Академический Документы
Профессиональный Документы
Культура Документы
TROUBLESHOOTING ..........................................................5-7
ORDERING INFORMATION.................................................5-8
DET-TRONICS Instructions
®
ALERT MESSAGES
CAUTION!
The following Alert Messages, DANGER, WARNING,
CAUTION, and IMPORTANT are used throughout 1. Be sure to read and understand the entire
this manual and on the system to alert the reader and instruction manual before installing or operating the
operator to dangerous conditions and/or important Eagle Quantum Premier system. Only qualified
operational or maintenance information. personnel should install, maintain or operate the
system.
DANGER!
2. The wiring procedures in this manual are intended
Identifies immediate hazards that WILL result in
to ensure proper functioning of the devices under
severe personal injury or death.
normal conditions. However, because of the many
variations in wiring codes and regulations, total
compliance with these ordinances cannot be
WARNING!
guaranteed. Be certain that all wiring complies
Identifies hazards or unsafe practices that COULD with the NEC as well as all local ordinances. If in
result in severe personal injury or death. doubt, consult the authority having jurisdiction
before wiring the system.
The EQP controller can be arranged in a redundant • ANSI/NFPA Class A, Style 7 performance of SLC
configuration, thereby increasing the availability of the
system. The controllers work in “Master” and “Hot • Peer-to-peer communications
Standby” mode. • Short message formats
A programmed Controller is configured to The Eagle Quantum Premier system is easily modified
automatically download the configuration data into the to accommodate design changes or plant
individual devices when they first communicate with expansions. This can involve adding LON sections,
the Controller. repositioning LON sections, or removing LON
sections from the loop. There are LON
In addition to Det-Tronics advanced flame and gas communication implementation details that affect and
detectors, Eagle Quantum Premier offers the limit how the LON loop is changed.
capability of incorporating third party fire and gas
protection equipment into the system. These can be Only devices that have been approved for use with
either input or output devices. Typical input devices Eagle Quantum Premier can be connected up to the
include manual fire alarm "call boxes", heat detectors, LON. All approved devices have been tested and
and analog combustible or toxic gas measurement certified to operate properly on the LON.
instruments. Typical output equipment includes
solenoids, strobes, and horns. All equipment is
monitored for wiring fault conditions.
DIGITAL INITIATING
X3301 X3302 UVHT/C7050 UV UV/IR IR
COMMUNICATION DEVICE
DETECTOR DETECTOR DETECTOR DETECTOR DETECTOR DETECTOR 8 CHANNEL DCIO MODULE
UNITS CIRCUIT
NOTE: CHANNELS CAN BE
CONFIGURED AS EITHER
ECLIPSE INPUTS OR OUTPUTS.
GAS
DETECTOR
ANALOG
INPUT 8 4-20 MA INPUTS
MODULE
– + – +
RS-232 CONFIGURATION
PC
RS-232
RS-232
RS-485
HSSL
LON COMMUNICATION HEARTBEAT LON fault isolation. In this situation, the device opens
one side of the LON and listens for a heartbeat on the
The Controller continuously broadcasts a heartbeat
other side. If the device doesn’t receive a heartbeat, it
signal over the LON loop. This heartbeat is used for
listens on the other side of the LON and opens the
verifying the integrity of the LON loop and for keeping
opposite LON connection.
the field devices from going into a fault isolation
mode. Once every second, the heartbeat contains the
current time and date, which are used by the field THEORY OF OPERATION
devices to log status events and calibrations.
During normal operation, the Controller continuously
checks the system for fault conditions and executes
The Controller continuously tests LON continuity by
user defined programmed logic that coordinates the
sending out a heartbeat on one LON port and then
control of the field devices. At the same time, the
listening for it on the other LON port. The Controller
field devices are continuously monitoring for device
also broadcasts the heartbeat signal in the opposite
based fault and alarm conditions.
direction around the loop. This ensures that all field
devices, the LON Network Extenders (NE), and
When a fault condition occurs, the Controller displays
communication wiring are correctly passing the digital
the fault condition on the Vacuum Fluorescent Text
information around the loop.
Display, activates the appropriate fault LED(s),
activates the Trouble signal using the Controller’s
The field devices use the heartbeat as a mechanism
internal enunciator, and de-energizes the Controller’s
to ensure that there is a communication path back to
Trouble relay.
the Controller. If the field device does not receive a
heartbeat for a period of time, the device will go into a
Number of Devices Output Devices Old Input Devices Newer Input Devices
*Alarms are transmitted immediately. For Eclipse, the Status Update Rate is 1 second for all network sizes.
cycle. NODE 1
Safety System Controller
Cancel
Time & Date
16:38:55
JAN 11/2002
High Gas
Low Gas
Reset
Trouble
Cntrl Flt
Lon Fault
Inhibit
Output Inhibit
Acknowledge Silence
Ack
Power
Supervisory
Silence
NODE 8
C1851
COMMUNICATION NETWORK FAULT OPERATION Figure 2-2—Normal Communication over the LON
NODE 1 NODE 8
Fire Alarm Trouble Inhibit Power
16:38:55
Low Gas Lon Fault Ack Silence
JAN 11/2002
C1852
NODE 3 NODE 6
NODE 1 Cancel
Time & Date
16:38:55
JAN 11/2002
Enter Next
High Gas
Previous
Low Gas
Reset
Cntrl Flt
Lon Fault
Output Inhibit
Ack
Acknowledge Silence
Supervisory
Silence NODE 8
C1853
IMPORTANT!
Since it is impossible to predict where a network
fault might occur or exactly what effect it will Controller Redundancy
have on actual system operation, it is important
to diagnose and repair any fault as soon as The EQP controllers can be configured as a
possible after it is detected to ensure continuous, redundant pair. See Figure 2-6. The redundancy
uninterrupted system operation. scheme is a hot standby system that offers the
following primary features:
registers
• Optional ControlNet communication board that Figure 2-6— Block Diagram of EQP System
with Redundant Controllers
supports redundant communication channels.
• Optional Serial Interface Board
Flame Detectors
EQ2110PS, EQ2130PS and EQ2175PS Power For flame detector installation, operation,
Supplies maintenance, specifications and ordering information,
refer to Table 2-5.
The Power Supply provides main and backup power
to the EQP System. The device includes many
features such as voltage regulation, high efficiency,
Table 2-5—Flame Detector Manuals
and high power factor.
Detector Manual Number
An equalize switch is located on the front panel of the
X3301 95-8527
charger for manual activation, or a multi-mode
electronic timer can be used for automatic activation. X3302 95-8576
Steady state output voltage remains within +/– 1/2% X5200 95-8546
of the setting from no load to full load for AC input X2200 95-8549
voltages within +/– 10% of the nominal input voltage. X9800 95-8554
The power supplies are internally filtered to be no
UVHT 95-8570
greater than 32dBrn (“C” message weighting) and 30
millivolts RMS for all conditions on input voltage and
output load, with or without batteries connected.
Refer to the DCIO Specification Data sheet (form Figure 2-10—Eight Channel Relay Module
number 90-1149) for additional information.
NOTE
For deluge and pre-action applications, the input Figure 2-13—Agent Release Module
voltage to the ARM or DCIO must be 21 VDC
minimum with connection to any solenoid listed
in Table 2-6 or 2-7. Wiring must be in Refer to the EQ25xxARM Specification Data sheet
accordance with the listed maximum wiring (form number 90-1128) for additional information
lengths.
FM Group Device
B ASCO T8210A107
D ASCO 8210G207
E Skinner 73218BN4UNLVNOC111C2
F Skinner 73212BN4TNLVNOC322C2
G Skinner 71395SN2ENJ1NOH111C2
H Viking HV-274-0601
Table 2-7—Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications
Refer to the EQ25xxSAM Specification Data sheet Refer to the EQ22xxIDC Specification Data sheet
(form number 90-1129) for additional information (form number 90-1121) for additional information.
NOTE
Input types (e.g. fire alarm, trouble, and gas
alarms) are configurable through Det-Tronics
Safety System Software (S3).
WARNING!
DO NOT open any junction box or device
enclosure when power is applied without first de-
classifying the hazardous area.
24 vdc Power 18 AWG Single Wire Resistance: R = 0.6385 Ohms per 100 ft
Supply 2 Conductor Resistance: CR = 2 • R
Total Current
695 mA Device 1
50 ft Device 1 Voltage = Supply Voltage – (Voltage Drop)
0.6385 Ohms = 24 – (I • CR)
65 mA
Current Draw = 24 – (0.695 • 0.6385)
= 23.55 vdc
Total Current
630 mA
150 ft =
1.9155 Ohms Device 2
+
Device 3 Device 2
Device 2 Voltage = Device 1 Voltage – (Voltage Drop)
65 mA = 23.55 – (I • CR)
Current Draw = 23.55 – (0.630 • 1.9155)
= 22.35 vdc
Total Current
565 mA
150 ft =
1.9155 Ohms Device 3
Device 3
Device 3 Voltage = Device 2 Voltage – (Voltage Drop)
565 mA = 22.35 – (I • CR)
Current Draw = 22.35 – (0.565 • 1.9155)
= 21.27 vdc
Device Type Number of Devices Standby Current Total Current for Device Type
EQP Controller X 0.360 =
DCIO Module X 0.075 =
Power Supply. Monitor X 0.060 =
IDC/IDCGF/IDCSC X 0.055 =
X3301 - without heater X 0.160 =
X3301 - with heater X 0.565 =
X3302 - without heater X 0.160 =
X3302 - with heater X 0.565 =
X2200 X 0.135 =
X9800 - without heater X 0.085 =
X9800 - with heater X 0.420 =
X5200 - without heater X 0.155 =
X5200 - with heater X 0.490 =
DCUEX X 0.145 =
DCU with EC Sensor X 0.060 =
DCU with PointWatch X 0.300 =
Relay Module X 0.120 =
Analog Input Module X 0.160 =
Intelligent Protection Module X 0.075 =
EQ2220GFM X 0.018 =
PointWatch Eclipse X 0.270 =
ARM X 0.075 =
SAM X 0.060 =
Network Extender X 0.090 =
EQ21xxPS Power Supply X 0.350 =
Other X =
Total Standby Current for System (in amperes) =
Note: Standby current is the average current draw for the device in normal mode.
This table is for battery calculations only.
Device Type Number of Devices Alarm Current Total Current for Device Type
EQP Controller X 0.430 =
DCIO 8 Inputs X 0.130 =
DCIO 8 Outputs X 0.075 =
Relay Module X 0.120 =
Power Supply Monitor X 0.060 =
IDC/IDCGF/IDCSC X 0.090 =
X3301 - without heater X 0.160 =
X3301 - with heater X 0.565 =
X3302 - without heater X 0.160 =
X3302 - with heater X 0.565 =
X2200 X 0.135 =
X9800 - without heater X 0.085 =
X9800 - with heater X 0.420 =
X5200 - without heater X 0.155 =
X5200 - with heater X 0.490 =
DCUEX X 0.160 =
DCU with EC Sensor X 0.075 =
Power Supply
Characteristic
EQ2110PS EQ2130PS EQ2175PS
Input Frequency 60 Hz 60 or 50 Hz 60 or 50 Hz
RELAY
SPARE
6 7 8 9 10
Wiring Note: *Use the same type of cable in each wiring segment between
network extenders.
All devices on the LON are wired in a loop that starts
**Maximum wire lengths represent the linear wire distance of
and ends at the System Controller. To ensure proper LON communications wiring between network extenders.
operation, the LON should be wired using high speed
Be sure that selected cable meets all job specifications.
communication grade cable. If necessary, consult factory for further suggested cable
types.
NOTE
Cable meeting the specifications listed in Table
3-6 is suitable for distances up to 2000 meters.
NOTE
If no network extenders are used, the distances
listed are for the entire loop. If network
extenders are used, the distances listed are for
the wiring length between network extenders or
between a network extender and the System
Controller.
IMPORTANT!
Be sure that the selected cable meets the 3. Connect shields to the designated "shield"
specifications. The use of other cable types can terminals. The two shield terminals are connected
degrade system operation. If necessary, consult internally to ensure shield continuity.
factory for further suggested cable types.
CAUTION!
1. Remove the cover from the Network Extender Do not ground either shield at the network
enclosure. extender enclosure. Insulate the shields to
prevent shorting to the device housing or to any
2. Connect 24 vdc power lead wires and other conductor.
communication network cable to the terminal
block. (See Figure 3-2 for terminal location and 4. Check ALL wiring to ensure that proper
Figure 3-3 for terminal identification). connections have been made.
See Table 3-8 to determine maximum wiring 5. Inspect the junction box O-ring to be sure that it is
length. in good condition.
COM 1 - Communication network connections: 6. Lubricate the O-ring and the threads of the
Connect to COM 2 terminals of the next junction box cover with a thin coat of grease to
device on the loop, A to A and B to B. ease installation and ensure a watertight
enclosure.
COM 2 - Communication network connections:
Connect to COM 1 terminals of the NOTE
previous device on the loop, A to A and The recommended lubricant is a silicone free
B to B. grease, available from Det-Tronics.
24 VDC - Connect the "+" terminal to the positive 7. Place the cover on the enclosure. Tighten only
side of the 24 vdc power source. (Both until snug. Do not over tighten.
"+" terminals are connected internally.)
TERMINAL NO. 1
A2021
2 A COM 1
GND
3 B
11
12
13
10
4 SHIELD
14
9
8
7
+
6
5
5
4
3
–
2
6
1
24 VDC
7 –
8 +
9 SHIELD
A1870
11 B COM 2
Wiring
12 SHIELD 1. Remove the cover from the device junction box.
A1947
2. Connect external system wiring to the appropriate
Figure 3-3—Network Extender Wiring Terminal Identification terminals on the terminal block. (See Figure 3-4
for terminal block location and Figure 3-5 for
terminal identification). The input to the IDC
consists of one or more normally open switches
(momentary pushbuttons are not recommended),
INITIATING DEVICE CIRCUIT (IDC) with a 10K ohm, 1/4 watt EOL resistor in parallel
INSTALLATION across the furthest switch from the input.
8 13 –
24 VDC
A 9 12 +
COM 1
B 10 11 +
B1922
5. Install the communication module in the device 1. Remove the cover from the device enclosure.
enclosure.
2. Remove the communication module from the
NOTE junction box. Connect external wiring to the
Be sure the ribbon cable is properly connected. appropriate terminals on device terminal block.
(See Figure 3-4 for terminal block location and
6. Set the node address for the device. (See “Setting Figure 3-7 for terminal identification.) The input to
Device Network Addresses” in this section) the IDCSC consists of a normally open switch with
a 3.3k ohm series resistor, and a 10K ohm, 1/4
When configuring the EQ22xxIDCGF, its “device watt EOL resistor in parallel across the switch.
type” should be configured as an initiating device
circuit (IDC). NOTE
An EOL resistor must be installed on both
Both inputs must be configured for a trouble IDCSC inputs (including unused inputs). Wiring
condition. impedance must not exceed 500 ohms. A 3.3K
ohm resistor must be installed in series with the
Circuit 1 – “Open” indicates a –24 VDC ground switch. For correct operation, only one switch
fault condition. “Active” indicates a +24 per input can be connected.
VDC ground fault condition.
3. Check wiring to ensure that ALL connections
Circuit 2 – “Active” indicates a loss of AC input have been properly made.
power.
“Open” indicates a loss of battery 4. Install the communication module in the device
power. enclosure.
7. Place the cover on the enclosure and tighten until 5. Inspect the enclosure O-ring to be sure that it is in
snug. DO NOT over tighten. good condition. Lubricate the O-ring and the
threads of the enclosure cover to ease both
installation and future removal of the cover.
EQ22xxIDCSC SERIES INITIATING DEVICE
CIRCUIT SHORT CIRCUIT NOTE
(Not FM Approved) The recommended lubricant is a silicone free
grease available from Detector Electronics.
The device should be securely mounted to a vibration 7. Place the cover on the enclosure and tighten until
free surface. (See “Specifications” in this manual for snug. Do not over tighten.
device dimensions.
A 9 12 +
NOTE
COM 1
If an enclosure does not have a keyed entry, a
B 10 11 +
B2076
special tool is required to gain entry into an
enclosure.
NOTE
The Controller and enclosure must be connected SERIAL INTERFACE BOARD
to earth ground.
An optional Serial Interface Board is available for the
EQP Controller. See Figures 3-8 and 3-9 for details
For ordinary locations when entry is required to
on the electrical connections.
operate the equipment, the cabinet should be a
dead-front construction and 16-gauge cold-rolled
steel. The door lock system shall accept different
keys for entry. An Authorized Persons key and a
Person-in-charge key will allow entry into the cabinet.
The cabinet should contain a window to view the
Controller’s text display and LED indicators.
P12: TERMINALS 66 TO 68
RS-232
P11: TERMINALS 63 TO 65
P13: HIGH SPEED SERIAL LINK (HSSL)
RS-232
RS-232 (REDUNDANCY ONLY)
P10: TERMINALS 60 TO 62
RS-485
68 66 65 63 62 60
CONTROLNET
DET-TRONICS
®
59
RS-232
EAGLE QUANTUM PREMIER
P8: TERMINALS 54 TO 56
CONTROLNET
54
BNC CONNECTOR A
Safety System Controller RS-485
Fire Alarm Inhibit Power Supervisory
53
16:38:55
JAN 11/2002 Low Gas Acknowledge Silence Output Inhibit P7: TERMINALS 48 TO 53
LON CONNECTIONS
48
B2105
1 4 5 12 13 20 21 32 33 44 45 47
P6: TERMINALS 45 TO 47
FAULT RELAY
P5: TERMINALS 33 TO 44
RELAYS 5 TO 8
P4: TERMINALS 21 TO 32
RELAYS 1 TO 4
P3: TERMINALS 13 TO 20
DIGITAL INPUTS 5 TO 8
P2: TERMINALS 5 TO 12
DIGITAL INPUTS 1 TO 4
P1: TERMINALS 1 TO 4
24 VDC INPUT POWER
1+ 5 COM 2 52 2B
RESET*
1– 6 53 2A
COMMON, – 6
2+ 7 54 GND
ACKNOWLEDGE* P8
P2
2– 8 55 B RS-485
PORT 1
DIGITAL INPUTS 1 TO 4 3+ 9 56 A
A2117
SILENCE*
3– 10 57 GND
P9
4+ 11 58 RxD RS-232 Figure 3-10—Unsupervised Input Wiring
N / A* CONFIG
4– 12 59 TxD PORT
5+ 13
ENTER*
5– 14
6+ 15
CANCEL* P4
P3
6– 16
DIGITAL INPUTS 5 TO 8 17
7+ 60 A
NEXT* P10 COMMON 21 +
7– 18 61 B RS-485
PORT 2
8+ 19 62 GND
PREVIOUS*
8– 20 63 TxD N. O. 22
P11
1 C 21 64 RxD RS-232
PORT 3
1 NO 22 FIRE ALARM* 65 GND
N. C. 23
1 NC 23 66 TxD
P12
2 C 24 67 RxD RS-232 A2118
PORT 4
2 NO 25 SUPERVISORY* 68 GND
–
P4
2 NC 26
RELAYS 1 TO 4 3 C 27
Figure 3-11—Unsupervised Relay Output
3 NO 28 LOW GAS ALARM*
P13
3 NC 29 RS-232 - HSSL
4 C 30 (Custom Connector,
for Redundancy Only)
4 NO 31 HIGH GAS ALARM*
4 NC 32
5 C 33
5 NO 34 INHIBIT*
5 NC 35
6 C 36
6 NO 37 OUTPUT INHIBIT*
P5
6 NC 38
RELAYS 5 TO 8 7 C 39
7 NO 40 LON FAULT*
7 NC 41
8 C 42
8 NO 43 BEEPER*
8 NC 44
* DIGITAL INPUTS AND RELAY OUTPUTS CAN BE
C 45 CONFIGURED AS THE STATIC FUNCTION NAME (AS
P6 SHOWN) OR CAN BE USER DEFINED.
NO 46
TROUBLE RELAY
NC 47 NOTE: INPUTS CANNOT BE CONFIGURED TO REPORT A
E2104
TYPE ALARM (FIRE, GAS, SUPERVISORY, TROUBLE).
3 3
P29 P28
1 1
P27
DET-TRONICS
® RS-485 Transmit LED (Amber)
3
1 3
P25
LON COM 1
Termination Jumper
Figure 3-12—Location of Termination Jumpers, Communication Indicator LEDs and Communication Ports
parity check for the serial port, and Modbus device Jumper P28 – RS-485 Termination Jumper
address. Software selectable baud rates are
1-2 Terminated (factory setting)
9600,19200, 38400, 57600, 115200 and 230400.
2-3 Unterminated
Software selectable parity is None, Odd, and Even.
The controller uses 8 data bits with 1 stop bit.
Jumper P29 – RS-485 Ground Fault Monitor
Port Pinout (3-position terminal block)
1-2 Enabled
60 — A 2-3 Disabled (factory setting)
61 — B
62 — GND
68 67 66 65 64 63 62 61 60 68 67 66 65 64 63 62 61 60
GND B A GND B A
3 3 3 3
DET-TRONICS DET-TRONICS
® ®
16:38:55 16:38:55
Low Gas Acknowledge Silence Output Inhibit Low Gas Acknowledge Silence Output Inhibit
JAN 11/2002 JAN 11/2002
Cancel Enter Next Previous Reset Acknowledge Silence Cancel Enter Next Previous Reset Acknowledge Silence
A2276
Figure 3-13—Controller to Controller Communication with Signaling Line Circuit Classification per NFPA 72
Use Port 2 to pass safety critical information between • The Termination jumper P28 must be set to
controllers. User logic can pass all alarm, trouble, Terminate (position 1-2) on all controllers.
and supervisory information between the controllers.
• The Ground Fault Monitor jumper P29 must be set to
Watchdog timers must be implemented in user logic
Enabled (position 1-2) on all controllers.
to verify the integrity of the SLC. Consult the local
authority having jurisdiction for annunciation • Connect terminals A (terminal number 60) and B
requirements. (terminal number 61) between the controllers. The
GND (terminal number 62) must not be connected.
Controller to Controller Communication with
See Figure 3-13 for wiring details.
Signaling Line Circuit Classification B4, Class B,
Style 4 per NFPA 72
Connector P11, Terminals 63, 64 & 65 —
To connect up to three controllers together and be
RS-232 Serial Interface – Port 3
able to transfer safety information between the
controllers, the communication link must be classified Configuration data downloaded into the controller
as a signaling line circuit per NFPA 72. With the serial configures the serial interface transmission baud rate,
board option, Port 2 (plug 10) is a RS-485 serial parity check and MODBUS device address for the
connection that is ground fault monitored. serial port. Software selectable baud rates are
9600,19200, 38400, 57600, 115200, and 230400.
To meet the signaling line circuit (Class B Style 4) Software selectable parity is None, Odd, and Even.
requirements, the following must be configured for The controller uses 8 data bits with 1 stop bit.
correct operation:
Port Pinout (3-position terminal block)
• All controllers must have the optional serial board
installed. 63 — TXD
64 — RXD
65 — GND
A 50
INSTALLATION S 48
A 53
POWER SUPPLY AND POWER SUPPLY 4. Connect external wiring to the appropriate points
MONITOR INSTALLATION on Power Supply. Refer to Figure 3-15 for
terminal block locations and Figures 3-16 and 3-
17 for terminal identification. Connect the 24 vdc
WARNING! power wires and the LON network cable to the
ALWAYS follow all safety notes and instructions appropriate points on J1. (Redundant “+”, “–” and
when installing power supply or batteries! shield terminals are connected internally.) Do not
ground any shield at the monitor / power distribution
WARNING! cabinet. Insulate the shields to prevent shorting to
the device housing or to any other conductor.
Make sure a.c. power is OFF at main a.c.
breaker before beginning power supply 5. Connect a two wire cable between the AC input of
installation! the power supply and terminals 1 and 4 on J3, the
AC input terminal block on the power supply
monitor. See Figure 3-17.
3.1 3-20 95-8533
J1: POWER AND LON WIRING LON ADDRESS SWITCHES J3: AC INPUT
+ +
1 TERMINAL NO. 1
+ + 1
SWITCH NO. 1
+
+ +
+
+
+ +
1
+ +
+
+
1
+ YELLOW LED
GREEN LED
A1949
TERMINAL NO. 1
J2: CURRENT TEST POINTS
TERMINAL "C"
TERMINAL "B"
1 SHIELD
2 A COM 1
3 B
4 SHIELD
5 +
8 +
4 AC INPUT 120 / 240 VAC
9 SHIELD A1950
10 A
Figure 3-17—J3: AC Input Terminal
11 B COM 2
12 SHIELD
A1947
AC POWER H – –
24 VDC
See Notes 1 & 3 N
OUTPUT
G + + + POWER DIST CKT #1 –
NRTL CABINET
Figure 3-18— Wiring Connections for a Power Supply Monitor, Power Supply and Backup Batteries
EQ3700DCIO
COMMON C 24
IN–/OUT+ B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A COMMON C 21
COMMON C 15
IN–/OUT+ B 14 CHANNEL 5
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
IN–/OUT+ B 11 CHANNEL 4
+ SUPPLY A 10
COMMON C 9
IN–/OUT+ B 8 CHANNEL 3
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC
– 5 – COMMON C 6
INPUT VOLTAGE
+ 4 + IN–/OUT+ B 5 CHANNEL 2
SHLD* 3 SHLD + SUPPLY A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + COMMON C 3
+ SUPPLY A 1 + SUPPLY A 1
B2092
Figure 3-23—Supervised Input Configuration (Opens and Shorts) Figure 3-24—Supervised Output Configuration (Notification)
NOTE
No connection should be made to the “+ Supply”
terminal.
Wire one or more releasing devices to the module The output of the DCIO module supervises the
output. releasing circuit via the coil of the releasing solenoid.
NOTE It is essential to use a releasing device approved for
Make no connection to the “+ Supply” terminal. use with this output module.
NOTE
The output of the DCIO module supervises the
This type of output does not require the use of
releasing circuit via the coil of the releasing solenoid.
EOL resistors or diodes to supervise the circuit.
It is essential to use a releasing device approved for
use with this output module.
NOTE
For new or retrofit installations, any
NOTE
manufacturer’s non-water based agent release
This type of output does not require the use of
valves can be wired into the outputs of the ARM
EOL resistors or diodes to supervise the circuit.
or DCIO modules as long as the devices utilize
24 vdc and do not exceed 2 amperes current
The output can be configured for latching, continuous draw.
or timed response.
NOTE
To ensure proper operating voltage, the maximum For FM system approval listing, pre-action and
wiring length from the power source to the DCIO deluge applications require that only FM
module must not exceed the values shown in Table 3- approved deluge valves can be wired into the
9 for automatic release applications. ARM or DCIO modules. Table 3-10 lists the
supported solenoid groups. Remember that the
NOTE valves must utilize 24 vdc and must not exceed 2
For solenoids, this wire length includes both the amperes current draw.
wiring from the power supply to the DCIO
module and the wiring from the module to the The output can be configured for latching, continuous
solenoid. or timed response.
NOTE
Squibs are not compatible with this output.
To ensure proper operating voltage, the input voltage When using the switches located on the DCIO
to the DCIO must be in the range from 21 to 30 vdc module, the address is binary coded and is the sum
and the maximum wiring length must not exceed the of all switches placed in the “closed” position.
values shown in Table 3-10 for deluge and pre-action
applications. Per FM Approval requirements, the Each discrete point of a DCIO module has a tag
secondary power must provide capacity for a 90 hour number and a descriptor for unique identification.
minimum standby operation followed by a minimum of
10 minutes of releasing and alarm operation. For
initiating device circuit(s) for use with the deluge 8 CHANNEL RELAY MODULE
and pre-action system configuration, an Enhanced INSTALLATION
Discrete Input/Output Module (EDIO) must be
used. The following paragraphs describe how to properly
install and configure the 8 Channel Relay Module.
Unsupervised Output Ancillary Applications
(Unrelated to Fire Detection/Protection)
MOUNTING
Connect external wiring to the appropriate terminals
on the DCIO terminal block. See Figure 3-26. The Relay Module must be properly installed in a
suitable enclosure that is rated for the location. The
NOTE enclosure must provide space to install and wire the
No connection should be made to the “+ Supply” relay module and must also provide for ground wire
terminal. termination. Access into the enclosure is gained by
using a special tool to open the enclosure. The
enclosure should be rated for the temperature range
CONFIGURATION
of the location plus the temperature rise of all
equipment installed inside the enclosure. The
Setting DCIO Network Address
enclosure must be rated for electrical equipment that
One unique network address must be assigned to is going to be installed. The device can be panel or
each DCIO module. The address is set by the 8 DIN rail mounted.
switch DIP assembly on the DCIO module.
NOTE
It is recommended to maintain a minimum of 4
inches clearance between the module and other
equipment to provide adequate room for wiring
and ventilation.
COMMON C 3
WIRING
IN– / OUT+ B 2
All electrical connections are made to the field wiring
+ SUPPLY A 1 NOTE: SHUNT/FLYBACK DIODES DO NOT NEED connectors furnished with the module. See Figure 3-
TO BE INSTALLED ON THE FIELD DEVICE.
CIRCUIT PROTECTION IS PROVIDED 27 below for terminal identification.
WITHIN THE IPM.
EQ3720RM
NC C 24
NO B 23 CHANNEL 8
SHLD 6 COM 2 SHLD COMMON A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A NC C 21
NC C 15
NO B 14 CHANNEL 5
COMMON A 13
TO
EARTH
GROUND NC C 12
NO B 11 CHANNEL 4
COMMON A 10
NC C 9
NO B 8 CHANNEL 3
COMMON A 7
SHLD* 6 SHLD
24 VDC
– 5 – NC C 6
INPUT VOLTAGE
+ 4 + NO B 5 CHANNEL 2
SHLD* 3 SHLD COMMON A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + NC C 3
POWER NO B 2 CHANNEL 1
COMMON A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES. C2206
EQ3730AIM
COMMON C 24
4-20 MA IN B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A COMMON C 21
COMMON C 15
4-20 MA IN B 14 CHANNEL 5
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
4-20 MA IN B 11 CHANNEL 4
+ SUPPLY A 10
COMMON C 9
4-20 MA IN B 8 CHANNEL 3
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC
– 5 – COMMON C 6
INPUT VOLTAGE
+ 4 + 4-20 MA IN B 5 CHANNEL 2
SHLD* 3 SHLD + SUPPLY A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + COMMON C 3
+ SUPPLY A 1 + + SUPPLY A 1 +
A2235 A2236
Figure 3-30—Two-Wire Transmitter with HART Interface Module — Figure 3-32—Three-Wire Transmitter with HART Interface Module —
Non-Isolated 4 to 20 mA Current Output (Sourcing) Non-Isolated 4 to 20 mA Current Output (Sourcing)
Controller Firmware S3
Version Rev. Version
3.04 B 2.9.1.1
COMMON C 15
CHANNEL 5
IN–/OUT+ B 14
ZONE-2
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
CHANNEL 4
IN–/OUT+ B 11
ZONE-1
+ SUPPLY A 10
COMMON C 9
CHANNEL 3
IN–/OUT+ B 8
SUPERVISORY
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC
– 5 – COMMON C 6
INPUT VOLTAGE
+ 4 + CHANNEL 2
IN–/OUT+ B 5
MANUAL RELEASE
SHLD* 3 SHLD + SUPPLY A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + COMMON C 3
CHANNEL 1
POWER IN–/OUT+ B 2
ABORT
+ SUPPLY A 1
* SHIELDS ON POWER WIRES ARE OPTIONAL
UNLESS REQUIRED BY LOCAL CODES. A2240
Channels 1 to 3, Terminals 1 to 9
Channels 1 to 3 Inputs
COMMON C 3
Refer to individual wiring configurations for terminal
descriptions. Only channel 1 is shown in each diagram.
The information is typical for channels 1-3.
IN– / OUT+ B 2
Unsupervised Input
Connect external system wiring to the appropriate + SUPPLY A 1
No connection should be made to “+ Supply” terminal. No connection should be made to “+ Supply” terminal.
NOTE
Unsupervised inputs are not recommended for
fire alarm applications.
COMMON C 3
EOL
NFPA - Class B, Style B RESISTOR
10 K Ω
(Two State – Open and Switch Closure) IN– / OUT+ B 2
BELL, HORN,
Channels 4 and 5, Terminals 10 to 15 STROBE, ETC.
IN IN IN
+ SUPPLY A 10 L1 -R L1 -R L1 -R
L1 L2 L1 L2 L1 L2
OUT OUT OUT
IN–/OUT+ B 11 A2241
+ SUPPLY A 13
1 2 1 2 1 2
3 3 3
7 6 7 6 7 6
IN–/OUT+ B 14 A2242
The output of the IPM supervises the notification circuit IN– / OUT+ B 17
approved for fire alarm notification. These devices are Figure 3-40—CH-6: Supervised Output Configuration (Notification)
polarized and would not require the use of an external
diode for the supervision of the circuit. Wire one or more
notification devices to the output, with a 10 K ohm, 1/4 COMMON C 21
watt EOL resistor in parallel across the last device.
No connection should be made to “+ Supply” terminal.
Each output channel is individually activated for IN– / OUT+ B 20
response pattern:
– supervisory + SUPPLY A 19 NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
– continuous output CIRCUIT PROTECTION IS PROVIDED
WITHIN THE IPM.
– 60 beats per minute
– 120 beats per minute Figure 3-41—CH-7&8: Supervised Output Configuration (Agent Release)
– temporal
Table 3-11—Maximum Wire Length for Releasing Applications
– trouble.
Device Maximum Wire Length in Feet
Channels 7 and 8, Terminals 19 to 24
12 AWG 14 AWG 16 AWG 18 AWG
Supervised Output Agent Release
890181* 150 100 60
Connect external system wiring to the appropriate
899175* 150 100 60
terminals on the terminal block. See Figure 3-41.
895630-000* 150 100 60
Wire one or more releasing devices to the module output. 897494* 190 120 75
No connection should be made to “+ Supply” terminal. 486500-001* 1500 1000 600 400
31-199932-004* 150 100 60
The output of the IPM supervises the releasing circuit via
the coil of the releasing solenoid. It is essential to utilize 2 Amp Load 190 120 75
a releasing device approved for use with this output *Fenwal Solenoid
module. This type of output does not require the use of
EOL resistors or diodes to supervise the circuit.
CONFIGURATION
The output can be configured for continuous or timed response.
Setting Module Network Address
To ensure adequate operating voltage for the output
device, the maximum wiring length from the power source One unique network address must be assigned to
to the output device must not exceed the values shown in each intelligent protection module. The address is
Table 3-11 for automatic release applications or Table 3-12 set by the 8 switch DIP assembly on the module.
for deluge and pre-action applications.
When using the switches located on the module, the
For solenoids, this wire length includes both the wiring
address is binary coded and is the sum of all
from the power supply to the IPM and the wiring from the
switches placed in the “closed” position.
module to the solenoid.
NOTE Each discrete point of an intelligent protection module
For FM system approval listing, pre-action and has a tag number and a descriptor for identification.
deluge applications require that only FM approved
deluge valves can be wired into the IPM module. Det-Tronics S3 Safety System Software is used for
Remember that the valves must utilize 24 vdc and device configuration. The following shows the
must not exceed 2 amperes current draw. minimum software/firmware releases:
NOTE Controller Firmware S3
Squibs are not compatable with this output. If Version Rev. Version
squib actuation is required, use EQ2500ARM. 3.04 B 2.9.0.11
Examples: WARNING!
Chlorine
Do not apply power to the system with the cover
Bromine
removed unless the area has been verified to be
Iodine
free of combustible gases or vapors.
Hydrogen Chloride, Bromide or Iodide
Organic halides:
The DCU utilizes the following:
Trichloroethylene
Dichlorobenzene
1. A terminal wiring board mounted at the bottom of
Vinyl chloride
the junction box.
Freons
Halon 1301
2. A communication module mounted above the
(Bromotrifluoromethane).
terminal wiring board using the standoffs
provided. See Figure 3-42.
NOTE
Brief exposure to these materials can temporarily
increase sensor sensitivity due to the surface of Assembly and Wiring Procedure
the active element being etched. Prolonged
Attach the sensor to the DCU enclosure. Do not over-
exposure continues this process until the
tighten. If a sensor separation kit is being used,
sensitivity of the sensor is degraded, resulting in
attach the sensor to the separation kit junction box
shortened sensor life.
and wire the device as described in the “Sensor
Separation” section.
D. Exposure to high concentrations of combustible
gases for extended periods of time can stress the
sensing element and seriously affect its
performance.
exposed.
NOTE
If a sensor has been exposed to a contaminant
or a high level of combustible gas, it should be
calibrated at the time of exposure. An additional
calibration a few days later should be performed
to determine whether a significant shift in
sensitivity has occurred. If necessary, sensor STANDOFFS (4)
should be replaced.
TERMINAL WIRING BOARD
NOTE
A combination of accessories such as rain
shields and dust covers is not recommended and
can result in slow response to a gas leak.
A1571
COM SHIELD
Attach the communication module to the standoffs as 13 –
8
shown in Figure 3-42. Connect the ribbon cable from 24 VDC
the terminal wiring board to the communication A 12 +
9
module.
COM 1
B 10 11 +
Set the address for the device. Refer to “Setting A1726
NOTE 4 TO 20 MA IN 2 BLACK
Before placing the cover back on the enclosure
following completion of assembly and wiring, – 3 RED
inspect the enclosure O-ring to be sure that it is
SENSOR POWER
in good condition and properly installed. + 4 GREEN
Lubricate the O-ring and the threads of the cover
with a thin coat of an appropriate grease to ease A 5
installation. Refer to the “Ordering Information”
COM 2
section for the part number of the recommended B 6
grease (available from Detector Electronics). If
the installation uses catalytic type combustible
7 14 –
gas sensors, it is imperative that lubricants
COM SHIELD
containing silicone not be used, since they will
8 13 –
cause irreversible damage to the sensor. Place 24 VDC
the cover on the enclosure. Tighten only until A 9 12 +
snug. Do not over tighten.
COM 1
B 10 11 +
Sensor Separation for DCU with H2S and O2 A1875
Sensors
Since the transmitter for the electrochemical sensor is Figure 3-44—Electrochemical Sensor Connected to DCU
already mounted within the sensor housing, simply
mount the entire sensor assembly to the sensor Table 3-13
separation kit junction box and wire it to terminals 2 Maximum Separation Distances — Electrochemical Sensor to DCU
and 4 inside the DCU, the same as a regular (without
sensor separation) installation. Connect the shield to Wire Size Maximum Wiring Distance
the ground terminal in the DCU junction box. (AWG) Feet Meters
POINTWATCH CALIBRATE
2. Loosen the screws on the communication module 1
2
– –
3. Disconnect the ribbon cable from the 3
NOTE 8 13 –
24 VDC
Make sure the ribbon cable is connected to the
terminal wiring board. A 9 12 +
COM 1
If a sensor separation kit is being used, attach 2 Connections Wired at the Factory.
Preferred Method
TERMINAL WIRING BOARD
1. Disassemble the DCUEX and remove the
transmitter board. (Refer to “Wiring” for
disassembly procedure.) Do not re-assemble at
CORRECT ORIENTATION OF TRANSMITTER BOARD this time.
NOTE
N G
SWITCHES ON OPPOSITE SIDES
(WRONG)
This assembly can be separated from the
DCUEX by up to 1000 feet using three conductor
18 AWG shielded cable. (Regardless of
R O
TRANSMITTER BOARD
separation distance, operating voltage at the
transmitter MUST be at least 18 vdc for proper
W
TERMINAL WIRING BOARD
device operation.) (See Figure 3-48.)
–
GR
18 AWG (1.0 mm2)* 40 12
N
+
16 AWG (1.5 mm2)* 60 18
14 AWG (2.5 mm2)*
–
100 30
GR
ELECTROCHEMICAL SENSOR
Alternate Method
SPARE CHASSIS
CAL CAL If the transmitter board must be mounted separate
4-20
RET
4-20
RET
from the sensor (high temperature applications, etc.),
GND
+
–
4 TO 20 TRANSMITTER BOARD
P2
SENSOR
B1878
CATALYTIC SENSOR
NOTE
Table 3-15—Maximum Wiring Length for Automatic Release
For testing purposes, a load resistor of 1200 to Applications
1500 ohms @ 1 watt can be placed across
terminals 1 and 4. Device Maximum Wire Length in Feet
12 AWG 14 AWG 16 AWG 18 AWG
When using an explosive 890181* 150 100 60
initiator, connect the resistor 899175* 150 100 60
between terminals 1 and 2
895630-000* 150 100 60
and the initiator between
terminals 3 and 4, as shown 897494* 190 120 75
in Figure 3-49. 486500-001* 1500 1000 600 400
31-199932-004* 150 100 60
CAUTION! Squib 190 120 75
DO NOT intermix different types of initiators in 2 Amp Load 190 120 75
release circuit.
*Fenwal Solenoid
SINGLE DUAL
SOLENOID SOLENOIDS
+ 1
– 2
+ 3
– 4
A 5
COM 2
B 6
7 14 –
COM SHIELD
8 13 –
24 VDC
A 9 12 +
COM 1
B 10 11 +
NOTE:
TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.
TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.
JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.
SEE NOTE 2.
NOTES:
1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED.
NOTE
This type of output does not require the use of A1902
–
NOTE 4
COM 2
B
Each circuit must have a 10 6
terminals 8 13 –
24 VDC
7 and 8 — s h i e l d
Figure 3-51—Wiring Configuration for Signal Audible Module
connections
Jumpers
JP1
Terminals 13 and 14 are connected by jumper JP2 11 12 13 14
JP2
and terminals 11 and 12 are connected by jumper
JP1. These two jumpers (JP1 and JP2) must be cut if
1 2 3 4 5 6 7 8 9 10
an auxiliary output power supply is being used. (See
Figure 3-52) for jumper locations.
Address Setting
B1903
Set device network address. (See “Setting Device
Network Addresses” in this section.) Figure 3-52—Signal Audible Module Wiring Terminals and Jumpers
1 2 3 4 5 6 7 8
SETTING DEVICE NETWORK ADDRESSES BINARY
VALUE 1 2 4 8 16 32 64 128
IMPORTANT
If the address is set to zero or an address above Example: for node No. 5, close rocker switches 1
250, the communication module will ignore the and 3 (binary values 1 + 4); for node No. 25, close
switch setting. rocker switches 1, 4 and 5 (binary values 1 + 8 + 16).
Duplicated addresses are not automatically detected. NOTE
Modules given the same address will use the number The field device sets the LON address only when
given and report to the controller using that address. power is applied to the device. Therefore, it is
The status word will show the latest update, which important to set the switches before applying
could be from any of the reporting modules using that power. If an address is ever changed, system
address. power must be cycled before the new address
will take effect.
Setting Field Device Addresses
After setting address switches, record the address
Selection of the node address for field devices is number and device type on the “Address
done by setting rocker switches on an 8 switch “DIP Identification Chart” provided with this manual. Post
Switch” within each device’s housing. the chart in a convenient location near the Controller
for future reference.
NOTE
Only the first eight of the 12 switches are used
for selecting the device address.
TYPICAL APPLICATIONS
The address number is binary encoded with each Figure 3-55 is a simplified drawing of a typical EQP
switch having a specific binary value with switch 1 system. This system includes an EQP Controller,
being the LSB (Least Significant Bit). (See Figure 3- DCIO and various LON field devices.
53) The device’s LON address is equal to the added
value of all closed rocker switches. All “Open”
switches are ignored.
NOTE
The address switches in the DCIO module and
relay module appear slightly different than those
in other devices. Refer to Figure 3-54.
1 2 3 4 5 6 7 8 1 2 3 4
OPEN OPEN
BINARY
VALUE 1 2 4 8 16 32 64 128
LEAVE IN
OPEN POSITION
NODE ADDRESS EQUALS THE ADDED VALUE OPEN = OFF
OF ALL CLOSED ROCKER SWITCHES CLOSED = ON
A1557
52 B 49 5 B 2 11 B 3 6 B 10 14 B 4 14 B 4 5 B 2
53 A 50 4 A 1 10 A 2 5 A 9 15 A 5 15 A 5 4 A 1
P6
SHUNT P3
C 45
C 1 N CIRCUIT 1 + 1
FAULT NO 46 P4 P3
B 2 CIRCUIT 1 – 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3 CIRCUIT 2 + 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H CIRCUIT 2 – 4
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3 59 TxD A 56 A + SUPPLY A
3-46
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17 EQ24xxNE EQ22xxDCU PIRECL EQ25xxARM EQ25xxSAM
10 3– 7– 18 C COMMON C
4 SHIELD 9 6 SHIELD 3
11 4+ 8+ 19
DIGITAL INPUTS
A + SUPPLY A
12 4– 8– 20 6 24 VDC – 7 13 24 VDC – 14 4 24 VDC – 1 13 24 VDC – 14 13 24 VDC – 14
B IN–/OUT+ B
CH 4
CH 8
P4 P5 5 24 VDC + 8 11 24 VDC + 12 5 24 VDC + 2 11 24 VDC + 12 11 24 VDC + 12
21 C C 33 C COMMON C
COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1
22 NO NO 34
RELAY 1
SHIELD SHIELD SHIELD SHIELD SHIELD
RELAY 5
12 1 7 8 12 9 7 8 7 8
23 NC NC 35
* LON AND POWER TERMINALS
24 C C 36 ALSO VALID FOR AIM, IPM, RM. 11 B 3 6 B 10 11 B 8 6 B 10 6 B 10
SEE INDIVIDUAL DEVICE FOR
25 NO NO 37 CHANNEL TERMINALS.
A A A A A
RELAY 2
10 2 5 9 10 7 5 9 5 9
RELAY 6
26 NC NC 38
27 C C 39 POINTWATCH
CALIBRATE 1 CALIBRATE 13 + 1 OUTPUT 1 + 1
28 NO NO 40
RELAY 3
4 TO 20 MA IN
RELAY 7
2 – 2 OUTPUT 1 – 2
29 NC NC 41
– 3 + 3 OUTPUT 2 + 3
30 C C 42 SENSOR
DUAL SOLENOIDS
SINGLE SOLENOID
POWER
31 NO NO 43 + 4 – 4 OUTPUT 2 – 4
RELAY 8
RELAY 4
B2100
32 NC NC 44
95-8533
Figure 3-55—A Typical System
Section 4 Enter chooses the menu item selected, and
advances the menu to the next options list. (See
Operation “Controller Menu Options“ in this section for additional
information.)
The Controller has seven pushbuttons (located on the Next allows the operator to scroll through options
front panel) for user interface. These pushbuttons listed within each menu. Each time the NEXT
allow the operator to interact with the Controller to pushbutton is pushed, the current options list indexes
respond to alarms and system status conditions, up one list item. (See “Controller Menu Options” in
access system status reports, and configure this section for additional information)
Controller time and date settings.
Previous allows the operator to scroll through options
The following paragraphs describe the function of listed within each menu. Each time the PREVIOUS
each pushbutton. Refer to Figure 4-1 for Controller pushbutton is pushed, the current options list indexes
pushbutton locations. down one list item. (See “Controller Menu Options” in
this section for additional information)
Cancel cancels the selected command, and returns
the menu to the last option list displayed. Reset resets all controller latched outputs that are no
longer active.
NOTE
Pressing and holding Cancel and Enter initiates Acknowledge silences the internal beeper.
a lamp test.
Silence turns on the Silence LED and sets Silence
status in user logic.
DET-TRONICS
®
16:38:55
Low Gas Lon Fault Ack Silence
JAN 11/2002
NOTE
TEXT DISPLAY
During normal operation (no alarms or trouble
The Controller uses a text based display to show conditions occurring), the display scrolls current
current system status, active Alarms and Faults. system time and date.
When an alarm or trouble condition occurs, the Main Menu displays a list of options to access
display scrolls a detailed message of the condition, information types available for display through the
including tag number, condition (alarm, trouble, Controller. This list also includes access to options
supervisory etc.) and time/date. If multiple alarms or used to set system date and time, and diagnostics
trouble conditions exist, the display scrolls through all options.
active status conditions until they go inactive and are
reset using the controller pushbutton.
DET-TRONICS
®
Det-Tronics Eagle Quantum Premier High Gas Cntrl Flt Output Inhibit Supervisory
16:38:55 JAN 11/2002
Low Gas Lon Fault Ack Silence
Figure 4-2—EQP Controller Message Display and System Status Indicator Location
Display Alarms
Enter
Display Alarms Screen
Next
Enter Prev
Alarm Types
Cancel Display Devices*
Next Fire
Reset
Prev Supervisory Pressing the ack
Device Tagname
Trouble switch acknowledges
Add: xxx Device Type
Low Gas the visible alarm.
Fault/ No Fault
High Gas
Device dependent info Current
Inhibit
Output Inhibit Input State
Main Menu
Device Tagnames*
Display Alarms Alarm Type Off/On Visible if the
Display Devices Tag Name for Device n
Previous
Next
Serial Ports*
Configuration Port
Serial Port 1
Serial Port 2
* Submenus with more detailed information are available.
Serial Port 3
Serial Port 4
Redundancy Port
Diagnostics
Redundancy Info
Fault:
Lst Flt:
Cntr Mode:
My Config:
Redun Mem:
HSSL Status:
Version Match:
Parser:
Comm Ack:
Lon Comm:
Msg Error:
--Master Errors--
Program Flow:
LON A Inf:
LON B Inf:
User Logic CS:
App CS:
User Logic:
Config:
--Standby Errors--
Program Flow:
LON A Inf:
LON B Inf:
User Logic CS:
App CS:
User Logic:
Config:
Power 1:
Power 2:
Option Bd:
Moving within the Main Menu is done by using the Device Tagnames
NEXT or PREVIOUS pushbuttons located on the
controller’s front panel. The menu options will scroll
Controller
upward (NEXT Pushbutton) or downward (Previous Z398-80 X
Pushbutton) while the Main Menu name remains
stationary. When the desired menu option is selected
by the “>” indicator, the ENTER pushbutton is
pressed to advance the menu display to the desired Pressing the NEXT or PREVIOUS pushbutton allows
information set. cycling through devices. Pressing the CANCEL
pushbutton will return the display to the Main Menu.
NOTE
Pressing the CANCEL pushbutton from within SET TIME AND DATE provides access to
any sub-menu returns the display to the Main configuration controls for system clock and date
Menu. The display will also return to the Main settings.
Menu if left unattended for a period of 20
minutes. If an alarm or trouble condition is
present after 20 minutes, the display will change
to the existing Alarm or Trouble message. Set Time & Date
DISPLAY ALARMS displays a list of existing Alarms 11:20:52
and Trouble conditions. Moving within this menu is Jul 29 / 2002
done by using the NEXT or PREVIOUS pushbuttons.
NOTE
Alarm Type Off/On
Off On When the Set Time and Date menu opens, the
Tag Name current hour will flash.
Alarm Description
To move within this menu, press the ENTER
Time & Date ack pushbutton until the desired property is flashing. To
set the desired property value, press the NEXT
Pushbutton to increase or PREVIOUS Pushbutton to
NOTE decrease the value. When the desired value is
Multiple alarm information can be viewed by displayed, press the ENTER pushbutton. This will
pressing the NEXT or PREVIOUS pushbuttons. advance the menu to the next property and it will
Pressing CANCEL will return the menu to the flash. When all desired properties have been entered,
DISPLAY ALARMS menu. press the ENTER pushbutton until the message
“Press ENTER to Save” is displayed. When the
ENTER pushbutton is pressed, the settings are saved
DISPLAY DEVICES displays device information on all
and the menu changes back to the MAIN MENU.
devices on the LON loop. Device tag name, type, and
node address are displayed.
Z398-63 U / I
Add:63 UV / IR Detect
No Fault
Lst Flt
Displays the last redundancy fault that occurred.
User Logic CS
Controllers continually conduct a checksum test of Table 4-2—EQP Controller Alarm Tone Patterns
the user logic program to ensure that the data
remains unchanged. A user checksum fault is Priority Controller Tone Tone Pattern
annunciated if the result is incorrect.
1 Fire Alarm Temporal
User Logic
Many checks are conducted while the controller
interprets and executes the user program. The user
logic error is generated if invalid or out of range data
is detected.
0.5 SEC 0.5 SEC 3.0 SEC 2. Ignore field device LON communications.
However, the controller continues to generate the
LON heartbeat.
GAS
B1855
A or B Cause Action
Off Channel disabled Program network for redundant media, if required.
Steady green Normal operation None
Flashing green/off Temporary errors None; unit will self-correct.
Listen only Cycle power.
Flashing red/off Media fault Check media for broken cables, loose connectors,
missing terminators, etc.
No other nodes present on network Add other nodes to the network.
Flashing red/green Incorrect network configuration Cycle power or reset unit.
If fault persists, contact the factory.
8. ControlNet communication continues. 12. Initialized the ControlNet option board with new
parameters.
9. Text display’s first line indicates "*** Program
Mode ***" 13. Enable static logic and user logic programs to
operate. The first scan program is run first.
10. Text display’s third line displays download status.
14. Accept field device LON communications.
a) "Config Download" indicates the serial transfer
into memory from the PC to the Controller. 15. Poll the device type variable from LON field
devices.
b) "Erasing Flash" indicates that the controller is
electronically erasing the entire contents of 16. Configure LON field devices.
the Flash memory.
17. Clear the Trouble condition.
c) "Writing to Flash" indicates that configuration
data stored in memory is being written down 18. Text display shows a normal operation marquee
into Flash memory. message.
d) "Flash Lock" indicates that the controller is a) Text display’s first line indicates "Det-Tronics
locking the configuration data into the Flash Eagle Quantum Premier".
memory.
b) Text display’s third line displays time (24 hour
CAUTION format) and date (month day/year).
The controller will be corrupted if power is
removed during a download. Contact the factory NOTE
if this occurs. Depending on the condition of the LON devices,
faults may persist for a number of minutes.
11. Initialize the RS-485 and configuration serial ports
with new parameters.
EMBEDDED LOGIC – CONTROL TRANSFER Controller Only: In this mode the I/O of the IPM will
SEQUENCE DESCRIPTION be controlled from the EQP Controller only and
embedded logic is inactive.
A user configurable selection is provided to choose
the operational mode of the IPM. Three modes are Back-up Mode: (The default selection) the IPM I/O is
provided, two of which utilize the embedded logic normally controlled by the EQP Controller but utilizes
feature. embedded logic in accordance with the “Control
Transfer Sequence Description” to control its I/O
If enabled, the embedded logic is armed at all times under certain circumstances.
but control of the outputs depends on the selected
mode. Embedded Only: In this mode the IPM continuously
operates from its embedded logic. The status of all
In the “back-up mode” control of the IPM outputs IPM I/O is available to the EQP Controller but control
transfers to the IPM’s embedded logic in the event of of the outputs are not; however, controller and S3
an IPM diagnosed loss of communications between reset commands are accepted.
itself and the EQP Controller.
Detection Style – Single or Cross Zoned: A
An IPM diagnosed resumption of normal software selection allows either “1 zone release” or “2
communications with the Controller will cause control zone release” (cross-zoned) operation.
of the IPM outputs to transfer back to the Controller
unless a release sequence has been initiated and is
not yet complete.
1 + +
+
1
+
AMBER LED
RED LED
GREEN LED
The IDC has three LEDs (located at the center of the Power-up Pulsed at a rate of 0.5 Hz
IDC communication module circuit board) to provide Calibration Pulsed at a rate of 1 Hz or on
a visual indication of device status. steady
Fault Pulsed at a rate of 4 Hz
Table 4-14—Initiating Device Circuit Status Indicators
Alarm On steady
LED Device status
Green When On indicates device has power.
Red When On indicates an Alarm or Fault condition is EQ25xxARM AGENT RELEASE MODULE
present.
The EQ25xxARM has three LEDs to indicate device
On steady = One of the inputs is active.
status. They are located at the center of the circuit
Blinking = Fault condition such as an open
board.
input circuit or not configured.
Amber When On indicates a device is disabled. Module must
be replaced.
Table 4-16—Agent Release Module Status Indicators
NOTE
If the communication module has not been
configured, the red LED blinks at a 4 Hz rate.
NOTE
The amber LED is provided for factory diagnostic
purposes and is not used in the system.
Illumination of the amber LED normally indicates
a failure in the communication chip.
Replacement of the communication module
circuit board is required.
Amber When On indicates a malfunction in the electronic Maintain a log of maintenance activities.
circuitry. Module replacement is required. Observe normal precautions for handling electrostatic
sensitive devices.
LON
EQ24xxNE NETWORK EXTENDER
Rocker switches for each LON device must be set to
The EQ24xxNE has three LEDs (one green, two the desired address prior to power-up.
amber) for indicating device status.
Test the loop with no power applied. DC resistance
should be equal on A and B.
Table 4-18—Network Extender Status Indicators Check polarity on A and B (no rolls). COM 1
LED Device Status connects to COM 2; COM 2 connects to COM 1. A
Green When On indicates device has power. connects to A and B to B.
Flashes to indicate messages are being transferred Measure voltage. A to chassis ground measures
over the LON. approximately +7.5 vdc. B to ground measures
Amber When On indicates a malfunction in the electronic approximately –7.5 vdc.
circuitry. Module replacement is required.
Measure signal (400 mv P-P min.). (Use oscilloscope
Note if possible).
When a network extender has an internal Check fault tolerance by introducing a short.
fault, the message display will only indicate
that there is a LON fault condition existing
somewhere on the LON. Controller
The I/O and LON wiring is correctly installed, Verify earth ground connections as specified in the
observing polarity. All cable shields are properly wiring instructions.
terminated and insulated.
Check power distribution to ensure that all devices
Power wiring is installed and power source is are receiving power.
operational.
Chassis ground stud must be connected to earth DCUs
ground.
Verify correct address setting.
The HSSL cable is connected between the two
controllers. Check modules for correct orientation.
Check for the presence of contaminants or poisoning
DCIO Module agents.
Device should be oriented with the sensor pointing
Verify correct address setting.
down.
Check signal circuits for correct polarity.
Check for correct installation of EOL resistors. IDCs
3. Inspect all devices to verify that they have not To verify that the Controller is powered-up and
been physically damaged in shipment. operating properly, ensure that:
4. Apply power to the system. 1. When power is first applied, all LEDs are on. The
ACK LED flashes while the memory test is
NOTE running. When initialization is complete, only the
To prevent the network modules from going into green power LED remains lit.
a fault isolation condition, apply power to the
EQP Controller prior to applying power to the 2. The serial link indicators if active continuously
network devices. flash.
5. Program the system for the desired operation 3. The Text display runs an initialization routine.
using Det-Tronics Safety System Software (S3). When initialization is complete and if all alarms
Download configuration data to all devices. and trouble conditions are cleared, the text
display shows the current time and date. If the
NOTE controller has been unpowered for more than 12
After system configuration has been completed, hours, the time and date may have to be set. If
the entire system should be tested for proper an alarm or trouble condition exists, it will be
operation to ensure that configuration was displayed until the condition is corrected and the
performed properly. Reset button is pressed.
6. Calibrate the sensors. If the controller has not been software configured,
unconfigured devices will be displayed.
7. Ensure that all trouble and alarm conditions have Configuration must be done using S3 Safety
been cleared and the EQP Controller is reset, System Software before proceeding.
then remove mechanical blocking devices (if
used) and restore power to the output loads. 4. The LEDs on the front panel provide an indication
of the system status.
2. The input circuits should indicate the proper state 2. The output circuits should indicate the proper
for the programmed device (channel active LED state for the programmed device (channel active
illuminates when the circuit is active). LED illuminates when the circuit is active).
3. The circuits should not indicate a fault condition 3. The circuits should not indicate a fault condition
(channel fault LED illuminates when the circuit is (channel fault LED illuminates when the circuit is
in fault). in fault).
4. Test the entire system for proper operation to 4. Test the entire system for proper operation to
ensure that the configuration was performed ensure that the configuration was performed
properly. properly.
MANUAL CHECK OF OUTPUT DEVICES All gas sensors must be calibrated on a regular basis.
Calibration should typically be performed every 90
It is important that response devices be checked days for catalytic and electrochemical sensors.
initially when the system is installed, as well as
periodically during an on-going maintenance Catalytic sensors have a finite lifespan. If a
program. successful calibration cannot be performed, replace
the sensor and recalibrate following the procedure
CAUTION! described in the “Calibration” section below. Always
compare part numbers to be sure that the correct
Be sure to secure all output devices that are replacement sensor is being used.
actuated by the system to prevent unwanted
activation of equipment, and remember to place
these output devices back into service when the CAUTION!
checkout is complete. Exposure of the sensor to high concentrations of
combustible gases for extended periods of time
O-RING MAINTENANCE can introduce stress to the sensing element and
seriously affect its performance. After exposure,
recalibration should immediately be performed,
WARNING! and the sensor should be replaced if necessary.
11
12
13
between regularly scheduled recalibrations can vary
10
14
9
8
from one installation to the next. In general, the more
7
SW1
6
5
frequently a system is checked, the greater the
4
3
MAGNETIC REED SWITCH *
2
reliability.
1
IMPORTANT!
4 to 20 ma devices not manufactured by Det-
Tronics must be pre-calibrated. To ensure A1881
12. Activate the reed switch. (The red LED blinks for NOTE
3 seconds while the reed switch is closed) Pressing the Sensor Replacement Switch aborts
calibration and starts over.
13. The calibration is complete. The calibrate LED
turns off. NOTE
Resetting the communication module will abort
NOTE the sensor replacement.
If the calibration is not completed within 12
minutes, the previous calibration values are
CALIBRATION ALGORITHM C
restored and the calibration is logged as aborted.
FOR COMBUSTIBLE GAS DCUs AND
The calibrate LED will flash.
AUTOMATIC CALIBRATION OF UNIVERSAL DCUs
Sensor Replacement
CAUTION!
WARNING!
After exposing the H 2 S sensor to high
The hazardous area must be de-classified prior concentrations of gas, it should be exposed to
to removing a junction box cover with power fresh air for at least 30 minutes, and re-
applied. calibrated.
7. The calibrate LED flashes when the input 5. Apply the calibration gas. (The calibrate LED
increases. flashes when the sensor detects gas.)
8. Activate the reed switch. (The red LED flashes for 6. When the sensor input has been stable for 30
3 seconds while the reed switch is closed.) seconds, the communication module records the
uncalibrated value in the calibration log, and
9. The communication module records the calibrates the span value.
uncalibrated value in the first register of the
calibration log and calibrates the span value. 7. The calibrate LED stays on steady.
10. The calibrate LED stays on steady. 8. Remove the calibration gas.
11. Remove the span gas and return the analog input 9. The communication module waits until the sensor
to normal. input drops below 4% full scale.
12. Activate the reed switch. (The red LED flashes for
3 seconds while the switch is closed.)
3.1 5-3 95-8533
10. The calibration is complete. (The calibrate LED 8. Activate the reed switch for 4 seconds. (The red
turns off.) LED flashes for 3 seconds while the switch is
activated.) The communication module records
NOTE the uncalibrated value in position one of the
If the calibration procedure is not completed calibration log and calibrates the zero value. The
within 12 minutes, calibration will be aborted and calibrate LED goes on steady.
the detector will revert back to the previous
calibration values. The red LED will flash and 9. Move the Calibration Switch to the “calibrate”
the calibration will be logged as aborted. position.
10. Apply the calibration gas and wait for the output
Sensor Replacement — Combustible Gas (CGS Sensor)
to stabilize.
NOTE
When replacing a sensor, compare part numbers 11. With 50% LFL calibration gas applied to sensor,
to be sure that the correct replacement sensor is adjust R3 for a reading of 1.2 vdc (12 ma) on the
being used. volt meter.
1. Remove the cover from the DCU enclosure. 14. The communication module records the
uncalibrated value in the first register of the
2. Press the Sensor Replacement Switch on the calibration log and calibrates the span value. The
communication module for approxImately 1 calibrate LED stays on steady.
second. (The calibrate LED on the communication
module flashes, indicating that it is ready for the 15. Remove the calibration gas and replace the DCU
zero input.) enclosure cover.
4. Wait at least 5 minutes for the sensor output to 8. Calibration is complete. (The calibrate LED turns
stabilize. off.)
I/O Type Normal (Off) Normal (On) Open (Off) Open (On) Short (Off) Short (On)
*Component certification
16:38:55
High Gas
Low Gas
Trouble
Acknowledge
Cntrl Flt
Silence
Lon Fault
Output Inhibit
5.5 HUMIDITY RANGE—
JAN 11/2002
(14.0) 5 to 95% RH, non-condensing.
Cancel Enter Next Previous Reset Acknowledge Silence
DIMENSIONS—
PANEL MOUNTING DIMENSIONS
See Figure 6-3.
SHIPPING WEIGHT—
10.75 2.70 0.5 pounds (0.2 kilograms)
(27.3) (6.86)
DET-TRONICS ®
CERTIFICATION—
EAGLE QUANTUM PREMIER
Safety System Controller
Time & Date
Fire Alarm Inhibit Power Supervisory
5.5 FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
(14.0)
High Gas Trouble Cntrl Flt Lon Fault
16:38:55
JAN 11/2002 Low Gas Acknowledge Silence Output Inhibit
Class I, Zone 2, Group IIC (T4).
Cancel Enter Next Previous Reset Acknowledge Silence
6.7
16:38:55
JAN 11/2002 Low Gas Acknowledge Silence Output Inhibit
0.7
DIMENSIONS OF CONTROLLER
WITH OPTIONAL SERIAL COMMUNICATION BOARD
E2103 (1.75)
2.95
(7.5)
A2253
1 6 1 6 1 6 1 6
5.0
(12.7)
4.5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (11.3)
4.5
A B C A B C A B C A B C A B C A B C A B C A B C (11.3) A B C A B C A B C A B C A B C A B C A B C A B C
5.2
5.2 1.8 (13.2) 1.9
C2096 (13.2) (4.6) (4.8)
Figure 6-2—Dimensions of the DCIO / Relay Module / AIM / IPM in Inches (Centimeters)
3.1 6-3 95-8533
OUTPUT / NOTIFICATION / RELEASING CIRCUITS EQ3720 RELAY MODULE
UNSUPERVISED OUTPUT RATING—
POWER REQUIREMENTS—
Short circuit protected: 2 amperes at 30 Vdc
3 watts nominal, 4 watts maximum.
maximum.
INPUT VOLTAGE—
SUPERVISED OUTPUT RATING—SIGNALING
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
TYPE, CLASS B, STYLE "Y".
not cause damage to the equipment.
MAXIMUM OUTPUT CURRENT—
RELAY CONTACTS—
2 amperes maximum, 15 Amp inrush.
30 VDC, 2 amps resistive.
Automatic short circuit protection provided.
125 VAC, 0.5 amp resistive (FM and CSA only).
SUPERVISORY CURRENT—
LON COMMUNICATION—
Reverse current monitored at 3.0 mA, ± 2.0mA.
Digital communication, transformer isolated (78.5
kbps).
RESPONSE TIME—
Output actuates in <0.15 second after acknowledging
TEMPERATURE RANGE—
an alarm command message.
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
EOL RESISTORS—
10 K ohms ±2 K ohms.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
DIMENSIONS—
– Continuous
Refer to Figure 6-2.
– 60 beats per second
– 120 beats per second
SHIPPING WEIGHT—
– Temporal Pattern.
1 pound (0.45 kilograms).
NOTE
CERTIFICATION—
All eight channels are synchronized when
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
programmed as a signaling output.
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.
SUPERVISED OUTPUT RATING— RELEASING Refer to Appendix B for CSA Approval details.
TYPE
CENELEC/CE: ATEX/EMC Directive Compliant.
MAXIMUM OUTPUT CURRENT— 0539 II 3 G
2 amperes maximum, 15 Amp inrush. EEx nC IIC T4
Automatic short circuit protection provided. DEMKO 03 ATEX 135246U
T4 (Tamb = –40°C to +85°C).
SUPERVISORY CURRENT— Vin = 24 vdc ±10%.
Monitored at 3.0 mA ±2.0 mA. Refer to Appendix C for CE Mark details.
Special conditions for safe use:
RESPONSE TIME— The device shall be installed in an enclosure that
Output actuates in <0.15 second after acknowledging complies with all relevant requirements of EN 50021:
an alarm command message. 1999, and provides a degree of ingress protection of
at least IP54. The device may only be installed,
RELEASING OUTPUT, TYPES— connected or removed when the area is known to be
Configurable for device applications: non-hazardous.
– Continuous
– Timed. RESPONSE TIME—
Actuates in <0.15 second after acknowledging an
alarm command message.
non-hazardous.
A2253
CERTIFICATION— VIBRATION—
FM / CSA: Ordinary locations. FM 3260.
DIMENSIONS—
See Figure 6-5.
9
(22.9)
4.7
0.28 (11.8)
8.5 (0.71) 3.4
(21.6) (8.6)
2.25 6.6
J1 J3 (5.7) (16.8)
4
(10.2)
5.2 2.7
(13.2) (6.8)
B C
1.28
(3.25)
2.5 B2046
(6.4) 0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)
A2038
Figure 6-4—Dimensions of Power Supply Monitor in Inches Figure 6-5—Dimensions of Tall Cover Junction Box in Inches
(Centimeters) (Centimeters)
CERTIFICATION—
2.9 1.2
(7.4) (3.0)
2.1
(5.3)
1.75
(4.4)
A2237
HUMIDITY—
5 to 95% RH at 70°C.
DIMENSIONS—
See Figure 6-7.
CERTIFICATION—
FM / CSA: Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4A).
Class I, Zone 2, Group IIC (T4).
Class II/III, Div. 2, Groups F & G (T4A).
NEMA/Type 4X.
ELECTROCHEMICAL SENSORS
Refer to the Electrochemical Gas Sensor Specification
Data sheet, form 90-1079, for specifications.
Electrochemical sensors available from Det-Tronics
include Hydrogen Sulfide, Oxygen, Carbon
5.20 2.69 Monoxide, Chlorine, Sulfur Dioxide, and Nitrogen
(13.21) (6.83)
Dioxide.
HAZARDOUS LOCATIONS
• National Fire Alarm Code performance verified per ANSI/NFPA 72-1999. Refer to Table A-1 for supervision
characteristics.
• Refer to the Model X3301, X5200, X2200 and X9800 manuals (see Table 2-4) for further FM flame performance
details. Additional 2 second response time applied for system communication.
• Models EQ3700 Series and EQ22xxARM Series are Approved as agent releasing circuits and are Approved for
use with the following automatic deluge and pre-action solenoids:
GAS DETECTION
• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320.
Accuracy: ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL. For the Model PIRECL, refer to the
PIRECL manual (form number 95-8526) for further FM gas performance details.
NOTE: Detector Electronics combustible gas detection K factors are not FM verified.
• H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FM requirements. Accuracy: ±2 ppm from 0 to 20
ppm, ±10% of concentration from 21 to 100 ppm. Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S)
Sensors Explosion-proof for Class I, Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model
C7064E5014 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous
(Classified) Locations per FM 3615. Operating temperature limits are –40°C to +40°C.
• Calibration of the above listed sensors has been FM verified using the respective EQ22xxDCU, EQ22xxDCUEX,
and PIRECL with the Det-Tronics 225130-001 (50% LFL methane) and/or 227115-001 H2S Calibration Kits.
• The EQ22xxDCU Series can be used with any FM Approved 4-20 ma device.
NOTE
FM Approval of the 4-20 ma input does not include or imply approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain FM Approval of the system, all
4-20 ma gas detection instruments connected to the input must also be FM Approved.
8 7 6 5 4 3 1
3.1
CL I, DIV 1, GRPS B, C & D
CL I, DIV 2 GRPS A, B, C & D (T4) CL I, ZONE 1, GRP IIB + H2 (T4)
CL I, ZONE 2, GRP IIC (T4) CL II, DIV 1, GRPS E, F & G, CL III
CL I, DIV 1, GRPS C & D
HAZARDOUS LOCATIONS CL I, DIV 2, GRPS A, B, C & D (T4A)
ORDINARY LOCATIONS CL I, DIV 2, GRPS A,B,C & D (T4A)
(Tamb = -40°C TO +85°C) CL I, ZONE 2, GRP IIC (T4)
(Tamb = 0°C to +50°C) HAZARDOUS LOCATIONS
EXCEPT WHERE SHOWN CL II, DIV 2, GRPS F & G (T4A) (Tamb = -40°C TO +40°C)
HAZARDOUS LOCATIONS NEMA/TYPE 4X
(Tamb = -40°C TO +75°C)
EXCEPT WHERE SHOWN
CGS SERIES
EAGLE QUANTUM PREMIER
Safety System Controller COMBUSTIBLE GAS SENSOR
D EQ22xxDCUEX SERIES (006888-001) D
F1=50mA F2=50mA
Fire Alarm Trouble Inhibit Power
CONTROLLER
1
Low Gas Lon Fault Ack Silence COMMUNICATION UNIT
1
(CLASS I LOCATIONS ONLY)
007390-002 REV. B
S/N:
DATE CODE:
MODEL: EQ3000
Cancel Enter Nex Previous Rese Acknowledge Silence
1
MODEL: EQ3800
(006691-001) S/N:
DATE CODE:
INPUT VOLTAGE: 24 Vdc NOM. 18-30 Vdc
C7064E5014 SERIES
INPUT CURRENT: 20A
OUTPUT VOLTAGE: 27 Vdc NOM.
BATTERY OUTPUT CURRENT: SEE MANUAL
POWER GROUND MUST BE INSTALLED IN
POWER FAULT FAULT SUITABLE NRTL LABELED
NEMA RATED ENCLOSURE HYDROGEN SULFIDE EQ2200DCU SERIES
2 3 + -
INPUT
+ -
CONTROLLER
+ - + -
LOCAL PWR FIELD PWR
+ - + - + - + -
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
BACK-UP SENSOR
EQ22xxDCU SERIES DIGITAL
(Tamb -40°C TO +40°C) COMMUNICATION UNIT
EQ3800 PDM DIGITAL (CLASS I, DIV 1 (006705-001)
CL I, DIV 2 GRPS A, B, C & D(T3A) COMMUNICATION UNIT LOCATIONS ONLY) (006684-001)
CL I, ZONE 2, GRP IIC (T3) (006684-001)
(007372-001)
6
LOCAL POWER
PIR9400 SERIES
EAGLE QUANTUM PREMIER 8 CHANNEL DCIO
MODEL: EQ22xxDCU SERIES INFRARED GAS SENSOR
DETECTOR ELECTRONICS CORPORATION S/N:
MINNEAPOLIS, MN, USA
DATE CODE:
(CLASS I (006535-001)
POWER COM 1 COM 2 DIGITAL
FM APPROVED + - S + - S ABS ABS LOCATIONS ONLY, T3C)
COMMUNICATION UNIT OR OTHER
INITIATING DEVICE, NOTIFICATION APPLIANCE FM APPROVED
EQ3700 DCIO ONLY ADDRESS P F
(006684-001)
OR SUPPRESSION ACTUATOR 4-20mA DEVICE 5
C INSTALL PER C
NFPA 70 & 72
HART INTERFACE MODULE C7064E4012 or C7064E5012
P/N 008056-001 FM APPROVED
(007949-001)
HYDROGEN SULFIDE
NOTIFICATION APPLIANCE
INSTALL PER SENSOR
(006705-001)
S3 NFPA 70 & 72
A-3
FM APPROVED FM APPROVED
OR INITIATING DEVICE 5
4-20mA DEVICE
KILLARK EXB-12128 N34 (SEALED OR UNSEALED)
WITH OR WITHOUT GLXR27 WINDOW INSTALL PER
CLASS I, DIV 1, GRPS B, C & D (T5); NFPA 70 & 72
CLASS I, ZONE 1, GROUP IIB (T5); EQ25EMSAM
CLASS II, DIV 1, GRPS E, F, G (T5); CLASS III; EQ22xxIDC/EQ22xxIDCGF SERIES
SIGNAL AUDIBLE MODULE INITIATING DEVICE CIRCUIT
B (Tamb = -40°C TO +60°C) (006753-001, ITEMS 10, 11,12 & 13)
B
NEMA/TYPE 4 (006685-001) CONNECTED IN
OR CONJUNCTION WITH
EAGLE QUANTUM
KILLARK EXB-122412 N34
WITH OR WITHOUT GLXR27 WINDOW FIELD DEVICES
CLASS I, DIV 1, GROUPS C & D;
CLASS II, DIV 1, GROUPS E, F, G; CLASS III EQ24xxNE SERIES
(Tamb = -40°C TO +60°C) EQ25EMARM NETWORK EXTENDER
NEMA/TYPE 4 AGENT RELEASE MODULE (006980-001)
(007568-001) (006752-001, ITEMS 10, 11,12 & 13)
TITLE
1. FM APPROVED DRAWING - NO MODIFICATIONS PERMITTED WITHOUT REFERENCE TO FM. DWG, DESIGN REFERENCE D 007545-001 E
EAGLE QUANTUM PREMIER SYSTEM "FMA"
CADDS NAME: 7545-01e
8 7 6 5 4 3 2 1
95-8533
APPENDIX B
CSA INTERNATIONAL CERTIFICATION DESCRIPTION
HAZARDOUS LOCATIONS
GAS DETECTION
• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 No. 152.
Accuracy: ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL. For the Model PIRECL, refer to the
PIRECL manual (form number 95-8526) for further CSA gas performance details.
NOTE: Detector Electronics combustible gas detection K factors are not CSA verified.
• Calibration of the devices has been CSA verified using the respective EQ22xxDCU, EQ22xxDCUEX and PIRECL
Series with the Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.
• The EQ22xxDCU Series can be used with any CSA Certified 4-20 ma device.
NOTE
CSA Certification of the 4-20 ma input does not include or imply approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain CSA Certification of the system,
all 4-20 ma gas detection instruments connected to the input must also be CSA Certified.
NOTE
CSA Certification allows the presence and operation of serial communications software in the Controller
(MODBUS, Allen Bradley protocols, etc.); however, the communications functions are not included in the
Certification.
8 7 6 5 4 3 1
3.1
CL I, DIV 1 GRPS B, C & D
CL I, DIV 2 GRPS A, B, C & D (T4) CL I, ZONE 1, GRP IIB + H2 (T5)
CL I, ZONE 2, GRP IIC (T4) CL II, DIV 1 GRPS E, F & G, CL III
CL I, DIV 1, GRPS C & D
HAZARDOUS LOCATIONS CL I, DIV 2 GRPS A, B, C & D (T4A)
ORDINARY LOCATIONS CL I, DIV 2, GRPS A,B,C & D (T4A)
(Tamb = -40°C TO +85°C) CL I, ZONE 2, GRP IIC (T4)
(Tamb = 0°C to +50°C) HAZARDOUS LOCATIONS
EXCEPT WHERE SHOWN CL II, DIV 2 GRPS F & G (T4A) (Tamb = -40°C TO +40°C)
HAZARDOUS LOCATIONS NEMA/TYPE 4X
(Tamb = -40°C TO +75°C)
EXCEPT WHERE SHOWN
CGS SERIES
EAGLE QUANTUM PREMIER
Safety System Controller COMBUSTIBLE GAS SENSOR
D EQ22xxDCUEX SERIES (006887-001) D
F1=50mA F2=50mA
Fire Alarm Trouble Inhibit Power
CONTROLLER
1
Low Gas Lon Fault Ack Silence COMMUNICATION UNIT
1
(CLASS I LOCATIONS ONLY)
007390-002 REV. B
S/N:
DATE CODE:
MODEL: EQ3000
Cancel Enter Nex Previous Rese Acknowledge Silence
1
B-2
(007569-001) CSA APPROVED
3
4-20mA DEVICE
OR CSA CERTIFIED
KILLARK EXB-12128 N34 SUPPRESSION ACTUATOR
WITH OR WITHOUT GLXR27 WINDOW
CLASS I, DIV 1, GRPS B, C & D (T5); EQ25EMSAM
CLASS I, ZONE 1, GROUP IIB (T5); SIGNAL AUDIBLE MODULE
B CLASS II, DIV 1, GRPS E, F, G (T5); CLASS III; (006772-001, ITEMS 10, 11,12 & 13)
B
EQ25xxARM SERIES
(Tamb = -40°C TO +60°C)
AGENT RELEASE MODULE
NEMA/TYPE 4 (006771-001)
OR
KILLARK EXB-122412 N34
WITH OR WITHOUT GLXR27 WINDOW CSA CERTIFIED CONNECTED IN
CLASS I, DIV 1, GROUPS C & D; INITIATING DEVICE
EQ25EMARM CONJUNCTION WITH
CLASS II, DIV 1, GROUPS E, F, G; CLASS III (SEALED OR UNSEALED) EAGLE QUANTUM
(Tamb = -40°C TO +60°C) AGENT RELEASE MODULE FIELD DEVICES
NEMA/TYPE 4 (006771-001, ITEMS 10, 11,12 & 13)
(007568-001)
EQ22xxIDC/EQ22xxIDCGF SERIES EQ24xxNE SERIES
INITIATING DEVICE CIRCUIT NETWORK EXTENDER
SUITABLE LOCKED NRTL LABELED 4 (006689-001)
NEMA RATED ENCLOSURE (006981-001)
EQ22xxUV SERIES
UV FLAME DETECTOR
(006690-001) C 7155 COMPLETE MODEL #S FOR NFP & EQ300X.
ADD AIM, IPM, GFM, HIM.
95-8533
APPENDIX C
CE MARK
EMC DIRECTIVE
The Eagle Quantum Premier Fire and Gas Detection/Releasing System was tested and found to be compliant with
EN50081-2, EN50082-2, EN50130-4, and EN50270. The following considerations must be given for installation of the
Eagle Quantum Premier system.
• For shielded cable installed in conduit, attach the wire shields to the “shield” connections on the terminal blocks, or
to the earth ground on the case.
• For shielded cable without conduit, the shields MUST be terminated at the earth ground on the case.
• For double shielded cable, terminate the outer shield to the earth ground on the case. Terminate the inner shield to
the “shield” connection on the terminal blocks.
ATEX DIRECTIVE
The Eagle Quantum Premier Fire and Gas Detection / Releasing System was tested and certified to hazardous
location and combustible gas performance standards. Refer to Figure C-1 for system classification details.
8 7 6 5 4 3 1
CONTROLLER
Fire Alarm Trouble Inhibit Power
MODEL:
4-20mA DEVICE 5
REV. A
AUX
MAIN
POWER
POWER
DIGITAL
INPUT 1
EQ22xxDCU SERIES
007390-002
+ - + - + -
TROUBLE
RELAY
OUTPUT 8
2 3 4 5
NO C NC NO C NC
Cancel Enter Next Previous Reset Acknowledge Silence 42 43 44 45 46 47
CENELEC APPROVED
SUPPRESSION ACTUATOR
EQ25xxARM SERIES
EQ3700 SERIES EQ3710 SERIES
AGENT RELEASE MODULE
DIRECT CURRENT I/O ANALOG INPUT MODULE
DCIO AIM (006976-001)
EEx nC IIC T4 EEx nC IIC T4
DEMKO O2 ATEX 133864U DEMKO O3 ATEX 136207U
T4(Tamb = -40°C TO +85°C) T4(Tamb = -40°C TO +85°C) CENELEC APPROVED
HAZARD LOCATION TESTING
PROJECT REPORT NO. 133864-XX (007944-001) INITIATING DEVICE
C-2
(007534-001) (SEALED OR UNSEALED)
EAGLE QUANTUM PREMIER 8 CHANNEL RELAY EAGLE QUANTUM PREMIER 8 CHANNEL IPM
EQ22xxIDC/IDCSC/IDCGF SERIES
MODEL: INPUT VOLTAGE: 24 Vdc NOM., 18-30 Vdc MODEL:
INPUT CURRENT: 0.12A
DETECTOR ELECTRONICS CORPORATION S/N: RELAY RATING: 30 VDC, S/N:
MINNEAPOLIS, MN, USA 2 AMPS RESISITIVE
DATE CODE: ELECTRONIC ASSEMBLY MUST BE INSTALLED IN DATE CODE:
SUITABLE NRTL LABELED NEMA RATED ENCLOSURE
INITIATING DEVICE CIRCUIT/SHORT CIRCUIT/GROUND FAULT
POWER COM 1 COM 2
+ - S + - S A B S A B S
1 2 3 4 5 6 1 2 3 4 5 6
(006976-001)
007383-003
REV. A
ADDRESS P F
CENELEC APPROVED
MANUAL CALL POINT
EQ22xxMCP SERIES
MANUAL CALL POINT
(006976-001)
B B
CONNECTED IN
EQ3720 SERIES EQ3740 SERIES CONJUNCTION WITH
RELAY MODULE INTELLIGENT PROTECTION MODULE EAGLE QUANTUM
EQ24xxNE SERIES
EEx nC IIC T4 IPM FIELD DEVICES
DEMKO O3 ATEX 135246U EEx nC IIC T4 NETWORK EXTENDER
T4(Tamb = -40°C TO +85°C) DEMKO O3 ATEX 136206U (006976-001)
HAZARD LOCATION TESTING T4(Tamb = -40°C TO +85°C)
PROJECT REPORT NO. 135246-XX C7050B SERIES
(007946-001)
(007804-001)
UV FLAME DETECTOR
EEX d IIC T4-T6 T130∞C
DEMKO 03 ATEX 135866
T6(Tamb = -55°C TO +75°C)
EAGLE QUANTUM PREMIER
POWER DISTRIBUTION
EQ22xxUVHT SERIES
DETECTOR ELECTRONICS CORPORATION MODULE T5(Tamb = -55°C TO +90°C)
MINNEAPOLIS, MN, USA
UV FLAME DETECTOR
MODEL: EQ3700
T4(Tamb = -55°C TO +125°C)
S/N: ELECTRONIC MODULE
DATE CODE:
INPUT VOLTAGE: 24 VDC NOM.
INPUT CURRENT:
OUTPUT VOLTAGE:
OUTPUT CURRENT: SEE MANUAL
HAZARDOUS LOCATION TESTING
POWER GROUND
007389-002 REV. A
POWER FAULT FAULT
+ - S + - S + - S + - S + - S + - S
(006976-001) PROJECT REPORT NO. 135866-XX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
(006924-001)
EQ2220GFM SERIES
EQ3800 SERIES GROUND FAULT MONITOR
POWER DISTRIBUTION MODULE GFM
PDM
EEx nA II T4
EEx nA II T3
DEMKO O3 ATEX 133222U
DEMKO O2 ATEX 133865U
T4(Tamb = -40°C TO +85°C) PIRECLx4 SERIES PIRTB SERIES
T3(Tamb = -40°C TO +85°C)
TERMINATION BOX
HAZARD LOCATION TESTING (007948-001) GAS DETECTOR
PROJECT REPORT NO. 133865-XX EEx d [ib] IIC T4-T5 EEx d IIC T5-T6
(007372-001) DEMKO 02 ATEX 131326
EEx d e [ib] IIC T4-T5 T6(Tamb = -55°C TO +60°C)
B 7150 ADD AIM, IPM, GFM, HIM.
DEMKO 01 ATEX 129485X 4 T5(Tamb = -55°C TO +75°C)
T5(Tamb = -40°C TO +40°C) A 6718 NEW RELEASE 7/03 KAT
T4(Tamb = -40°C TO +75°C) HAZARDOUS LOCATION TESTING
5 WARNING: ENSURE SENSOR HAZARDOUS (CLASSIFIED) LOCATION X3301xxx14 SERIES X2200xxx14 SERIES X9800xxx14 SERIES X5200xxx14 SERIES PROJECT REPORT NO. 131326-XX REV ECO NO. DESCRIPTION DATE APPROVED
RATING IS APPLICABLE FOR THE INTENDED USE. HAZARDOUS LOCATION TESTING DRAWN DATE UNLESS OTHERWISE SPECIFIED
A IR FLAME DETECTOR UV FLAME DETECTOR IR FLAME DETECTOR UVIR FLAME DETECTOR PERFORMANCE TESTING TOLERANCES ARE : A
PROJECT REPORT NO. 129485-XX CDS 6/6/03 DIMENSION TOLERANCE
PROJECT REPORT NO. 132113-XX INCH (MM) INCH (MM)
CHECKED DATE
PERFORMANCE TESTING 0.0 (0) ±.02 ±(0.5)
DETECTOR ELECTRONICS CORP.
4 CONFORMS TO EN 61779-4 FOR COMBUSTIBLE GAS PERFORMANCE EEx d IIC T4-T6 EEx d IIC T5-T6 T86°C PROJECT REPORT NO. 132370-XX (007007-001) 0.00 (0.0) ±.01 ±(0.25)
APP'D DATE MINNEAPOLIS, MINNESOTA 55438
EEx de IIC T5-T6 0.000 (0.00) ±.005 ±(0.13)
EEx de IIC T5-T6 T86°C (007263-001) ANGLE ±1'
DEMKO 01 ATEX 130204 DEMKO 02 ATEX 132195 APP'D DATE REMOVE ALL BURRS BREAK ALL
3 SPECIAL CONDITIONS FOR SAFE USE ('X'): T6(Tamb = -55°C TO +60°C) EDGES AND SHARP CORNERS
T6(Tamb = -55°C TO +60°C)
PERFORMANCE TEMP. RATING -40°C TO +75°C T5(Tamb = -55°C TO +75°C) FIRST USED ON THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY
T5(Tamb = -55°C TO +75°C)
T4(Tamb = -55°C TO +125°C) INFORMATION AND ANY REPRODUCTION DISCLOSURE OR USE
HAZARDOUS LOCATION TESTING BILL OF MAT'L REQ. THEREOF IS EXPRESSLY PROHIBITED WITHOUT THE WRITTEN
2. PART NUMBERS IN PARENTHESIS DEFINE THE DESIGN REFERENCE DRAWING HAZARDOUS LOCATION TESTING PROJECT REPORT NO. 132195-XX NO PERMISSION OF DETECTOR ELECTRONICS CORPORATION.
ASSOCIATED WITH A DEVICE UNLESS OTHERWISE SPECIFIED. PROJECT REPORT NO. 130204-XX (007380-001) SHEET SCALE
1 OF 1 DO NOT SCALE DRAWING N/A SIZE DRAWING NO. REV
(007288-001)
1. DEMKO APPROVED DRAWING - NO MODIFICATIONS PERMITTED TITLE DWG, DESIGN REFERENCE
WITHOUT REFERENCE TO DEMKO. EAGLE QUANTUM PREMIER SYSTEM D 007547-001 B
"DEMKO"
CADDS NAME: 7547-01b
8 7 6 5 4 3 2 1
95-8533
Figure C-1 (Drawing 007547-001)
APPENDIX D
1 X O O O O O O O 71 X X X O O O X O
2 O X O O O O O O 72 O O O X O O X O
3 X X O O O O O O 73 X O O X O O X O
4 O O X O O O O O 74 O X O X O O X O
5 X O X O O O O O 75 X X O X O O X O
6 O X X O O O O O 76 O O X X O O X O
7 X X X O O O O O 77 X O X X O O X O
8 O O O X O O O O 78 O X X X O O X O
9 X O O X O O O O 79 X X X X O O X O
10 O X O X O O O O 80 O O O O X O X O
11 X X O X O O O O 81 X O O O X O X O
12 O O X X O O O O 82 O X O O X O X O
13 X O X X O O O O 83 X X O O X O X O
14 O X X X O O O O 84 O O X O X O X O
15 X X X X O O O O 85 X O X O X O X O
16 O O O O X O O O 86 O X X O X O X O
17 X O O O X O O O 87 X X X O X O X O
18 O X O O X O O O 88 O O O X X O X O
19 X X O O X O O O 89 X O O X X O X O
20 O O X O X O O O 90 O X O X X O X O
21 X O X O X O O O 91 X X O X X O X O
22 O X X O X O O O 92 O O X X X O X O
23 X X X O X O O O 93 X O X X X O X O
24 O O O X X O O O 94 O X X X X O X O
25 X O O X X O O O 95 X X X X X O X O
26 O X O X X O O O 96 O O O O O X X O
27 X X O X X O O O 97 X O O O O X X O
28 O O X X X O O O 98 O X O O O X X O
29 X O X X X O O O 99 X X O O O X X O
30 O X X X X O O O 100 O O X O O X X O
31 X X X X X O O O 101 X O X O O X X O
32 O O O O O X O O 102 O X X O O X X O
33 X O O O O X O O 103 X X X O O X X O
34 O X O O O X O O 104 O O O X O X X O
35 X X O O O X O O 105 X O O X O X X O
36 O O X O O X O O 106 O X O X O X X O
37 X O X O O X O O 107 X X O X O X X O
38 O X X O O X O O 108 O O X X O X X O
39 X X X O O X O O 109 X O X X O X X O
40 O O O X O X O O 110 O X X X O X X O
41 X O O X O X O O 111 X X X X O X X O
42 O X O X O X O O 112 O O O O X X X O
43 X X O X O X O O 113 X O O O X X X O
44 O O X X O X O O 114 O X O O X X X O
45 X O X X O X O O 115 X X O O X X X O
46 O X X X O X O O 116 O O X O X X X O
47 X X X X O X O O 117 X O X O X X X O
48 O O O O X X O O 118 O X X O X X X O
49 X O O O X X O O 119 X X X O X X X O
50 O X O O X X O O 120 O O O X X X X O
51 X X O O X X O O 121 X O O X X X X O
52 O O X O X X O O 122 O X O X X X X O
53 X O X O X X O O 123 X X O X X X X O
54 O X X O X X O O 124 O O X X X X X O
55 X X X O X X O O 125 X O X X X X X O
56 O O O X X X O O 126 O X X X X X X O
57 X O O X X X O O 127 X X X X X X X O
58 O X O X X X O O 128 O O O O O O O X
59 X X O X X X O O 129 X O O O O O O X
60 O O X X X X O O 130 O X O O O O O X
61 X O X X X X O O 131 X X O O O O O X
62 O X X X X X O O 132 O O X O O O O X
63 X X X X X X O O 133 X O X O O O O X
64 O O O O O O X O 134 O X X O O O O X
65 X O O O O O X O 135 X X X O O O O X
66 O X O O O O X O 136 O O O X O O O X
67 X X O O O O X O 137 X O O X O O O X
68 O O X O O O X O 138 O X O X O O O X
69 X O X O O O X O 139 X X O X O O O X
70 O X X O O O X O 140 O O X X O O O X
3.1 D-2 95-8533
Rocker Switch Table
Node Rocker Switch Node Rocker Switch
Address 1 2 3 4 5 6 7 8 Address 1 2 3 4 5 6 7 8
141 X O X X O O O X 211 X X O O X O X X
142 O X X X O O O X 212 O O X O X O X X
143 X X X X O O O X 213 X O X O X O X X
144 O O O O X O O X 214 O X X O X O X X
145 X O O O X O O X 215 X X X O X O X X
146 O X O O X O O X 216 O O O X X O X X
147 X X O O X O O X 217 X O O X X O X X
148 O O X O X O O X 218 O X O X X O X X
149 X O X O X O O X 219 X X O X X O X X
150 O X X O X O O X 220 O O X X X O X X
151 X X X O X O O X 221 X O X X X O X X
152 O O O X X O O X 222 O X X X X O X X
153 X O O X X O O X 223 X X X X X O X X
154 O X O X X O O X 224 O O O O O X X X
155 X X O X X O O X 225 X O O O O X X X
156 O O X X X O O X 226 O X O O O X X X
157 X O X X X O O X 227 X X O O O X X X
158 O X X X X O O X 228 O O X O O X X X
159 X X X X X O O X 229 X O X O O X X X
160 O O O O O X O X 230 O X X O O X X X
161 X O O O O X O X 231 X X X O O X X X
162 O X O O O X O X 232 O O O X O X X X
163 X X O O O X O X 233 X O O X O X X X
164 O O X O O X O X 234 O X O X O X X X
165 X O X O O X O X 235 X X O X O X X X
166 O X X O O X O X 236 O O X X O X X X
167 X X X O O X O X 237 X O X X O X X X
168 O O O X O X O X 238 O X X X O X X X
169 X O O X O X O X 239 X X X X O X X X
170 O X O X O X O X 240 O O O O X X X X
171 X X O X O X O X 241 X O O O X X X X
172 O O X X O X O X 242 O X O O X X X X
173 X O X X O X O X 243 X X O O X X X X
174 O X X X O X O X 244 O O X O X X X X
175 X X X X O X O X 245 X O X O X X X X
176 O O O O X X O X 246 O X X O X X X X
177 X O O O X X O X 247 X X X O X X X X
178 O X O O X X O X 248 O O O X X X X X
179 X X O O X X O X 249 X O O X X X X X
180 O O X O X X O X 250 O X O X X X X X
181 X O X O X X O X
182 O X X O X X O X
183 X X X O X X O X O = OPEN
184 O O O X X X O X X = CLOSED
185 X O O X X X O X
186 O X O X X X O X
187 X X O X X X O X
188 O O X X X X O X
189 X O X X X X O X
190 O X X X X X O X
191 X X X X X X O X
192 O O O O O O X X
193 X O O O O O X X
194 O X O O O O X X
195 X X O O O O X X
196 O O X O O O X X
197 X O X O O O X X
198 O X X O O O X X
199 X X X O O O X X
200 O O O X O O X X
201 X O O X O O X X
202 O X O X O O X X
203 X X O X O O X X
204 O O X X O O X X
205 X O X X O O X X
206 O X X X O O X X
207 X X X X O O X X
208 O O O O X O X X
209 X O O O X O X X
210 O X O O X O X X
3.1 D-3 95-8533
Printed in USA
PRODUCT OVERVIEW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
EQP System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
EQP Safety System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
EQP Safety Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EQP Safety Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
EQPSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
X3301-SIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Eclipse-SIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
EDIO-SIL Enhanced Digital Input/Output Module . . . . . . . . . . . . . . 7
Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
S3 Configuration Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
PROOF TESTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
EDIO Input Channel Proof Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
EDIO Output Channel Proof Test. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
X3301 Visual Field Inspection Proof Test. . . . . . . . . . . . . . . . . . . . . 10
X3301 Magnetic Oi Proof Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PIRECL Visual Field Inspection Proof Test. . . . . . . . . . . . . . . . . . . . 10
PIRECL Gas Response Proof Test. . . . . . . . . . . . . . . . . . . . . . . . . . 11
EQP User Logic Verification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SUITABLE APPLICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General Application Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . 12
INTRODUCTION SCOPE
This Safety Manual describes the actions that must be The Det-Tronics EQP Safety System is intended for use as
taken to use the Det-Tronics Eagle Quantum Premier® part of a programmable electronic system as defined by
(EQP) Safety System in safety-related applications. IEC61508. It is suitable for low demand safety functions
up to safety integrity level 2 (SIL 2).
The actions that are described can be either technical or
procedural. For example, a procedural action would be The safety critical functions for the EQP Safety System
the need to maintain password protection of configuration include the following:
programs, so that non-approved staff cannot modify – Fire input from X3301 and/or EDIO
these.
– Gas alarm from PIRECL and/or EDIO
This document is limited to those actions that are – Annunciation/Release from EDIO
required to ensure compliance with the relevant safety – System logic for processing and mapping inputs and
certifications and standards. Other documents such outputs.
as Manuals and Data Sheets must be referred to for
information outside the scope of this document. These The safety related functions of the EQP Safety System
documents can be found on the Det-Tronics website include the following:
www.det-tronics.com.
– Trouble annunciation for compromised safety function
The Safety Manual is approved and certified by TÜV- by de-energizing the Controller’s Trouble relay
Nord as part of the overall EQP Safety System. Satisfying – Digital input for lockout of inhibits.
the requirements it describes is a necessary part of using
the EQP Safety System in safety-related applications. The EQP Safety System employs a 1oo1D (i.e. 1 out of
1 with diagnostics) architecture to achieve SIL 2. EQP
Failure to complete the actions described in this document Safety Controllers may be used in redundant mode to
would contravene the certification requirements. increase system availability, but this is not required for
the safety-related performance of the system.
Completing the actions described in this document
will only satisfy some of the requirements defined by Configuring and programming the EQP Safety System
IEC 61508 for safety-related applications. It will be must be via a software program known as Safety System
necessary to satisfy the full requirements of IEC 61508, Software (S3).
and for Process Industry applications, the requirements
1.6
1.6 ©Detector Electronics Corporation 2007 8/07 95-8599
95-8599
In addition to completing the actions specifically related PRODUCT OVERVIEW
to the EQP Safety System, it is necessary to satisfy the
wider requirements of IEC 61508. This includes such
EQP SYSTEM
elements within the framework of the safety lifecycle,
such as hazard and risk analysis and defining the safety The EQP System (on which the Det-Tronics EQP Safety
instrumented function. This work must be carried out System is based) was originally developed to meet the
through appropriate and competent Safety Management requirements of industrial fire and gas detection and
procedures and staff. mitigation. The system comprises (see Figure 1):
This Safety Manual describes the actions that must • Field devices for fire and gas detection
be taken to use the Det-Tronics EQP Safety System in • Controllers which can be programmed to carry out the
safety-related applications. The main sections are as control of the fire and gas system
follows: • Power supplies and other miscellaneous hardware
• S3 software which is used to configure the system and
Introduction to generate the logic programs which will be run by
Product Overview gives an overview of the Det-Tronics the Controllers
product range in general and the EQP Safety products in • A proprietary protocol known as Eagle Quantum
particular. Premier Safety Loop (EQPSL), which provides
communication between field devices and the
Proof Testing describes the proof testing that is Controllers.
necessary.
NOTE
Suitable Applications describes the use of the For additional information regarding set-up and
Det‑Tronics EQP Safety System in practical applications. installation of the EQP system, refer to the EQP
Included are failure rate data and PFDavg calculations. system manual, form number 95-8533.
Smoke Detector
Heat Detector
Beacon
Cylinder
1.6 95-8599
EQP SAFETY SYSTEM • EQ2500ARM – Agent Release Module
The Det-Tronics EQP Safety System uses the following • EQ2500SAM – Signal Audible Module
specifically developed components (see Figure 2): • EQ2100PSM – Power Supply Monitor
• EQ300X – EQP Controller • EQ2220GFM – Ground Fault Monitor
• EQ3730EDIO – Enhanced Discrete Input/Output • 008056-001 – HART Interface Module
(EDIO) Module
• X3301 – Multispectrum IR Flame Detector
• PIRECL – Eclipse Infrared Gas Detector Configuration Software
The data required to establish the suitability of the EQP • Det-Tronics Safety System Software (S3)
Safety System for safety-related applications is given in
Appendix A of this Safety Manual.
Non-Interfering Modules
1.6 95-8599
EQP Safety System Component Overview
Figure 2 gives an overview of the role that each element
of the EQP Safety System has in implementing the safety
function.
X3301 MULTISPECTRUM IR FLAME MODEL PIRECL IR COMBUSTIBLE GAS EDIO SAFETY MODULE CONFIGURED EDIO SAFETY MODULE CONFIGURED
DETECTOR IS A SINGLE INPUT DEVICE DETECTOR IS A SINGLE INPUT DEVICE FOR DIGITAL INPUTS. MONITORS THE FOR DIGITAL OUTPUTS. OBEYS
SUITABLE IN LOW DEMAND SIL 2 SUITABLE IN LOW DEMAND SIL 2 INPUTS AND ALSO CHECKS FOR LINE COMMANDS TO SET THE OUTPUTS
SAFETY INSTRUMENTED SYSTEMS. SAFETY INSTRUMENTED SYSTEMS. FAULTS. INTERNAL DIAGNOSTICS SENT BY THE CONTROLLER. INTERNAL
CHECK THAT THE MODULE IS DIAGNOSTICS CHECK THAT THE
OPERATING CORRECTLY. MODULE IS OPERATING CORRECTLY.
IF A FAULT IS DETECTED, OUTPUTS
WILL BE SET TO THEIR SAFE STATE
OF HOLD LAST STATE.
1.6 95-8599
EQP SAFETY CONTROLLERS Communication with Remote Modbus Devices
The EQP Safety Controllers share a common hardware EQP Safety Controllers can read or write data to Remote
and software platform with standard EQP Controllers. Modbus devices. Any data read from such devices
The SIL rated version of the Controller conducts is not safety-related and shall not be used to block or
additional diagnostic checks and annunciates additional disable safety-related logic.
fault conditions.
EQP Controller Inhibit Lockout
Safety compliance is assured by additional diagnostics,
which detect failures and take appropriate action should Device inhibits allow input and output signals to be
errors be detected. blocked to allow the user to perform maintenance and
testing without affecting system outputs. Example: If a
If the EQP Safety Controller detects a “dangerous” flame detector is inhibited, a flame can be presented to
fault in itself (i.e. one that would prevent the EQP the detector and the fire alarm will not be registered by
Safety System from carrying out its safety function) it the controller. Subsequently, no action will be performed
will de‑energize the trouble relay. The fault causing by the controller. Therefore inhibits are classified as a
the Controller’s trouble relay to de-energize must be safety related issue. If a device is inhibited, it will no
investigated and corrected within the time period longer perform its safety function. For this reason, there
determined by SIF verification calculations for the is a global inhibit lockout feature.
particular application.
Input channel four of the safety controller is designated
as the inhibit lockout channel. The channel must be
Run Mode
configured as “Inhibit Enabled” via the EQP controller
Run Mode is the state in which the Det-Tronics EQP configuration screen in the S3 software. A normally open
Safety System is acting as a safety-related system and switch must be wired to channel four to perform the
carrying out its safety function. When the system is in inhibit enable function. When the switch is open, inhibits
this state, it is not possible to make modifications to are not allowed. When the switch is closed, inhibits can
configuration parameters or control logic. be activated from the controller via user configured logic
or from the individual device point displays on the S 3
software.
Program Mode
The system enters Program Mode when configuration When the inhibit lockout switch changes state, it is
parameters are downloaded to the system. The logged in the EQP controller. Additionally, individual
Controller trouble relay is de-energized while in this devices are logged when they are put into the inhibit
mode as an indication. When the EQP System is in state.
Program Mode, the user is responsible for maintaining a
safe state. It is the user’s responsibility to create and enforce an
appropriate lockout policy for the site.
NOTE
When there is a change of configuration, the user is
required to perform a validation test of the change.
1.6 95-8599
EQP Safety Controller Diagnostic Checks EQP SAFETY DEVICES
The EQP Safety Controller automatically carries out a EQP Safety rated field devices share many of the same
number of diagnostic checks on a continuous basis. A attributes as standard EQP devices. They have the same
number of other diagnostic tests are also conducted physical form factor and are connected to the system in
to ensure the integrity of the EQPSL communication the same manner as standard devices. However, SIL
network and proper operation of the user’s logic versions of field devices are not directly interchangeable
program. with the standard versions. Each version has a unique
ID. Each field device must be configured for the
All checks conducted by the Controller are completed at proper type of device or a trouble is annunciated. SIL
least once an hour. This period is called the diagnostic rated devices differ from the standard modules in that
test interval. they perform additional software diagnostic checks
specifically designed for safety‑related applications. SIL
Note rated Controllers and EDIOs have red labels for easy
Other devices have different diagnostic test identification. A mixture of SIL and non‑SIL rated field
intervals. See EQP Safety Device Diagnostics. Be devices can be used on the system at the same time,
sure to account for this in calculations. however, non‑SIL rated devices shall not block or inhibit
the safety function in user logic.
The certifying authority that has granted the Det‑Tronics
EQP Safety System approval for use in low demand Self‑detected failures of the diagnostics will result in
SIL 2 safety-related applications has confirmed the a fault state where the condition is reported to the
completeness of the diagnostic tests. The user program controller and annunciated to the user. Depending on
requires no additional on-line diagnostic tests. Proof the type of fault, the field device may restart and attempt
testing, which is the responsibility of the user, is to re-establish communication with the controller.
discussed in the “Proof Testing” section of this manual.
EQPSL
Redundant EQP Safety Controllers
The EQP controller and associated field devices are
Using Det-Tronics EQP Safety Controllers in redundant connected via the EQPSL communication loop. Only
mode will increase their availability, but will have no EQP system approved devices can be connected to
effect on their ability to perform a safety-related function. EQPSL network (closed network). Devices from other
The redundant controller system is certified for use as manufacturers shall not be connected to the EQPSL.
part of a SIL 2 system. Special test pattern messages are periodically sent end
to end on the EQPSL to detect faults in the transceivers
When a second Controller is added for redundancy, the and memory buffers.
firmware versions must match. Controllers configured
for redundant operation operate in either Master or Extensive diagnostics are implemented in the EQPSL
Standby mode. Refer to the EQP system manual to detect degraded conditions and ensure that reliable
(number 95‑8533) for more details regarding controller communications are available when needed to respond
redundancy set-up. to a demand. This is especially important as Fire and
Gas systems are traditionally energize to trip and it is,
therefore, unacceptable for them to trip based on loss of
power or network communications.
1.6 95-8599
EQP Safety Device Diagnostics EDIO-SIL Enhanced Digital Input/Output
Module
The EQP Safety devices (EDIO/X3301/Eclipse)
automatically carry out a number of diagnostic checks The SIL EDIO module provides eight channels of
on a continuous basis. All checks are completed at configurable digital input or output. The EDIO Module
least once every two hours (diagnostic test interval). is specially designed to meet the requirements of
IEC‑61508 and expands the input and output capability
Failure of any field device diagnostic will cause the of the Det-Tronics Eagle Quantum Premier System.
trouble relay on the Controller to open. It is the user’s The EQP Controller continuously monitors the status
responsibility to determine what course of action is of the EDIO and controls the outputs with EQPSL
appropriate for their situation when the Controller’s communications.
trouble relay opens.
Each channel of the EDIO safety module can be
The internal diagnostic tests carried out by EQP Safety configured as an input to accept fire detection devices
devices are sufficient to meet the requirements for use in such as manual alarm stations, or as an output for
a low demand SIL 2 safety function. Proof testing, which signaling or releasing. Both input and output circuits
is the responsibility of the user, is discussed in the “Proof can be configured for supervised (line monitoring) or
Testing” section of this manual. unsupervised operation. Channels are only SIL rated
when configured for the supervised mode of operation.
Unsupervised channels can be used for non-safety
X3301-SIL
related uses and are considered non-interfering. It is
The SIL EQP Model X3301 flame detectors are the responsibility of the user to select suitable SIL rated
configured with the use of S3 software and the device is I/O devices to connect to the EDIO.
safety rated at all available sensitivity settings. The fire
alarm status should be used as the safety input signal for This table indicates which EDIO channel configurations
user logic. System “Proof Testing” should be conducted are IEC-61508 SIL rated.
after any change in configuration is made.
Definition SIL Rated
ECLIPSE-SIL Unsupervised Input No
The SIL EQP Model PIRECL combustible gas detectors Unsupervised Output No
are configured via S3 software and the device is safety Smoke Detector No
rated. High and low alarm status should be used as the
safety input signal for user logic. The floating point gas Class A Output Yes
concentration value is available for information, but is not Class A Input Yes
safety rated and should not be used as part of the safety Solenoid Output Yes
function. System “Proof Testing” should be conducted
after any change in configuration is made. Class A Solenoid Output Yes
Class A Smoke Detector Input No
warning Class B Output with Monitoring Yes
The Safety Certification of the PIRECL PointWatch
Eclipse does not include the external HART Class B Input with Monitoring Yes
communication port. HART communication cannot
be used while operating in the Safety operation Detailed information regarding the use of the EQP
mode. EDIO Safety Module is given in the appropriate data
sheets and user documentation (EQP instruction manual
number 95-8533). The information given here only refers
to the safety-related aspects of the module.
1.6 95-8599
EDIO Digital Input Channel S3 CONFIGURATION SOFTWARE
A change in input state is only recognized if the new S 3 Software is an engineering tool for configuring
input state is held for a filter time interval to ensure that parameters and writing control programs (known as
noise is not incorrectly interpreted as a change in the Projects) that are downloaded to EQP Controllers. The
input state. The input must be active for at least 750 creation of the Project is the responsibility of the user
milliseconds in order to be recognized. and must conform with the restrictions in this manual.
For descriptions and examples of how to provide open, This Section describes the features of S 3 Software
and open/short circuit monitoring, and Class A or Class applicable to the EQP Safety System. More general
B wiring on EDIO inputs, refer to the Installation section information regarding the operation and use of S 3 can
of the EQP Instruction Manual, 95-8533. Refer to be found in the S3 manual (number 95-8560).
Appendix A for the different lDU values for open versus
open and short circuit monitoring. A summary of S 3 Software features specific to its use
with EQP Safety Systems is given below.
EDIO Digital Output Channel • Only input data from safety approved field devices
(X3301-SIL/Eclipse-SIL/EDIO-SIL) can be used as
The EDIO output channel is normally de-energized and safety data in EQP Safety Logic.
must employ line supervision to be safety rated.
• Safety-related inputs and outputs are colored red to
For descriptions and examples of how to provide open, distinguish them from non-safety related I/O.
and open/short circuit monitoring, and Class A or • User function blocks that are suitable for safety-related
Class B wiring on EDIO outputs, refer to the Installation data are colored red to distinguish them from functions
section of the EQP Instruction Manual, 95-8533. Refer that are not suitable for safety-related data.
to Appendix A for the lDU value for open and open and • Floating point values are not safety rated and must not
short circuit monitoring. be used in the safety-related logic.
• Numeric calculations are not error checked for overflow
POWER SUPPLIES or underflow and the results of such calculations are
The power supply selected must provide over-voltage not defined. It is the user’s responsibility to bound
protection to the EQP System. The over-voltage inputs so such a condition cannot happen.
protection must be set for a maximum of 33 Vdc. • Change control logging and event recording are
available within S3 and EQP Safety Controllers.
The EQP Safety System is NFPA-72 certified for use
with Det-Tronics EQP Power Supplies, power supply While S3 is acceptable for configuring a low demand SIL
monitoring, and ground fault monitoring. 2 EQP System, it shall not be part of the safety function.
1.6 95-8599
S3 Password Protection Restricted Access Enabled
The user must define what measures are to be applied to This feature is intended to give limited access of the
protect against project changes. S3 provides safeguards EQP port configurations for viewing and documentation
described in the following paragraphs. purposes.
Access to the S 3 software program is restricted by User accounts can be created with only the “restricted
password protection. Passwords can be changed at access” checkbox selected, or combined with the
any time by the user with correct privileges. other checkboxes — configure system, quit online, port
diagnostics.
S 3 supports up to 63 unique user accounts, each
capable of having a different password and access
S3 Change Control Log
privileges. These user accounts are controlled by the S3
system administrator. S3 maintains a Configuration Log that records changes
in the master project file. The log can be viewed from
S3.
Configuring User Accounts
There are five parameters that are used to configure the A record is made in the Configuration Log when:
users account. • IO Modules are added, deleted, or moved
• Tags are added to, removed from, or moved within an
User Level IO Module
A user level between 0 and 65535 is used to determine • IO Configuration parameters are saved
what a user can do. Each command or button that a • External node numbers are entered or modified
user can interact with in S3 has a user level assigned to
it. The higher the number, the higher the “privileges” for • Serial communications parameters are entered or
that user. A user level of “0” would allow “browsing” only modified
with no command capability. • A successful download is made to a Controller
• A project is removed.
Configure System Enabled
When selected, this option allows the user access to S3 Function Block Logic
the engineering and configuration aspects of the S 3 The S 3 software allows users to customize application
software suite. This includes the ability to make, move, software with the use of function block logic. For SIL
configure and delete ports and the ability to create or certified systems, SIL rated function blocks must be
modify points like fire detectors, gas detectors, analog used to comply with the SIL-2 certification.
transmitters, digital inputs, etc. attached to one or more
of the available ports. The SIL rated function blocks and associated input and
output links are color coded red to help the user identify
Quit “Online” Operations Enabled quickly if there are any non-compliant blocks. Refer to
Appendix B for a list of available function blocks.
When selected, the user is able to quit online operations
and return to the S 3 main screen for access to the Clearly separate safety-related function logic from
various engineering and maintenance utilities. non‑interfering logic. Place all safety functions on their
own logic pages, and place all non-interfering functions
Port Diagnostics Viewing Enabled on their own logic pages.
1.6 95-8599
PROOF TESTING weekly to confirm that there are no obstructions in
the optical field of view. Corrective action will include
After installation and start-up have been completed, removal of such impediments should they exist.
Proof Tests must be performed for the Det-Tronics EQP
Safety System.
X3301 MAGNETIC Oi PROOF TEST
Personnel performing Proof Test procedures must be Tools Required:
competent to perform the task. All Proof Test results • Magnetic oi test tool (part number 102740-002)
must be recorded, analyzed, and any errors in the safety
functionality must be corrected. The Proof Tests must All flame detectors must be performance tested using
be performed at a frequency as shown in the following the Magnetic oi Procedure and inspected to ensure that
table. they are capable of providing expected performance
and protection. Note that the Magnetic oi Procedure
WARNING and Manual oi Tests are not interference free. During
To prevent undesired actuation of alarm equipment, these tests the unit is not performing normal flame
systems or signaling devices, be sure to secure detection functions. Model X3301 provides an onboard
these devices prior to performing the test. status LED, which indicates Green color when internal
operational parameters are normal. Upon successful
EDIO INPUT CHANNEL PROOF TEST completion of the Magnetic oi test, the LED changes
to a Red color and an alarm status is sent to the EQP
Tools Required: None controller. In the event the proof test is unsuccessful, the
LED remains Green and the controller does not indicate
Initiate the input channel via the connected contact a fire alarm.
closure device. Verify correct operation at the EDIO
by the local channel LED turning red. If the input is
classified as a flame or gas device, verify correct alarm PIRECL VISUAL FIELD INSPECTION PROOF TEST
display at the EQP controller. Tools Required: None
EDIO OUTPUT CHANNEL PROOF TEST Visual inspection of all Safety-Certified PIRECL Gas
Detectors shall be conducted weekly to confirm that no
Tools Required: None external blockage of gas/vapor path into the sensing
chamber exists, e.g. debris, trash, snow, mud, external
Initiate the EDIO output channel by the user logic or equipment, etc. Corrective action shall include removal
activate the associated input devices (EDIO input, flame of such impediments should they exist. All gas detectors
detectors, gas detectors, etc.). Verify correct operation must be inspected to ensure that they are capable of
at the EDIO by the local channel LED turning red. Verify providing expected performance and protection. Model
that the end device connected to the EDIO channel is PIRECL provides an onboard status LED that indicates
activated. Green color upon inspection when internal operational
parameters are normal. Abnormal operating parameters
X3301 VISUAL FIELD INSPECTION PROOF TEST are indicated by Amber color (Fault) or Red color (Gas
Alarm).
Visual inspection of all Safety- Certified X33 01
Multispectrum IR Flame Detectors shall be conducted
1.6 10 95-8599
PIRECL GAS RESPONSE PROOF TEST INSTALLATION
Tools Required:
General installation instructions are found in the
• Compressed Calibration Gas Kit (part number instruction manual for the EQP system, form number
006468‑001) available from Det-Tronics 95‑8533.
This proof test, commonly referred to as a “gas bump Like other Det-Tronics EQP products, the ingress
test”, requires application of high accuracy compressed protection rating of the EQP Safety Controller and EDIO
calibration gas to the detector while in NORMAL is IP20. It will be necessary to mount the EQP Safety
operational mode and inspecting the signal output level Controller and EDIO in a suitable enclosure to provide
to ensure that the signal output is accurately indicative of mechanical and ingress protection appropriate to the
the applied test gas concentration. particular application. X3301 is IP66 minimum and
PIRECL is IP67 minimum.
When test gas is flowing into the detector, inspection
of proper gas response can be made by reading the Access can be restricted by mounting the EQP controller
output displayed on the controller. Criteria for inspection in a locked enclosure.
pass is a response signal within ±3% of applied gas
concentration (50% LEL test concentration applied).
If response test is not within acceptable limits, then a SUITABLE APPLICATIONS
Full Calibration procedure must be performed and Gas
Response Proof Test re-performed. The EQP Safety System can be used to provide safety
functions up to Safety Integrity Level 2 (SIL 2). It can be
EQP USER LOGIC VERIFICATION used in low demand applications only.
All user Safety Logic needs to be fully tested and Typical low demand applications are:
verified using the safety inputs and outputs. This is a
• Fire and Gas protection systems, which monitor for the
commissioning activity, however, if logic is modified
presence of fire or a release of gas, and annunciate/
in the future, proof testing must be repeated. If the
release when demanded upon.
Controller is replaced, project information must be
loaded into the new Controller and verified. The CRC
In this case, the process safety time must be greater
of project related data is calculated and saved by the
than the response time of the EQP Safety System.
controller after each project download. The project CRC
can be viewed on the Controller’s display under User
Logic/General Info/Logic CRC. The project CRC should
be recorded and saved when proof testing is completed.
The project CRC from the Controller must be compared
to the saved value when a Controller is replaced to avoid
complete proof testing of the system.
1.6 11 95-8599
GENERAL APPLICATION REQUIREMENTS S3 Safety System Software
Programming, downloading safety-related parameters
System Application Restrictions
and programs and switching between operating states
The following application level restrictions have been is carried out via an engineering workstation using S 3
assumed: Software.
• The EQP system is only used for safety applications
that are low demand according to IEC-61508 Access to the Programming Interface shall only be
definitions. permitted for authorized and suitably qualified personnel.
Access must be restricted by the use of passwords (and
• Only Det-Tronics EQP system devices may be the options to do this are provided for within S3 Software)
connected to EQPSL network (closed network). and/or some other forms of restricting access.
• Physical EQPSL network topology is limited to a single
loop. The Programming Interface may be used as the Operator
• Indication of degraded conditions through opening of Interface, but use of the Programming Interface must be
the EQP controller’s fault relay must be investigated restricted to authorized and qualified personnel.
and corrected within time period determined by SIF
verification calculations for the particular application. Instructions for using S 3 and typical application
examples are provided in the S 3 Instruction Manual
• Periodic proof testing of trip signals through (number 95‑8560).
EQPSL network at least once per 5 years (1 year
recommended).
Hardware Fault Tolerance, Safe Failure Fraction
• Periodic proof test of input sensors at least once per 3
and Sub-System Type
years (1 year recommended).
• Product life limited to 20 years. The EQP Safety System is a Type B system, with a
hardware fault tolerance of 0 and a safe failure fraction
• The EQP System is operated within the environmental of >90%. It is, therefore, suitable for use in safety
conditions described in the Specifications section of functions requiring a safety integrity level of 2.
EQP Instruction Manual (number 95-8533).
1.6 12 95-8599
Table 1 provides the low demand EQP SIL 2 Safety Example 2 (Figure 3B)
Function model and recommendations for complex
Gas alarm from a PIRECL and output to an EDIO.
modeling (see Note 3).
PFDavg = 0.58 x 10 -3 + (0.38 x 10 -3 + 0.1 x 10 -3) +
PFDavg for each element is calculated according to the
0.1 x 10 -3 + valve & supply = 1.16 x 10 -3 + valve & supply
equation above, where lDU is the undetected dangerous
failure rate per 109 hours and T1 is the proof test interval.
(In this example, T1 is chosen as 1 year (8760 hours) for Example 3 (Figure 3C)
all components of the safety function).
Input from an EDIO and output to the same EDIO.
The value of PFDavg for the system is the sum of
PFDavg = 0.003 x 10 -3 + (0.38 x 10 -3 + 0.1 x 10 -3) +
PFDavg for the individual elements.
0.1 x 10 -3 + valve & supply = 0.58 x 10 -3 + valve & supply
note
Using the table given in the standard, this value would
The EQP system is an energize to trip system.
be suitable for a low demand SIL 2 safety function.
The power supply to the output device should be
Other conditions (hardware fault tolerance and safe
monitored and annunciated when lost. This is
failure fraction) also allow its use in a SIL 2 application.
counted as a Dangerous Detected (DD) fault. If the
power supply is not monitored, it must be counted
See IEC 61508-6 for a more comprehensive guide to the
as a Dangerous Undetected (DU) fault.
calculation of PFDavg.
EDIO OUTPUT
X3301 Fire Input 96.6% 7,070 FIT 242 FIT 226 FIT 2,980 FIT
(OPEN MONITORING)
NOTE 1: The table includes consideration to a 246 node system with 6 Network Extenders, 14 Physical Layer Repeaters, maximum
cable distance, and a 1-year Proof Test Interval (NFPA 72 requirement) with usage of less than 65% of the SIL 2 budget.
NOTE 2: One EDIO provides both the input channel and the output channel.
NOTE 3: For complex modeling of the EQP System, reference the Exida tool at www.exida.com.
1.6 13 95-8599
X3301 Simplex EQ300x EQ3730EDIO
IR FLAME EQP SAFETY EQP SAFETY VALVE
DETECTOR CONTROLLER* EDIO**
λDU IS FAILURE RATE PER 109 HOURS, TP OF 1 YEAR = 8760 HOURS, PFDavg IS THE PROBABILITY OF FAILURE ON DEMAND.
λDU IS FAILURE RATE PER 109 HOURS, TP OF 1 YEAR = 8760 HOURS, PFDavg IS THE PROBABILITY OF FAILURE ON DEMAND.
λDU IS FAILURE RATE PER 109 HOURS, TP OF 1 YEAR = 8760 HOURS, PFDavg IS THE PROBABILITY OF FAILURE ON DEMAND.
* Single Input Configuration with Open & Short Monitoring.
λDU for Components Common to both Inputs
and Outputs Contained in EDIO and Output
Calculation
PFDavg = Σ (1/2 • T1 • λDU) ** Includes Worst Case Safety Communication
(λDU = 22.8, PFDavg = 0.1 x 10-3)
***Single Output Configuration, Monitored for Opens
****See note in Calculating PFD for Low Demand Applications
1.6 14 95-8599
System Response Time Applicable Standards
The EQP Safety System will have a typical response • IEC 61508:2002. “Functional Safety of Electrical/
time of less than 1 second, to which must be added Electronic/Programmable Electronic Safety-related
the response time of the final elements to give the total Systems”.
response time.
• IEC 61511:2003. “Functional Safety - Safety
The worst case theoretical response time of the EQP Instrumented Systems for the Process Sector”.
Safety System, the time taken from an input transition • EN 54-2:1998. “Fire Detection and Fire Alarm Systems
being detected to an output being asserted, is estimated Part 2: Control and indicating equipment”.
by the following: • NFPA 72: 2002. “National Fire Alarm Code”.
• Detection at field device to the Controller over EQPSL • EN 50270:1999. “Electromagnetic Compatibility
network - Electrical apparatus for the detection and
measurement of combustible gases, toxic gases or
– Small system <100 field devices < 3.2 seconds oxygen”.
(user logic constrained to 0.5 seconds)
• EN 50130-4:1996 Re-affirmed 2004. “Electromagnetic
– Large system >100 field devices < 9.1 seconds compatibility- Product family standard: Immunity
(user logic constrained to 1.5 seconds). requirements for components of fire, intruder and
social alarm systems”.
• Worst case response times assume user logic • ANSI/FM 3260 (Flame perf.)
execution time is constrained to
• FM 6310/6320 (Gas Perf.)/ISA-12.13.01.
– Small system < 0.5 seconds
• CSA C22.2 #152 (Gas Perf.)
– Large system < 1.5 seconds.
• EN 61779-1 & -4 (Gas Perf.)
• Worst case Controller to EDIO output < 6.3 seconds. • IEC 61779-1 & -4 (Gas Perf.)
• ANSI/ISA 12.13.01. “Performance Requirements for
• Worst case response times assume a high level of Combustible Gas Detectors”.
lost messages due to internal or external influences,
and three subsequent retries.
note
The worst case theoretical response time, as
required by IEC 61508, will only occur once per
1,000,000 trips. It must occur during the worst
case degraded communication conditions possible
without generating a communication fault.
NOTE
The process safety time must be compared with
the response time of the entire safety function. In
addition to the response time of the EQP Safety
System, the response time of the input sensors and
output actuators must be included.
1.6 15 95-8599
APPENDIX A
SUMMARY OF SAFETY RELATED DATA
Part Model lDU (dangerous undetected failure rate per 109 hours)
Common = 20.9
EDIO Safety Module -
EQ3730EDIO Input Monitored for Opens = 6.6
Configured as Input*
Input Monitored for Opens & Shorts = 0.68
* “Common” are components common to both inputs and outputs. For lDU calculation:
Example 1: Input and output on same EDIO
lDU = Common + Input + Output
lDU = 20.9 + 0.68 + 0.92 = 22.5
Example 2: Input and output on different EDIOs
lDU = lDU EDIO #1 + lDU EDIO #2
= (Common + Input) + (Common + Output)
= (20.9 + 0.68) + (20.9 + 0.92) = 43.4
1.6 16 95-8599
Appendix B
The “SIL” column indicates if the instruction is suitable for use with alarm processing with a 61508 approved system.
Instructions that utilize stored values which are not duplicated, or instructions that depend on the floating-point or
string libraries are not safety rated.
1.6 17 95-8599
AVG d, AVG d n Average. The first form reads all the values from the stack. The second Yes for all but
form reads n values. The values on the stack can be integer, double or floating-point
float. All values will be of the same type and the result will be of the same values
type. The values are popped from the stack and the result is placed on
the stack. Average is the value obtained by dividing the sum of the value
on the stack by the number of values. (8.0 + 7.0 + 8.0) / 3 = 17.6. The
instruction is followed by the data type and then the count, if present. i.e.
AVG 3 4 or AVG 3
BINT Boolean to Integer. The value on stack is a Boolean. The result will be a Yes
“0” or a “1”.
BRA X Branch. If the accumulator is a one then branch the number of lines Not supported
equal to X. X will always be greater than zero. If X is greater than the yet
number of lines remaining in –the program/section then jump to the
beginning of the next program/section.
BRZ X Branch on zero. Same as BRA but branches on a zero in the Not supported
accumulator. yet
BTW d Between. The values on the stack can be integer, double or float. All Yes for all but
items will be of the same type. The stack has three items on it. The first floating-point
two are the comparison values and the third is the compare item. All values
items are removed from the stack and the third item is compared against
the first two items. If the third item is <= the first item and >= the second
item a one is placed in the accumulator else a zero is placed in the
accumulator. The result is a Boolean. Ex.: I1 = 50 I2 = 25 I3= 40 then a
one is place in the accumulator. The instruction is followed by the data
type.
BTWT Time compare. The BTWT instruction is followed by three time/date No
memory locations. The high time, followed by the in value, followed by
the low time. The result, a Boolean, is placed on the stack. The output is
true if the in value is between or equal to the high and low.
CEIL Ceiling. The value on the stack is a float. The result will be a double. No
Round up. –2.8 = -2, 2.8 = 3, -1 = -1
CST Clear stack. The stack pointer is set to the top of the stack Yes
CTD Down Counter. Three items are pushed onto the stack. The “count down No
(CD)” a Boolean, the “Load (LD)” a Boolean and the “Present (PR)” a
double. All items are removed from the stack.
Then the CTD instruction followed by the current value location, a double
and the CD prior state, a Boolean. Ex. “CTD 12.24.0 10.89” When the
CD input is true and the LD input is false the counter counts down. The
current value is then placed on the stack.
The Boolean result is true if the current value is less than or equal to zero
and is placed on the stack. The counter stops counting when the current
value reaches –2,147,483,648. When the LD is true the PR is loaded
into the current value to initialize the counter and the counter does not
increment.
CTD-SIL SIL Down Counter. The SIL Down Counter operates the same as the Yes
standard CTD but provides duplicate storage for the persistent values.
Then the CTD-SIL instruction followed by two current value locations,
doubles and two locations for the CD prior state, Booleans.
1.6 18 95-8599
CTU Up Counter. Three items are pushed onto the stack. The “count up (CU)” No
a Boolean, the “Reset (R)” a Boolean, and the “Present (PR)” a double.
All items are removed from the stack. Then the CTU instruction followed
by the current value location, a double and the CU prior state, a Boolean.
Ex. “CTU 12.25.0 10.15” When the CU input is true and the R input is
false the counter counts up. The current value is then placed on the
stack. The Boolean result is true if the current value is greater than or
equal to the PR and is placed on the stack. The counter stops counting
when the current value reaches 2,147,483,647. When the R is true the
current value is set to zero.
CTU-SIL SIL Up Counter. The SIL Up Counter operates the same as the standard Yes
CTU but provides duplicate storage for the persistent values. Then the
CTU instruction followed by two current value locations, doubles and two
locations for the CU prior state, Booleans. Example: “CTU-SIL 12.25.0
12.26.0 10.15 10.16”
CTUD Up/Down Counter. Five items are pushed onto the stack. The “count up No
(CU)” a Boolean, the “count Down (CD)” a Boolean, the “Reset (R)” a
Boolean, the “Load (LD)” a Boolean and the “Present (PR)” a double. All
items are removed from the stack.
If the current value is greater than or equal to the PR, a Boolean true is
placed on the stack else a Boolean false is placed on the stack. This is
the QU result.
If the current value is less than or equal to zero, a Boolean true is placed
on the stack else a Boolean false is placed on the stack. This is the QD
result.
Then the CTUD instruction is followed by two locations for the current
value, doubles, two locations for the CU prior state, Booleans and two
locations for the CD prior state, Booleans.
1.6 19 95-8599
DIV d Divide. The values on the stack can be integer, double or float. The first Yes for all but
item is the dividend followed by the divisor is pushed on the stack. The floating-point
items are removed from the stack. The result type is the same as the two values
inputs.
(X / Y) Y is pushed on the stack and then X. The instruction is followed
by the data type.
DBLTOSTR When the enable input is high the 32-bit double input value is converted No
to a string. The input value can come from any valid double source. The
instruction is followed by the enable (boolean), last enable (boolean),
source and destination reference.
DTTOINT Date/Time to integers. The conversion is executed and the seconds, No
minutes, hour, day, month and year are placed in local memory locations.
The instruction is followed by the address of the date/time structure and
the starting address in the local memory integer area. The results are
placed in the first location and subsequent 5 locations
END This instruction shall be placed as the very last instruction of the Yes
program. Logic execution will loop back to the beginning when this
instruction is seen.
ET d Equal To. The values on the stack can be integer, double or float. Pop Yes for all but
the values from the stack, the instruction is executed and the results are floating-point
stored on the stack. The result is a Boolean. The instruction is followed values
by the data type.
EventTrigger (Add an Event to the Controller Alarm List): No
This function is used to add an event to the controllers alarm list. This
can be used to trigger, log and display events that are initiated by user
logic. When the enable input is activated the event information defined
in this function is entered into the controllers alarm list (info displayed on
the controllers faceplate). This function also provides an input to control
if the event is self-clearing or latched until the controller reset is activated.
The word “Event” will be displayed in the screen position that normally
displays the type of alarm. Must be in the normal program, must not be
in the first scan or moves programs.
FLOOR Floor. The value on the stack is a float. The result will be a double. No
Round down. –2.8 = -3, 2.8 = 2, -1 = -1
FRAC Fraction. The value on the stack is a float. The result will be a float. No
123.456 = 0.456.
GT d Greater Than. The values on the stack can be integer, double or float. Yes for all but
Pop the values from the stack, the instruction is executed and the results floating-point
are stored on the stack. The result is a Boolean. (X > Y) Y is pushed on values
the stack and then X. The instruction is followed by the data type.
GTE d Greater Than / Equal To. The values on the stack can be integer, double Yes for all but
or float. Pop the values from the stack, the instruction is executed and floating-point
the results are stored on the stack. The result is a Boolean. (X >= Y) Y is values
pushed on the stack and then X. The instruction is followed by the data
type.
IF d The first value can be Boolean, integer, double, string or float. It will be No
of the same type as the output address referenced. The second value
on the stack is a Boolean. The items are popped from the stack. If the
second input is false nothing is done. If the second input is true the
value on the stack is stored in the address referenced. The instruction is
followed by the data type and the address to store the result.
1.6 20 95-8599
FLTTOSTR When the enable input is high the floating-point input value is converted No
to a string. The input value can come from any valid floating point source.
The precision number determines the number of decimal digits. The
instruction is followed by the enable (boolean), last enable (boolean),
source, precision (integer) and destination references. Valid values for
precision are 0 to 6, if the value is out of range 6 is used.
IN Load the value of the item referenced into the accumulator. The item Yes for all but
referenced must be from local memory. In the case of stings the floating-point
reference is place on the stack. and string
values
INN This instruction is the same as IN except the value is NOT’d before it is Yes for all but
placed into the accumulator. floating-point
and string
values
INTBOOL Integer to Boolean. The value on the stack is an integer. The result will Yes
be a Boolean. If the integer is non-zero then the Boolean will be true.
INTDBL Integer to double. The value on the stack is an integer. The result will be Yes
a double.
INTTODT Integer(s) to Date/Time. The INTTODT is followed by the memory No
references to the seconds, minutes, hour, day, month and year and the
result memory location. The conversion is done. The result, Date/Time, is
stored in the referenced location.
INTFLT Integer to float. The value on the stack is an integer. The result will be a No
float.
INTTOSTR When the enable input is high the 16-bit integer input value is converted No
to a string. The input value can come from any valid integer source. The
instruction is followed by the enable, last enable, source and destination
reference.
LIMIT d Limit. The values on the stack can be integer, double or float The high Yes for all but
limit, the value and the low limit are pushed on the stack. The values are floating-point
removed and the result is placed on the stack. The result will be between values
the high and low values. If the value is 102 and the high is 100 and the
low is 0 then the result will be 100. The instruction is followed by the data
type.
LT d Less Than. The values on the stack can be integer, double or float. Pop Yes for all but
the values from the stack, the instruction is executed and the results are floating-point
stored on the stack. The result is a Boolean. (X < Y) Y is pushed on the values
stack and then X. The instruction is followed by the data type.
LTE d Less Than / Equal To. The values on the stack can be integer, double or Yes for all but
float. Pop the values from the stack, the instruction is executed and the floating-point
results are stored on the stack. The result is a Boolean. (X <= Y) Y is values
pushed on the stack and then X. The instruction is followed by the data
type.
MAX d, input Maximum Select. The values can be integer, double or float. Same as Yes for all but
count, inputs minimum except the maximum values is selected. The result will be of floating-point
the same type as the inputs. The result is placed on the stack. The data values
type, input count and the inputs follow the MAX instruction.
1.6 21 95-8599
MEDIAN d, input Median. The values can be integer, double or float. All values will be Yes for all but
count, inputs of the same type and the result will be of the same type. The result is floating-point
placed on the stack. Median is the value midway between the values. values
Definition: a) designating the middle number in a series containing an
odd number of items (Ex.: 7 in the series 1, 4, 7, 16, 43) b) designating
the middle number midway between the two middle numbers in a series
containing an even number of items (Ex.: 10 in the series 3, 4, 8, 12, 46,
72) The maximum number of inputs is 32. The instruction is followed by
the data type, input count and the inputs.
MIN d, input Minimum select. The can be integer, double or float. All inputs will be Yes for all but
count, inputs of the same type. The result will be of the same type as the inputs. The floating-point
result is placed on the stack. The data type, input count and the inputs values
follow the MIN instruction.
MOD d Modulo. The values on the stack can be integer or double. The Y and Yes
then the X are pushed on the stack. The items are removed and the
operation is executed The result, the same type as the inputs, is placed
on the stack. The mod operator returns the remainder obtained by
dividing its operands. In other words, x mod y = x – (x div y) * y. For
example: 9/4 is 2.25, but 4 goes into 9 twice with one left over, so 9 mod
4 is 1. The instruction is followed by the data type.
MODBUS Modbus. The Modbus instruction has 9 inputs and 4 outputs. No
Inputs
Enable Boolean, Port # integer (1..4), slave ID integer (0-247), function
code integer (see supported Modbus functions), source register integer
(zero based), count integer, destination register integer (zero based),
timeout integer (1000 to 2000 ms.) and clear error Boolean.
Outputs.
Pending Boolean is set when a read is pending in the queue, Done
Boolean output is true when the read response is received. It is set to
false on error and when the enable input goes from false to true, error
Boolean output is true when an error is detected. It is cleared when the
Clear Error input is true, and error code integer fault (see error codes in
the Modbus section).
“Enabled” and “Clear Error” are pushed on the stack. All other inputs are
constants and are resolved at compile time.
All outputs are referenced addresses and are part of the instruction.
Since the function is asynchronous the outputs values are resolved when
the function is handled.
The port # must be a valid port configured for Modbus Master protocol.
Instruction Example:
MODBUS port #, slave id, function code, source register, count,
destination register, timeout, pending, done, error, error code
1.6 22 95-8599
MODMOVF Used to move a floating-point value to Modbus memory. A floating-point No
value is moved from memory to two adjacent Modbus holding registers.
Example: MODMOVF 13.1.0 (src) 5.3.1.0 (dest)
This example will move the first floating-point value from local memory to
the first and second holding registers.
MOFN M of N. Up to 31 (Boolean) values, followed by the MOFN instruction, the Yes
PR (integer) and the number of inputs (integer). All values are removed
from the stack. The instruction counts the number of inputs (NOI) that are
true. All or the results are Boolean. Then it does three comparisons using
the PR and the NOI. A NOI < PR is done and the result is placed on the
stack. A NOI = PR is done and the result is placed on the stack. And
finally a NOI > PR is done and the result is placed on the stack.
MOV This is used to move data from one location another location. Data can Yes for all but
not be moved to or from the stack and constants can not be used with floating-point
this instruction. and string
Example: MOV 10.0.0 (src) 10.4.0 (dest) values
MOVC This instruction is a compile time instruction. It’s used to move constant Yes for all but
data into local memory area. It has the same format as the MOV floating-point
instruction. The constant value and the destination local memory and string
reference follow the MOVC. The MOVC instruction is not executed as values
part of logic, it’s done at compile time.
Example: MOVC &I123456 11.34
MOVMODF Used to move a floating-point value from Modbus memory to global No
memory. A floating-point value is moved from two adjacent Modbus
holding registers to a global floating-point memory location.
Example: MOVMODF 5.3.1.0 (src) 23.1.0 (dest)
This example will move a floating-point value from the first and second
holding registers to the first global memory location.
MUL d Multiply. The values on the stack can be integer, double or float. The first Yes for all but
item is the multiplicand followed by the multiplier. The items are removed floating-point
from the stack. The result type is the same as the two inputs. The values
instruction is followed by the data type.
MUX selector, Multiplex. X values of Boolean, integer, double, string or float, all values Yes for all but
input count, are the same type. The item indexed by the selector index is placed on floating-point
inputs the stack. The output will be the same type as the inputs. If the selector and string
is out of range a “zero” is placed on the stack. If the selector is zero then values
the output is zero. The legal range for the selector is 1 to 31. The input
count, selector, and the inputs follow the MUX instruction.
NOT Read the value of the accumulator, logically negate the value and write Yes
the result into the accumulator overwriting the original value. Boolean
value only.
NOTX Read the value of the accumulator performs a 16 bit logical complement Yes
of the value and writes the result into the accumulator overwriting the
original value.
ODD d ODD. The value on the stack can be integer or double. The result is a Yes
Boolean.
OR, OR n The first form, OR, reads all the values from the stack, decrements the Yes
stack pointer, performs a logical OR function and writes the result into
the new accumulator location. OR n reads the top n values and performs
the same operation. 0 = False, Non-0 values = True.
1.6 23 95-8599
ORW d, ORW Logical OR. The values on the stack can be integer or double. All values Yes
d, n will be of the same type and the result will be of the same type. Values
are popped from the stack and the result is placed on the stack. The
first form, ORW, reads all the values from the stack, ORW n reads the
top n values. All of the bits of the word are operated on. The instruction is
followed by the data type and the count if included
OSP One shot pulse. The value of the input, a Boolean, is placed on the stack. No
The instruction followed by the local storage, a Boolean, of the last state.
The result, a Boolean, is placed on the stack overwriting the input value.
OSP-SIL One shot pulse SIL. The value of the input, a Boolean, is placed on the Yes
stack. The instruction followed by two local storage locations, a Boolean,
of the last state. The result, a Boolean, is placed on the stack overwriting
the input value.
OUT The value of the accumulator is moved to the item referenced. The stack Yes for all but
is not decremented. floating-point
and string
values
PCK Bit Packing. 16 values are put on the stack via the IN or PUSH instruction Yes
The sixteen values are popped off the stack and the bit weighted result is
placed into the accumulator.
POP Pop the stack. Pop pops the last value off the stack and discards it. The Yes
stack pointer decrements to point to the next item on the stack.
PUSH Push constant data onto the stack. The item is placed on the top of the Yes
stack and the stack pointer is incremented by one.
ROUND Bankers rounding. The value on the stack is a float. The result will be a No
double.
RS Reset/Set instruction. Same as the SR with the following exception: This No
instruction is Reset dominant bistable. If the reset input is true then the
output is false regardless of the set input.
RS-SIL SIL Reset/Set instruction. The SIL Reset/Set instruction operates Yes
the same as the standard RS but provides duplicate storage for the
persistent value.
Example: RS-SIL 10.19.0 10.20.0
RTM Retentive Timer. The timer has three inputs and two outputs. The inputs No
are pushed on the stack in the following order. Enabled a Boolean, timer
preset a double, reset a Boolean, RTM instruction and timer number. All
of the items are removed from the stack and the timer is executed. The
timer complete status, a Boolean and the timer elapsed time, a double,
are placed on the stack in that order. The accumulator is not cleared
unless the reset input is true.
RTM-SIL SIL Retentive Timer. The SIL Retentive Timer operates the same as 15.17 15.18
the standard Retentive Timer but provides duplicate storage for the
persistent values.
Example: RTM-SIL
SCALE d Scale. The values on the stack can be integer, double or float. All the No
values will be of the same type. The output will be of the same type. The
first value is the input. The second value is the low range for the input.
The third value is the high range for the input. The fourth value is the low
range for the output and the fifth value is the high range for the output. All
values are removed from the stack. The instruction is executed and the
result is placed on the stack. The instruction is followed by the data type.
1.6 24 95-8599
SEL d Selector. The first two values can be Boolean, integer, double, string or Yes for all but
float. They will be of the same type and the output will be of this type. floating-point
The third value on the stack is a Boolean. The items are popped from the and string
stack. If the third input is false then the first value is placed on the stack values
and if the third input is true the second value is placed on the stack. The
instruction is followed by the data type.
SQR Square. The value on the stack is a float. The result will be a float. No
SQRT Square Root. The value on the stack is a float. The result will be a float. No
SR Set/Reset instruction. The three items on the stack are the set address, No
reset address the instruction SR followed by the result address. The
items are removed from the stack, the instruction is executed, and the
result is stored in the result location and is pushed onto the stack. This
instruction is the set dominant bistable. If the set input is true then the
output is true, regardless of the reset input.
SR-SIL SIL Set/Reset instruction. The SIL Set/Reset instruction operates the Yes
same as the standard Set/Reset instruction, but provides duplicate
storage for the persistent value.
Example: SR-SIL 10.19.0 10.20.0
STORE Remove and store the value of the accumulator to the memory location Yes for all but
referenced. The location will be a local or global memory. floating-point
and string
values
STRAPD When the enable input is high source string 2 is appended to the end of No
source string 1 and placed in the destination string. If the resulting string
exceeds the maximum string length it will be trimmed. The instruction is
followed by the enable (boolean), last enable (boolean), source 1, source
2 and destination references.
STRCPY When the enable input is high the source string is copied to the No
destination string. The instruction is followed by the enable (boolean),
last enable (boolean), source reference and destination reference.
STRNCPY This function is used to extract parts from a string. When the enable is No
high not more then ‘Count’ characters starting with character ‘Index’ are
copied to the destination string. A null termination will be applied to the
destination string. The instruction is followed by the enable (boolean),
last enable (boolean), count (int), index (int), source and destination
references.
STRTOMB Source string (including the null terminator) is copied to Modbus holding No
registers. The string will be packed into Modbus memory with two
characters per holding register. The first character of the string is placed
in the high order 8-bits of the lowest numbered register. The source
string can be from local memory or from a device item. The destination
must be a Modbus holding register. The instruction is followed by the
source and destination references.
SUB d Subtract. The values on the stack can be integer, double or float. The Yes for all but
first item is the subtrahend followed by then minuend. The items are floating-point
removed from the stack. The result type is the same as the two inputs.
(I had to look up that in 5-3 5 is the minuend and 3 is subtrahend. ;) The
instruction is followed by the data type.
1.6 25 95-8599
TIMEDATE- (TimeDate to String): No
TOSTR When the enable input is high the timedate value is converted to a string.
The input value can come from any valid timedate source. The output
format is selectable. The instruction is followed by the enable (boolean),
last enable (boolean), source (time/Date), format (integer), destination
references. See the format table below.
TOF Off Timer. The timer has two inputs and outputs. The inputs are pushed No
on the stack in the following order. Enabled a Boolean, timer preset a
double, TOFF instruction and timer number. All of the items are removed
from the stack and the timer is executed. The timer complete status, a
Boolean and the timer elapsed time, a double, are placed on the stack in
that order.
TOF-SIL The SIL version of the Off Timer is the same as the normal TOF function Yes
with the addition of duplicate storage for elapsed time variable.
TON On Timer. The timer has two inputs and outputs. The inputs are pushed No
on the stack in the following order. Enabled a Boolean, timer preset a
double, TON instruction and timer number. All of the items are removed
from the stack and the timer is executed. The timer complete status, a
Boolean and the timer elapsed time, a double, are placed on the stack in
that order.
TON-SIL The SIL version of the On Timer is the same as the normal TON function Yes
with the addition of duplicate storage for elapsed time variable.
TRUNC The value on the stack is a float. The result will be a double. 123.456 = No
123
UPCK Bit unpacking the reverse of the pack instruction (PCK). An integer value Yes
is place on the stack. The UPCK instruction is followed by a starting
address in the local Boolean memory area. The resulting bits are placed,
beginning at the starting address and the following fifteen sequential
memory locations.
XOR, XOR n Exclusive OR. The first form reads all the values from the stack. The Yes
second form reads n values. The output is high when the number of high
inputs is odd.
1.6 26 95-8599
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, MN 55438 USA
T: 952.941.5665 or 800.765.3473
F: 952.829.8750
W: http://www.det-tronics.com
X3301 Multispectrum PointWatch Eclipse® Eagle Quantum Premier® Eagle Logic Solver
IR Flame Detector IR Combustible Gas Detector Safety System Safety System E: detronics@detronics.com
Det-Tronics, the DET-TRONICS logo, Eagle Quantum Premier, and Eclipse are registered trademarks or trademarks of Detector Electronics
Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.