Академический Документы
Профессиональный Документы
Культура Документы
TABLE II
RANGE OF LOSSES IN POWER SYSTEM EQUIPMENT
Component Energ\, oBss,
(full load.)
A. Outdoor Circuit Breakers ..002 - .015
(15 to 230 KV)
B. Generators . . . .09 - 3.50
C. Medium Voltage Switchgear . . . . .005 - .0'
(5 & 15 KV)
Electrical \ / Electrical
Energy Lost _ _ Equipment D. Current Limiting Reactors . . . .09 - .30
in Process _ Energy Loss (600 V to 15 KV)
5- 20%- - .5 - 20%
E. Transformers . . . . . . . . . .40 - 1.90
Fig. 1. Consumption of energy in industrial process. F. Load Break Switches .003 - .025
G. Medium Voltage Starters . . . . . .02 - .15
ELECTRICAL LOSSES H. Busway (480 \V & Below) . . . . .05 - .50
.34
Electrical losses vary over a wide range depending on the I. Low Voltage Switchgear . . . . . . .13 -
complexity of the power system, the geographical area that it J. Motor Control Centers ..01 - .40
covers, and the kind of plant process involved. A rough estimate K. Cable . . . . . . 1.00 - 4.00
. . .
would be that these would vary from 0.5-20 percent. Though L. Motors
little has been done to document the breakdown of energy a. 1 10 hp
- . . 14.00 - 35.00
. . . . . . . .
b. 10 200 hp . . 6.00 - 12.00
consumption in industrial plants, Fig. 1 shows a probable
- . . . . . . .
c. 200 1500 hp . - 4.00 - 7.00
. . . . .
picture of total system energy and where it goes. d. 1500 & up . . 2.30 - 4.50
. . . . . . . .
It might first be thought that since electrical losses are such M. Rectifiers (large) . 3.00 - 9.00 . . . . . .
a small part of the total loss it would be futile to spend much N. Static Variable Speed Drives . . 6.00 - 15.00
effort on them. To the contrary, however, it must be noted 0. Capacitors (watts loss/var.) .. .50 2.00 -
ditioning units where components have been located indoors The percent energy losses of breaker units with load at 0.9
in power control rooms. For that reason, it has sometimes PF for all ratings are
been on the high side. In some cases, it is now getting a closer
look. The following data has been calculated or gathered from Voltage Efficiency Losses
(kilovolts) (percent) (percent)
various product engineering groups. It is based on rated load
flowing through the equipment and must be reduced to actual 2.4 99.98 0.02
4.16 99.99 0.01
load for a particular case. It is representative data to give the 13.8 99.994 0.006
user an estimate of equipment energy losses. Specific units
may vary considerably depending on their particular appli-
Reactors
cation. The data are on General Electric products, but they
should be very similar to that of other manufacturers. Energy losses in watts in current limiting reactors are shown
Since the designation of watts is a rate function, actual below as a function of equivalent single-phase reactor kVA
energy lost must be a function of time such as watt-hours. To 12X
convert watt-hours to Btu, multiply watt values by 3.413 to kVA (equivalent) =
get Btu/h. 1000
Generators where I is the current in amperes and X is the reactance in
ohms. Multiply watt losses by three for three-phase reactor.
Losses for 3600 r/min 13.8 kV industrial generators are as
follows. Equivalent KVA 600 V 5 KV 15 KV
5 360 400 445
KVA P.F. Cooling % Eff. % Loss 10 565 625 695
20 830 922 1 025
5 000 .8 Direct Air 97.2 2.8 30 1 074 1 193 1 315
7 500 .8 " " 97.2 2.8 40 1 259 1 399 1 555
9 375 .8 97.6 2.4 50 1 437 1 597 1 775
12 500 .85 98.1 1.9 60 1 559 1 732 1 925
18 750 .85 98.3 1.7 80 1 867 2 074 2 305
29 412 .85 98.3 1.7 100 2 126 2 362 2 625
44 118 .85 98.3 1.7 140 2 673 2 970 3 300
200 3 240 3 600 4 000
29 412 .85 30# - H2 98.7 1.3 300 4 131 4 590 5 100
64 000 .85 " 98.7 1.3 400 4 981 5 535 6 150
90 000 .9 98.9 1.1 500 5 710 6 345 7 050
115 000 .85 " 98.9 1.1 600 6 399 7 110 7 900
150 000 .9 " 99.0 1.0 800 7 695 8 550 9 500
175 000 .9 " 99.1 .9 1 000 8 829 9 810 10 900
196 000 .9 " 99.1 .9 1 200 9 881 10 980 12 200
1 400 10 935 12 150 13 500
220 000 .9 45# - H2 99.0- 1.0 1 600 11 931 13 257 14 730
246 000 .85 " if
99.0 1.0 1 800 12 887 14 319 15 910
300 000 .85 it
^^ 99.0 1.0 2 000 13 810 15 365 17 050
2 200 14 580 16 200 18 000
2 400 15 390 17 100 19 000
Note: Losses include windage and friction but not seal and 2 600
2 800
16 200 18 000 20 000
17 010 18 900 21 000
bearing losses as per standard ANSI C50.10. 3 000 17 820 19 800 2 2 000
3 500 19 602 21 780 24 200
Medium- Voltage Switchgear-S and 15 Kv 4 000
4 500
21 303
23 085
23
25
670
650
26 300
28 500
5 000 24 786 27 540 30 600
Estimated full-load losses for both 5 and 15 kV are 6 000 27 783 30 870 34 300
7 000 30 699 34 110 37 900
8 000 33 534 37 260 41 400
Breaker Units Air Magnetic 9 000 36 207 40 230 44 700
(amperes) (watts) Vacuum 10 000 38 718 43 020 47 800
12 000 43 335 48 150 53 500
1200 1000 500 14 000 47 628 52 920 58 800
15 000 49 734 55 260 61 400
2000 1500 750
3000 2500 1250
Notes
Auxiliary compartment averages 500 W for air magnetic 1) The data are for indoor units; for outdoor units add
and 300 for vacuum. The bus duct includes losses: 10 percent.
1200 A 75 W/ft 2) Interpolate for losses for intermediate kVA.
2000 A 100 W/ft 3) To above values, add losses generated by field of
3000 A 175W/ft. reactor in surrounding magnetic material such as
metallic beams, walls, floor, etc. These generally
Notes approach zero if they are outside the magnetic clear-
1) Above losses are for indoor units. For outdoor units ances shown on reactor drawings unless they are
add 500 W/unit for heaters if air magnetic and add surrounded by a complete loop of magnetic material
300 W/unit if vacuum. such as structural building steel.
2) Losses are approximately the same for an aluminum 4) The value of R in ohms of a reactor is in the order of
or copper bus. 1/50-1/1 00 of value of X in ohms.
3) Losses vary as the square of the current throughout 5) Values above are for aluminum windings. Values for
range. copper are approximately the same.
376 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-14, NO. 5, SEPTEMBER/OCTOBER 1978
6) Throughout the load range, losses vary as a square of For a 69 kV insulation class, delta primary 350 kV BIL,
the through kVA and PF. 2400-14 400 V wye or delta secondary,
Percent energy losses for typical reactors are
1000 3200 13 500 1.50
3 0 Equivalent Losses 1500 4100 17 100 1.27
Voltage Drop 5500 26 000 1.16
Voltage Reactor (percent) Circuit (kVA) (kVA) (percent) 2500
3750 8000 33600 1.00
5000 9500 42 500 0.94
480 1000A, 0.01 3.61 830 10 0.227
7500 12 500 58 000 0.86
2400 1200A, 0.10 8.65 5000 144 0.180 10 000 16 500 70 500 0.78
4160 1200A, 0.10 5.00 8640 144 0.105
13 800 1200A, 0.5 7.53 28 600 864 0.094
For a 69 kV insulation class, delta primary-350 basic
impulse insulation level (BIL)-2400 to 14 400 V wye or delta
Transformers secondary,
Representative energy losses in transformers at self-cooled 1500 5000 18 000 1.33
rating, rated kVA, and 550C rise are as follows. 2500 6000 27 900 1.24
1) Load Center Type-three-phase, oil, or Pyranol. For a 3750 8500 36 200 1.07
5000 10 500 44 000 0.98
2.4, 4.16, 6.9, 12, 13.2, or 13.8 kV delta primary 480,480Y/ 7500 14 000 59 000 0.87
277 V delta or wye, 10 000 17 000 72 000 0.80
Oil-Air No-Load Note Load tap changing transformers (LTC) will add 5-10
Rating Loss Total Loss Loss
(kVA) (watts) (watts) (percent) percent to no-load losses and 5-10 percent to load losses plus
adjustment for tap connection above or below rated voltage.
750 1940 15 670 1.79 3) Large Power Type-without load tap changing. For
1000 2660 16 170 1.60
1500 3390 22 910 1.51 69 kV class delta primary 350 kV BIL, 15 kV class wye
2000 3850 27 100 1.34 secondary, 110 kV BIL,
2500 5220 31 960 1.27
Oil-Air No-Load
Rating Loss Total Loss Loss
2) Substation Type-three-phase, oil, or Pyranol for a 2.4, (kVA) (kW) (kW) (percent)
4.16, 6.9, 12, 13.2, or 13.8 kV delta primary 480, 480Y/ 12 000 32.3 89 0.82
277 V delta or wye secondary, 20 000 42.5 128 0.71
25 000 50 150 0.67
Oil-Air No-Load 30 000 57 171 0.63
Rating Loss Total Loss Loss 35 000 64 191 0.61
(kVA) (watts) (watts) (percent) 40 000 70 210 0.58
50 000 82.5 247 0.55
750 1950 9 300 1.38
1000 2500 11800 1.31
1.21
For a 1 15 kV class delta primary, 550 kV BIL-15 kV class wye
1500 3400 16300
2000 4400 21 000 1.17 secondary, 110 kV BIL,
2500 5200 24 700 1.10
Oil-Air No-Load
Rating Loss Total Loss Loss
For a 6.9, 12.0, 13.2, or 13.8 kV delta primary 2400- (kVA) (kW) (kW) (percent)
4160 V delta or wye secondary, 14.5 55.0 1.22
5 000
7 500 21.7 70.5 1.04
Oil-Air No-Load 10 000 32.3 81.0 0.90
Rating Loss Total Loss Loss 45.5 114.1 0.79
16 000
(kVA) (watts) (watts) (percent) 20 000 47.2 130.0 0.72
10 000 1.22 25 000 55.5 153.0 0.68
1000 2400 30 000 63.5 174.0 0.64
1500 3200 15 200 1.13
1.06 35 000 71.0 195.0 0.62
2000 4300 19 000 40 000 78.0 214.0 0.59
2500 5000 22 500 1.00
0.92 50 000 91.5 252.0 0.56
3750 6800 31 000
5000 8700 39 700 0.88
7500 11 500 54 000 0.80 For a 138 kV class delta primary, 650 kV BIL-1 5 kV class wye
10 000 15 000 64 000 0.71
secondary, 110 kV BIL,
For a 22.9, 26.4, or 34.4 kV delta primary 2400-14 400 V 5 000 19.0 54.0 1.20
wye or delta secondary, 7500 23.5 73.5 1.09
10 000 30.7 87.5 0.97
1000 2700 12 600 1.40 16 000 47.8 120.0 0.83
1500 3600 16 700 1.24 20 000 48.0 132.0 0.73
2500 5600 24 000 1.07 25 000 56.5 155.0 0.69
3750 7700 33 000 0.98 30 000 64.5 177.0 0.66
5000 8500 42 500 0.94 35 000 72.0 198.0 0.63
7500 12 000 58 000 0.86 40 000 79.0 217.0 0.60
10 000 16 000 68 000 0.76 50 000 92.0 255.0 0.57
HICKOCK: LOSSES IN POWER SYSTEMS 377
TABLE III
700 A CONTACTOR
Load Fuse Contactor Cable *Coil, CPT Blowouts Total
Amps Size Watts Watts Size Watts %OL-Watts Watts Watts
240 18R 134.7 69 300M 41.5 268 0 513.2
24R 101.9 69 300M 41.5 268 0 480.4
600A 20.2 69 500M 24.2 268 0 381.4
700A 16.7 69 500M 24.2 268 0 377.9
Note: Transformers with LTC will raise no-load losses 5-20 600 A Switch- 15 kV
percent and load losses 10-25 percent.
Notes on transformer losses Watt Loss
1) Load losses vary as the square of the current. Load Current Unfused
2) No-load losses are based on nameplate voltage and (amperes) Switch Fuse Total
vary directly as a function of voltage. Taps above or
50 5 468 473
below nameplate rating will raise or lower losses by 100 14 840 854
the percent voltage change. 200 55 - -
Low- Voltage Switchgear- Type ADK-5 or AKD-6 Motor Control Centers-600 V Class, Type 7700
The total losses per indoor cubicle are the sum of those for Total watt losses for equipment are the sum of the losses
breakers in the cubicle plus the power bus loss. for components applicable and listed below.
1) Various breaker losses, three pole, including tap and 1) Combination starters, fused or breaker, including
run back bus and direct acting or static trips (240, control power transformer and pilot light:
480, or 600 V. NEMA Size Watt Loss
Breaker Trip Watt
Frame Sizes Coil Amps Loss 1 27
2 57
225A 15 55 3 99
Only 20 55 4 165
30 65
40 60 5 280
225A and 50 60
600A 70 70
90 70
100 65 2) Feeder tap units.
125 105
150 80
175 110 Rating
200 #105-110 Frame (ampere) Watt Loss
225 140
Circuit breakers-based on 80 percent loading
600A 250 95
only 300 119
350 150 TEF,THEF 15-30 4
400 165 40-50 16
500 225 70-100 27.5
600 215
1 600A 200 60 TFJ, TFK 70-100 20
225 75 THFK 125-150 26
250 55 175-225 37
300 40
350 55 TJJ, TJK 125-225 27
400 60
500 90 THJK 250-275 50
600 120 300 55
800 195 350-400 65
1000 180 500-600 85
1200 260
1600 460
TKM, THKM 400 70
3 OOOA 2000 480 500-600 75
2500 750 700-800 140
3000 1080 1000-1200 140
4 OOOA 2000 N.A.
2500 N.A. Fusible switches
3000 N.A.
4000 960 30 12
# Note: 105 for 225 A frame breaker. 110 for 600 A frame breaker. 60 18
100 30
200 35
2) Bus Losses with aluminum or copper:
3) Power and lighting transformers for 480 to 120/
Main Bus Rating 240 V single phase or 480 to 208/120 V three phase
Equipment Size (amperes) Watt Loss
are shown.
20 or 22 in stack 1600 570
3000 1350 Single Watt Three Watt
Phase Loss Phase Loss
27 in stack 1600 645
3000 1500 1 60 9 295
2 90 15 460
30 in stack 3000 1700 5 190 30 1400
4000 2100 7.5 240
10 290
Notes 15 350
25 430
1) For outdoor equipment add 250 W/unit for heaters.
2) Losses apply to an aluminum or copper bus. 4) Lighting panelboards are 0.8 W/A handled, single- or
Losses vary with the square of the feeder current plus the
adjusted losses of the power bus. Typical percent energy losses three-phase based or mixture of 15, 20, and 30 A
of a cubicle of 4-600 A breakers with 400 A trips and 0.9 PF circuits.
loads and a 3000 A bus are 5) Vertical bus. For a 300-A vertical bus with 600 A the
main loss is 75 W. For a 300-A vertical bus with 1 200A
240 V, 0.34 percent; the main loss is 105 W.
480 V, 0.17 percent; Note: Losses vary generally as the square of the current
600 V, 0.13 percent. though control power transformers, individual lights, etc.,
380 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-14, NO. 5, SEPTEMBER/OCTOBER 1978
HorizonLal
add fixed losses regardless of load. Energy losses for a typical Svn. Drripproof TEFC
480 V cubicle of say two-size one starters, one-size two and Speed Eff. Loss r, Eff. Loss
one-size three with 1200 A power bus would be 0.24 percent. 1/2 3600 69. 0 31.0 69.0
69.0
31.0
31.0
1800 69.0 31.0
70. 5 29. 5 70. 5 29. 5
Cable 1200
900 62 .5 37 .5 62.5 37. 5
Energy losses are a function of 12R. Values of R for use in 1 3600 ,7 4 . 5 74.5 25.5
calculating losses for copper cable at 60 H and 75°C are as 75.0 75.0 5. 0
2
1800 25.0
1200 73.0
27. 0 73.0 2
7. 0
follows. (Multiply ohms by three for three-phase circuiit.) 900 70.0
30(.0 70.0 30.0
2 3600 79.0
21.0 .0
21. 0)
Size Conductor Feet 1800 79.5O 20. 5 79 5 20. 5
AWG or kcmil (Ql/1000) 1200 78.5
70.0
21.5
30. 0
78.5
70.0
21.5
30.0
900
8 0.780 3 3600 80.0 20 .0t 75.5 24. 5
6 0.489 1800 80.5 19.5 80.5 19.5
4 0.309 1200 76.0 24.0 78.0 22.0
0.195 900 74.0 26.0 74.0 26.0
2
1 0.155 5 3600 83.0 17.0 80. 5 19.5
1/0 0.124 1800 84.0 16.0 84.0 16.0
2/0 0.010 1200 79.0 21.0 78.0 22.0
0.078 22 0 78.0 22.0
3/0 900 78.0
4/0 0.064 712 3600 84.5 1
5. 5 79.0 21.0
250 0.055 1800 82.0 18.0 82.5 17.5
300 0.046 1200 84.5 15.5 83.0 17.0
0.040 21.0 79.0 21.0
350 900 79.0
400 0.035 10 3600 84.5 15.5 82. 5 17. 5
450 0.032 1800 83.0 17.0 83.0 17.0
10.0
Example of Loss Calculation: Determine loss in 2-500
13. 5
kcmil/phase three conductor cable circuit 500 ft, 480 V, 900 40 3600
1800
88.0
88.5
12.0
11. 5
86.5
90. 5 9.5
A load at 0.9 PF: 1200
900
89.0
88.0
11.0
12.0
90.0
90.0
10.0
10.0
circuit kW = IE 3 cos 0 50 3600 89.0 11.0 88.0 12. 0
=
673.4 75 3600
1800
90.5
91.0
9.5
9.0
90.5
92.0
99.5. 5
8.0
1200 91.0 9.0 92.0 8.0
loss kW = P2R 900 91.0 9.0 92.0
8.0
a. 2300 V
10,000 -
a. 2300 V Notes
HP Speed , Efficiencv i Loss 1) For brushless type motors either 2300 or 4000 V
500 1800 95.3 4.7
decrease efficiency, as follows:
1200 95.2 4.8
900 95.3 4.7 Reduction Required
720 9 5 . 1. 4. 9
Listed Full-Load
600 1800 95.5 4.5 Efficiency Full Load 3/4 Load
1200 95.5 4.5
900 95.6 4.4 >97.0 0.1 0.2
720 95.3 4. 7 96.1-97.0 0.2 0.2
800 1800 95.7 4.3
95.1-96.0 0.2 0.3
1200 95.8 4.2 94.1-95.0 0.3 0.4
900 96.0 4.0 93.1-94.0 0.3 0.4
720 95.8 4.2 92.1-93.0 0.5 0.6
91.1-92.0 0.6 0.8
1000 1800 95.9 4.1
1200 96.0 4.0
900 96.2 3.8
720 96.1 3.9 2) For synchronous motors operated at rated excitation
1200 1800 96.1 3.9 for less than full load, adjust losses in terms of full-
1200
900
96.2
96.4
3.8
3.6
load losses as follows:
720 96.4 3.6
96.3 3.7
Losses
1500 1800 PF Load (% Full-Load Losses)
1200 96.4 3.6
900 96.6 3.4
720 96.6 3.4 1.0 3/4 85
1/2 75
17 50 1800 96.4 3.6 1/4 69
1200 96.5 3.5 0 67
900 96.7 3.3
720 96.7 3.3
0.8 3/4 94
2000 1800 96.2 3.8 1/2 90
1200 96.7 3.6 1/4 88
900 96.7 3.3 0 87
720 96.7 3.3
8000 1800 from the nameplate on the lamp in watts; it is the energy input.
1200
900
97. 4
97.6
2.6
2.4
The total plant lighting energy is a matter of adding up the
720
97.6
2.4 number and wattage of all lamps and adding to them various
10,000 1800
97 ,65 ballast losses, which though small, are significant. An impor-
1200 97.5 2.5
2.3
tant factor to consider is a lamp's conversion ratio of electrical
97.7
energy to light energy or lumens per watt. Typical conversion
900
720 97.7 2.3
HICKOCK: LOSSES IN POWER SYSTEMS 383
F) Losses vary from unit to unit of the same design because from plant to plant. To convert ideas to actual dollar savings is
of difference in materials, workmanship, and production a specific study for each application.
methods. A) Quite naturally, the place to start is in the power gener-
G) Since measurements are not made at rated voltage, ation area. Efficiency improvements in converting fuel
dielectic losses, which though small, are neglected energy to electrical energy can be dramatic. The days
completely. of low pressure boilers and steam turbines or low effi-
As an example, the losses of a 2000 A 5 kV breaker in a ciency simple cycle gas turbines as drivers for small
cubicle with a 2000 A power bus and a 2000 A run back-bus generators are fading fast under today's high fuel
was measured by the three methods, and results were energy cost. Power companies exist because they can
deliver a kilowatt-hour of energy at your plant even
calculated 100 W with all of their transmission system at a cheaper cost
dc resistance assumed 1500 W than you could generate it because of better cycle effi-
(with multiplier for skin and proximity effects) ciency and larger generating units.
wattmeter 2084 W B) Examine cable sizes in your distribution system, partic-
(corrected by power factor). ularly in the low voltage area of 208 and 480 V. The
code says that a feeder circuit should have no more
The apparent resistance of the unit assuming 1500 W loss than 3 percent voltage regulation. New economic factors
would be 0.000375 Q2. Based on full-load current at 13.8 kV may say that in actual practice this should be no more
and a load power factor of 0.9, the efficiency of the unit than l½ percent.
would be 99.994 percent. If in measurement, the value of R C) Reduce lighting loads by the following.
through any of the above reasons increased by 0.0001 &2, the 1) Use more efficient light sources such as sodium in
loss would increase to 1900 W or about 25 percent. place of mercury vapor on structures and towers. In
Until now, there have been little or no requests for accurate cost per million lumen hours, the lighting of a 400 W
loss data and if it is to be an important item for comparison high-pressure sodium lamp is 31¢, a 100 W incandes-
purposes, it must first be agreed as to how they will be meas- cent source is $2.26, and a common candle is $3000.
ured in these kinds of equipment. If it is to be used as a guide 2) Use more efficient laminaires.
as to where to find and improve losses, present data are suffi- 3) Use lighter colors on walls, structures, etc., to reflect
ciently accurate. There are many hundreds of configurations more light.
of bus, bus size, breakers of various ratings, a wide variety of 4) Keep lighting equipment clean.
instrumentation, protective relaying, metering and potential 5) Cut down footcandle levels of lighting, particularly in
current, and control power transformers on switchgear and nonworking areas such as cat walks, halls, etc. The
other control type equipment. It would require a very expen- Federal Energy Administration recently passed a
sive and time consuming task to accurately measure, if and guideline for
when the measurement procedures were all agreed upon. workstations and desks 50 fc
Today only a base or average figure per given unit of a given general work area 30 fc
type is available. The cost of accurate measurement of losses halls and corridors 10 fc
could well eat into the savings of power consumed by the
equipment unit during its life. In passing, it might be noted This guide, though not mandatory yet, will generally
that the difference in losses between manufacturers of like cut present levels in half. In building interiors, a
units in the switchgear area is probably less than the accuracy secondary savings is in decreased air conditioning load.
of data they could provide. 6) Cut wasted light. Put lighting on timers or photo-
Loss data are nearly always given on the basis of the equip- electric controls. In general it has been estimated that
ment being fully loaded. In most cases it is not, and for any potential savings in lighting loads with the same light-
reasonable use, the values must be modified down by its actual ing effectiveness are
load. In many instances, the loss goes down mainly as an I2R residential 10-20 percent
function, but this does not hold true for some circuit compon- commercial 1 5 -3 5 percent
ents and usually does not hold at light loads. It is an important industrial 5-20 percent.
factor to consider when analyzing a specific plant's losses. The
above mentioned 2000 A metal-clad breaker would consume D) Use power factor correction capacitors to reduce sys-
only 375 instead of 1500 W of power at half load. tem losses. Normally we think of capacitors being
installed to improve power factor, release system
CHECK LIST OF POSSIBLE SAVINGS capacity, and lower billing demand charges. They also
produce an important savings in energy losses. The
The main purpose of this paper is to point power system resultant improvement in power factor may result in
engineers in the direction of where energy losses are or where an annual gross return in less energy of as much as 20
to go to start plugging energy leaks. We would miss an oppor- percent of the annual capacitor equipment investment.
tunity, however, not to provide a simple check list of ideas on Capacitors in reducing reactive currents reduce the I in
possible energy savings. Their worth may vary considerably P2R system losses. Since current is reduced in direct
HICKOCK: LOSSES IN POWER SYSTEMS 385
TABLE VI automatically, they do not get turned off. These are generally
NEMA EFFICIENCY INDEX STANDARD much easier to find and eliminate. A multistory administration
Index Nominal Minimum building in Houston recently found that they could save
Letter Efficiency Efficiency $2500/month by operating their air conditioning and heating
blower motors only when heating or cooling was taking place
A >95.0
instead of operating them continuously. Turning off unloaded
-
B 95.0 94.1
C 94.1 93.0 transformers over a weekend and longer saves their no-load
D 93.0 91.7 kilowatt-hours of energy though both motors and transformers,
E 91.7 90.2
F 90.2 88.5 and control equipment should be checked for excessive start-
G 88.5 86.5 ing operations. These losses may be eliminated at some incon-
H 86.5 84.0 venience, and our plant life style may have to be changed. It is
K 84.0 81.5
L 81.5 78.5 comparable to the type of energy savings achieved in our 55
M 78.5 75.5 mi/h speed limit on automobiles. The real savings here in
N 75.5 72.0 chemical and petroleum plants is in the process operation and
P 72.0 68.0
R 68.0 64.0 must be achieved with close coordination with process engi-
S 64.0 59.5 neers. It is mentioned here only as a big potential area for
T 59.5 55.0 investigation towards saving kilowatt-hours of power.
U 55.0 50.5
V 50.5 46.0 This paper is concerned only with electrical energy losses,
W - <46.0 but it should be noted that there is probably equal savings to
be made in improvement in energy wasted in mechanical losses.
For 0.8 PF motors above, decrease efficiency by 0.6 percent. Better pump and blower efficiency, less friction in conveyor
bearings, less losses in gear and belt systems for speed changing
86.5 88.5 90.2 91.7 93.0 94.1
are a few places to start.
F-------F -- ------
FUTURE SAVINGS
Fig. 3. Efficiency index letters. Recent detailed investigation of overall savings in residential
homes has led to the conclusion that 56 percent of the energy
now being consumed could be saved with little or no incon-
index" classification in the form of a code letter will be venience to those living there [3]. In a comprehensive two-
included on the name plate for the motor full-load efficiency. year energy conservation program undertaken by the Bell
These are shown in Table VI. Telephone System, the company found that it reduced energy
The new standard recognizes variations in material, manu- a little over 10 percent. This was accomplished in spite of a 21
facture, and test results in a group of motors of a given design percent increase in business. It resulted in the equivalent
and rating. Consequently, individual efficiencies of the group savings of 5 million barrels of oil or enough to meet the needs
will form a band. The code letter for nominal efficiency of the of 80 000 families for a year [4]. No known studies have been
group is stamped on the nameplate. On the basis of probabil- made in our petroleum and chemical industry on a plant basis,
ities, half of the motors in a group will be above the nominal and because of wide variations in processes and equipment, it
efficiency listed for that code letter and half below, with the would be hard to make much of a guess even as a broad gener-
lowest not to be less than the minimum value listed. The upper alization except on a plant by plant basis. The writer has asked
end of the band will reach up to the nominal value of the next a number of power system engineers for their estimates on
better code letter. Fig. 3 indicates how this works out. savings in their plants, and roughly averaged, these lead to a
Since the cost of actual testing of an individual motor is a conclusion that potential electrical savings would be
significant adder to its price, this band type classification of improved component and system efficiency 5-7 percent
efficiency indexes" is a means of supplying the user with a savings in operating losses 2-1 5 percent
close value of efficiency without the trouble of an individual Total 2.5-22 percent.
test. Of course, the motor can always be tested for a more
exact value. For years everyone fussed about poor gas mileage and
inefficiency in automobiles, but the automobile industry did
OPERATING LOSSES not do anything about them until the government intervened.
Now the industry is living under harsh design restrictions. It
Though this paper is primarily concerned with eliminating could happen the same way in our industry. The Federal
energy losses by improving efficiency of components, at least Energy Administration has already issued instructions to
a note must be said about its closely allied copartner in crime- reduce lighting. It has also issued instructions to federal agen-
operating losses. Their possible savings are likely to be much cies as to which home appliances may be purchased as a func-
greater. They involve energy wasted in performing useless tion of energy consumption and losses. The government is
work. This loss, for instance, is typified by the process whose ready to step in if we do not get busy ourselves. Now is the
outdoor lights burn all day because somehow, manually or time for each of us to become "energy conscious."
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-14, NO. 5, SEPTEMBER/OCTOBER 1978 387
REFERENCES Herbert N. Hickok (M'53) was born in San
[1] E. Raia, "Are motors wasting too many kilowatts?" Purchasing, "\i' Antonio, TX. He received the B.S. degree
p. 41, Jan. 13, 1976. from the University of Texas, TX.
[2] J. Maloney, "Engineer convinced plugging leaks best bet for He has been employed by the General
saving energy," Austin Amer., Dec. 15, 1975. Electric Company, Houston, TX, for more
[3] H. L. Kertz, "How bell pinches power," IEEE Spectrum p. 54-58, than thirty years, and he presently holds the
Feb. 1976. position of Industrial Application Engineer
[4] C. W. Beardsley, "Let there be light, but just enough," IEEE Spec- in the Gulf Coast Area. He works mainly with
trum, p. 28-32. a refineries, and chemical, petrochemical, and
[5] D. C. Montgomery, "Efficiency-A new emphasis in motor selec- electrochemical plants.
tion," Fig. 11, TAPPI Conf. Rec., 1977, Atlanta, GA. Mr. Hickok has been active in both local
[6] A. D. Little, "Energy efficiency and electric motors," National and national IEEE activities for many years and is a Registered Profes-
Tech. Inform. Service Publication, PB-259129, p. ES-3. sional Engineer for the State of Texas.