Tehnical instructions

Cm Pelet-set

REGULATION

120°C

30%
80°C

READY 1700 60°C


70°C

15k 55°C

0% 50°C

THE FIRST START-UP MUST BE DONE BY AUTHORIZED PERSON


OTHERWISE PRODUCT WARRANTY IS NOT VALID

Cm Pelet-set
TURPS- 09/2017-v1_14
Screen

SWITCHING ON
After turning on the main switch, screen will display language selection menu and software version.
You can choose between various languages. To select the language, press the flag of language you want.

Possibility of online boiler


monitoring and management
(Additional equipment:
Cm WiFi-box)

Software version
Boiler power
- 14 kW (Cm Pelet-set 14)
- 20-35 kW (Cm Pelet-set 35)
- 40/50 kW (Cm Pelet-set 50)
- 60-90 kW (Cm Pelet-set 90)

Language selection

If option "Language selection" is set to OFF under "DISPLAY" menu, initial message screen will be shown (picture
below). This screen will be shown as long it's set in the "Initial message time" option, under "DISPLAY" menu or until you
press "OK" button.

Software version
Boiler power
- 14 kW (Cm Pelet-set 14)
- 20-35 kW (Cm Pelet-set 35)
- 40/50 kW (Cm Pelet-set 50)
- 60-90 kW (Cm Pelet-set 90)

’’OK’’ button

Initial message countdown

When turning on the main switch, touch screen must not be pressed. Otherwise
regulation will enter firmware update mode which is used only by authorized
technican. If this happens, please turn off main switch and turn it back on without
pressing the touch screen.

2 Technical instructions REGULATION Cm Pelet-set


Main Menu, Buttons

MAIN MENU
The main menu is used to select the desired submenu. To select a specific submenu you must press the appropriate icon
on the screen. To switch between the ’’Main menu’’ and ’’Boiler working display’’ press the button ’’View selection’’. To
switch between graphic view, numeric view or additional equipment of the boiler press ’’Boiler operation view’’ button.

Time
Date
View selection:
main menu / work

Boiler operation view:


graphic / numeric / additional
equipment

Current boiler status

Boiler start / stop

BUTTONS

Button ’’ON / OFF’’


Button ’’OK’’
options: on / off boiler operation’’

Button ’’VIEW SELECTION’’


Button ’’START’’/’’STOP’’
options: main menu / work

Button ’’BOILER OPERATION DISPLAY’’ Navigation buttons:


options: ’’LEFT’’, ’’RIGHT’’, ’’UP’’, ’’DOWN’’
graphic / numeric / additional equipment

Button ’’ENTER’’ Button ’’DELETE’’

Button ’’BACK’’ Button ’’FACTORY SETTINGS’’

Button ’’PREVIOUS SCREEN’’ Button ’’INFORMATION’’

Button ’’NEXT SCREEN’’ Button ’’COPY’’ Button ’’PASTE’’

Technical instructions REGULATION Cm Pelet-set 3


Screen, Symbols

SYMBOLS

1 9 10 11 12 13

6 7 8

Symbols:

1 - Boiler temperature
2 - Fuel level *
3 - Transporter working
4 - Photocell
5 - Flame symbol
6 - Igniter working
7 - Burner fan working
8 - Burner fan rpm
9 - Burner working hours counter
10 - Burner working hours reset buttom
11 - Dynamic configuration view
(view is depending of set configuration)
12 - Work mode (winter/summer) / Additional
equipment view (cascade, wifi...)
13 - Outside temperature

* - additional equipment

4 Technical instructions REGULATION Cm Pelet-set


Screen, Symbols

SYMBOLS

60°C
Room thermostat
Hydraulic crossover with the
current temperature
(there are configuration without
temp. sensor)

Next to the room thermostat


symbol bright blue circle (the
room thermostat has requested
for operating the pump, the pump 70°C
does not work if you have not met
all the conditions for its operation, Accumulation tank with current
for example. low temp. in the temperature at top of the tank and
boiler, otherwise normally works) at the bottom of the tank.
50°C

Heating circuit
3-way diverter valve (showing the
open and closed pipe)

55°C
Domestic hot water tank
with current temperature Chimney sweeper

Winter working mode


External control ( / ) (heating + DHW)

Summer working mode


(only DHW)
View/additional equipment button
(All items of additional equipment
are enabled)

Cm WiFi-box - not connected

Some items of the additional


equipment are disabled
Cm WiFi-box - connected

All items of additional equipment


Cascade
are disabled

Technical instructions REGULATION Cm Pelet-set 5


Symbols, Adjusting the paramteres

SYMBOLS - RETURN FLOW PROTECTION

3-way thermostatic mixing valve 4-way manual mixing valve


+ pump + pump

3-way mixing valve with actuator and 4-way mixing valve with actuator and
return flow temp. sensor return flow temp. sensor
+ pump + pump

ADJUSTING THE PARAMETERS

A B

C D

There are 4 different menu types for adjusting the parameters:

A - this menu is used to set the parameters that have numerical values (°C, RPM, time...)
example: adjust the burner fan rpm, adjusting the boiler temp. etc...

B - this menu is used to set parameters that must be selected (marked) to be enabled and there can be multiple selected
(enabled) items
NOTE: some enabled options disable another one (they can't be enabled at the same time)
example: enable additional equipment: flap, air cleaning, CM2K, Cm-WiFi-box...

C - this menu is used to set the parameters that must be selected but there can be only one selected item
example: set the type of the DHW sensor
D - this menu is used to set the parameters where are many items to be adjusted
example: adjust the burner working parameters on power P2

6 Technical instructions REGULATION Cm Pelet-set


Adjusting the parameters

ADJUSTING PARAMETERS METHODS (examples)


1 3 4
1 -parameter you are adjusting
2 - value adjustment box
2 5 3 - set value
4 - value type
5 - info button (displays factory, min. and max. values)
6 6 - resets the current value to the factory value

1 5
1 - parameter you are adjusting
2 2 - value adjustment box
3 - selected option (only one option can be selected)
3 4 - confirm button
5 - factory value

1 3
1 - parameter you are adjusting
2 - items that can be enabled
2 3 - next page button
4 - confirm button
5 - selected (enabled) item
5 6 - deselected (disabled) item

4
6

1 4
1 - parameter you are adjusting
2 2 - switch between sheets (only for parameters which
have multiple sheets)
3 - parameter description
3 5 4 - parameter current value (press 2 times to enter
adjusting mode)
5 - up/down scroll buttons

NOTE: after parameter changing press the "CONFIRM" button to store new value. If you don't want to save the set
value, press "BACK" button.

Technical instructions REGULATION Cm Pelet-set 7


Maintenance, Cleaning

1.0. MAINTENANCE

1.1. CLEANING THE BURNER


Under "CLEANING" menu are two options:

Cleaning: this option is used to start the burner fan on the set RPMs to
clean the burner grate (note: depending of the pellets quality grate will
be more or less clean. After this procedure, burner grate should be
removed and cleaned and the burner head should also be cleaned.)

Burner fan: this option sets the burner fan RPMs during cleaning

1.1.1. CLEANING
Press the "START" button to start the burner fan for 10 min.
After pressing the "START" button countdown is started for 10 min,
after which burner fan stops automaticaly

Press "AIR VALVE" button to open the electro-magnetic valve and to


clean the burner with compressed air.
After pressing the "AIR VALVE" countdown ist started for 60 sec in
which time "AIR VALVE" button is disabled to alow compressor to fill its
tank.

1.1.2. BURNER FAN


This option is used to adjust burner fan RPMs during cleaning
procedure

Possible adjustment:
- Factory adjustment: 3000 rpm
- Minimal adjustment value: 500 rpm
- Maximal adjustment value: 3000 rpm

NOTE: burner cleaning option is not replacing the need for manual
cleaning of the burner and burner grate. It should be manually cleaned
regulary according to the technical manual.

8 Technical instructions REGULATION Cm Pelet-set


Temperature , Schedule

2.0. TEMPERATURE

Temperature menu shows only items applicable to the set configuration. In next section of the manual all avalible
configurations and schemes are listed.

Availible temperature settings will be described at every individual configuration and scheme in
"CONFIGURATIONS" section of this manual.

NOTE: this is only representation picture, actual possible adjustment depends on set configuration.

3.0. SCHEDULE / 3.1. BOILER

This option is used to set the burner working time according to the set time. You can set 3 tables with different settings
and only 1 table can be active. You can set ON/OFF 3 times during 1 day and every day can be individualy set.

NOTE: in the same way you can set other schedules: BOILER, DHW, RECIRCULATION

3.1.1. SCHEDULE

This option is used to select active "SCHEDULE TABLE" that you have set

Possible adjustment:
- Factory adjustment: OFF
- Table 1
- Table 2
- Table 3

Technical instructions REGULATION Cm Pelet-set 9


Table, History

3.1.2. TABLE 1/2/3


This option is used to set "SCHEDULE TABLES". Every table can be
individualy set.

2 1 1 - current table you are adjusting (table 1 / table 2 / table 3)


2 - day of the week
3 - green - burner start (on)
red - burner stop (off)

3 Press the box to adjust the time


You can adjust 3 start and stop during 1 day
You can copy/paste from one day to another by pressing the "day box"
of the day which you want to copy, press the "COPY" button and press
the desired "day box" and press "PASTE" button.

COPY PASTE
BUTTON BUTTON

4. HISTORY
This option is used to see the
history of the occured "ERRORS"
and "WARNINGS"

This option is used to see the history of the occured "ERRORS"


1 2 1 - error code
2 - error description
3 - time and working stage (OFF) when error occured

Error codes are marked with letter "E"

List of all error codes are listed in the "Cm Pelet-set manual"
3

This option is used to see the history of the occured "WARNINGS"


1 2 1 - warning code
2 - warning description
3 - time and working stage (OFF) when warning occured

Warning codes are marked with letter "W"

List of all warning codes are listed in the "Cm Pelet-set manual"
3

10 Technical instructions REGULATION Cm Pelet-set


Operation, Forced shutdown, Manual test

5. OPERATION

This menu is used to set various parameters, enable/disable various additional equipment and functions, various work
modes, manual test etc.... This menu is designed for end user.
NOTE:
some of the options in this menu are GREYED OUT (disabled) and they can't be changed.
They are only shown to see settings/values of some options.
View in this menu depend of selected options and additional equipment.

5.1. FORCED SHUTDOWN


This option is used to forced shut down of the burner in any working
stage. Before pressing the "FORCED SHUTDOWN" you must switch
off the burner on the ’’ON/OFF’’ switch and confimt ’’STOP’’ action on
the main display.

NOTE: after "FORCED SHUTDOWN" you must open the boiler


door with burner, and clean the burner grate before starting the
burner again.

5.2. MANUAL TEST

This option is used to check relay outputs, connection to the electric devices and the working of the electric devices.

Items:
- Burner fan - you can check working of the burner fan on 2 speeds (max rpm and 1700 rpm) - when you start the test,
measured rpms are displayed on screen
- Feeder screw - you can check working of the feeding transporter
- Heater + burner fan - you can check working of the burner heater (igniter) - to protect the heater from burning out,
burner fan is started automatically when you start the heater
- Pump P1/DHW/RECIRCULATION - you can check working of the connected pumps
- 1. Circuit / 2. Circuit - you can check working of the devices of the mixing heating circuits (pumps, motor valves open
close)
- Additional equipment - submenu for manual test of the installed additional equipment

NOTE: Items displayed in this menu and in "Additional equipment" submenu depends of set configuration and
installed additional equipment.

Technical instructions REGULATION Cm Pelet-set 11


Filling conveyors, Save/load

5.3. FILLING CONVEYORS


Filing conveyors:
This option is used for the initial filling of the transporter. Also it can be
used if the transporter becomes empty. Recommended is to start the
filling process and wait until it finishes to be sure that transporter is full
(20 min.).
Before starting this option, disconnect the PVC tube from the burner
and put a bucket/bag under it. After process is finished put the pellet
from the bucket/bag back to the tank and connect PVC tube back to
the burner.

Check filling at start:


NOTE: This otion is used to check filling at start. Pressing the ’’START’’ button
if the transporter gets empty, you must fill it transporter starts to work and works continuously for set time (counter
before starting the burner. is started). This time can be adjusted under option Filling at start under
’’INSTALLATION’’ menu. After this process is finished, open the door
with burner and check if the pellets have cover the el. heater. If not,
filling at start must be adjusted and checked again.

5.4. VEIGHING CHECK

This option is used to check pellet delivery amount.


You can set the transporter working time (1) after which you want to weight the pellet.
On screen is displayed factory amount and last measuring which can be done only by authorized serviceman (if has
been done, if not factory and last weighning is the same).

5.5. SAVE/LOAD
This option is used to save parameters, load / load service parameters
and delete saved parameters.

SAVE - save current settings


LOAD - load saved setting
LOAD SERVICE - load setting autorized serviceman saved
DELETE - delete saved settings

You can save multiple setting under different names and you can load
and delete saved setting.

12 Technical instructions REGULATION Cm Pelet-set


Standard equipment, Sensors, Photocell, Circuits

5.6. STANDARD EQUIPMENT

This option is used for adjusting standard equipment of Cm Pelet-set


Options:
- Sensors - you can set the sensor type (PT1000 - factory or NTC 5K)
- Photocell - you can adjust photocell parameters
- 1.Circuit / 2. Circuit - you can adjust mixing heating circuits parameters
- DHW - you can adjust DHW parameters

5.6.1. SENSORS

This option is used for adjusting the sensors type (NTC 5K or PT1000)
Factory: PT1000
Option: PT1000 / NTC 5K

5.6.2. PHOTOCELL
This option is used for adjusting photocell parameters

5.6.3/5.6.4. 1. CIRCUIT / 2. CIRCUIT


This option is used for adjusting the mixing heating circuits.

NOTE:
some parameters are shown in"OPERATION" menu but can't be
changed. They can be changed only in "INSTALLATION" menu
which is under PIN (only for authorized serviceman).

Technical instructions REGULATION Cm Pelet-set 13


Circuits

5.6.3.1 - 5.6.4.2 1. CIRCUIT / 2. CIRCUIT


It's possible to view all enabled mixing heating circuits (set temperatures, measured temperatures, heating type,
working of the pumps etc...). To enter this view press / button and then .

If there are more than 2 mixing heating circuits enabled you can switch view betwen them with buttons.

2 1

05:08
9
5°C
2a 3a 5a
1a 6a
50.0°C
8.a
22.0°C +5.0°C
58°C -°C
x
7a
4a 22°C

1 50.0°C
-°C
5 20.0°C +0.0°C
8 OFF
x
45°C 20°C
7
4
2 3 6
For each heating circuit can be specifically select items.
For example, you can Include / exclude heating circuits, turn on/off room corrector, choose heating type in each circuit
(radiators / floor), choose the mode (day / night).

1. Mixing valve (1.circuit) 6. The desired temperature + deviation by room corrector


2. The calculated flow temperature (1.circuit) (1.circuit)
3. Current measured flow temperature (1.circuit) 7. Current measured room temperature (shown only
4. Heating type on 1. circuit (radiators or floor heating) if the room corrector is turned on) in 1.circuit
5. Room corrector „CSK“ on 1. circuit (if turned off, 8. Mode (1.circuit) (day / night)
icon disappears) 9. Outer temperature (outer sensor)

Items 1a - 8a have the same meaning as items 1-8 (described above) which
only relate to 2. heating circuit or some other circuit depend how many circuits
is selected.

14 Technical instructions REGULATION Cm Pelet-set


Circuits settings
SETTING PARAMETERS FOR EACH HEATING CIRCUIT

Regulation can control up to two mixing heating circuits. They must be enabled and set under "INSTALLATION" menu.
To make adjustment of each circuits go to the "OPERATION" menu then "STANDARD EQUIPMENT" menu.

Possible selection:
Factory: ON
Option: ON, OFF
By using this option you can enable/disable heating circuits.

Possible selection:
Factory: 1.0
Option: 0.1 - 4.0
By using this option you can set heating curve value.

Possible selection:
Factory: 1.0
Option: 0,1 - 5,0
By using this option you can set correction value.

Technical instructions REGULATION Cm Pelet-set 15


Circuits settings

Possible selection:
Factory: 20,0°C
Option: 5.0°C - 30.0°C
By using this option you can set day room temperature.

Possible selection:
Factory: 20,0°C
Option: 5.0°C - 30.0°C
By using this option you can set night room temperature.

Possible selection:
Factory: DAY TEMP.
Option: Day temp. / Night temp. / Table
By using this option you can set working mode of the heating circuit

By using this option you can set table for working mode of the heating circuit.

NOTE: you can change settings of any heating circuit in the same way.

16 Technical instructions REGULATION Cm Pelet-set


Additional equipment, Freeze guard, Work mode

5.7. ADDITIONAL EQUIPMENT


This option is used to set additional equipment that isn't part of
standard delivery.

Options:
- Air cleaning - turn on/off burner air cleaning
- Flap - turn on/off burner flap
- External control - turn on/off external control (start)
- Cascade - turn on/off the cascade and set some of its options
- CM-GSM - turn on/off CM-GSM module
- Internet supervision - turn on/off internet control and adjust some of
its options
- CMSR100 - turn on/off fuel level sensor and adjust some of its
options
- Suction system - turn on/off suction system and adjust some of its
options
NOTE:
additional equipment must be enabled under "INSTALLATION"
menu (PIN required) and only then is shown in this menu.
Some of the items shown here can be adjusted only under
"INSTALLATION" menu and can be changed only by authorized
serviceman.

5.8. FREEZE GUARD


This option enables to set on/off freeze guard

Possible adjustment:

Freeze guard:
- Factory adjusted: OFF
- Options: ON / OFF

Type of protection:
- Factory: "Heating + Pumps"
- Options: "Heating+Pumps" / "Pumps only"

Option:
- Factory: "To._min/Taf_min"
- Options: "To._min/Taf_min" / "Toutside"

5.9. WORK MODE


This option enables to set working mode

Possible adjustment:
- Factory adjusted: WINTER
- Options: WINTER (heating circuits + DHW) / SUMMER (only DHW)

Technical instructions REGULATION Cm Pelet-set 17


Time to burner extinguishing, Display, Info, Correction

5.10. TIME TO BURNER EXTINGUISHING


This option is used to set time for burner shut down. In case of
continuous burner working for this time, burner will shut down (in this
process it will clean the grate, with burner fan or air cleaning if it’s
installed). After burner shutdown process, burner will start again and
this counter will be reset. Also at every shut down, this counter is reset.

Posible adjustment:
- Factory adjustment: 0 min (OFF)
- Options: 0 - 360 min

NAPOMENA: this option DOESN’T EXLUDE the need for manual cleaning of the burner grate and it must be done
according the intervals written in the Cm Pelet-set manual.

6. DISPLAY

This option is used to set display/sound parameters


Options:
- Screensaver - you can set the screensaver time
- Language selection - you can turn on/off language selection menu after turning on main switch
- Initial message time - you can set time of the initial message if you turn off language selection menu (after this time
runs out, main screen will be shown)
- Show timers - show timers on the lower part of the screen
- Date & time - you can set the date and time
- Sound volume - you can set the touch sound type
- Sound type - you can set the touch sound volume

7. INFO

This option is used to see various informations regarding regulation and burner
Options:
- Statistics - you can see working times of various parts (burner working, working in summer mode, freeze guard,
burner starts, burner fan working, heater working, heater starutups, screew working, pumps working...)
- Software version - you can see burner power (14 kW, 20-35 kW, 40/50 kW or 90 kW), regulation software version and
WiFI ID number (if Cm WiFi-box is installed)
- Selected configuration - you can see set configuration
- Current file - you can see which saved file is currently in use
- Selected burner power - you can see set burner power

18 Technical instructions REGULATION Cm Pelet-set


Correction, Chimney sweeper, Installation

9. CORRECTION

1 2 3

This option is used make correction of pellet delivery. You can decrease delivery by 3 steps. Steps are factory
configurated (or configured by authorized serviceman in "INSTALLATION" menu, under PIN) for every working stage
(power). Icon changes according the set step. "0" is no change and factory set.

10. CHIMNEY SWEEPER

10

10

This option is used to enable and set "CHIMNEY SWEEPER MODE"

Options:
- Chimney sweeper - you can enable/disable "CS" mode
- Power - you can set burner power for "CS" mode
- Minimum boiler temerature - you can set the minimum boiler temperature for "CS" mode

"CS MODE" - this mode enables you make flue gas measurement on selected burner power and set minimum boiler
temperature. In this mode boiler will be exluded from cascade, external control etc. and work only according boiler
temperature. Also in this mode modulation temperatures are lower so burner will modulate later, to enable longer
measurement on set power.

11. INSTALLATION

11

This menu is used only by authorized servicemen


For entry in "INSTALLATION" menu is necessary to input PIN.

Technical instructions REGULATION Cm Pelet-set 19


Configurations

13. CONFIGURATIONS

13.1. CONFIGURATION A-0-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)

bar

1 2

13.2. CONFIGURATION A-0-1

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tbuf min.: 20°C (5-85°C)

bar

4 6

7
1 2 M

20 Technical instructions REGULATION Cm Pelet-set


Configurations

13.3. CONFIGURATION A-0-2

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit (2x)
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tbuf min.: 20°C (5-85°C)

6
bar

4 6

1 2 8 7
M M

13.4. CONFIGURATION A-1-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - DHW tank
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

8
1 2 2
7

Technical instructions REGULATION Cm Pelet-set 21


Configurations

13.5. CONFIGURATION A-1-1

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

bar

4 6

10
1 2 8 7
M 9

13.6. CONFIGURATION A-1-2


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit (2x)
7 - DHW tank
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - 2. circuit flow sensor (CIRCUIT1) + pump (P5) + actuator (MVAL2)
10 - DHW tank pump (P2)
11 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

6
bar

4 6

11
1 2 8 9 7
M M 10

22 Technical instructions REGULATION Cm Pelet-set


Configurations

13.7. CONFIGURATION A-2-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - DHW tank
7 - DHW recirculation (P3)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
4

1 2 9 6
8

13.8. CONFIGURATION A-2-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - DHW recirculation (P3)
9 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
10 - DHW tank pump (P2)
11 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

bar

8
4 6

1 2 9 11 7
M 10

Technical instructions REGULATION Cm Pelet-set 23


Configurations

13.9. CONFIGURATION A-2-2

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - DHW recirculation (P3)
9 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
10 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)
11 - DHW tank pump (P2)
12 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

6
bar

8
4 6

1 2 7
M M

13.10. CONFIGURATION B-0-0


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)

bar

1 2

5
M
3

24 Technical instructions REGULATION Cm Pelet-set


Configurations

13.11. CONFIGURATION B-1-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER1)
6 - DHW tank
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)

bar

8
1 2 7 6

5
M
3

13.12. CONFIGURATION B-1-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

bar

4 6

10
1 2 8 7
M 9

5
M
3

Technical instructions REGULATION Cm Pelet-set 25


Configurations

13.13. CONFIGURATION B-2-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - DHW tank
7 - DHW recirculation (P3)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
4

1 2 8 9 6

5
M
3

13.14. CONFIGURATION B-2-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - DHW recirculation (P3)
9 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
10 - DHW tank pump (P2)
11 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
Tdhw: 50°(10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

bar

8
4 6

1 2 9 11
M 10

5
M
3
HV

26 Technical instructions REGULATION Cm Pelet-set


Configurations

13.15. CONFIGURATION C-0-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

13.16. CONFIGURATION C-0-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

1 5
M

Technical instructions REGULATION Cm Pelet-set 27


Configurations

13.17. CONFIGURATION C-0-2

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit (2x)
5 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
6 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)

Temperatures:
Boiler temp.: 80°C (70-90°C)

4
bar

1 6 5
M M

13.18. CONFIGURATION C-1-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - DHW tank
5 - DHW tank pump (P2)
6 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

6
1 5 4

28 Technical instructions REGULATION Cm Pelet-set


Configurations

13.19. CONFIGURATION C-1-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

8
1 6 5
M 7

13.20. CONFIGURATION C-1-2


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit (2x)
5 - DHW tank
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
7 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

4
bar

9
1 7 6 5
M M 8

Technical instructions REGULATION Cm Pelet-set 29


Configurations

13.21. CONFIGURATION C-2-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - DHW tank
5 - DHW recirculation (P3)
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

1 6 7 4

13.22. CONFIGURATION C-2-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - DHW recirculation (P3)
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

6
4

1 7 9 5
M 8

30 Technical instructions REGULATION Cm Pelet-set


Configurations

13.23. CONFIGURATION C-2-2

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - DHW recirculation (P3)
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

4
bar

6
4

1 8 7 10 5
M M 9

13.24. CONFIGURATION D-0-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

2
M
3

Technical instructions REGULATION Cm Pelet-set 31


Configurations

13.25. CONFIGURATION D-0-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

1 5
M

2
M
3

13.26. CONFIGURATION D-1-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - DHW tank
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

6
1 5 4

2
M
3

32 Technical instructions REGULATION Cm Pelet-set


Configurations

13.27. CONFIGURATION D-1-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

8
1 6 5
M 7

2
M
3

13.28. CONFIGURATION D-2-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - DHW tank
5 - DHW recirculation (P3)
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

1 6 7 4

2
M
3

Technical instructions REGULATION Cm Pelet-set 33


Configurations

13.29. CONFIGURATION D-2-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - DHW recirculation (P3)
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

6
4

1 7 9 5
M 8

2
M
3

13.30. CONFIGURATION E-0-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)

bar

1 4

34 Technical instructions REGULATION Cm Pelet-set


Configurations

13.31. CONFIGURATION E-0-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)

bar

1 4 6
M

13.32. CONFIGURATION E-0-2


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit (2x)
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
7 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)

5
bar

1 4 7 6
M M

Technical instructions REGULATION Cm Pelet-set 35


Configurations

13.33. CONFIGURATION E-1-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
1 4 5
6

13.34. CONFIGURATION E-1-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

9
1 4 7 6
M 8

36 Technical instructions REGULATION Cm Pelet-set


Configurations

13.35. CONFIGURATION E-1-2

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit (2x)
6 - DHW tank
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

10
1 4 8 7 6
M M 9

13.36. CONFIGURATION E-2-0


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW recirculation (P3)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

1 4 8 5
7

Technical instructions REGULATION Cm Pelet-set 37


Configurations

13.37. CONFIGURATION E-2-1

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - DHW recirculation (P3)
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
5

1 4 8 10 6
M 9

13.38. CONFIGURATION E-2-2


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way themostatic mixing valve + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit (2x)
6 - DHW tank
7 - DHW recirculation (P3)
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - 2. circuit flow sensor (CIRCUIT2) + pump (P5) + actuator (MVAL2)
10 - DHW tank pump (P2)
11 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

7
5

1 4 8 9 11 6
M M 10

38 Technical instructions REGULATION Cm Pelet-set


Configurations

13.39. CONFIGURATION F-0-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)

bar

1 4

2
M
3

13.40. CONFIGURATION F-0-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)

bar

1 4 6
M

2
M
3

Technical instructions REGULATION Cm Pelet-set 39


Configurations

13.41. CONFIGURATION F-1-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
1 4 5
6

2
M
3

13.42. CONFIGURATION F-1-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

9
1 4 7 6
M 8

2
M
3

40 Technical instructions REGULATION Cm Pelet-set


Configurations

13.43. CONFIGURATION F-2-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW recirculation (P3)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

1 4 8 5
7

2
M
3

13.44. CONFIGURATION F-2-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 3-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - DHW recirculation (P3)
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp.: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

1 4 8 10 6
M 9

2
M
3

Technical instructions REGULATION Cm Pelet-set 41


Configurations

13.45. CONFIGURATION I-0-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )

bar

M
1 2

3 5

13.46. CONFIGURATION I-0-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )
Tbuf min.: 20°C (5-85°C)

bar

4 6

M
1 2 7
M

3 5

42 Technical instructions REGULATION Cm Pelet-set


Configurations

13.47. CONFIGURATION I-1-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - DHW tank
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

8
M
1 2 6
7
3 5

13.48. CONFIGURATION I-1-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)
dTbuf min.: 20°C (5-85°C)

bar

4 6

10
M
1 2 8 7
M 9
3 5

Technical instructions REGULATION Cm Pelet-set 43


Configurations

13.49. CONFIGURATION I-2-0

1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing + with actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - DHW tank
7 - DHW recirculation (P3)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

7
4

M
1 2 9 6
8
3 5

13.50. CONFIGURATION I-2-1


1 - Boiler + Cm Pelet-set
2 - Accumulation tank
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Accumulation tank upper temp. sensor (BUFFER1)
5 - Accumulation tank lower temp. sensor (BUFFER2)
6 - Mixing heating circuit
7 - DHW tank
8 - DHW recirculation (P3)
9 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
10 - DHW tank pump (P2)
11 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (80-90°C)
Tpuf: 80°C (65-80°C)
dTpuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C )
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)
Tbuf min.: 20°C (5-85°C)

bar

8
4 6

M
1 2 9 11 7
M 10
3 5

44 Technical instructions REGULATION Cm Pelet-set


Configurations

13.51. CONFIGURATION J-0-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

M
1

3
2

13.52. CONFIGURATION J-0-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)

bar

M
1 5
M

3
2

Technical instructions REGULATION Cm Pelet-set 45


Configurations

13.53. CONFIGURATION J-1-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - DHW tank
5 - DHW tank pump (P2)
6 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

6
M
1 4
5
3
2

13.54. CONFIGURATION J-1-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

4
bar

8 5
M
1 6
M 7
3
2

46 Technical instructions REGULATION Cm Pelet-set


Configurations

13.55. CONFIGURATION J-2-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - DHW tank
5 - DHW recirculation (P3)
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

M
1 7 4
6
3
2

13.56. CONFIGURATION J-2-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - Mixing heating circuit
5 - DHW tank
6 - DHW recirculation (P3)
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

4
bar

M
1 7 9 5
M 8
3
2

Technical instructions REGULATION Cm Pelet-set 47


Configurations

13.57. CONFIGURATION K-0-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)

bar

4
M
1

3
2

13.58. CONFIGURATION K-0-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) +return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)

bar

5
4
M
1 6
M

3
2

48 Technical instructions REGULATION Cm Pelet-set


Configurations

13.59. CONFIGURATION K-1-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW tank pump (P2)
7 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

4
7
M
1 5
6
3
2

13.60. CONFIGURATION K-1-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - 1. circuit flow sensor (CIRCUIT1) + pump (P4) + actuator (MVAL1)
8 - DHW tank pump (P2)
9 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

4
9
M
1 7 6
M 8
3
2

Technical instructions REGULATION Cm Pelet-set 49


Configurations

13.61. CONFIGURATION K-2-0

1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - DHW tank
6 - DHW recirculation (P3)
7 - DHW tank pump (P2)
8 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

bar

4
M
1 8 5
7
3
2

13.61. CONFIGURATION K-2-1


1 - Boiler + Cm Pelet-set
2 - Hydraulic crossover (CRO)
3 - 4-way mixing valve + actuator (MVAL2) + return flow temp. sensor (CIRCUIT2) + pump (P1)
(return flow protection)
4 - CRO temp. sensor (BUFFER1)
5 - Mixing heating circuit
6 - DHW tank
7 - DHW recirculation (P3)
8 - 1. circuit flow sensor ( CIRCUIT1) + pump (P4) + actuator (MVAL1)
9 - DHW tank pump (P2)
10 - DHW tank sensor (DHW)

Temperatures:
Boiler temp.: 80°C (70-90°C)
CRO temp: 75°C (65-80°C)
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (3-20°C)

5
bar

7
4
M
1 8 10 6
M 9
3
2

50 Technical instructions REGULATION Cm Pelet-set


Internet supervision
5.7.1. INTERNET SUPERVISION
This option is used to connect regulation to the internet trough Cm Wifi-box via WiFi network. Cm WiFi-box is additional
equipment and is not part of standard delivery.

This option is used to enable/disable Cm WiFi-box and set its parameters.

NOTE: view in this menu depends of enabled additional equipment.

Internet supervision options:

- Factory: "Sup. + control"


- options: "OFF" / "Supervision" / "Sup.+control"

Wifi AP - this option is used to enter the name of the WiFi network you
want to connect

WiFi key - this option is used to enter password of the WiFi network
you want to connect
1 Time sync. - this option is used to syncronise time betwen web portal
and boiler

Time zone - this option is used to set the time zone if boiler time zone is
different from web portal time zone

Connection reset - this option is used to reset the connection betwen


Cm WiFi-box and boiler

1 1
Regulation is connected Regulation is not connected
with web portal with web portal
(internet supervision is enabled) (internet supervision is not enabled)

IMPORTANT NOTES
CM WiFi-box requires active DHCP server of Access Point (e.g. router)
because manual setting of network parameters is not possible. For more
informations contact administrator of your home network

For detailed configuration of the Cm WiFi-box please refer to the Cm WiFi-


box manual received with the Cm WiFi box.

Technical instructions REGULATION Cm Pelet-set 51


52
MAIN
SWITCH

PELET SE T
OUTPUTS SAFETY
THERMOSTAT
ELECTRIC SCHEME 1/5

DOOR
M V A L1 M V A L2 PUMPS1 PUMPS2 SCREW BURNER1 POW1
SWITCH
N CL OP N CL OP P1 N P2 N P3 N P4 N P5 N SC N H N SC F N L1 S W S W

L
N POWER SUPPY
230 V
PE

4 P O LE
4 P BLACK
BLACK L1 L2 N MALE

MALE

L N PE L N PE L N PE L N PE
CONNECTION
OUTPUT OUTPUT OUTPUT OUTPUT TO THE
P 2 P 3 P 4 P 5 PELLET BURNER
PUMP TR A NSPOR TER
1

Project: Drawing number: Init.: Rev.: Page:

REGULATION SCHEME Date: Function: Location: Total pages: Next page:


CENTROMETAL
CPREG

Technical instructions REGULATION Cm Pelet-set


Electric scheme
Electric scheme

ELECTRIC SCHEME 2/5

Technical instructions REGULATION Cm Pelet-set


MO TOR ACTUATOR MO TOR ACTUATOR
OF THE MIXING OF THE MIXING
VALVE 2 VALVE 1

Project: Drawing number: Init.: Rev.: Page:

REGULATION SCHEME Date: Function: Location: Total pages: Next page:


CENTROMETAL
CPREG

53
54
B A G 12V BUS BUS
RJ45 RJ45
BUS

K EY
CMSR50
PRESS.
PELET SE T - INPUTS PHO TO.

E X T1
12V 01 0 2
TEMP1 TEMP 2 TEMP3 COR1 COR2 RPM

BURNER2
+5V
ELECTRIC SCHEME 3/5

GND

GND
GND

POS.
POS.

DHW

5 V IN
T EMP.
T EMP.

BOILER
SP ARE1
SP ARE2

BUFFER1
CIRCUIT1
OUT SIDE

BUFFER2
CIRCUIT 2

EXT2
G
S G S G S G S G S G S G S G S G S G 1 2 3 1 2 3

6 P O LE 6 P BLACK
L1 N L1 N MALE

1 2 3 1 2 3 BLACK
MALE
SK SK
CONNECTION
TO THE
BURNER
SENSOR SENSOR SENSOR SENSOR SENSOR SENSOR OUTSIDE ROOM ROOM
P T 10 0 0 P T 10 0 0 P T 10 0 0 P T 10 0 0 P T 10 0 0 P T 10 0 0 SENSOR CORRECTOR CORRECTOR
P T 10 0 0

Project: Drawing number: Init.: Rev.: Page:


REGULATION SCHEME
CENTROMETAL Date: Function: Location: Total pages: Next page:
CPREG

Technical instructions REGULATION Cm Pelet-set


Electric scheme
Electric scheme

ELECTRIC SCHEME 4/5

TFT DIS

UTP1 USB1

Technical instructions REGULATION Cm Pelet-set


Project: Drawing number: Init.: Rev.: Page:

REGULATION SCHEME Date: Function: Location: Total pages:


CENTROMETAL
CPREG

55
56
Electric scheme

6 P O LE L1 N L1 N 6 P BLACK
FEMALE
BLACK
FEMALE
ELECTRIC SCHEME 5/5

4 P O LE
BLACK L1 L2 N 4 P BLACK
FEMALE

FEMALE

3 P O LE 3 P GREEN
MALE
L1 N
GREEN
MALE

3 P O LE L1 N 3 P GREEN
FEMALE
FILING AND GREEN
TEMPERATURE FEMALE
SENSOR
2
FILLING AND
TEMPERATURE
SENSOR
3
1 3 2 1
+5V S IG G ND

PHOTOCELL
brown

PR E SSURE SWITCH green


FAN WITH white
RPM SENSOR

brown
green
white

Project: Drawing number: Init.: Rev.: Page:


BURNER SCHEME
CENTROMETAL Date: Function: Location: Total pages:
C P P L 14 - 5 0 K W

Technical instructions REGULATION Cm Pelet-set


Notes

NOTES

Technical instructions REGULATION Cm Pelet-set 57


120°C

30%
80°C

1700 60°C
70°C

15k 55°C

0% 50°C

Centrometal d.o.o. assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting, all the pictures and diagrams are principal and it is necessary to adjust each actual
situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.

Centrometal d.o.o. Glavna 12, 40306 Macinec, Croatia

central tel: +385 40 372 600, fax: +385 40 372 611


service tel: +385 40 372 622, fax: +385 40 372 621

www.centrometal.hr
e-mail: servis@centrometal.hr HEATING TECHNIQUE