Modbus Communication Parameters

Protocol: Modbus RTU (Serial)


Device ID: 10
Baud rate: 19200
Parity: None
Stop bits: 1
Addressing 0
convention

Modbus Coils
Address Description Access
100 Start Request from Scrubber (from Network) R/W
101 Request Response / Start Permit R
102 Diesel Generator No1 RUN R
103 Diesel Generator No2 RUN R
104 Diesel Generator No3 RUN R

Modbus Holding Registers


Address Description Access Data Type Units Range
100 Request Response / Start Permit R Integer16 - 0 or 1
101 Diesel Generator No1 RUN R Integer16 - 0 or 1
102 Diesel Generator No2 RUN R Integer16 - 0 or 1
103 Diesel Generator No3 RUN R Integer16 - 0 or 1
104 Diesel Generator No1 Power (Raw Value) R Integer16 kW x 10 0..2000
105 Diesel Generator No2 Power (Raw Value) R Integer16 kW x 10 0..2000
106 Diesel Generator No3 Power (Raw Value) R Integer16 kW x 10 0..2000
107 Diesel Generator No1 Frequency (Raw Value) R Integer16 Hz x 10
108 Diesel Generator No2 Frequency (Raw Value) R Integer16 Hz x 10
109 Diesel Generator No3 Frequency (Raw Value) R Integer16 Hz x 10
110 Diesel Generator No1 Power R Float32 kW 0..1300
112 Diesel Generator No2 Power R Float32 kW 0..1300
114 Diesel Generator No2 Power R Float32 kW 0..1300
116 Diesel Generator No1 Frequency R Float32 Hz 42..70
118 Diesel Generator No2 Frequency R Float32 Hz 42..70
120 Diesel Generator No3 Frequency R Float32 Hz 42..70