This space is designed for 20 occupants, yet the Toblerone trunking along with the

island benches is designed for 24 occupants.


C-033 Toblerone trunking along the perimeter benches need updating in line with MM
design.
C-033 AV equipment are shown in the Revit model which the codebook
does not specify any.
MM has not allowed for any data and power outlets for AV equipment.
C-033 4 twin sockets are used to feed equipment on the east wall

C-031 Toblerone trunking along the perimeter benches need updating in line with MM
design.
C-031 Some clashes in Toblerone trunking along the perimeter benches
C-031 only two twin sockets are used behind the perimeter cupboards/benches ( for
freezers and fridges in the west wall)
C-031 no flat panel displays shown in the model as specified in AV solution K. MM
has not allowed for any power and data outlets accordingly

C-030 4 twin socket has been placed on the east wall to feed freezers
and fridges. No socket used for cupboards of other walls.

C-032 Sockets and data points clash with FF&E equipment


C-032 AV equipment are shown in the Revit model while the codebook
does not specify any.
MM has not allowed for any data and power outlets for AV equipment as per
codebook/RDS.

C-023 The room is designed for 18 occupants while the occupancy


number prescribed in the codebook is 16
C-023 MM allowed for sockets and data points for the two additional occupants from
general outlets specified in the codebook.
C-023 Toblerone trunking along the island benches need
updating in line with MM design.
C-023 AV equipment are shown in the Revit model while the codebook
does not specify any.
MM has not allowed for any data and power outlets for AV equipment as per
codebook/RDS.

c-026 Toblerone trunking is required to replace Dador trunking


for the two desks.

C-021 only one motorised panel is shown in the model while the codebook
specifies 2. MM included power requirements for two panels.
C-021 only one projector is shown in the model while the codebook
specifies 2. MM included power requirements for two projectors as per
the codebook.

C-414-1-F,C-414-1-A,C-414-1-C-414-1-B,C-414-1-E ,C-414-1-D AV type G is specified


in the codebook. However, no AV equipment
are shown. MM has not allowed for any power and data outlets
for AV equipment.

c-314 The codebook does not show any data and power sockets for this
space. MM included the same type and quantities as in room C-313.

Telec Rooms RDS/Codebook does not allow for any universal sockets and data points.
MM recommends including three twins and 3 data points per space.

Labs it's challenging to establish the power requirements of all pieces of


equipment in
perimeter benches ( washing machines, fridges etc.). Architects to
advise the exact location of these in each space along with associated data sheets
to ensure the correct type of power supplies are specified.