
132 7
2
4
3
2
2
05
0
0
2
0
2
7
5
0
73
00
7
0
5
0
5
.
2
1
7
2
0
A
M
P 3
3
5
8
0
6
0
?
1
5
2
0
5
4
~
0
5
2
5
.
2
1
5
7
.
1
2
2
7
.
0
0
0
1
D
ri
v
e
R
e
a
d
y
P 0 5
R
u
n
DIGITAL DC MOTOR
0 2
R
u
n
F
o
r
w
a
rd
0 6 6
CONTROLLER V65D
S
R
u
n
R
e
v
e
rs
e
0
A
l
a
r
m
5
2
.
8
7
1
?
1
0
55
? 7
1
1
.
3 2 27
2
1
5
22
3
0
7
0
3
0
2
4 6
04
00
2
0
5
2
7
5
.
2
7
1
3
0
No-parity check:
LSB MSB
1 2 3 4 5 6 7 8 9 10
Communication
Delay Time, setting
3.5 bits “SERIAL TIME”
parameter to 5ms
Communication above
Delay Time, setting
“SERIAL TIME” 3.5 bits
parameter to 5ms
above
Command Response
The
Function Message Message
Command Function
code Byte Byte Byte Byte
(Min.) (Max.) (Min.) (Max.)
V6.0