Академический Документы
Профессиональный Документы
Культура Документы
Introduction
Storage configurations may be fitted with elevated walkways in aisles to allow access to goods by personnel
who manually store and retrieve the goods. This configuration may be used by facilities such as customer
order fulfillment centers, distribution centers, and records retention warehouses.
This document provides guidelines for storage configurations with elevated walkways in aisles which are
aligned with published third-party automatic sprinkler standards. In addition, Zurich loss experience is
consistent with the guidelines.
Discussion
Scope of this document
This document applies to storage configurations where two or more adjacent aisles have elevated walkways
and the aisles do not exceed 2.4 m (8 ft.) wide, and may be subject to change based upon either research or
loss experience.
Storage configurations
Elevated walkways may be used with a variety of storage configurations including:
• Rack storage
• Shelf storage
• Solid decking may include walkways with a solid surface such as plywood
• Open grate decking may include walkways formed with open metal grate
View below an open metal grate mezzanine covered with an engineered wood deck
(Photo source: Rich Gallagher, The Zurich Services Corporation)
• Solid walkways may form a ceiling and capture heat from a fire occurring in the aisle below. The captured
heat may then be directed horizontally in the form of a “ceiling jet” towards the nearest sprinklers under
the solid walkway.
• Open grate walkways may allow heat from a fire below to pass through the walkway and continue rising
vertically. A ceiling jet may not be formed, and heat may not be directed horizontally to the nearest
sprinklers under the walkway. If a fire is not located directly below a walkway sprinkler, there may be a
delay in the operating sprinklers below the walkway.
• Solid walkways may form obstructions to the water discharged from ceiling sprinklers.
2
Open grate walkways may not fully obstruct the passage of water; however, they may adversely disrupt a
descending water spray distribution. In addition, NFPA’s Automatic Sprinkler Systems Handbook (2016)
points out that fire experience shows burning goods may fall onto a walkway and form an obstruction to
water spray even if the walkway has an open grate deck.
The typical rack fire scenario may have a sequence such as:
• In-rack sprinklers operate once they are exposed to sufficient heat within the vertical heat plume within the
rack flue
• Where the fire spreads to the top of the rack, the vertical heat plume exits the top of the rack, travels
vertically to the ceiling, forms a ceiling jet, reaches nearby ceiling sprinklers, and heats the nearby ceiling
sprinklers until they operate
• Discharge from operating in-rack and ceiling sprinklers penetrate down into the rack flues to help control
or suppress the fire and help limit horizontal fire spread along the rack
• Discharge from ceiling sprinklers also pre-wet goods across aisles to help limit horizontal fire spread from
rack to rack
3
Example of full-scale rack fire test with open aisle
(Photo source: Rich Gallagher, The Zurich Services Corporation)
A number of sprinkler arrangements have been proposed or installed to protect storage with elevated
walkways. These arrangements have included:
• Sprinklers in the storage racks only (no sprinklers under the elevated walkways)
• Sprinklers under elevated walkways only (no sprinklers in the storage racks)
These arrangements should be validated by full-scale fire tests to help ensure their appropriateness for the
specific storage and walkway configuration.
4
Guidance
For storage configurations within the scope of this document, protect storage configurations with elevated
walkways using a design proven by full-scale fire test. Where a design is based upon full-scale fire tests, see
the Risktopic titled Zurich Recognized Solutions for Property Risks for additional guidance. When storage
configurations are not backed up by full-scale fire tests, consider the following guidelines:
• Closing all openings between solid walkways and solid shelves where the shelves form part of the
mezzanine ceiling.
Example of a storage array with solid elevated walkways and solid shelving at the elevated walkway levels
(Image source: Rich Gallagher, The Zurich Services Corporation)
Example of opening at the rack uprights (Photo source: Malcolm Davies, Zurich Risk Engineering)
5
As a note, no publically available research has been identified that establishes the allowable size of gaps
around each rack upright. Floors and shelving should be installed without gaps; however, until research is
available, consider limiting gaps to 12 mm (0.5 in.) around each individual rack upright.
Loss Scenario – Solid mezzanine floors with gaps between rack uprights
A five-level pick module was formed around single-row racks. Rack depths and aisle widths both were
estimated at about 1.2 m (4 ft.). Mezzanine floors were solid except for 80 mm (3 in.) wide gaps between
the rack uprights.
A fire started on the second mezzanine level. The fire spread to the third, fourth, and fifth mezzanine
levels via the gaps in the mezzanine floor between the rack uprights. One sprinkler operated in the second
mezzanine level, four sprinklers operated in the third mezzanine level, six sprinklers operated in the fourth
mezzanine level, and six sprinklers operated at the ceiling above the fifth mezzanine level. In all, 17
sprinklers operated.
It is anticipated this fire could have been more challenging had the fire started on the first mezzanine
level.
It is anticipated the fire damage may have been limited to one mezzanine level and smoke and water
damage would have been reduced if the mezzanine floors did not have gaps between the rack uprights.
A fire started on the second mezzanine level. The fire was contained to the second mezzanine with one,
control mode sprinklers operating.
• Configuration of the storage (open-frame rack, solid shelf, solid shelf with vertical bulkheads)
• Clearance from the top of storage to the sprinkler deflectors below the mezzanine
6
Provide sprinklers of appropriate response time index (RTI)
Sprinklers installed below a mezzanine should have a RTI equal to or less than the RTI of the building ceiling-
level sprinklers.
Where roof level sprinklers have a fast RTI (such as ESFR sprinklers), also install sprinklers with a fast RTI below
each mezzanine.
Where roof level sprinklers have a fast RTI (such as ESFR sprinklers) but standard RTI sprinklers have been
installed below the mezzanines, provide a draft curtain at least 0.6 m (2 ft.) deep around the perimeter of the
mezzanines.
See Appendix B for further information regarding sprinkler response time index (RTI).
Conclusion
Elevated walkways in storage have become common place. Unless the selected sprinkler design for the
specific walkway and storage configuration is proven by full-scale fire test:
• Provide automatic sprinklers below each mezzanine using a design suitable for the storage below
References
Risktopic. Zurich Recognized Solutions for Property risks. Zurich, Switzerland: Zurich Insurance Group Ltd.,
2016. Web. Web accessed 20170228.
http://www.zurichservices.com/zsc/reel.nsf/9f359b3938a6bdd448257a4f001c4596/72e45b8bedeaf19dc1257
ffc002df342/$FILE/rf_RecognizedSolutions_Property.pdf
LPC Rules for Automatic Sprinkler Installations Incorporating BS EN 12845. United Kingdom: Fire Protection
Association (FPA), 2015. Print
CEA 4001en. Sprinkler Systems: Planning and Installation. Brussels: European insurance and reinsurance
federation, 2009. Web. Web site accessed 20140306. http://www.denikoo.com/wp-
content/themes/GoMag/doc/zakoni/CEA%204001%20-%201237304692_cea4001s.pdf
NFPA 13. Standard for the Installation of Sprinkler Systems. Quincy, MA; NFPA, 2016. Online.
Klaus, Matthew J. Automatic Sprinkler Systems Handbook. Quincy, MA: National Fire Protection Association,
2016.
Richards, Gwynne. Warehouse Management: A Complete Guide to Improving Efficiency and Minimizing
Costs in the Modern Warehouse. London: Kogan Page, 2011. Print.
7
Appendix A
This appendix captures definitions for terms used in this document. Most definitions are based upon guidance
from the Zurich Property Protection Principles listed in the following table.
NFPA 13 NFPA 13. Standard for the Installation of Sprinkler Systems. Quincy, MA;
NFPA, 2016.2
The following table summarizes storage configurations likely to be found in pick modules addressed by this
document. The table offers a comparison of storage designations and descriptions as found in the LPC Rules
(specifically technical bulletin TB234) and NFPA 13.
Note: This configuration consists of shelves without vertical bulkheads. This configuration is similar to
ST4 (a rack) due to its depth; however, this configuration includes shelves that introduce a need for in-
rack sprinklers.
Note: This configuration is only addressed in NFPA 13. Protection guidance is based upon full-scale fire
tests.
8
Back-to-back shelf storage
“Back-to-back shelf storage” is a term defined in NFPA 13 term. It is a storage configuration that is formed by
two shelves separated by a vertical, longitudinal bulkhead.
The shelf on either side of the vertical, longitudinal bulkhead is limited to a depth of 760 mm (30 in.). This
means the overall depth of the back-to-back shelf storage system is not to exceed 1,520 mm (60 in.).
Guidance for back-to-back shelf storage was based upon full-scale fire tests.
Bin box
“Bin box storage” is a term defined in NFPA 13. See “shelf storage with vertical bulkheads”.
Flues
The typical double-row rack configuration includes longitudinal and transverse flues as shown in the following
figure.
Longitudinal and transverse flues in racks (Image source: Rich Gallagher, The Zurich Services Corporation)
Flues are nominally 150 mm (6 in.) wide, and transverse flues normally occur at 1.2 to 1.5 m (4 to 5 ft.)
intervals along the length of a rack.
“Nominally 150 mm (6 in.)” means the flue is at least 75 mm (3 in.) wide. This width may be formed due to
the non-uniform alignment of flues vertically from tier-to-tier, or it may be formed due to the careful
placement of goods (e.g. the case of an automatic storage and retrieval system).
In multiple-row racks, longitudinal flues are not required; however, where they are provided, they are to be
nominally 150 mm (6 in.) wide. This nominal width is needed to allow the fire plume to grow vertically (rather
than horizontally) and to allow water from sprinklers to penetrate down into the rack.
Rack
A rack is a structure used to support goods.
A rack may consist of an open frame used to support pallet loads of goods. The pallet loads are placed in an
organized manner to maintain longitudinal and transverse flues. See “flues” for further information on
longitudinal and transverse flues
A rack may include shelves to provide support to goods stored with or without a pallet.
9
Many full-scale fire tests are based upon goods on pallets stored in double-row, open-frame racks with open
aisles at least 1.2 m (4 ft.) wide. The following photo is an example of a rack storage fire test array.
Shelf storage
This is a term used in BS EN 12845 and NFPA 13.
Within the scope of BS EN 12845, shelves may have any depth. In TB 234, shelf depths not exceeding 0.8 m
(30 in.) are designated ST15, and in-rack sprinklers are only recommended. Where shelf depth exceeds 0.8 m
(30 in.), the storage system is designated ST16, and in-rack sprinklers are required.
Within the scope of NFPA 13, shelf storage is limited to shelves with a depth of 0.8 m (30 in.). Where shelves
are wider, the storage system becomes a rack.
Example of shelf storage (Image source: Rich Gallagher, The Zurich Services Corporation)
This storage system uses solid shelves; however, in addition, longitudinal and transverse bulkheads are also
provided. This configuration provides 5-sided compartments where goods are stored. The open side faces an
aisle.
10
NFPA 13 defines bin boxes as being made of metal, wood, or cardboard. Zurich interprets this to mean all five
sides of the storage system is to be made of the same material. For example, if the compartments are made of
cardboard, the shelves are to be made of cardboard. Applying this interpretation means the compartments
will often be formed entirely of metal or they will be treated as shelf storage.
BS EN 12845 requires bulkhead material to meet the requirements of Euroclass A1 or A2. This essentially
means the bulkheads are to be noncombustible.
This storage configuration may be desirable as it tends to direct a fire out to the aisle of the storage system
before a fire can spread horizontally or vertically. This tends to allow sprinklers to control a fire to a more
limited volume.
Shelves
Shelves may be provided to support goods in place of pallets.
Whether a shelf is solid, slatted, or open grate, storage may be placed across the entire shelf area. As such,
any shelf should be treated as a solid shelf unless controls are provided to maintain longitudinal and
transverse flues.
Example of solid shelves (Image source: Rich Gallagher, The Zurich Services Corporation)
11
Example of a slatted shelf (Photo source: Stuart Lloyd, Zurich Risk Engineering)
Example of an open grate shelf (Photo source: Rich Gallagher, The Zurich Services Corporation)
12
Appendix B
Response time index, or RTI, is a measure of the thermal sensitivity of a sprinkler’s fusible element.
Sprinklers are typically rated as fast response or standard response. As explained in the NFPA’s Automatic
Sprinkler Systems Handbook (2016), fast response sprinklers have an RTI of 50 (meter-second) 1/2 or less
while standard response sprinklers have an RTI of 80 (meter-second) 1/2 or more.
The fast response sprinkler, whether of the quartzoid bulb or fuse link type, will have a fusible element of
lower mass compared to a similar standard response fusible element. The lower mass promotes faster
operation in response to heat.
For any given set of conditions, the fast response sprinkler is expected to operate sooner than the standard
response sprinkler.
Two quartzoid bulb-type sprinklers, fast response on left and standard response on right
(Photo source: Rich Gallagher, The Zurich Services Corporation)
Two fuse link-type sprinklers, fast response on left and standard response on right
(Photo source: Rich Gallagher, The Zurich Services Corporation)
13
Zurich Insurance Company Ltd
Mythenquai 2, CH-8002 Zurich – Switzerland
www.zurich.com
The information contained in this document has been compiled and obtained from sources believed to be reliable and
credible but no representation or warranty, express or implied, is made by Zurich Insurance Company Ltd or any of its
subsidiaries (hereinafter ‘Zurich’) as to their accuracy or completeness.
Some of the information contained herein may be time sensitive. Thus, you should consult the most recent referenced
material.
Information in this document relates to risk engineering / risk services and is intended as a general description of certain types
of services available to qualified customers. It is not intended as, and does not give, an overview of insurance coverages,
services or programs and it does not revise or amend any existing insurance contract, offer, quote or other documentation.
Zurich and its employees do not assume any liability of any kind whatsoever, resulting from the use, or reliance upon any
information, material or procedure contained herein. Zurich and its employees do not guarantee particular outcomes and
there may be conditions on your premises or within your organization which may not be apparent to us. You are in the best
position to understand your business and your organization and to take steps to minimize risk, and we wish to assist you by
providing the information and tools to assess your changing risk environment.
rt_Storage_ElevatedWalkways
In the United States of America, risk services are available to qualified customers through Zurich Services Corporation and in
Canada through Zurich Risk Services as also in other countries worldwide, risk engineering services are provided by different
legal entities affiliated with the Zurich Insurance Company Ltd as per the respective country authorization and licensing
requirements.