Вы находитесь на странице: 1из 13

ARTICLE IN PRESS

Energy 32 (2007) 2038–2050


www.elsevier.com/locate/energy

Exergetic comparison of efficiency indicators


for combined heat and power (CHP)
Ivar S. Ertesvåg
Department of Energy and Process Engineering, Norwegian University of Science and Technology, NO-7491 Trondheim, Norway
Received 15 December 2006

Abstract

Legislative regulations in favor of combined heat and power (CHP) production have been implemented in many countries. Although
these regulations put different emphasis on power production vs. process heat production, they are based on energy quantities and not on
exergy. In order to analyze and compare the exergetic consequences of the various legislations, a relative avoided irreversibility (RAI) is
defined. This can be regarded as the exergy loss that is avoided when reference plants with separate production are replaced by an actual
CHP plant. Some series of industrial and district heating CHP plants, under varying operational conditions, are used as test cases. It is
seen that some, but not all, CHP cases are exergetically beneficial to separate generation. Comparison with the RAI allows a quantitative
assessment of the various performance indicators. It is seen that exergetic improvements were only captured to a limited degree
by the various energy-based efficiency indicators. Some legislatively defined indicators even appear to discourage thermodynamic
improvements.
r 2007 Elsevier Ltd. All rights reserved.

Keywords: Exergy; Cogeneration; CHP; Legislation; Efficiency

1. Introduction comparison with other plants. However, efficiencies


compare the actual ‘‘useful output’’ to the ‘‘input’’, without
Cogeneration or combined heat and power (CHP) is considering alternative systems that can provide the same
sometimes regarded as the materialization of the second services. This ratio often has a certain maximum within the
law of thermodynamics. First, electricity is produced from range of operation, which does not necessarily comply with
the high-exergy heat, and second, thermal energy is the required amounts of delivery. In certain cases a plant
produced from heat at lower temperatures. On a first law may then be supplemented by separate production. Thus,
basis, CHPs provide a substantially higher efficiency than the optimum for the specific plant may not coincide with
plants for separate electricity generation. This aspect is the optimum for the total system of energy production and
readily taken by public media and politicians. Several use, and vice versa. Therefore, some of the indicators
countries have implemented legislation promoting CHP, include comparison with reference systems, i.e. plants for
with the requirement to define and set performance limits separate production of heat and electricity.
for these energy systems. The objective of this study was to develop a procedure
The increasing number of national definitions shows for quantitative comparison of different CHP systems
considerable differences in how to evaluate CHP perfor- based on first and second law considerations that is also
mance. A common feature, though, is that they are based related to separate production of the same amounts of
on the first law only. A second law efficiency can be used electricity and heat. In the following, a number of
to measure the performance of a plant and make a performance indicators for CHP, including the exergy
efficiency, are briefly reviewed. Several of these are
Tel.: +47 73 593839; fax: +47 73 593580. discussed and compared for a series of industrial CHP
E-mail address: Ivar.S.Ertesvag@ntnu.no cases in [1,2]. These studies gave qualitative relations

0360-5442/$ - see front matter r 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.energy.2007.05.005
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2039

between the indicators. The present study also aims at energy to the exergy of the input:
giving a quantitative comparison of such indicators.
c ¼ ðW þ E Q Þ=E F . (2)
One finding in [1,2] was that all indicators, except
the exergy efficiency, favored delivery of low-temperature Here, EQ and EF are, respectively, the exergy of the
steam to high-temperature steam. However, only a delivered thermal energy and the input exergy, while the
few indicators credited the thermodynamically better exergy of electricity or mechanical energy is equal to its
utilization of a combined gas-turbine/steam-turbine energy W.
system to a boiler/steam-turbine system. Some of the In most systems, the thermal energy is delivered by a
indicators are widely known and presented in textbooks, heating medium, e.g. steam, hot water, air, or hot oil. The
while others are unique to certain national or regional heat Q is then the enthalpy difference between the delivered
legislation. and the returned medium (or fresh medium when it is not
Next, in Section 3 a procedure for quantitative exergetic circulated). The exergy EQ is the corresponding difference
comparison of heat and electricity production is outlined. in thermomechanical exergy of the medium. The ratio of
This includes both the first and second laws and these two quantities,
comparison with the alternatives. For high-temperature
aQ ¼ E Q =Q, (3)
heat delivery, a separate boiler is the most relevant
alternative. However, for low-temperature heat delivery can be regarded as a ‘‘measure of the quality’’ of the
such as district heating, a heat pump will be a more delivered thermal energy.
relevant alternative. When a reference exergy-to-heat ratio
is defined, both high-temperature and low-temperature 2.2. Combined and separate production
heat can be included in the comparison.
This method can give a quantitative comparison and Heat and electricity are usually produced separately.
assessment of the different CHP systems. On this basis, the Heat, with steam or water as carrier, is produced in boilers
various concepts for CHP evaluation can also be compared near the site of use. Electricity is often produced in large,
and the exergetic consequences of the various legislations centralized power plants. Alternatively, heat can be
can be discussed. In Section 4, some test cases are specified. produced from a heat pump. Three schemes for providing
These are realistic cases for industrial and district heating, the same amounts of electricity and heat are sketched in
and will be used for the exergetic comparison and Fig. 1.
assessment of the different indicators found in various For the purposes of analysis and comparison, it is
legislations and the literature. Data from the test cases are convenient to define reference plants for separate produc-
used in Section 5 to evaluate each of the performance tion. The electric and heat efficiencies for the reference
indicators. plants are denoted Zel,ref and ZQ,ref, respectively. The
reference amounts of fuel energy can then be defined
2. Comparison of systems for production of heat and Hel,ref ¼ W/Zel,ref and HQ,ref ¼ Q/ZQ,ref, and the sum
electricity Href ¼ Hel,ref+HQ,ref is the total reference fuel energy.

2.1. Efficiencies defined for heat and power


W
H CHP plant
The ratio of delivered usable energy to the energy input
Q
is called the total energy efficiency. For a system producing
heat and electricity this can be expressed by

Ztot ¼ ðW þ QÞ=H ¼ Zel þ ZQ . (1) Href Hel,ref


Power plant W
Here, W is the mechanical work or electricity produced, Q
the thermal energy in delivered steam or other medium,
HQ,ref
and H the input energy, usually the LHV of the fuel. For Boiler Q
specific use, the quantities of ‘‘heat’’ (usually an enthalpy
difference) and electricity (or work) have to be defined
precisely, cf. [2]. The ratios Zel ¼ W/H and ZQ ¼ Q/H are,
Hel,ref + HHP,ref
respectively, called electric efficiency and heat efficiency. W
These ratios are useful when evaluating the different Power
plant
methods of qualifying CHP and apply to separate WHP Heat
production as well. pump Q
The exergy efficiency can be defined to describe the
quality difference between electricity and heat. This is the Fig. 1. Three schemes for production of the same amounts of electricity
ratio of exergy in the products electricity and thermal (W) and heat (Q). The input amounts of fuel energy (H) are different.
ARTICLE IN PRESS
2040 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

These are the amounts required to produce the same Here, the quantity added to the electric energy in the
electricity and heat separately in the reference plants. The numerator is the electric energy generated in a reference
ratio of the actual fuel energy to the reference fuel energy is power plant consuming the reference fuel for heat, HQ,ref.
then expressed as The efficiency can be rewritten as ZBrz ¼ Zel,refHref/H.
Hence, the ‘‘output’’ here is the electricity produced when
H=H ref ¼ ðZel =Zel;ref þ ZQ =ZQ;ref Þ1 . (4) the total reference fuel is used in a reference electric plant.
The reference electric efficiency, Zel,ref, becomes the
The values of the reference efficiencies can be determined
reference for the Brazil efficiency, ZBrz, as well.
based on the notion of best available technology (BAT) or
The US and Brazil efficiencies are sometimes presented
based on an average of existing installations. In legislative
as simplified exergy efficiencies, without really taking
regulations, the choice of reference values may be based on
into account the actual exergy content of the heat. Feng
a compromise between existing installations and BAT. As
et al. [8] suggested an adjusted exergy efficiency with the
the choice will affect the regarded goodness of any CHP
definition
plant, it is quite often an outcome of intense lobbying by
the involved parties. Zadex ¼ ðW þ E Q þ xðQ  E Q ÞÞ=H, (10)
When the heat is produced from a heat pump, the
electric energy required for it is denoted WHP and where x ¼ 0.12 is an adjusted exergy factor.
the delivered exergy is expressed as EQ ¼ aQQ (Eq. (3)). A seemingly different parameter for CHP has been
The exergy efficiency of a heat pump can then be defined as established in the UK, the quality index (QI) [9]:

cHP ¼ E Q =W HP ¼ aQ Q=W HP . (5) QI ¼ X Zel þ Y ZQ ¼ X ðZel þ ðY =X ÞZQ Þ. (11)


Here, X is a coefficient related to alternative electricity
The coefficient of performance can then be expressed as
supply options, and Y is a coefficient for heat generation
COP ¼ Q=W HP ¼ cHP =aQ . (6) related to alternative heat supply options. The values of X
and Y vary for different sizes and types of scheme. For
The COP will depend on the temperature levels, while the natural-gas based CHP, Y equals 114 while X varies from
exergy efficiency will show less variation. The definition of 200 to 168 depending on the (increasing) size of the electric
a reference heat pump will be discussed below. power. From Eq. (11) it is readily seen that the quantity
QI/X can be regarded as an efficiency similar to the
2.3. Energy-based efficiencies of heat and electricity PURPA efficiency, Eq. (8), only with a different weighting
production factor for heat.

Thermodynamically, technically and economically, elec- 2.4. Energy and emissions savings indicators
tric energy differs from thermal energy. Several parameters
have been defined to account for this difference. The efficiencies reviewed above are, basically, ratios of
While electricity generation can be conducted nearly some desirable output to some input. Other indicators may
anywhere, heat has to be produced near the user, and it has focus on the savings of energy or emissions in comparison
to be scaled according to the local consumption. Thus, it with the separate generation in reference plants. The
may be useful to regard a CHP as a heat generator with primary energy savings (PES) [1–3] can be written as
surplus electricity generation. This is expressed by defining PES ¼ HrefH. This is the fuel energy that is saved when
an equivalent electrical efficiency (EEE) [3] as using the CHP instead of separate generation. This
EEE ¼ Zeel ¼ W =ðH  Q=ZQ;ref Þ. (7) quantity divided by the reference fuel is the relative
primary energy savings, RPES:
Here, the fuel energy to the CHP plant is supposed to be
reduced by the fuel needed to produce the heat in a RPES ¼ 1  H=H ref ¼ 1  H=ðW =Zel;ref  Q=ZQ;ref Þ.
separate boiler with efficiency ZQ,ref. Hence, the remaining (12)
fuel Heel ¼ HHQ,ref is regarded as the input to electricity
generation and Zel,ref becomes the reference for Zeel. In the This is used as an indicator for the goodness of CHP
legislation of Spain [4] and (with a slight modification) systems in the Flemish legislation (Belgium) [10], in Italy
Portugal [5], this concept is used (cf. [1,2]). and France [11], and also included in the EU Directive on
In the efficiency defined by the US legislation PURPA CHP [12].
[6], a fraction of the heat is added to the work in the If the saved energy is attributed to electricity generation,
numerator: it can be expressed as the fuel-free electricity. As in the
EEE, Eq. (7), heat is attributed to the reference amount of
ZUS ¼ ðW þ 0:5QÞ=H ¼ Zel þ 0:5ZQ . (8) fuel for heat. Then the remaining part of the fuel actually
An efficiency close to this is used in Brazil [7]: used is attributed to electricity generation in a reference
power plant to generate some of the electricity. The rest of
ZBrz ¼ ðW þ Zel;ref Q=ZQ;ref Þ=H. (9) the generated electricity is then called fuel-free electricity,
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2041

which can be expressed as expressed as [1,2,10]


W free ¼ RPESðZel;ref H ref Þ ¼ PESZel;ref . (13) ðgQ Q  gF HÞ
RCES ¼ 1 þ . (17)
gel W
This indicator is used in the legislation of the Netherlands
[10]. When the emission factors are equal for fuel to both the
A different approach is followed in the Danish legisla- actual and the reference plants, they cancel from this
tion [13]. There, only a part of the fuel LHV used in the expression. As in the Brussels region, this is the case for
CHP is taxed: natural-gas fired CHPs in the Walloon. Then, it is
  convenient to re-express the RCES as
Q W
H tax ¼ min ; H . (14) RCES ¼ PES=ðW =Zel;ref Þ
1:25 0:65
¼ RPESðZel;ref =Zel ÞH ref =H. ð18Þ
For comparison with other indicators, this can be
expressed as the nontaxed fraction of the fuel energy: For comparison, it can also be noted that this indicator is
related to the EEE of Eq. (7) by (1RCES) ¼ Zel,ref/Zeel.
H notax H tax Z Z 
Q All these indicators are based on energy considerations.
¼1 ¼ 1  min ; 1  el
H H 1:25 0:65 At first sight the RPES, for example, seems to represent the
 ZQ Zel  mass of fuel and thus the energy and the exergy of the fuel
¼ max 1  ; . ð15Þ
1:25 0:65 as well. However, when the ‘‘saved’’ energy is evaluated, all
forms of usable energy are accounted for equally. That is,
Alternatively, it can be expressed as a fraction of the
electric energy, fuel energy, and thermal energy in medium-
reference amount of fuel energy for separate electricity
pressure (MP) and low-pressure (LP) steam are considered
production, Hel,ref. That is, multiply Eq. (15) by (Zel,ref/Zel).
equivalent. Similarly, the avoided emissions in Eqs. (16)
The notion behind this concept is that fuel for heating
and (17) are weighted on the basis of energy. From a
should be taxed, while fuel for electricity is not. However,
thermodynamic consideration, a system delivering an
there is a high tax on electricity when it is consumed. The
amount of heat in LP steam has higher losses than a
Danish policy also includes a ban on the use of electricity
system delivering heat in MP steam at a higher tempera-
for heating and extensive promotion of CHP for district
ture. And actually, the system has a lower first law capacity
heating. In the present context, it is interesting to note that
when producing MP steam.
the high tax also applies to electricity used in heat pumps
but not to mechanical work directly transferred to heat
pumps [14]. 3. Comparison of CHP based on exergy
When certain amounts of emissions are assigned to the
fuel of the actual plant and of the reference plants, 3.1. Relative avoided irreversibility (RAI)
indicators of emissions savings can be defined. Such
indicators are [1,2,10] the relative CO2 emissions savings As noted above, the energy-based efficiencies and
(RCES) of the Walloon and Brussels-region legislation. indicators do not consider the thermodynamic value of
In the Brussels region, the emission savings are taken heat. On the other hand, the exergy efficiency is determined
relative to the emissions of the reference plants for both only on the basis of the specific plant and does not take
heat and electricity generation. Thus, the Brussels RCES is alternatives into account. A combination of the notions
expressed as [10] behind the exergy efficiency and the energy savings (PES,
RPES) will be outlined in the following.
gF H The exergy loss (irreversibility) of a certain case can be
RCES ¼ 1  . (16)
ðgel W þ gQ QÞ expressed as (1c)Ein, where c is the exergy efficiency, that
is, the ratio of usable exergy output to exergy input, and Ein
Here, gF is the CO2 emission per unit of fuel energy,
is the exergy input (usually the fuel exergy).
while gQ and gel are the CO2 emission per unit of heat and
A case or process can be compared to a specified
electric energy, respectively. This is supposed to include
reference case. The irreversibility that is avoided by
emissions during transportation, preparation, handling,
replacing the reference case by the actual case will be
and combustion. If the fuels for the actual CHP plant and
the reference plants have the same emissions, i.e. gQ ¼ gF/ ð1  cref ÞE in;ref  ð1  cÞE in , (19)
ZQ,ref and gel ¼ gF/Zel,ref, the factor gF cancels from Eq. (16) where the subscript ‘‘ref’’ denotes a reference case. The
and the Brussels RCES becomes equal to the RPES above. term ‘‘avoided’’ presumes that the case is an improvement
This is the case for natural-gas fired plants. However, if from the reference case. However, the quantity will be
desired, different emission factors can be used for the negative if the utilization is worsened. The term can be
actual and reference plants. made dimensionless by the input to the reference case, and
In the Walloon region, the CO2 emission savings the RAI is expressed as
are taken relative to the emissions of the reference
electricity generation. Thus, the Walloon RCES is RAI ¼ ð1  cref Þ  ð1  cÞE in =E in;ref . (20)
ARTICLE IN PRESS
2042 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

In a general notion, this quantity can be regarded as the Here, the reference is separate generation of the same
irreversibility of the specific case or system, subtracted amount of heat at the specified exergy-to-heat ratio and
from the irreversibility that would have been there if the with a specified heat efficiency. For cases with an actual aQ,
case or system was not applied. this approach will give a reference amount of fuel
The exergy-weighted relative avoided carbon emissions exergy:
(RACE) can be expressed similar to Eq. (16), although on
aQ Q aF aQ Q
an exergy basis, E F;Q;ref;B ¼ ¼ . (24)
cQ;ref;B aQ;ref ZQ;ref
gEF E F
RACE ¼ 1  . (21) Now, the reference amounts of fuel exergy for separate heat
ðgel W þ gEQ E Q Þ
and electricity production are defined, and the reference
Here, gEF and gEQ are the CO2 emission per unit of fuel efficiency can be expressed:
exergy and per unit of exergy in heat, respectively. To
account for CO2 neutral fuels, e.g. sustainably produced W þ EQ
cref ¼
biomass, this expression has to be modified. One possibility is E F;el;ref þ E F;Q;ref;B
to add the emissions from reference plants fired by fossil fuel. Zel þ aQ ZQ
The expression will then account for both the substitution of ¼ . ð25Þ
aF ðZel =Zel;ref þ aQ ZQ =ðaQ;ref ZQ;ref ÞÞ
fossil fuels and for the benefit of cogeneration.
Here, the expressions in Eqs. (3), (22) and (24) are used
3.2. Exergy-based definition of reference plants for separate together with the definitions of electric and heat efficiencies
production (Section 2.1). This procedure allows a comparison of
different systems and recognizes the quality of the thermal
The reference plants defined as referred in Section 2.2 do energy. The ratio of actual fuel exergy input to the reference
not recognize the exergetic value or ‘‘quality’’ of thermal input is
energy. The reference amount of fuel for separate heat
E F =E F;ref ¼ ðZel =Zel;ref þ aQ ZQ =ðaQ;ref ZQ;ref ÞÞ1 . (26)
generation is taken as the same value regardless of the
temperature of the steam (or other heating media: water, The expressions in Eqs. (25) and (26) can alternatively
oil, air, etc.). It can be argued that a conventional boiler be developed from an approach defining a reference heat
has about the same efficiency for HP steam and LP steam, pump for the heat production. When the heat Q with
and even for hot water. Actually, this efficiency is exergy EQ ¼ aQQ is provided by a heat pump, an amount of
determined more by the state of the effluent flue gas than work WHP is required. These quantities can be related
by the state of the heating medium. However, it can be by the exergy efficiency of the heat pump, Eq. (5).
observed that for a CHP producing LP steam, the Furthermore, the heat-pump work can be assumed to be
electricity generation is relatively lower than for a similar generated in a reference power plant as described above.
CHP producing MP or HP steam. Hence, the amount of fuel for separate generation of heat
Low-temperature thermal energy can be produced by varies with the exergy of the steam (or other heating
heat pumps. A system of separate electricity generation and medium). It also depends on the exergy efficiency of the heat
a heat pump can supply an amount of heat that is larger pump.
than the fuel LHV used. Thus, for a proper exergetic If the heat is provided by a reference heat pump
comparison, the reference heat efficiency has to depend on (subscript ‘‘HP’’) using electricity (or work) from a
the exergy of the heat. This corresponds to defining a reference plant for separate power generation, the heat-
reference heat-pump exergy efficiency. generation exergy efficiency for the combined system of
Similar to energy above, the reference fuel exergy for power plant and heat pump is expressed as
separate electricity generation can be expressed:
aQ Q Z c
E F;el;ref ¼ aF H el;ref ¼ aF W =Zel;ref , (22) cQ;ref;HP ¼ ¼ el;ref HP;ref . (27)
aF ðW HP;ref =Zel;ref Þ aF
where aF is a constant, usually close to unity (e.g. 1.04 for
The reference fuel exergy for separate production of heat at
natural gas at standard state).
exergy-to-heat ratio aQ in the heat-pump approach can be
To determine the reference fuel exergy for heat genera-
expressed as
tion, two alternative approaches can be followed: (1) specify
a reference exergy-to-heat ratio, aQ,ref (cf. Eq. (3)) for heat aF W HP;ref aF aQ Q
generation, or (2) specify a reference exergy efficiency or a E F;Q;ref;HP ¼ ¼ . (28)
Zel;ref Zel;ref cHP;ref
heat pump providing the heat. In the first approach, the
reference exergy efficiency for separate heat generation in a This approach can be joined with the boiler approach
boiler (subscript ‘‘B’’) can be expressed as above by setting the efficiencies of Eqs. (23) and (27)
equal. This implies that aQ,ref ZQ,ref ¼ Zel,refcHP,ref and that
aQ;ref Q aQ;ref ZQ;ref
cQ;ref;B ¼ ¼ . (23) the expressions of EF,Q,ref from Eqs. (24) and (28) become
aF Q=ZQ;ref aF equal.
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2043

The heat-pump approach also leads to an expression for increases from 40 to 100 tonnes per hour (t/h) with the
the coefficient of performance (Eq. (6)) of a heat pump nominal load at 70 t/h. Both configurations are considered
with the reference exergy efficiency, cHP,ref: with LP and MP steam delivery. The LP steam is delivered
at a state of 2.5 bar and 140 1C, while the MP steam is
COPref ¼ Q=W HP;ref ¼ cHP;ref =aQ
delivered at 21 bar and 330 1C. The ambient state is 1 bar
¼ ðZQ;ref aQ;ref =Zel;ref Þ=aQ . ð29Þ and 11 1C, which is assumed both for air and for make-up
and cooling water. The ‘‘heat’’ is calculated as the enthalpy
The lower the temperature level of the delivered heat, the
difference between delivered steam and the mixture of
higher the reference COP will be. Yet this will have the
return and make-up water. The associated exergy is the
same exergetic performance. It is readily seen that for a
corresponding difference in thermomechanical exergy. The
heating medium with aQ ¼ aQ,ref, the fuel-exergy ratio of
exergy-to-energy ratio aQ of the delivered thermal energy is
Eq. (26) is equal to the fuel-energy ratio of Eq. (4). The
0.28 for LP steam and 0.39 for MP steam.
reference exergy-to-heat ratio, aQ,ref, or, alternatively, the
The BST cases selected from [1,2] are operational mode
reference heat-pump exergy efficiency, cHP,ref, has to be
III, here denoted B3-LP and B3-MP. In these series, the
specified. This will be discussed below.
firing is maintained and the condensing ST load is reduced
to increase the steam delivery load. Operational mode III is
4. Test cases of CHP chosen here because it shows a range of variation in electric
and heat efficiencies. It should be noted that the last
4.1. Industrial CHP fired with natural gas case (100 t/h) in each of these series also represents the
operational mode I in [1,2].
Two different configurations for industrial CHP have For the GT/HRSG/ST plant, the cases of operational
been considered, Fig. 2: A boiler with back-pressure steam mode II are selected, denoted GT2-LP and GT2-MP. Here,
turbine (ST, BST plant) and condensing ST, and a plant the nominal steam delivery (70 t/h) was achieved by a
with gas-turbine, flue-gas heat-recovery steam generator nominal GT firing load and no use of condensing ST. This
(HRSG) and condensing ST. These are a selection from the GT load was held constant. Supplementary firing in the
cases studied in [1,2]. The fuel for all cases is natural gas. HRSG was used to increase the steam delivery load from
Within each of the series of cases, the steam delivery load 70 to 100 t/h while load reduction from 70 to 40 t/h was

BPST

HP

OPTIONAL
BOILER CTST
PROCESS
GAS HEAT

BPST

GAS SF
OPTIONAL
CTST
HP LP
PROCESS
HEAT
GT

Fig. 2. Configuration flow sheets of boiler (upper) and gas-turbine with HRSG and supplementary duct firing (SF) (lower) systems, both with back-
pressure steam turbine (BPST), optional condensation tail steam turbine (CTST) and process heat delivery. From [2].
ARTICLE IN PRESS
2044 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

Table 1 Table 2
Cases of industrial CHP, boiler/steam-turbine (B3-) and gas-turbine with Cases of natural-gas fired reciprocating engines, with district heating
HRSG (GT2-) series with low-pressure (LP) and medium-pressure (MP) (aQ ¼ 0.19)
steam delivery
Case RR1 RR2 RR3 RR4 RR5 RR6
Steam delivery load (t/h)
W/H 0.419 0.416 0.397 0.407 0.413 0.450
40 55 70 85 100 Q/H 0.341 0.445 0.531 0.521 0.515 0.450
RAI 0.010 0.049 0.068 0.077 0.083 0.102
B3-LP (aQ ¼ 0.28)
W/H 0.240 0.224 0.207 0.191 0.174 Rolls Royce Marine Diesel, Bergen K-type or Bergen B-type engines, data
Q/H 0.281 0.386 0.491 0.597 0.702 from [15].
RAI 0.336 0.197 0.084 0.010 0.088 Location and installed electric power:
RR1: Vengazi, Latvia, 1  2.3 MWel.
B3-MP (aQ ¼ 0.39) RR2: Verona, Italy, 9  2.2 MWel.
W/H 0.144 0.128 0.111 0.095 0.079
RR3: El Grado, Spain, 8  3.0 MWel.
Q/H 0.319 0.439 0.559 0.678 0.798 RR4: Brønderslev, Denmark, 7  3.1 MWel.
RAI 0.275 0.044 0.120 0.243 0.337 RR5: Leon, Spain, 2  2.75 MWel.
GT2-LP (aQ ¼ 0.28) RR6: Tørring, Denmark, 1  5.1 MWel (B-type).
W/H 0.462 0.449 0.438 0.423 0.409
Q/H 0.241 0.332 0.418 0.452 0.483
RAI 0.098 0.156 0.207 0.213 0.219
4.3. Cases of CHP with district heating
GT2-MP (aQ ¼ 0.39)
W/H 0.410 0.396 0.373 0.351 0.332
Q/H 0.274 0.377 0.464 0.512 0.545 In some countries, particularly Denmark, the legislation
RAI 0.171 0.264 0.320 0.340 0.350 has been designed to promote small-scale CHP for district
heating. This has brought forth a substantial number of
BioB3-LP (aQ ¼ 0.28)
W/H 0.213 0.199 0.184 0.170 0.155 natural-gas fired power-plants in the range 3–30 MW
Q/H 0.250 0.343 0.437 0.530 0.624 electric power, supplying their neighborhood with space
RAI 0.209 0.110 0.026 0.046 0.108 heating. Often, such plants only operate during the heating
BioB3-MP (aQ ¼ 0.39) season. A number of such cases are specified in Table 2.
W/H 0.128 0.114 0.099 0.084 0.070 These data were taken from [15] and the specific cases were
Q/H 0.284 0.390 0.496 0.603 0.709 chosen because both the electric and heat (or total energy)
RAI 0.233 0.036 0.109 0.221 0.310 efficiencies were given. The efficiencies are ratios of long-
From [1,2]. term average energy quantities for plants in operation. The
cases of this series are individual plants, whereas each of
the series described above represent one plant at different
obtained by increasing the steam flow to the condensing loads.
ST. The fuel-energy (LHV) consumption rate was 101 MW The plants in this series (denoted RR) are based on the K
for the BST and from 117 to 147 MW for the GT plant. type (one B type) of natural-gas fired engine from Rolls
As the issue here is to investigate the efficiency indicators, Royce Marine Diesel of Bergen, Norway. We will regard
most details of the plants and simulations will be left these as being representative for a number of existing
out and can be found in [1,2]. The key data are shown in plants. For such plants, the water supply and return
Table 1. temperatures, respectively, are typically 95 and 50 1C. Here,
All these cases are simulated as steady-state steady-flow aQ ¼ 0.19 is assumed, although the value may be lower
cases and the efficiencies are calculated as ratios of rate during parts of the heating season.
quantities.
4.4. Reference plants for separate production
4.2. Industrial CHP fired with biomass
In the present study, the chosen values for the reference
Although gasification and combustion in gas turbines efficiencies of natural-gas fired plants are 0.55 and 0.90,
will be the future, biomass-fired CHP plants today are respectively, for electricity and heat. These values represent
boilers like the BST cases just described. The energy- modern technology. In the legislation referred to, the
conversion efficiency of a biomass-fired boiler is, however, chosen values show some variation. For instance, Dutch,
somewhat lower than for natural gas. The biomass cases French and Flemish legislation prescribe lower reference
evaluated here are taken to be identical to the BST cases heat efficiencies for steam production than for hot water,
above, except that the boiler efficiency is reduced from while in Italy it is lower for industrial heat than for district
90% to 80%. Thus, the actual electric and heat efficiencies heating. This can be regarded as an attempt to account for
are scaled by the factor 80/90. This gives the series denoted the exergy difference. Furthermore, different values are
BioB-LP and BioB-MP. Table 1 also shows key data for used for various fuels. This reflects the fact that coal or
these series. biomass-fired plants have considerably lower electricity
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2045

production compared to natural-gas fired plants, and a 0.40


somewhat lower total energy production as well. Thus, for
the biomass-fired cases here, the reference efficiencies for
heat and electricity are set to 0.40 and 0.80, respectively.
0.20
The effects of these choices will be investigated.
For the reference exergy-to-energy ratio aQ,ref, a value of
0.28 will be adopted. This is the ratio of exergy to enthalpy
differences for instance of steam at 2.5 bar and 140 1C 0.00
(LP steam), a return water temperature of 53 1C, and an

RAI
ambient temperature of 11 1C. In combination with
reference electric and heat efficiencies of 0.55 and 0.90,
respectively, this corresponds to a heat-pump exergy -0.20
efficiency cHP,ref of 0.46. With this choice, the three values
of exergy-to-thermal energy assumed above, aQ ¼ 0.39 B3-LP
(MP steam, 21 bar, 330 1C), aQ ¼ 0.28 (LP steam), and B3-MP
-0.40
aQ ¼ 0.19 (hot water) give COP values of 1.18, 1.64 and GT2-LP
2.4, respectively, for the reference heat pump, Eq. (29). The GT2-MP
first value shows that the heat pump is only of theoretical biB3LP
interest for these cases while the value for LP steam is -0.60
technically achievable. The hot-water COP of 2.4 is a 40 55 70 85 100
reasonable value for space heating in the relevant areas. Steam delivery (t/h)
This indicates that the chosen reference values are reason-
Fig. 3. Relative avoided irreversibility (RAI), Eq. (20), as a function of
able for a quantitative analysis, although this choice of steam delivery load for the five series of cases shown in Table 1.
‘‘quality’’ for the reference is modest.
An alternative choice of aQ,ref ¼ 0.39 (MP steam, 21 bar,
330 1C) corresponds to a reference heat pump exergy
efficiency cHP,ref of 0.64. Even at this level, the reference 5.1. RAI
COP of 1.64 is technically feasible although very demand-
ing. On the other hand, a low-exergy reference, e.g. hot Some of the indicators reviewed above have been
water with aQ,ref ¼ 0.19, would be an alternative with a calculated and presented in [1,2] for ten series of cases.
thermodynamically very modest requirement upon the Fig. 3 shows the RAI, Eq. (20), for five of the BST and GT
reference system. This would mean a reference COP of 1.64 series described above in a graph similar to those for the
for space heating, which is less than that achieved by simple other indicators presented in [2]. The RAI is used as
air-to-air heat pumps. It can be argued that for space the abscissa in the figures below, and the relation between
heating, separate production should give more than 90% of the results and the specified cases can be found from Tables
the LHV. In fact, more than 105% can be achieved by 1 and 2. For all series, the RAI is increasing from left to
using furnaces that condense some of the flue-gas water right, both in the tables and in the figures.
vapor. This figure corresponds to the combination of a From Fig. 3, it is noted that cases with low steam
separate electric plant with 55% efficiency and a heat pump delivery from BST plants have a negative RAI. This means
with COP of 1.91. Hence, also this alternative gives less that the alternative, i.e. separate production, gives a lower
output than the chosen reference. irreversibility than the CHP plant. It is seen that MP steam
Nevertheless, the choice of reference for exergy is to delivery gives a higher RAI than LP steam. It is also
some extent a matter of taste, at least within the technically observed that the GT systems give a higher RAI than the
possible range. One issue is whether a medium-exergy boiler/ST systems with condensing ST. The GT plants
thermal system should be accounted ‘‘positive’’, ‘‘neutral’’, show positive RAI values. The decreasing values towards
or ‘‘negative’’ compared to the reference system. From a the low steam delivery load are due to the increasing use of
pedagogical viewpoint, it is preferred to have both steam in the condensing ST. Furthermore, it is seen that
‘‘negative’’ and ‘‘positive’’ categories, as the choice made MP steam delivery gave higher RAI than LP steam, and
here implies. that the GT systems gave higher RAI than the BST
systems.
5. Results and discussion One may keep in mind that separate boilers have lower
irreversibilities with MP steam delivery than with LP-steam
This section will give a quantitative exergetic evaluation delivery, while the energy efficiencies are similar. On the
of the various indicators for CHP. Here one should keep in other hand, MP-steam delivery CHP systems typically have
mind that all indicators are defined or chosen with the a lower electricity-to-heat ratio, W/Q. As heat production
purpose of promoting CHP. Moreover, thermodynamics is has a higher irreversibility than electricity production, the
more or less an underlying motivation for promoting CHP. shift towards more heat gives a larger specific irreversibility
ARTICLE IN PRESS
2046 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

(1cref) for separate generation in MP systems compared higher electricity production. The possible benefits of these
to LP systems. In spite of this, the avoided irreversibility CHP plants will depend on other factors, such as the losses
(RAI) for combined production with MP steam is larger due to the transport of fuel, district heating water and
than for the corresponding LP-steam delivery system electricity. It should also be noted that for space heating,
(cf. Table 1). Apparently, the beneficial effect of combined heat pumps available on the market are more efficient than
production is stronger for MP than for LP steam delivery. the reference heat pumps chosen here.
A notable result is the series B3-MP, where the last cases Figs. 5 and 6 show the other indicators as functions of
have high RAI values. The reason for this is that the the RAI for the six investigated series. In particular, two
electricity is produced in HP to MP expansion turbine only. aspects are interesting to look for. The first is the change
The efficiency of this marginal electric production is from one case to the next within a series. When the change
considerably higher than for separate production. On the represents an increase in RAI, the issue is whether and to
other hand, it requires that the amount of electric energy is which degree this improvement is captured and made
much lower than the amount of thermal energy produced. visible by the indicator in question. The second is the
The variation with choices of reference plants are shown relative evaluation between the different series, i.e. between
in Fig. 4 for the series B3-LP. The legend shows (in %) the the different technologies and between different steam-
values of the reference electric efficiency (55%, 45%), the delivery conditions. When a series has higher RAI values
reference heat efficiency (90%, 80%), and the reference than another, the issue is whether and to which degree this
exergy-to-heat ratio (32%, 28%, 24%). The main effect of better performance is shown by the investigated indicator.
a lower reference electric or heat efficiency is to shift the The biomass-fired series BioB3-MP is not shown in the
RAI to a higher value. It is seen that changing the reference figures. The results from this series are related to the
exergy-to-heat ratio has an effect similar to changing the corresponding natural-gas fired series B3-MP very much in
reference heat efficiency. the same way as the series BioB3-LP is related to B3-LP.
The RAI of the gas engines (RR series) are shown in
Table 2. The cases of this series are arranged in the 5.2. Exergy efficiency
sequence of increasing RAI. The relatively modest RAI
values indicate that the benefits of CHP for district heating As the RAI is based on the exergy efficiency, Fig. 5(a)
compared to use of heat pumps with electricity from essentially shows a comparison of the actual plant with the
separate power plants are fairly small, if present at all. The reference separate production. Here we see that within each
reason for this is that the low exergy-to-energy ratio of series, a higher RAI usually corresponds to higher exergy
district heating is not sufficiently compensated by the efficiency. This is in particular seen when comparing the low
steam load cases (far left in the graph) of the BST and GT
plants. However, a general observation is that the two
0.40 indicators may give different guidance. A high level of exergy
efficiency does not necessarily correspond to a high RAI.
One interesting result is seen for the GT plants.
Although the RAI is increasing, the exergy efficiency is
0.20
reduced for the cases to the right. In these cases, the steam
delivery load is increased by supplementary duct firing.
Compared with the nominal load with no duct firing, this
0.00 has a higher irreversibility per unit of fuel. However,
compared to separate production of the additional heat
and electricity, the steam production by supplementary
RAI

firing is beneficial.
-0.20 When a larger fraction of the produced steam is used for
55/90/28
condensing ST, the irreversibilities associated with its use
55/80/28
are moved from the outside to the inside of the system
45/90/28 boundaries. However, while the exergy efficiency is
-0.40 45/80/28 marginally reduced for the CHP, it is increased for the
55/90/24 reference system of separate generation. Hence, the RAI
55/90/32
decreases in increased condensing ST while the exergy
-0.60 efficiency is nearly maintained.
40 55 70 85 100 It is also seen that the exergy efficiencies are relatively
Steam delivery (t/h) high for the gas engines, while the RAI is close to zero.
These engines have high electric efficiencies, which are
Fig. 4. Variation of RAI, Eq. (20), for series B3-LP (boiler/steam turbine/
LP steam delivery) calculated for different reference values. The legend combined with high heat efficiencies. Although the exergy
shows (in %) the reference electric efficiency, the reference heat efficiency of the delivered heat is low, the total amount is high. Thus,
and the reference exergy-to-heat ratio. high exergy efficiency can be achieved. On the other hand,
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2047

0.6 B3-LP 1.0


B3-MP

Total energy efficiency


0.9
GT2-LP
0.5

Exergy efficiency
GT2-MP 0.8
bioB3LP
0.4 RRengine 0.7

0.6
0.3
0.5

0.2 0.4
-0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4
RAI RAI

1.0 0.7
Equivalent electric efficiency

0.9

US PURPA efficiency
0.8 0.6
0.7
0.6 0.5
0.5
0.4 0.4
0.3
0.2 0.3
-0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4
RAI RAI

0.8 0.6

0.7
Feng et al efficiency

0.5
Brazil efficiency

0.6
0.4
0.5

0.3
0.4

0.3 0.2
-0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4
RAI RAI

Fig. 5. Efficiencies as functions of RAI, Eq. (20), for the six series of CHP, including boiler/steam-turbine (B3-) and gas-turbine with HRSG (GT2-) series
with low-pressure (LP) and medium-pressure (MP) steam delivery, and the series (RRengine) of gas engines with district heating. (a) Exergy efficiency,
Eq. (2). (b) Total energy efficiency, Eq. (1). (c) Equivalent electric efficiency, Eq. (7). (d) US PURPA efficiency, Eq. (8). (e) Brazil efficiency, Eq. (9).
(f) Feng et al. adjusted exergy efficiency, Eq. (10).

the alternative production with heat pumps also has high total energy efficiency. However, for cases with the
exergy efficiency. Hence, in comparison, the avoided loss is same RAI, the total energy efficiency can have a
modest. wide variation. Moreover, cases with a lower RAI
Above it was observed that the BST plant with a high may have higher energy efficiencies. This is seen when
delivery load of MP steam has a high RAI. This is not comparing LP steam delivery to MP steam delivery.
captured by the exergy efficiency. On the contrary, it is at Both conditions deliver approximately the same energy,
the level of the BST plant with LP steam (much lower while the electricity production in combination with
RAI), and much lower than the GT plant (same or lower MP steam delivery gives less irreversibility and hence a
RAI). higher RAI.
Energy is conserved, and all the input will become some
5.3. Total energy efficiency kind of output or effluent. As pointed out above, this
efficiency is determined more by the state of the outflow
The total energy efficiency is shown in Fig. 5(b). flue gas than by the state of the heating medium and the
For each series, a higher RAI corresponds to higher energy production.
ARTICLE IN PRESS
2048 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

0.4 0.6
0.4
0.2
0.2

Walloon RCES
0.0 0.0
-0.2
RPES
-0.2
-0.4
-0.4 -0.6
-0.8
-0.6
-1.0
-0.8 -1.2
-0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4
RAI RAI

160.0 3.0
UK Quality Index (QI)

140.0 2.5

Hnotax/Helref (DK)
120.0 2.0

100.0 1.5

80.0 1.0

60.0 0.5
-0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4
RAI RAI

Fig. 6. Energy-based performance indicators as functions of RAI. (a) Relative primary energy savings. (b) Walloon relative carbon emissions savings, Eq. (17).
(c) UK quality index, Eq. (11). (d) Danish nontaxed fuel energy divided by reference fuel for separate electricity production. For legend, see Fig. 5.

5.4. Equivalent electric efficiency (EEE) EEE. Heat is included in these efficiencies, however
without considering its exergy. The Feng et al. efficiency
For the present cases, the efficiency of the Portuguese includes part of the actual exergy of heat, and the results to
legislation becomes equal to the EEE, which is also used in some degree approach the results of the exergy efficiency.
Spain. This efficiency is shown in Fig. 5(c), and represents The weighting factor given to heat is, however, larger than
the marginal electricity production from a heat-producing the exergy content.
system. Thus, to some extent it includes comparison with
the reference production. As the gain is expressed in terms 5.6. RPES
of electricity production, it may seem to include an
exergetic evaluation as well. However, this is a false The RAI was conceived as an exergy version of the
impression as the heat still is evaluated on an energy basis. RPES, which is shown in Fig. 6(a). While the comparison
Accordingly, the EEE does not acknowledge the higher between RAI and exergy efficiency shows the exergetic
thermodynamic value of MP steam compared with LP effects of comparison with the reference separate produc-
steam and hot water. Actually, the contrary is observed. tion, a comparison between RPES and the total energy
In general for the series investigated, increased RAI efficiency shows the energetic effects.
values correspond to larger EEE values. However, large As for the total energy efficiency, it is seen that for each
increases in RAI may give moderate increase in EEE. And series, a higher RAI corresponds to a higher RPES. It is also
for some series, very small increases in RAI values seen that cases with the same RAI show a wide variation of
correspond to large increases in EEE. RPES. The difference between RPES and RAI is primarily
the shift towards higher RAI for higher exergy-to-heat ratios.
5.5. US PURPA efficiency, Brazil efficiency, Feng et al. The RPES provides comparison with the alternatives, but
efficiency does not account for the fact that the alternatives can be
energetically more efficient for lower exergy-to-heat ratios.
The three efficiencies presented in Figs. 5(d)–(f) show As the reference exergy-to-enthalpy ratio is chosen equal
similar patterns. The observations made for the EEE are to to that of the LP steam, the LP cases lie on the line
a large extent made here as well. The difference is that the RPES ¼ RAI. Improving a plant by replacing the boiler
gradients of the curves in these graphs are less than for the with a GT/HRSG is encouraged by this indicator.
ARTICLE IN PRESS
I.S. Ertesvåg / Energy 32 (2007) 2038–2050 2049

However, it is seen that steam delivery at a higher for these cases. The Danish formula, on the contrary, gives
temperature and exergy (MP steam) is punished by the a close to neutral evaluation, which is nearly in accordance
energy indicator, giving a lower RPES in spite of an with the close-to-zero RAI values.
increased RAI. The higher B3-MP cases are even found in
the fourth quadrant, as the RPES takes negative values for 5.10. Other possible, more general indicators of conversion
positive RAI. and emissions
The Dutch fuel-free electricity, Eq. (13), normalized with
the reference amount of fuel energy, is proportional to the This study focuses on exergy and on existing criteria for
RPES and exhibits the corresponding behavior. performance. All the legislative indicators are based on
energy, although the Brussels and Walloon regions of
5.7. Walloon RCES Belgium have defined indicators that focus on CO2
emissions as well. Exergy, energy and CO2 emissions are
Fig. 6(b) shows the RCES of the Walloon legislation. This directly related to the amount of fuel and the efficiency of
is similar to the RPES above, except that the points are conversion. Emissions of NOx, SOx, soot, particles, heavy
moved clockwise such that the impact of improvements are metals, etc. are important aspects of CHP. Their relations
enhanced and several cases are raised above the to conversion efficiency and performance are, however,
RCES ¼ RAI line in the first quadrant and below on the much more complex. Also ‘‘upstream’’ and indirectly
negative side. The relative positions of the cases in this graph caused energy consumption and emissions could be
are similar to those of the EEE of Fig. 5(c). This results from included as ‘‘embodied’’, ‘‘extended’’ or ‘‘life cycle’’
the relation shown above between the two indicators. quantities. Such joint indicators including conversion and
emissions in general would require other and additional
5.8. UK QI methodology, with tracking of consumption, conversion
and emissions and ‘‘transformities’’, weighting rules or
As shown above in Eq. (11), the QI is proportional to an similar expressions. This is beyond the scope of the present
efficiency similar to the US and Brazil efficiencies. Hence, the study but may call for further investigations.
relations to the RAI (Fig. 6(c)) are similar and the comments
above apply here as well. The curves in the diagram are 6. Concluding remarks
relatively steeper than for the US efficiency, due to the larger
weight given to the heat production (Y/X in Eq. (11) is larger The purpose of this study was to assess various
than 0.5 in Eq. (8)). Moreover, the parameter X is increased efficiencies and indicators for evaluating CHP systems.
for lower electric power capacity. This causes higher values of An expression for relative avoided irreversibility (RAI) was
QI for the gas engines (RR series), which have low RAI developed to enable exergetic evaluation of CHP plants,
values. It may be noted that when calculated for a including comparison with separate production of the same
combination of separate production, the QI is larger than electricity and heat. The relative performance according to
for the actual CHP for all the investigated cases. various technically or legislatively defined efficiency in-
dicators was then expressed and compared to the RAI.
5.9. Danish nontaxed fuel Each efficiency alone, also the exergy efficiency, only
measures the performance of the specified system. They do
In the Danish legislation, CHP is supposed to be promoted not consider alternative production in separate plants for
by tax exemption for part of the fuel. As fuel for separate heat and electricity production. All first law based
electricity production is not taxed, it is reasonable to compare indicators evaluate electric and thermal energy on an equal
the nontaxed CHP fuel to the reference fuel for electricity basis. Contrary to this, the RAI pays respect to the second
production. This ratio, (Hnotax/Hel,ref), is shown in Fig. 6(d). law and includes comparison with separate production in
However, the pictures are similar when using the total reference systems.
reference fuel or the actual fuel as the denominators, although The results for the investigated test cases show that
they are less exposed. In all cases, except the three last cases of industrial CHP systems with gas turbines, back-pressure
GT2-LP and the cases RR3 to RR6, the first term of the steam turbines and steam delivery clearly are exergetically
minimum expression of Eq. (14) is invoked. beneficial to separate production. Variation of steam
The results for this indicator differ from the others. It delivery load is better obtained by variation in supplemen-
should be noted that for enterprises in Denmark, virtually tary firing rather than variation in condensing steam
all energy tax is refunded when the energy is used for turbines. Also back-pressure steam-turbines used with
industrial production. Thus, in practice, the tax exemption steam-delivery boilers show good performance. Then,
formula mainly applies to low-temperature heat (district steam delivery should be varied by varying the firing load
heating, space and tap-water heating) and a few instances rather than using condensing steam turbines. On the
of steam production for hospitals and other public service. contrary, the results indicate that CHPs with low-
The results for the gas engines (RR series) are interest- temperature heat delivery have marginal or no benefits
ing. All the other energy-based indicators give high values compared to separate generation of heat and electricity.
ARTICLE IN PRESS
2050 I.S. Ertesvåg / Energy 32 (2007) 2038–2050

It was seen that exergetic improvement (or impairment) [2] Nesheim SJ, Ertesvåg IS. Efficiencies and indicators defined to
only to a limited degree was captured by the various promote combined heat and power (CHP). Energy Convers Manage
2007;48:1004–15.
energy-based efficiency indicators. The differences in
[3] Horlock JH. Cogeneration—combined heat and power (CHP). 2nd
exergetic performance for different configurations were ed. Malabar, FL: Krieger; 1997.
not acknowledged, that is, boiler/steam-turbine plants [4] Royal Decree No. 436, 12 March 2004, Spain.
versus gas turbine plants and low-pressure steam delivery [5] Establishment of the governing co-generation activity. Decree-Law
versus medium-pressure delivery. Most of the indicators No. 538/99, Diário da República Serie I-A No. 288/99, 13 December
give higher values when a given configuration is improved. 1999; 8801-9 [In Portuguese], /http://dre.pt/pdfgratis/1999/12/
288a00.pdfS.
It is observed that several indicators overstate the relative [6] US Public Utility Regulatory Policies Act 18CFR292.205.
improvement of systems that already have a positive RAI, [7] Szklo AS, Tolmasquim MT. Analysis of Brazil’s cogeneration legal
while they underestimate improvements of systems that framework. Energy Convers Manage 2003;44:369–80.
have a negative exergetic evaluation. Some legislatively [8] Feng X, Cai Y-N, Qian L-L. A new performance criterion
defined indicators appear to discourage thermodynamically for cogeneration system. Energy Convers Manage 1998;39(15):
1607–9.
based improvements and favor exergetically poor systems. [9] CHPQA quality assurance for combined heat and power: introducing
CHPQA. Guidance notes Nos. 0, 10, and 24, /http://www.chpqa.
Acknowledgment comS.
[10] Mertens D. Certificates, an engine for growth in Belgium. In:
Proceedings of the annual conference at COGEN Europe, 26
The author is grateful to Dr. S.J. Nesheim of Statoil,
February 2004, Brussels.
Norway, for several discussions on this issue, and for data [11] Cardona E, Piacentino A. Cogeneration: a regulatory framework
provided for the industrial CHP test cases. toward growth. Energy Policy 2005;33:2100–11.
[12] EU CHP Directive 2004/8/EC 11 Feb 2004.
References [13] Heat supply in Denmark. Copenhagen: Danish Energy Authority;
2005. /http://www.ens.dk/graphics/Publikationer/Forsyning_UK/
[1] Nesheim SJ. Combined heat and power fired with natural gas. Heat_supply_in_Denmark/pdf/varmeforsyning_uk.pdfS.
[14] Jacobsen SH. CO2 heat pump can give plants large gas savings.
Thermodynamical, industrial, and societal considerations. PhD thesis
no 2005:167. Trondheim: Norwegian University of Science and Energinyt 2004(2):24–5 [In Danish].
Technology; 2005. [15] Rolls-Royce. Power Generation. /http://www.rolls-royce.com/S.

Вам также может понравиться