Regional District of Central Kootenay

Box 590, 202 Lakeside Drive, Nelson, BC V1L 5R4 Web: www.rdck.ca
Telephone: (250) 352-6665 Email: info@rdck.bc.ca
BC Toll Free: 1-800-268-7325 Fax: (250) 352-9300

Invitation to Tender
CDCC – Creston Community Park
RDCK Contract: 18CS-RF-CCDC-002
ADDENDUM NO. 3 - ISSUED January 08, 2019
CLOSING DATE: 2:00PM, January 15, 2019

This Addendum shall be read in conjunction with and considered as an integral part of the Contract
Documents; revisions supersede the information contained in the original specifications or previously
issued Addendum. Price submitted shall include all items of this Addendum.

No consideration will be allowed for any extra due to any Bidder not being familiar with the contents of this
Addendum. This addendum consists of five (5) cover pages.

By this Addendum No. 3, dated January 08, 2019, the Invitation to Tender documents for the CDCC –
Creston Community Park shall be amended as specified below.

1. Front End Document Items

1. Section 00_41_13 has been revised to include line item #21 for the Metal Guard Rail per detail 5,
sheet LD-02A and removal of Optional Items 9 (Waste receptacle) and 10 (Picnic table). See
Date: Jan. 09/2019

attached Section 00_41_13 Addendum 3 –January 8, 2019.

2. Section 01_11_05B - Contract Time and Time Control has been revised and is attached.

3. Electrical Clarifications and Questions

1. Question: “Dwg. LN-01 Not 6.9 specifies that a ground rod is to be installed at all fence posts and
poles over 6ft in height. Electrical specifications and Dwgs. have no indication on requirement.
Clarify intent”.
By: Janice Haynes

Answer: Earth rods will only be required at the electrical kiosk.

2. Question: “Detail 4 Dwg. E-04 indicates a power pedestal. Confirm a modified Valid EVPF10-M 1-
120V20A GFI 1-50A 2018V3ph5W TL will be acceptable”.

Answer: Yes – this will be acceptable.

3. Question: “Dwg. E-01 Note 1 indicates an in-ground pull box is required for Communication and
Power. Confirm if a Channel BULK2436 24”W x 36”L x 24”D Pull Box c/w Tier 22 Lid will be
acceptable”.
Source: BidCentral

Answer: Yes – this will be acceptable.

4. Question: “Kiosk feeders sized for #2 AWG appear to resolve in a 4% voltage drop. Please confirm
feeders should be upsized to #1/0 AWG to reduce voltage drop to 2.7%”?

MUNICIPALITIES: Cities: Castlegar, Nelson Town: Creston Villages: Kaslo, Nakusp, New Denver, Salmo, Silverton and Slocan
ELECTORAL AREAS:  A-Wynndel/East Shore Kootenay Lake B C D E F G H-The Slocan Valley IJ-Lower Arrow/Columbia K-The Arrow Lakes
Answer: Please price as per current design.

5. Question: “Please confirm size of future phase conduits shown E-01 should all be 2” ?

Answer: Yes – these should all be 53mm.

6. “If available, please issue pictures of existing Main Distribution.”

Please see attached Photos.

7. Question: “Please confirm if 50A receptacles in Pedestals are to be straight blade, twist lock or Pin
and Sleeve style”?

Answer: The 50A 3P outlets shall be twist lock.

4. Civil Clarifications

1. FCMH detail updated per Drawing CD-01 CIVIL DETIALS Detail 1.

2. Additional grades added per Drawing CV-05A GRADING PLAN A and CV-05B GRADING PLAN B.

3. Gutter elevations added in Drawings CV-05A GRADING PLAN A and CV-05 GRADING PLAN B.

4. Refer to attached MMCD Curb detail.

5. Landscape Clarifications and Questions

1. Landscape Detail 2 updated per Drawing LD-05C PLAYGROUND DETAILS – added 6 separation
plates.

2. Landscape Detail 3 updated per Drawing LD-05C PLAYGROUND DETAILS – minor dimension and
reinforcement changes.

3. Plant sizes have been added to L-04A.

4. Marathon Surfaces Inc. information included in LD-05A PLAYGRPUND DETAILS Detail 1 and 3

Marathon Surfaces Inc.


Contact: Julie O’Shea
Office (604) 878-062 ext 3
Email julie@marathonsurfaces.com

Please note: Approved equals will also be considered.

5. Drawing LD-01D – Detail 1 Volleyball Post Footing. 30 MPA concrete pile.

Correction – Assume 32 MPA for concrete pile

6. Drawing LD-05C – Detail 1 Vertical Climbing Logs. 25 MPA concrete footing.


Correction – Assume 32 MPA for concrete footing

7. Rubber Safety Surface – Drawing LD-05A Detail 1


Question: “Please clarify which material is to be used for the 100mm base course permeable
aggregate compacted 95% MPD. Is this material to be ¾” crush or some other type of granular
material”?

Answer: See attached Landscape Base Specifications, sieve gradient.

8. 100 diameter HDPE


Question: “A 100mm HDPE channel – flow single wall pipe is called for and a product number is
provided. Please specify the manufacturer for this pipe”.

Answer: PVC pipe is acceptable.

9. 100mm perforated pipe – Drawing LD-05A Detail 2


Question: “Is the 100mm perforated pipe shown in Detail 2 different than the proposed 100mm pipe
shown in Detail 1”?

Answer: Yes, but PVC pipe is also acceptable.

10. Thickness of Base Course


“On Detail 1 of Sheet LD-05A it calls for a 100mm base course whereas, on Detail 3 it calls0 for
150mm base course. Which depth of base course is going to be specified one”?

Answer: 150mm depth. The landscape spec says minimum 100mm but we want 150mm.

11. Geotextile
Question: “On Detail 3 on Sheet LD-05A it calls for a geotextile between the sub grade and
structural fill. Please specify the geotextile at this location”.

Answer: Nilex Nonwoven 4545

12. Concrete Dome – Drawing LD-05B Detail 5


Question: “We have attached product information for an alternate sealer – VOCOMP-20 in lieu of
the specified Pentra-sil244. Please advise if this alternate sealer is acceptable”.

Answer: No substitutions.

13. Concrete Slide


Question: “On Sheet LD-05E one of the drawings appears to show two (2) concrete slides whereas,
Detail 3 on Sheet LD-05C shows one (1) concrete slide. Please clarify how many concrete slides
are required”.

Answer: There is only 1 concrete slide as shown on Detail 3, LD-05C. The confusion on LD-05E
may be a rending issue. On image 2 the central staircase is poorly defined and may have been
interpreted as a slide. This stair shows more clearly in image 4 / LD-05E. The second slide is a
plastic 5” tall slide as shown on Detail 3/ LD-05B.

14. Timber Stairs


Question: “On Detail 4 under the “Notes” it calls for all steel to be hot dip galvanized. Is the rebar to
be hot dip galvanized or will regular rebar suffice in this instance”?
Answer: The rebar can be painted with Galvacon or be epoxy coated to provide full rust protection.

Question: “What is anchoring the stairs from lateral movement or long-term creep of the soil”?

Answer: Each landing has two vertical post anchors as shown in the detail. Assume an additional
10 x 2.4m long, 6x6 Pressure treated lumber with a 900mm long rebar stake. This will provide 10
deadman elements for the staircase where it is acting against the slope. This will be detailed in an
SI post tender.

15. Vertical Climbing Logs Drawing LD-05C Detail 1


Question: “Please provide the height for each of the three (3) vertical climbing logs as currently the
Detail calls for a variation between 1.5 and 2.5 meters”.

Answer: 1.5m, 2.0m, and 2.5m from the top of the metal girdle.

16. Log Climbing Structure Drawing LD-05A Detail 5


Question: “There appears to be 6 logs climbing structure shown on the Drawings LD-03E. However,
the logs are not dimensioned for lengths. Please provide dimensions for each of the 6 logs as
shown”.

Answer: The logs are 2 at 3.3m long, 3 at 4.0m long, and 1 at 5.3m long. There will be some
flexibility within the layout, but the logs should be near these dimensions and combined total of
23.9m.

17. Sand Volleyball Court – Drawing LD-01C Detail 4


Question: “Currently the aggregate below the volleyball sand is called up as 150mm depth
aggregate sub grade. Please specify if this is to be ¾” crushed material or something else”.

Answer: ¾” crush or 1” crush or torpedo drain rock are acceptable beneath the playing court.
However, the 150mm depth of 19 minus is required to support the concrete curb wall.

Question: “Also it calls for filter fabric between the sand and aggregate sub base. Please specify the
model and type of filter fabric that is required”.

Answer: Nilex nonwoven 4545.

18. Subgrade Elevations


Question: “On Sheet L-02 on the left-hand side it states, “Note: Site will be delivered at subgrade
elevations +/- 20cm”. Please confirm if this is still true for the entire site or just where the new skate
park will be. Please advise through Addendum”.

Answer: Site will be delivered at elevations as outlines in Addendum 2. (+/- 20cm)

19. Question: “With reference to the Unit Costs provided in Addendum #2, is the Unit Cost for Retaining
Wall “B” as requested on Sheet 10 of 12, the same as Detail 4 on Sheet LD-01A”?

Answer: Correct

6. General Items
1. Deadline for questions is Thursday January 10, 2019 and Final Addendum will be issued on Friday,
January 11, 2019.

Except as modified by Addendum No. 2 issued December 20, 2018, the Invitation to Tender – CDCC –
Creston Community Park documents shall remain unchanged. All bidders must acknowledge Addendum 2
on their Tender Form as part of their submission.

AJ Evenson
Senior Project Manager
Regional District of Central Kootenay

- END OF DOCUMENT -