General
Genset Type : TNK625DO
Rating : 500kW / 625kVA (Prime Power)
: 560kW / 700kVA (Standby Power)
Fuel Consumption : 134 l/h (Prime Power), 147.7 l/h (Standby Power)

Rating Definition
Limited-Time Running Power (LTP): Prime Power (PRP):
Applicable for supplying power to a constant Applicable for supplying power to varying
electrical load for limited hours. Limited-Time electrical load for unlimited hours. Prime
Running Power (LTP) is in accordance with Power (PRP) is in accordance with ISO 8528.
ISO 8528. Ten percent overload capability is available in
accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.

Engine Data Alternator Data


Type : DP180LBF Type : STAMF. HCI544F
Speed [Rpm] : 1500 : [3Ph, Single Bearing]
Frequency (Hz) : 50 Rated Output [kVA] : 625
No of cylinders : 12 (V) Speed [Rpm] : 1500
Displacement [l] : 21.927 Frequency [Hz] : 50
Bore/Stroke [mm] : 128 / 142 Voltage [V] : 400/230
Compression Ratio : 15 : 1 Insulation : Class H
Governor : Electronic Protection : IP 23
Cooling System and Accessories
Radiator Cooling : as Doosan standard
Coolant Capacity [l] : 145
Starting Volt. : 24V
Exhaust System : Industrial / residential exhaust silencer
Baseframe : Steel Channel/Plate construction (incl. 8hrs daily tank)
Engine and Alternator Mounting : Rubber metal elements
Set of Operation books, consist of : Engine operating instruction
: Certificate of Origin
: Alternator operating instruction
: Genset Test Report

Genset Controller

DSE7320
Auto Mains (Utility) Failure Control Modules

The DSE7320 is a feature packed Auto Mains (Utility) Failure


Control Module designed to control single diesel or gas gen-
set applications.

KEY FEATURES
-3-phase generator and mains (utility) sensing
-Power monitoring (kW h, kV Ar, kV Ah, kV Ar h)
-Remote communications (RS232 & RS485)
-Configurable inputs/outputs (9/8)
-Fuel usage monitor and low level alarms
-Manual/automatic load transfer.
- Power save mode.
-DSE Configuration Suite PC Software.
-etc

Genset Dimension and Dry Weight


Open Type Silent Type
Dimension [LxWxH] : 3500x1560x2120(mm) Dimension [LxWxH] : 5030x1800x2250(mm)
Dry Weight : 4812(kg) Dry Weight : 6100kg

OPEN TYPE SILENT TYPE

PT. Tan Energy Indonesia (TANEKO)


Alamanda Tower Lt. 28-D
Jl. TB Simatupang Kav. 23-24 Cilandak Barat
Jakarta 12430 – Indonesia
Ph. +6221 - 75905072, +6221 - 75905073
Email : marketing@taneko.co.id
Website : www.taneko.co.id MEMBER OF ARVON CORP INTERNATIONAL

According to ISO 8528-5. Continuous Power: No time limitation, plus 10% addictional, power for governing purpose only. Prime Power: Average output 80%, no time limitation, plus 5%
addictional power for governing purpose only. Limited Time Running Power: for up to 500 h/year, thereof a maximum of 300 h/year continuous running. In consideration of a generator
efficiency level of 89% - 90% and a power factor of 0.8