Вы находитесь на странице: 1из 8

SIMULATION OF ENERGY CONSUMPTION FOR DEHUMIDIFICATION

WITH COOLING IN NATIONAL MUSEUM IN KRAKÓW


J. Radon1, F. Antretter2 , A. Sadlowska3, M. Łukomski4, L. Bratasz5

ABSTRACT promotes the search for reducing of energy use and


It has been monitored, that about 35 % of all energy operating costs.
in the main building of the National Museum in Passive inner climate in a museum is a result of
Kraków is used in the summer period for cooling and interaction between building assemblies with outer
dehumidification. To refine the process and possibly climate and inner air including internal and external heat
reduce energy demand a series of simulations have and moisture sources. Since inner climate parameters do
been carried out. The main calculative tool was the not meet conservative requirements and cannot provide
WUFI®PLUS software, developed at the Fraunhofer- comfort for visitors, active ventilating, heating, cooling,
Institute for Building Physics, to model the humidifying and dehumidifying systems must be used in
hygrothermal performance of the multi-zone building. most of existing museums.
There is a universal consensus that the museum building
In the analyzed building dehumidification of the air is
and the HVAC should be regarded as a single system.
performed by cooler-heater coils integrated into the
mechanical ventilation system. The process alters Appropriate adjustment of active systems to hygrothermal
significantly temperature and humidity of ventilation building performance and their efficiency has obviously
and recirculated air and thus affects also the energy great impact on energy use in museums [2][5]. The
and heat balance of the simulated zones. The building climate control scenario, defining allowed temperature
and HVAC must therefore be regarded as one coupled and humidity range [6], influences primarily the energy
system. use. In consequence, modeling museum building in terms
of energy, needs clear understanding of building
To account for the dehumidification process in the envelopes and functions of the climate control systems,
museum in a more realistic way a simulation model but at the same time equally clear understanding of
for a cooler-heater coil was built and set into the main climate control strategies to maintain high standards of
loop of zone iteration process. The model is based on collection care.
design assumptions (contact factor, temperature of This paper presents modeling of inner climate and energy
cooling coil, reheating temperature). The model use in the main building of the National Museum in
includes heat recovery from outlet air, mixing of Kraków. Since lot of energy (about 35 % of all energy)
ventilation air with recirculation air, dehumidification was used in recent years for cooling and dehumidification
with cooling and reheating. in summer periods in this building a special focus has
been set on this processes.
Simulation results allowed obtaining the annual
The main calculation tool is the WUFI®PLUS software,
amount of moisture, which must be condensed from
developed, to model the hygrothermal performance of the
the air and energy demand by different indoor
multi-zone building exposed to real climate conditions
environment scenarios including 3 relative humidity
[11]. The software, however, can calculate active systems
ranges and 3 air change rates.
using simplified, idealistic model. Therefore a calculation
Keywords model for cooling and dehumidification was developed
Museum, Dehumidification, Cooling, Energy use, and applied to reflect cooling and dehumidification
Simulation. process in analyzed museum building in more realistic
way.
1. Introduction
2. Building and climate control system
Managing indoor environment in historical buildings,
especially museums, is regarded as energy- and cost- The Main Building of the National Museum in Krakow
intensive. Increasing cost of energy and budget cuts was designed in 1934 as a monumental brick/stone
structure (Figure 1). The design was clearly driven by the

1
Engineering Consulting & Software Development, Poland, jradon@kki.pl
2
Fraunhofer Institute for Building Physics, Germany, florian.antretter@ibp.fraunhofer.de
3
PhD student, Technical University of Kraków, Poland, asadlowska.ar@krakow.pl
4
Institute of Catalysis and Surface Chemistry, Polish Academy of Sciences, Poland, anclukomsr@cyf-kr.edu.pl
5
The National Museum in Kraków, Poland, ncbratas@cyf-kr.edu.pl
Humidifying or dehumidifying of the air is obtained by
steam humidifiers and cooler-heater coils, respectively.
Heater coils are also used in winter to aid the hot water
radiator heating system operating in the building.
Mechanical ventilation both distributes the air
conditioned in the climatic units and provides fresh air
from outside. Level of air recirculation in the building can
be adjusted and energy from exhaust air is partially re
used thanks to recuperators with 50-80% effective
thermal efficiency. Not every unit has HRV. It has been
estimated, that about 18% of ventilation energy is
effectively recovered from exhaust air in the whole
building.

Figure 1 Main façade of National Museum in


Kraków 3. Modeling
function of the building – among others, thick walls with 3.1 Calculation tool
small windows providing a good isolation of the
exhibitions rooms from the direct impacts of the external WUFI®PLUS is a holistic model based on the
environment and the advantageous thermal inertia were hygrothermal envelope calculation model developed by
design’s characteristic features. The project of Krakow Künzel [10]. The hygrothermal behavior of the building
National Museum was presented during “General envelope affects the overall performance of a building.
Conference on Architecture and Development of Art WUFI®Plus is a building performance simulation tool
Museums” in Madrid 1934. The committee of experts which computes the coupled heat and moisture transfer in
from eighteen countries emphasized modern character of the building envelope. Moisture sources or sinks inside
technical solutions adapted especially in designing the rooms or building components, input from the
lightning, ventilation and communication in the building. envelope due to capillary action, diffusion and vapour ab-
and desorption as a response to the exterior and interior
The first part of the building, encompassing climate conditions as well as the thermal parameters are
approximately a one third of the entire design, was taken into account.
accomplished by 1939 when further construction was
interrupted by the outbreak of World War 2. The second A stable and efficient numerical solver had been designed
part of the museum was finished between 1970 and 1989 for the solution of the coupled and highly nonlinear
according to a modified design increasing the interior equations. The conductive heat and enthalpy flow by
floor area to 19 500 m2 (interior volume of 68 600 m3). vapour diffusion with phase changes in the energy
The modification was made using materials similar to equation are strongly dependent on the moisture fields.
those used in original construction and involved among The vapour flow is simultaneously governed by the
others the addition of a vast expanse of glass at the temperature and moisture field due to the exponential
northern façade, making the modified design arguably changes of the saturation vapour pressure with
less energy-efficient than the original one. Air temperature. The differential equations are discretized by
conditioning was introduced to control stability of the means of an implicit finite volume method.
climate in 80-ies of the past century. Further expansion The model was validated by comparing its simulation
and modernization of the climatic control machinery was results to the measured data of extensive field
done at the beginning of 2000s. As the result, the HVAC experiments [1][3][8][11]. The indoor climate is user
system in the Main Building consists of 11 independently appointed with minimal and maximal design conditions.
controlled units (Figure 2). The software can calculate heat and moisture balances for
more than one building zone, with all the sources, sinks
and transfers. As long as heat and moisture balance is not
il
il

co
co

er
ifi
g
g

equal zero during calculation step the interior temperature


in
in

id
at
ol

m
he

filter
co

hu

supply fun and humidity is adapted. For example, if the heat loss
conditioned through the building envelope and ventilation is more
heat recovery

space
RH
than the internal heat gains plus space heating capability,
T the interior temperature is iteratively decreased as long as
exhaust fun the loss and the gain is the same.

Figure 2 HVAC units operating in the National 3.2 Building model


Museum Main Building As far as the climate control is concerned, the building
can be divided into three distinct zones: unheated zone at
the vehicle entrance to the museum and reloading area,
partially heated zone in the basement of the building and (exhibition rooms) floor area [m2] 19500
heated/air conditioned zone encompassing most of the net volume [m ] 3
15073
building – the floor area of 19 500 m2 and volume of Partially heated
68600 m3. The heated/air conditioned premises house basement floor area [m ] 2
5980
several permanent galleries, a space for temporary 3
Unheated space net volume [m ] 2612
exhibitions, stores, offices, the library, conservation (vehicle entrance, 2
floor area [m ] 503
studios and technical workshops. The collections range reloading area)
widely from paintings on canvas, decorative art objects,
Assemblies
militaria to mixed-media modern works of art.
The model of the Main Building of the National Museum area [m2] 2050
Outer wall old part (by the
2
in Krakow took into account its most important features, year 1939), (plaster, U [W/m K] 1.1
including the building materials and technologies used in ceramic bricks 51 cm, λ [W/mK] 1
0,8/0,8/1,7
the building’s two-phase construction. The external walls cladding sandstone 10 cm) 2
were represented in the model as multilayer structures in μ [-] 19/22/73
2
accordance to the energy audit performed. The partitions area [m ] 4147
and floors were taken into account in the calculations as Outer wall newer part (by
2
the year 1989), (plaster, U [W/m K] 0.83
thermal and moisture reservoir instantaneously interacting
with the indoor air. aerated concrete 51 cm, λ [W/mK] 1
0,8/0,5/1,7
cladding sandstone 10 cm) 2
Each building material was selected from WUFI®PLUS μ [-] 19/8/73
database and was characterized, among others, by thermal 2
area [m ] 5928
and moisture conductivity and sorption isotherms. Roof (plaster, reinforced 2
Calculations took into account not only the construction U [W/m K] 0.78
concrete 15 cm, mineral 1
of the building envelop but also heat and moisture gains wool 5cm) λ [W/mK] 0,8/1,8/0,04
from people working and visiting the building. The latter μ [-] 2
19/76/1,3
number was assessed basing on the number of tickets sold 2
during 2010-2012 and the assumption that a visitor area [m ] 5234
Ceiling to basement
spends 2 hours on average in the museum. 2
(cladding marble 5 cm, U [W/m K] 1.68
The analysed building has heavyweight type of reinforced concrete 15 λ [W/mK] 1
1,7/1,8/0,8
construction with great heat and moisture capacity. It has cm, plaster) 2
μ [-] 54/76/19
been observed, that initial conditions, especially initial
2
moisture content of assemblies, has great impact of Inner wall (plaster, bricks area [m ] 3500
moisture balance and relative humidity. To obtain proper 12 cm, plaster) λ [W/mK] 1
0,8/0,8/0,8
initial conditions calculation started at 1th July and 2
covered 18 month, but only results for the last year were μ [-] 19/22/19
2
evaluated. Inner wall (plaster, area [m ] 1627
Figure 3 shows visualisation of the building in concrete 20 cm, plaster) λ [W/mK] 1
0,8/1,8/0.8
WUFI®PLUS software. The most important building 2
μ [-] 19/76/19
parameters are summarized in Table 1. Moisture storage
2
functions for building materials are set together in Figure Inner wall (plaster, area [m ] 8359
4. concrete 40 cm, plaster) λ [W/mK] 1
0,8/1,8/0.8
2
μ [-] 19/76/19
2
area [m ] 2418,0
2
Windows U [W/m K] 3.0/(5,0)
g-Value [-] 0,60/(0,73)
1
– thermal conductivity
2
– water vapor diffusion resistance factor
Fig
ure 3 Visualization of National Museum Building in
WUFI®PLUS software

Table 1 Main building parameters


Specification Value
Zones
Conditioned zone net volume [m3] 68601
350
ceramik brick
300
Wat er cont ent [ kg m- 3 ]

aerated concrete
250 reinforced concrete
marble
200 sandstone

Air temperature [ oC ]
plaster
150

100

50

0
0 0,2 0,4 0,6 0,8 1,0
Relative humidity [-]
Figure 4 Moisture storage functions for building
materials

3.3 HVAC modeling


As already mentioned WUFI®LUS software models Water content [g/kg]
HVAC in idealized way. According to defined plant
capacities appropriate heat and moisture amount is Figure 5 Exemplary dehumidification with cooling
provided or removed from inner air. As dehumidification
process applied in the museum alters not only humidity Amount of condensed water is equal to absolute moisture
but also temperature of ventilation and recirculated air, content difference between points 1 and 2 (Figure 5).
the simplified model cannot be used efficiently. Therefore Dehumidification efficiency depends significantly on
a more detailed model for air conditioning process in the cooling coil temperature. If coil temperature is too high
museum was developed and integrated into the software. then too little or no moisture is condensed and upper
According to ventilation system (Figure 2) inlet air humidity limit of inner air cannot be maintained.
regains energy from exhausted air. Then the air is mixed After cooling with dehumidification the air is reheated to
with recirculated air. It is assumed, that recirculation is 19 oC. Heating coil is used in winter together with water
constant in time with 4 ACH (274404 m3/h). If relative radiators for heating and in summer for reheating.
humidity of inner air exceeds upper limit (eg. 60 %) the
coil is cooled down and, if its temperature drops below If relative humidity of inner air drops below lower limit
dew point of flowing air, some amount of vapour is (eg. 35 %) the air is humidified by spraying of water in
condensed. This process can be linearly depicted on the humidifier.
Mollier chart [10]. Figure 5 shows exemplary Calculations were carried out using explicit model with
dehumidification with cooling for inlet air of 26 oC and maximal time step 1 min. During each time step inner and
60 % rel. humidity (point 1) and 9 oC (3a), 12 oC (3b) and outer air parameters are constant and enthalpy change in
14 oC (3c) cooling coil temperature. Point 2 (a,b,c) can be every process (heat recovery, mixing, cooling with
calculated from contact factor between cooling coil and dehumidification, reheating, and humidification) is
air. Contact factor was assumed 80 %. accordingly accounted for. After every time step heat and
moisture balance of inner air is made and new
temperature and relative humidity calculated (initial
conditions for the next time step). Figure 6 shows
simplified algorithm for the calculations.
Start
Temperatures higher than 26.0 0C 1.86 % of the year
Average rel. humidity 77.7 %
Minimum rel. humidity 22 %
Initialisation building model
Maximum rel. humidity 100 %

Initialisation plant equipment model Design climates were also used to account for the
conditions in the unheated and partly heated zones of the
building. Yearly sinusoidal variability of the temperature
Set initial conditions for next schedule time - step was assumed with the amplitude of 5 oC (maximum on
August 1) and the yearly average temperatures of 10 oC
and 15 oC at the unheated and partially heated zones,
Calculate combined heat and moisture transfer in respectively.
building components, Calculate heat and moisture
flows
4. Results and discussion
According to presented calculation model a series of
Calculate inner and external heat and moisture
simulations have been carried out to find out the impact
sources/sinks
of control strategy (allowed RH band), air change rate
and cooling coil temperature on energy use for
Calculate HVAC, Calculate heat and moisture flows dehumidification with cooling in the main building of the
related to plant equipment National Museum in Kraków.
The following climate control scenarios in the heated/air
Heat balance, conditioned part of the building were used in the
Moisture balance simulations. The temperature was assumed to be in the
New inner air temperature and humidity range between 19 oC and 25 oC, that is, the heating and
cooling systems were operated when temperature dropped
Results for the current time step
below 19 oC or surpassed 25 oC, respectively. Three
different bands of allowable RH variations were analysed:
45-60%, 35-60%, and 35-65% [6]. Various ventilation
yes rates (0 - 2,5 ACH) in the museum building were also
Time < End calculation considered. Mean ACH measured in the last 2 years gave
0.7 1/h. Measurements were made twice a year (in spring
no and autumn) in two weeks cycles using CO2 as a tracer.
End Every calculation was made for 18 month but only results
for last 12 month were evaluated. Figure 7 shows
Figure 6 Simplified calculation algorithm for building exemplary results of inner air temperature and relative
and HVAC humidity, heating/cooling, humidification and
dehumidification in the main zone by 35-60% RH-
3.4 Outer climate control, 19-25 oC temperature-control, cooling coil
For the outdoor climate, the test Reference Year (TRY) temperature 9 oC and ACH 0,7 1/h. It can be observed,
data for Krakow, provided by the Technical University of that both temperature and humidity of inner air are
Lodz, Poland was used [7]. The most important maintained within assumed ranges. No additional cooling
parameters of the Krakow climate are summarized in was necessary to keep air temperature below 25 oC.
Table 2. Whereas humidification and dehumidification had to be
applied in winter and summer time respectively.
Table 2 Features of the TRY outdoor climate for
Krakow
Specification Value
Minimum temperature - 20.1 C
Maximum temperature 31.0 C
Yearly average temperature 8.3 C
Average temperature (V-IX) 15.8 C
Average temperature (X-IV) 3.0 C
Figure 8 Amount of condensed water and net energy
used for cooling and reheating depending on climate
control scenarios (RH band and air change rate)

As can be seen (Figure 8) about ACH = 0.05 amount of


condensed water and energy use take minimum at nearly
zero. Then both condensed water and energy grow almost
linearly with air change rate. RH band of 45-60% and 35-
60% give nearly the same results. It means that lower RH
Figure 7 Yearly patterns of inner air temperature,
limit has no effect on energy for dehumidification.
relative humidity, heating/cooling and
humidification/dehumidification Relaxing upper limit from 60 to 65% (only 5 %) caused
reduction of both condensed water amount and energy
consumed by more than 60 %. The zero energy range
Beside allowed RH variations air change rate has great extended to 0.5 ACH. The RH range above 60 % is also
impact on energy use for dehumidification. Therefore a very sensitive to energy use but also regarded as
series of calculation were carried out assuming different favourable for mould grow and biological impact. The
RH variations and air change rate from 0 to 2,5 1/h. results show, that even one percent RH above upper limit
Figure 8 shows yearly sum of condensed water and net means significant energy saving in analysed building.
energy demand for cooling and reheating. Cooling coil Hitherto calculations assumed cooling coil temperature
temperature was set to 9 oC for all calculations. Net 9 oC. This value seems to be the highest acceptable
energy means the heat removed from air for cooling down temperature by which dehumidification is sufficient.
and vapor condensing (enthalpy change) or heat provided Assuming higher cooling coil temperature results in
to reheat air up to 19 oC. Energetically performance of surpassing of upper RH limit. Figure 9 shows patterns of
cooling system (heat pump, circulations, etc.) or reheating temperature and relative humidity inside the building for
system was not modeled in detail.
25 times and for ACH = 0.4 more than 12 times respectively.
cooling coil 9 oC
24
Air temperature [C]

23

22

cooling coil 11 oC
21

20

19
63

62
cooling coil 11 oC
Relative humidity [%]

61

cooling coil 9 oC
60 Figure 10 Energy demand depending on cooling coil
temperature and air change rate
59

As already mentioned, cooling coil temperature higher


58
than 9 oC should not be applied in analyzed building
because upper RH limit cannot be preserved. Furthermore
57
10 July 11 July 12 July
too high cooling coil temperature can cause huge energy
consumption for dehumidification if control system does
Figure 9 Air temperature and relative humidity by not work properly.
cooling coil temperature 9 and 11 oC
5. Conclusions
The paper presents calculation model of mechanical
3 consecutive days in July for cooling coil temperature 9 system with air treatment coupled with a building. All
and 11 oC. I can be clearly seen, that relative humidity relevant processes in the system like heat recovery,
exceeds 60 % when cooling coli temperature is equal 11 recirculation/mixing, dehumidification by cooling coil,
o
C. In such a case dehumidification system is working reheating and humidification are accounted for. The
constantly and ineffectively in contrast to highly effective, model has been integrated into hygrothermal building
intermittent dehumidification obtained by the system with simulation software WUFI®PLUS. Exemplary
low temperature cooling coli. Paradoxically inner air calculations were made for the main building of National
temperature is lower (Figure 9) when cooling coil Museum in Kraków. The results obtained allowed to
temperature is higher. Recirculated and ventilation air is assess quantitatively the influence of assumed
cooled down and reheated regardless of dehumidification microclimate control strategies and some system
efficiency. parameters on net energy use for dehumidification.
Lower air temperature increases relative humidity. This It could be observed, that upper RH limit and air change
causes even more moisture to be condensed in rate have significant impact on energy consumption for
comparison with lower coil temperature. dehumidification. At about ACH = 0.05 1/h amount of
To show how cooling coil temperature influences energy condensed water and energy takes minimum at nearly
use for dehumidification, next simulations were carried zero, then grows almost linearly with air change rate.
out for cooling coil temperature 9-14 oC and ACH 0,4;0,7 Relaxing upper RH limit from 60% to 65% gives over
and 1,2 1/h. The results are shown in Figure 10. Energy 60% energy reductions, regardless of ACH.
use increases moderately with cooling coil temperature
till 11-12 oC then grows rapidly achieving maximum at Highest, acceptable cooling coil temperature for the
about 13 oC (0,7 1,2 ACH). For lower ACH (0,4 1/h) the analysed museum building is 9 oC. Increasing cooling coil
maximum is shifted beyond 14 oC. It can be assessed that temperature means inefficient dehumidification (surpass
for 1,2 ACH maximum energy use is about 3 times higher upper RH zone limit) and grow of energy use. For
in comparison with energy use by 9 oC cooling coil analyzed building the maximum of energy use, depending
temperature. For ACH = 0.7 1/h the difference is about 5 on ACH, can be from 3 to more than 12 times higher than
energy used by acceptable cooling coil temperature.

6. Acknowledgements
The research is supported by EU project “Climate for
Culture”. Our thanks to the European Commission for
Project funding (http://www.climateforculture.eu).

7. References
[1] Antretter, F., Sauer, F., Schöpfer, T., Holm, A. 2011.
Validation of a hygrothermal whole building simulation
software. Proceedings of Building Simulation 2011: 12th
Conference of International Building Performance
Simulation Association, Sydney, Australia.
[2] Ascione, F., Bellia, L., Capozzoli, A., Minichiello, F.,
(2009), ‘Energy saving strategies in air-conditioning for
museums’. In Applied Thermal Engineering, Vol 29 676–
686.
[3] ASHRAE Standard 140, 2007. Building Thermal
Envelope and Fabric Load Tests.
[4] DIN EN 15026: Wärme- und feuchtetechnisches Verhalten
von Bauteilen und Bauelementen - Bewertung der
Feuchteübertragung durch numerische Simulation (EN
15026:2007)
[5] Erhardt, D., Tumosa, C.S., Mecklenburg, M.F., (2007),
‘Applying science to the question of museum climate’. In:
Proceedings of ‘Museum Microclimates’, Copenhagen,
Denmark.
[6] European Standard EN 15757:2010 - Conservation of
Cultural Property – Specifications for Temperature and
Relative Humidity to Limit Climate-induced Mechanical
Damage in Organic Hygroscopic Materials, 2010.
[7] Gawin D., Kossecka E. 2002.Typowy rok meteorologiczny
do symulacji wymiany ciepła i masy w budynkach,
(Typical meteorological year for simulation of heat and
mass exchange in buildings). Komputerowa Fizyka
Budowli, Drukarnia Wydawnictw Naukowych S.A., Łódź.
[8] Holm, A., Radon, J., Künzel, H. M., Sedlbauer, K. 2004.
Berechnung des hygrothermischen Verhaltens von
Räumen. WTA Schriftenreihe (2004), H. 24, S. 81–94.
[9] Jones W., P. 1994. Air Conditioning Engineering, 4th
Edition. Reed Educational & Professional Publishing,
Oxford, UK.
[10] Künzel, H., M., 1994. Simultaneous Heat and Moisture
Transport in Building Components. Dissertation.
University of Stuttgart, Available from: www.building-
physics.com
[11] Lengsfeld, K., Holm, A. 2007. Entwicklung und
Validierung einer hygrothermischen Raumklima-
Simulationssoftware WUFI®-Plus, Bauphysik 29 (2007),
Magazin 3, Ernst & Sohn Verlag für Architektur und
technische Wissenschaften GmbH & Co. KG, Berlin

Вам также может понравиться