Вы находитесь на странице: 1из 6

Glossary — Lighting Terminology

Glossary — Lighting Terminology


Acrylic room shape (RCR), and fixture distribution.
The generic term for a family of high performance light- Color Rendering
stabilized plastics frequently for fixture diffusers General expression for the effect of a light source on the
and lenses. color appearance of objects when compared with their
Ambient color appearance under a reference light source.
The surrounding environment of a device such as a fixture Color Rendering Index (CRI)
or ballast. It usually refers to temperature or sound A measurement of the color shift an object undergoes
conditions. when illuminated by the light source, as compared to a
Ballast reference source at the same color temperature. Color
A device which provides the circuit conditions necessary rendering is measured on an index from 0-100, with
to start and operate electric discharge lamps (fluorescent natural daylight and incandescent lamps both equal to 100.
and HID). Objects and people viewed under lamps with a high color
rendering index (CRI) generally appear more true
Beam Lumens to life.
The lumens contained within the beam spread of a
floodlight. Color Temperature (of a light source)
The absolute temperature of a blackbody radiator having a
Beam Spread chromaticity equal to that of the light source.
See “Floodlighting Concepts” Table 1k. Cutoff and Shielding Angle
Brightness The lamp cutoff angle of a luminaire is the angle between
As commonly applied, brightness (or luminance) is the the vertical axis (nadir) and the first line of sight when the
light intensity from a surface which directs light into bare source is no longer visible. Lamp image cutoff is
the eyes. measured the same way as lamp cutoff, but it occurs when
the image of the lamp is no longer visible in the reflector.
Candela / Candlepower
The shielding angle is the compliment of the cutoff angle.
Light sources may not project the same amount of light in
every direction. The directional characteristic of a light Efficacy
source is described by the candlepower in specific The ratio of light from lamp lumens to the electrical power
directions. This directional strength of light or luminous (watts) consumed. Usually expressed in lumens per watt.
intensity is measured in candelas. System efficacy includes ballast losses.
Candlepower Elliptical Reflector (ER)
Light intensity measured in candelas. Candlepower is A lamp with an elliptical-shaped reflector designed to
often used to indicate the directional intensity of focus light in front of the lamp. Used in deeply shielded
light sources. downlights.
Candlepower Distribution Curve Explosion Proof Luminaire
A curve, generally polar, representing the variation of A luminaire which is completely enclosed and capable of
luminous intensity of a lamp or luminaire in a plane withstanding an explosion of a specific gas or vapor that
through the light center. may occur within it and preventing the ignition of a
specific gas or vapor surrounding the enclosure by sparks,
Cavity Ratio (CR)
flashes or explosion of the gas or vapor within. It must
Geometric proportions of the ceiling, floor and operate at such an external temperature that a surrounding
room cavities. flammable atmosphere will not be ignited.
( Room Length + Room Width )
Room Cavity Ratio = 5H
----------------------------------------------------------------------------------- Fire Rated Ceilings
(RCR) Room Length × Room Width
Fire resistance ratings provide a measure of the ability of a
where ceiling assembly to act as a heat barrier between a fire
h=hRC for the Room Cavity Ratio, RCR below and the building support structure above.
= hCC for the Ceiling Cavity Ratio, CCR Fire resistance ratings apply only to ceiling assemblies in
= hFC for the Floor Cavity Ratio, FCR their entirety. Individual components are not assigned a
fire resistance rating, and are not intended to be
interchanged between assemblies. Rather they are
Chromaticity (of a color) designated for use in a specific ceiling/structural design in
The dominant or complementary wavelength and purity order that its rating may be achieved.
aspects of the color taken together, or the aspects specified Generally, fluorescent fixtures bearing the UL listing mark
by chromaticity coordinates of the color taken together. can be utilized in most floor-ceiling designs as long as the
Coefficient of Beam Utilization (CBU) utilized fixture area does not exceed the specified ceiling/
The percentage of light from a floodlight which reaches fixture area ratio, and the fixtures are installed as required
the illuminated task relative to total beam lumens. by the specific construction details of the UL Design No.
being considered.
Coefficient of Utilization (CU)
The percent of initial generated lamp lumens that reaches
TECHNICAL

the work plane as determined by the surface reflectances,

Hubbell Lighting
351
Glossary — Lighting Terminology
Glossary — Lighting Terminology

Specific construction details will vary but, if considering the bulb wall) back onto the filament surface.
an exposed “T” ceiling grid system, most designs require Hazardous Location
additional hanger wires at the midpoint of ceiling grid tees
An area where ignitable materials may cause a fire or
along each 4' side of nominal 2' x 4' and 1' x 4' luminaires
explosion is ignited.
as well as hanger wires at each of the four corners of
the fixtures. Heavy Duty Floodlight (HD)
In addition to hanger wire requirements, most designs also A directional weatherproof fixture having a substantially
require the use of fixture protection which is usually constructed metal housing into which is placed a separate
fabricated from available ceiling acoustical material and removable reflector. A weatherproof cover glass
bearing the UL Classification Marking with application encloses the assembly and provides an unobstructed light
details as specified by the specific UL Design No. The opening at least equal to the effective diameter of
extent of fixture protection may range from as little as a the reflector.
single piece of material over the back of the luminaire, Highbay
with air gap between the fixture and material, to the use of Generally refers to the industrial lighting where high
a complete five-sided box enclosing the sides and back of mounting heights may be encountered. Many industrial
fixture. HID type fixtures are called high bays.
Care should be observed in the application of luminaires in HID (High Intensity Discharge)
fire rated assemblies to ensure that ballasts do not
High intensity discharge lighting, including mercury
overheat, thereby resulting in shortened ballast life and/or
vapor, metal halide and high pressure sodium light
nuisance tripping of the ballast thermal protector.
sources. Although low pressure sodium lamps are not HID
The use of low loss ballasts and reduced wattage sources, they often are included in the HID category.
lamps will reduce potential thermal problems in most
applications involving elevated plenum temperatures. High Intensity Discharge Lamps
Consult factory with specific details for questionable Mercury - Mercury HID lamps are made of an inner
applications. quartz arc tube containing electrodes and argon mercury.
This entire assembly is enclosed with an outer borocillate
The final approving authority is the local code
glass jacket. Mercury lamps are known for their long life.
enforcement official and as such should be consulted for
Their efficacy is better than incandescent lamps but not as
local requirements and code interpretation. These
good as the other HID or fluorescent sources. Phosphor
requirements should be determined before construction,
coated mercury lamps have better color rendering.
preferably during the specification period. Check the latest
Mercury lamps are used primarily in landscape
edition of the UL “Fire Resistance Directory” for specific
lighting where long life is important.
assembly hour ratings and design constraints.
Metal Halide - Metal halide lamps are similar in design
Fluorescent Dimming and operation to mercury. These lamps have additives in
Single-lamp and two-lamp electronic dimming ballasts are the arc tube which result in better color rendering. Metal
available for varying light output of standard fluorescent halide lamps also have an efficacy - approximately 100%
lamps, straight or U-shaped. Dimming ballast higher than mercury vapor lamps. Some use separate
compatibility should be verified from the specific electronic lamp ignitors and some do not. Metal halide
dimming control manufacturer. lamps are used where efficiency and color are
Fluorescent Lamp important and dusk-to-dawn applications where low
A lamp in which electric discharge of ultraviolet energy initial cost is important.
excites a fluorescing coating (phosphor) and transforms Hubbell Electro-Reg® Metal Halide System -
some of that energy to visible light. A ballast circuit approach to electrically support the metal
Flux (Luminous Flux) halide discharge lamp. It processes energy to the lamp in a
much more lamp-compatible manner than the constant
See lumen.
wattage autoregulator CWA/PLA circuit. The Electro-Reg
Footcandle (fc) ballast is a three coil magnetic structure in which the line
The unit used to measure how much total light is reaching energy is processed through one magnetic field to an
a surface, such as a wall or table. One lumen falling on one energy transfer capacitor, through a second magnetic field
square foot of surface produces one footcandle. One to the lamp arc. This multi-stage energy transfer system
footcandle is equal to 10.76 lux. (see Lux) allows for electrical isolation between the arc discharge
General Purpose Floodlight (GP) and the very low impedance power source. It provides
excellent operating waveform control with significant
A weatherproof unit so constructed that the housing forms
lamp performance improvements.
the reflecting surface. The assembly is usually enclosed.
Glare
The sensation produced by luminance within the visual
field that is significantly greater than the luminance to
which the eyes are adapted.
Grid (lay-in)
A type of ceiling construction where each supporting
TECHNICAL

member is generally shaped like an inverted T, and the


ceiling tiles and lighting fixtures are laid-in on the flanges
of the Ts.
Halogen Lamp (Tungsten Halogen Lamp)
An incandescent lamp containing a halogen gas which
recycles tungsten (which would ordinarily be deposited on
Hubbell Lighting
352
Glossary — Lighting Terminology

Glossary — Lighting Terminology


High-Pressure Sodium Lamp - High pressure sodium Lamp
lamps are similar to mercury and metal halide lamps in The technical term for electric light bulb or tube.
operation: however, construction and physical appearance
differ. HPS lamps contain xenon as a starting gas to initiate Lamp Lumen Depreciation (LLD)
the arc which vaporizes a sodium mercury amalgam. This A factor used in lighting calculations to account for the
lamp has a high efficacy of approximately 125 lumens per light loss that takes place in a lamp due to the gradual
watt†. Other characteristics of this lamp are a golden color, decay in lumen output over a designated period of burning
long lamp life, and an excellent lumen depreciation. time. The LLD is contingent upon relamping schedules
Special ballasting circuitry is usually require to produce and the specific lamp involved.
high voltage pulses to start these lamps. High pressure Light
sodium lamps are used where efficiency is the most The term generally applied to the visible energy from a
important factor and color is not as important. source. Light is usually measured in lumens or
† Based on published data of 400 watt HPS lamp. Lower watt- candlepower. When light strikes a surface, it is either
ages are rated at lower lumens per watt. absorbed, reflected or transmitted. It is not visible until it is
Illuminance reflected into your eye.

1. The density of luminous flux on a surface. Measured


Lighting Distribution
in footcandles or lux (metric.) The former term for Luminaires are classified according to the manner in
this quantity was illumination. which they distribute the luminous flux.

2. Illuminance is the measure of the quantity of lumi-


Light Loss Factor (LLF)
nous flux that arrives on a surface. Illuminance is A factor used in calculating illuminance after a given
affected by the intensity of the fixture in the direction period of time and under given conditions. It takes into
of the lighted surface, the distance from the luminaire account temperature and voltage variations, dirt
to the surface, and the angle of incidence of the arriv- accumulation on luminaire and room surfaces, lamp
ing light. Although illuminance cannot be detected by depreciation, maintenance procedures and atmosphere
the eye, it is the most often used criteria in specifying conditions. Formerly called maintenance factor.
lighting designs. Generally light loss factors are divided into two groups,
Units: Lux or Footcandles (fc)Symbol: E classed as “recoverable” (with cleaning and relamping)
and “nonrecoverable.”
Incandescent Lamp
A lamp in which light is produced by a filament heated to Nonrecoverable Recoverable
incandescence by an electric current.
Temperature Factors Lamp Lumen
Instant Start Depreciation Factor (LLD)
Line Voltage Factor
A fluorescent lamp designed for starting by a high voltage
without preheating of the electrodes. Also known as a Ballast Factor (BF) Lamp Burnout Factor
cold-start lamp in some countries. Lamp Position (Tilt) Luminaire Dirt
Inverse Square Law Factor Depreciation Factor (LDD)
The law stating that the illuminance, E, at a point on a Luminaire Surface Room Surface Dirt
surface varies directly with the intensity, I, of the light Depreciation Factor Depreciation Factor
source and inversely as the square of the distance, d,
between the source and the point. If the surface at the point Not all factors are applicable for all luminaire types and/or
is perpendicular to the direction of the incident light, the applications. However each lighting design should be
law is expressed by E=I/d2. It is applicable for point or evaluated to determine appropriate light loss
near point light sources. considerations.
Isocandela Line For example:
A line plotted on any appropriate set of coordinates to Temperature Factor has an insignificant effect on H.I.D.
show locations in space, about a source of light, in which and incandescent lamps; however, it is a major factor
the intensity is the same. A series of such curves, usually affecting fluorescent lamp lumen output.
for equal increments of intensity, is called an isocandela Lamp Position (Tilt) Factor is not a consideration for
diagram. incandescent or fluorescent. It is however, significant for
Isolux (Isofootcandle) Line Mercury Vapor and Metal Halide HID lamps. A typical
A line plotted on any appropriate set of coordinates to lumen output characteristic curve for a Metal Halide lamp
show all points on a surface where the illuminance is the as a function of tilt from its vertical position is shown as
same. A series of such lines for various illuminance values follows. Minor variations exist between manufacturers.
is called an isolux (isofootcandle) diagram.
100
Percent of Vertical Lumens

Kilowatt (kw)
A measure of electric power. A thousand watts 90
(watts x 1000 = kilowatts).
80
Kilowatt Hour (kwh)
TECHNICAL

The measure of electrical energy usage from which 70


electricity billing is determined. For example, a 100-watt
bulb operated for 1000 hours would consume 100 kilowatt
hours, (100 watts x 1 kw/1000 watts x 1000 hours = 100 0 10 20 30 40 50 60 70 80 90
kwh). At a billing rate of $0.10/kwh, the electric energy to Operating Angle from Vertical in Degrees
operate this bulb would cost $10.00 (100 kwh x $0.10/
*IESNA Lighting Handbook.
kwh) to operate for 1000 hours.
Hubbell Lighting
353
Glossary — Lighting Terminology
Glossary — Lighting Terminology

Room Surface Dirt Depreciation Factor is not generally standard lamps down to 0°F, with low-temperature HO
applicable in outdoor lighting calculations. This should be ballasts good for -20°F. Some standard 1500 ma ballasts
evaluated for interior calculations and is a significant provide for cold starting, but do not improve the reduced
recoverable loss for “indirect” lighting systems. light output that normally results. Recommended
Ballast Factor is a consideration for both H.I.D. and temperature limits should be verified from the
Fluorescent. Ballast factor is the difference of lamp lumen manufacturer. High pressure sodium ballasts will start
output produced from typical commercial ballasts versus lamps down to -40°F, and metal halide ballasts down
the lumen output of lamps operated on reference ballasts. to -20°F. Electro-Reg® will start metal halide lamps down
More definitive data is available for fluorescent systems to -40° F.
and variations exist depending upon types of ballast-lamp Lumen
combinations. Some Fluorescent “low power factor” The basic unit of measurement for light. A dinner candle
ballasts may yield initial light output as low as 50% of puts out about 12 lumens. A 60-watt Soft White bulb is
rated lamp lumen output and some electronic ballasts as much more powerful: 855 lumens. If a uniform point
high as 120% of rated lamp lumen output. source of 1 candela is at the center of a sphere of one
Luminaire Efficacy Rating (LER) foot radius which has an opening of one square foot area
The Energy Policy Act of 1992 requires that the lighting at its surface, the quantity of light that passes through
industry develop a rating for luminaires that allows one lumen.
designers to compare the energy efficiency of lighting Lumens Per Watt (lpw)
products. Luminaire Efficacy Rating (LER) for some types A measure of the efficacy of a light source in terms of the
of illumination have been developed by the National light produced for the power consumed. For example, a
Manufacturer’s Association (NEMA) and approved by the 100-watt lamp producing 1750 lumens gives 17.5 lumens
National Lighting Collaborative to fulfill the requirements per watt. Examples:
for the Energy Policy Act. The Collaborative represents a
Edison’s first lamp 1.4 lpw
broad spectrum of industry professionals including
manufacturers, industry associations, government, Incandescent lamp 10-40 lpw
designers and energy conservation groups. This rating has Fluorescent lamps 35-104 lpw
already begun to be incorporated on Hubbell specification Halogen lamps 20-45 lpw
sheets and catalog information. NEMA document LE5
Mercury lamps 37-63 lpw
describes the calculation of LER as:
EFF × TLL × BF Metal halide lamps 80-125 lpw
LER = -------------------------------------------
Input Watts High pressure sodium lamps 54-153 lpw
where:
EFF = luminaire efficiency Luminaire
TLL = # lamps per luminaire × rated lumens per lamp A complete lighting unit consisting of a lamp (or lamps),
or ballasts where applicable together with the parts
BF = ballast factor
designed to distribute the light, position and protect lamps
Input Watts = total system watts of the luminaire and connect them to the power supply.
This results in a lumens per watt rating that can be used to Luminaire Dirt Depreciation (LDD)
compare the energy efficiency of various products. The
A factor used in lighting calculations to account for the
initial implementation of luminaire labeling covers 10
light loss due to the accumulation of dirt on the luminaire.
categories of common fluorescent 4' and 8' luminaires. In
addition to the LER value, a prefix indicating the type of
source and general category of luminaire (such as FL for
Fluorescent Lensed or FP for Fluorescent Parabolic)
ensures that comparisons can be made among similar
products.
This rating also recommends the use of photometric data
from a National Voluntary Laboratory Accreditation
Program (NVLAP) photometric lab. The NVLAP
accreditation is administered by the National Institute for
Standards and Technology (NIST) and includes on-site
assessments as well as proficiency testing.
Light Trespass
A situation which occurs when light from a source is
distributed onto areas where the illumination is not
wanted.
Louver
A series of baffles used to shield a source from view at
certain angles or to absorb unwanted light.
Low Temperature Starting
TECHNICAL

Standard ballasts for standard bipin-base, 2-lamp slimline


and high output fluorescent lamps are designed to provide
reliable starting at ambient temperatures down to 50°F. All
reduced wattage lamps will start reliably with standard
ballasts down to 60°F. Special ballasts are available for
applications where standard lamps must be started at lower
temperatures. Most low temperature ballasts will start

Hubbell Lighting
354
Glossary — Lighting Terminology

Glossary — Lighting Terminology


The LDD is contingent upon environment, cleaning Parabolic
schedules and the type of luminaire involved. The term applied to certain louver and reflector shapes
Luminaire Efficiency derived from the geometric shape (curve) called a parabola
Luminaire efficiency is the ratio of lumens emitted by a where, if a light source is placed at the focal point of the
luminaire in relation to those produced initially by the parabola, the resultant emitted light will be redirected
lamps contained within. parallel to the parabola’s geometric axis.
Luminance Parabolic Aluminized Reflector (PAR) Lamp
(Photometric brightness) The luminous intensity of any A type of sealed beam lamp that controls its light beam by
surface in a given direction per unit area of that surface as an internal reflector coating and sometimes a prismatic
viewed from that direction. Measured in candela/m2. All lens.
visible objects have some luminance. Plenum
Units: Candela per unit area, Symbol L That space between the structural ceiling and the finished
Luminous Flux ceiling. This space may contain air ducts, electrical wiring,
etc. It’s the area which conceals the housing part of a
Luminous flux (lumens) is the measure of the total light recessed fixture.
producing power of the light source. It is the amount of
light leaving the source without regard to direction. A Preheat
typical 100 watt incandescent lamp has about 1700 lamp A circuit used on fluorescent lamps wherein the electrodes
lumens. A 400W HPS lamp has 50,000 lumens. The are heated or warmed to a glow stage by an auxiliary
luminous flux rating is provided by the lamp switch or starter (can be a glow switch, thermal type, or a
manufacturers and a listing of common lamp and lumen mechanical device like a push button) before the lamps are
values can be found in the lamp matrix. lighted. This system was used on the original fluorescent
Units: Lumens (lm) Symbol: φ lamps and is still sometimes used today.
Luminous Intensity Rapid Start
The luminous intensity (candelas) is the strength A circuit designed to start fluorescent lamps by
(intensity) of the light produced in a specific direction. The continuously heating or preheating the electrodes. This
luminous intensity of an optical system is compiled circuit is a modern version of the trigger start system and
graphically into diagrams known as candela or requires lamps designed for this circuit. In the rapid start
candlepower distribution curves. Both polar and Cartesian as well as the preheat circuit, each end of each lamp has
graphs are used within the lighting industry for this two separate contacts.
purpose. This information is also available in numeric Recessed
tabular form. The term for a fixture mounted in a ceiling opening so that
Units: Candela (cd) Symbol: l the housing of the fixture is hidden from view. The
fixture’s lens/door assembly may be slightly protruding,
Lux flush or slightly regressed relative to the ceiling surface.
The metric unit of measurement of illuminance. The light
on a surface of one meter square on which there is a Reflectance
uniformly distributed flux of one lumen. 10.76 lux equal 1 Reflectance is the ratio of luminous flux (lumens) reflected
footcandle. One lux is equal to.09 footcandle. Decalux = from a surface in relation to luminous flux (lumens)
10 lux. incident onto the surface. Types of surface reflectance
range from specular (mirror like) to the diffuse (non
Mounting Height glossy), with many objects exhibiting combinations.
The vertical distance between the luminaire light center or Typically, reflectance becomes more specular with larger
ceiling plane and the surface or work plane to be lighted. incident angles. Reflectances of room surfaces are
In outdoor lighting it includes both the pole length and the important consideration when calculating illuminances
base (above grade) to which the pole is affixed. using the “Lumen Method.”
NRTL/C Reflector
The NRTL/C indicator adjacent to the CSA mark signifies A device used to direct the light from a source by the
that the product has been evaluated to the applicable process of reflection.
ANSI/UL and CSA standards, for use in the U.S. and
Canada. NRTL, i.e. Nationally Recognized Testing Refraction
Laboratory, is a designation granted by the U.S. The process by which the direction of a ray of light
Occupational Safety and Health Administration (OSHA) changes as it passes obliquely from one light transmitting
to laboratories which have been recognized to perform material to another.
certification to U.S. standards. Refractor
Optical System A device used to redirect the light from a source by
The light control portion of the luminaire including bending the light (refraction.)
reflectors, lenses, diffusers, baffles and louvers. The lamp
cavity or environment (including diffusing media) is
considered as part of the fixture for the purpose of
TECHNICAL

controlling the light output.


Overhang
In roadway lighting, the distance between a vertical line
passing through the luminaire and the curb or edge of
the roadway.

Hubbell Lighting
355
Glossary — Lighting Terminology
Glossary — Lighting Terminology

Setback Vapor-Tight Luminaire


The distance that the center of the luminaire is behind the A luminaire designed for installation in damp or wet
area to be lighted by that luminaire. locations. Also described as “enclosed and gasketed.” It is
SLD - Switch Level Dimming not designed to keep out vapors.
Switch level dimming of HID sources provides hi-low Visual Comfort Probability (VCP)
control for significant energy savings. It is useful when The rating of a lighting system expressed as a percent of
full output is not required, in unoccupied areas. It is also people who, when viewing from a specified location and
applicable for utility demand power reduction in a specified direction, will be expected find it acceptable
requirements. in terms of discomfort glare.
Spacing Voltage
In roadway lighting, the distance between successive The electrical potential between two points. It is analogous
luminaires measured along the center line of the street. In to hydraulic system pressure (pounds per square inch). The
interiors, the distance between luminaire centers. voltage of a circuit is the electrical “pressure” available to
Spacing Criterion (SC) push current through the circuit. In an incandescent lamp,
“voltage” designates the supply voltage to which the lamp
The ratio of the distance between luminaire centers to the
should be connected.
mounting height above a reference plane, usually the
work plane. Watt (W)
Specular Surface Unit used to measure electric power. See “Kilowatt” and
“Kilowatt Hours”.
Shiny or glossy surfaces (including mirror and polished
metal) that reflect incident light. Work Plane
Spill Light The plane at which work is usually performed, and at
which the illumination is often specified and measured.
Lumens distributed by the luminaire which are outside the
Unless it is otherwise specified, the work plane is assumed
beam spread.
to be a horizontal plane 2.5 ft. above the floor.
Surface Mounted Fixture
Zonal Cavity
Any fixture mounted directly on a ceiling or wall.
The most common method used by the lighting industry to
Suspended or Pendant Mounted Fixture calculate coefficients of utilization for indoor luminaires.
Any fixture hung by supports (chains, hangers,
stems, etc.).

Abbreviations
A LP Lamp
Ampere
AC lx Lux
Alternating Current
BF m Meter
Ballast Factor
CRI mm Millimeter
Color Rendering Index
CSA MH Metal Halide
Canadian Standards Association
DC MV Mercury Vapor
Direct Current
ft NPF Normal Power Factor
Foot
fc Footcandle(s) NRTL Nationally Recognized Testing Laboratory
(UL, CSA, ETL, etc.)
HPF High Power Factor
NRTL/C Evaluated to both ANSI/UL and CSA
HPS High Pressure Sodium standards by CSA
IESNA Illuminating Engineering Society of North POMB Position Oriented Mogul Base
America
UL Underwriters Laboratories
kg Kilogram(s)
UV Ultraviolet
kW Kilowatt
V Volt(s); Vdc—volts DC; Vac—volts AC
kWh Kilowatt-Hour
VA Volt-Ampere
LDD Luminaire Dirt Depreciation
VCP Visual Comfort Probability
TECHNICAL

LLD Lamp Lumen Depreciation


W Watt
LLF Light Loss Factor
lm Lumen

Hubbell Lighting
356

Вам также может понравиться